Finder 22.34.0.230.4640 Relay 2 NO/2 NC 230V DC/AC IP20 Industrial Relay Data Sheet

Finder 22.34.0.230.4640 Relay 2 NO/2 NC 230V DC/AC IP20 Industrial Relay Data Sheet

Below you will find brief information for 22 Series 22.32.0.xxx.1xx0, 22 Series 22.32.0.xxx.4xx0, 22 Series 22.34.0.xxx.1xx0, 22 Series 22.34.0.xxx.4xx0, 22 Series 22.44.0.xxx.4xx0. These contactors are designed for use in a variety of applications, including industrial, commercial, and residential settings, can be used to control various types of loads, such as motors, lights, and appliances. These contactors are designed for use in a variety of applications, including industrial, commercial, and residential settings. They can be used to control various types of loads, such as motors, lights, and appliances. They are available in a variety of configurations, including 2-pole and 4-pole versions. They are also available in a variety of contact materials, including AgNi and AgSnO2. They can be used in various applications, including industrial, commercial, and residential settings.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Finder 22 Series 22.32.0.xxx.1xx0 Datasheet | Manualzz

22 Series - Modular contactors 25 - 40 - 63 A

Features

22.32.0.xxx.1xx0

25 A modular contactor - 2 pole

17.5 mm wide

NO contact gap ≥ 3 mm, double break

Continuous duty for the coil and contacts

AC/DC silent coil (with varistor protection)

Protective separation (reinforced insulation) between coil and contacts

Mechanical and LED indicators as standard

Auto-On-Off selector version available

AgNi and AgSnO

2 contact versions available

Compliant with EN 61095: 2009

Auxiliary contact module available, quick-assembly with the main contactor

(1 NO + 1 NC and 2 NO versions)

35 mm rail (EN 60715) mount

AgNi contacts, specifically intended for resistive and slightly inductive loads as well as for motor loads

22.32.0.xxx.4xx0

AgSnO

2 contacts, specifically intended for lamp loads and for high inrush current loads

22.32...1xx0 / 22.32...4xx0

Screw terminal

22

SERIES

2 NO

(x3x0)

1 NO + 1 NC

(x5x0)

2 NC

(x4x0)

* Contact gap ≥ 3 mm for NO contacts only;

NC contacts ≥ 1.5 mm

For outline drawings see page 8

Contact specification

Contact configuration

Rated current/Maximum peak current

Rated voltage

A

V AC

Rated load AC1 / AC-7a (per pole @ 250 V) VA

Rated current AC3 / AC-7b

Rated load AC15 (per pole @ 230 V)

Single-phase motor rating (230 V AC)

A

VA kW

Rated current AC-7c A

230 V lamps rating: incandescent or halogen W compact fluorescent (CFL) W electronic ballast fluorescent tubes W electromagnetic ballast compens. fluorescent tubes W

Breaking capacity DC1: 30/110/220 V A

Minimum switching load mW (V/mA)

Contact material

Coil specification

Nominal voltage (U

N

) V DC/AC (50/60 Hz)

Rated power AC/DC VA (50 Hz)/W

Operating range

Holding voltage

Must drop-out voltage

Technical data

DC/AC (50/60 Hz)

DC/AC (50/60 Hz)

DC/AC (50/60 Hz)

Mechanical life AC/DC

Electrical life at rated load AC-7a cycles cycles

Operate/release time ms

Insulation between coil and contacts (1.2/50 μs) kV

Ambient temperature range °C

Protection category

Approvals (according to type)

2 NO, 3 mm * (or 1 NO + 1 NC or 2 NC)

25 / 80 25 / 120

250 / 440 250 / 440

6,250

10

1,800

1

25/5/1

1,000 (10/10)

AgNi

6,250

10

1,800

1

10

2,000

200

800

500

25/5/1

1,000 (10/10)

AgSnO

2

12 - 24 - 48 - 60 - 120 - 230 12 - 24 - 48 - 60 - 120 - 230

2 /2.2

2 / 2.2

(0.8…1.1) U

N

0.4 U

N

0.1 U

N

(0.8…1.1) U

N

0.4 U

N

0.1 U

N

2 · 10 6

70 · 10 3

30 / 20

6

–20…+50

IP20

2 · 10

30 · 10 3

30 / 20

6

–20…+50

IP20

6

1

22

SERIES

22 Series - Modular contactors 25 - 40 - 63 A

Features

22.34.0.xxx.1xx0

22.34.0.xxx.4xx0

25 A modular contactor - 4 pole

35 mm wide

NO contact gap ≥ 3 mm, double break

Continuous duty for the coil and contacts

AC/DC silent coil (with varistor protection)

Protective separation (reinforced insulation) between coil and contacts

Mechanical and LED indicators as standard

Auto-On-Off selector version available

AgNi and AgSnO

2 contact versions available

Compliant with EN 61095: 2009

Auxiliary contact module available, quick-assembly with the main contactor

(1 NO + 1 NC and 2 NO versions)

35 mm rail (EN 60715) mount

AgNi contacts, specifically intended for resistive and slightly inductive loads as well as for motor loads

AgSnO

2 contacts, specifically intended for lamp loads and for high inrush current loads

22.34...1xx0 / 22.34...4xx0

Screw terminal

4 NO

(x3x0)

3 NO + 1 NC

(x7x0)

2 NO + 2 NC

(x6x0)

* Contact gap ≥ 3 mm for NO contacts only;

NC contacts ≥ 1.5 mm

For outline drawings see page 8

Contact specification

Contact configuration

Rated current/Maximum peak current A

Rated voltage V AC

Rated load AC1 / AC-7a (per pole @ 250 V) VA

Rated current AC3 / AC-7b A

Rated load AC15 (per pole @ 230 V) VA

Three-phase motor rating (400 - 440 V AC) kW

Rated current AC-7c A

230 V lamps rating: incandescent or halogen W compact fluorescent (CFL) W electronic ballast fluorescent tubes W electromagnetic ballast compens. fluorescent tubes W

Breaking capacity DC1: 30/110/220 V

Minimum switching load

A mW (V/mA)

Contact material

Coil specification

Nominal voltage (U

N

) V DC/AC (50/60 Hz)

Rated power AC/DC VA (50 Hz)/W

Operating range

Holding voltage

Must drop-out voltage

Technical data

DC/AC (50/60 Hz)

DC/AC (50/60 Hz)

DC/AC (50/60 Hz)

Mechanical life AC/DC

Electrical life at rated load AC-7a

Operate/release time cycles cycles ms

Insulation between coil and contacts (1.2/50 μs) kV

Ambient temperature range °C

Protection category

Approvals (according to type)

4 NO, 3 mm * (or 3NO + 1NC or 2NO + 2NC)

25 / 80 25 / 120

250 / 440

6,250

250 / 440

6,250

10

1,800

4

25/5/1

1,000 (10/10)

AgNi

10

1,800

4

10

2,000

200

800

500

25/5/1

1,000 (10/10)

AgSnO

2

12 - 24 - 48 - 60 - 120 - 230 12 - 24 - 48 - 60 - 120 - 230

2 / 2.2

(0.8…1.1) U

N

0.4 U

N

0.1 U

N

2 / 2.2

(0.8…1.1) U

N

0.4 U

N

0.1 U

N

2 · 10

150 · 10

18 / 40

6

IP20

6

3

–20…+50

2 · 10

30 · 10

6

6

18 / 40

3

–20…+50

IP20

2

22 Series - Modular contactors 25 - 40 - 63 A

Features

22.44.0.xxx.4xx0

22.64.0.xxx.4xx0

40 - 63 A modular contactor - 4 pole

NO and NC contact gap ≥ 3 mm, double break

Continuous duty for the coil and contacts

AC/DC silent coil (with varistor protection)

Protective separation (reinforced insulation) between coil and contacts

Mechanical indicator as standard

AgSnO

2 contacts

Compliant with EN 61095: 2009 and with

EN 60947-4-1: 2009

35 mm rail (EN 60715) mount

For high inrush current loads

176 A

Contact material AgSnO

2

Specifically intended: for high inrush current loads

240 A

Contact material AgSnO

2

22.44.../22.64...

Screw terminal

22

SERIES

4 NO

(4310)

3 NO + 1 NC

(4710)

2 NO + 2 NC

(4610)

For outline drawings see page 8

Contact specification

Contact configuration

Rated current/Maximum peak current A

Rated voltage V AC

Rated load AC1 / AC-7a (per pole @ 250 V) VA

Rated current AC3 / AC-7b (400 V) A

Rated load AC15 (per pole @ 230 V) VA

Three-phase motor rating (400 - 440 V AC) kW

Rated current AC-7c A

230 V lamps rating: incandescent or halogen W compact fluorescent (CFL) W electronic ballast fluorescent tubes W electromagnetic ballast compens. fluorescent tubes W

Breaking capacity DC1: 30/110/220 V A

Minimum switching load mW (V/mA)

Contact material

Coil specification

Nominal voltage (U

N

) V DC/AC (50/60 Hz)

Rated power AC/DC VA (50 Hz)/W

Operating range DC/AC (50/60 Hz)

Holding voltage

Must drop-out voltage

Technical data

DC/AC (50/60 Hz)

DC/AC (50/60 Hz)

Mechanical life AC/DC

Electrical life at rated load AC-7a

Operate/release time cycles cycles ms

Insulation between coil and contacts (1.2/50 μs) kV

Ambient temperature range °C

Protection category

Approvals (according to type)

4 NO, (or 3NO + 1NC or 2NO + 2NC) ≥ 3 mm

40 / 176

250 / 440

16,000

22

11

4,000

1,000

1,500

1,500

40/4/1.2

1,000 (17/50)

AgSnO

2

63 / 240

250 / 440

24,000

30

15

5,000

1,500

2,000

2,000

63/4/1.2

1,000 (17/50)

AgSnO

2

12 - 24 - 110...120 (110 V DC) - 230...240 (220 V DC)

5

(0.85…1.1) U

N

0.85 U

N

0.2 U

N

5

(0.85…1.1) U

N

0.85 U

N

0.2 U

N

3 · 10

100 · 10

20 / 45

6

–5…+55

IP20

6

3

3 · 10

6

IP20

6

100 · 10

20 / 45

–5…+55

3

3

22

SERIES

22 Series - Modular contactors 25 - 40 - 63 A

Ordering information

Exemple: 22 series, modular contactor 25 A, 4 NO contacts, coil 230 V AC/DC, AgSnO

2 contacts, Auto-On-Off selector + mechanical indicator + LED.

A B C D

2 2

.

3 4

.

0

.

2 3 0

.

4 3 4 0

Series

Type

3 = 25 A modular contactor range

4 = 40 A modular contactor range

6 = 63 A modular contactor range

Number of contacts

2 = 2 pole

4 = 4 pole

Coil version

0 = AC (50/60 Hz)/DC

Coil rated voltage

See coil specifications

D: Special versions

0 = Standard

C: Options

1 = Mechanical indicator

2 = Mechanical indicator + LED

4 = Auto-On-Off selector + mechanical indicator + LED

B: Contact circuit

3 = All NO contacts

4 = All NC contacts (22.32 only)

5 = 1 NO + 1 NC

6 = 2 NO + 2 NC

7 = 3 NO + 1 NC

A: Contact material

1 = AgNi

4 = AgSnO

2

Selecting features and options: only combinations in the same row are possible.

Preferred selections for best availability are shown in bold.

Type

22.32

22.34

22.44

22.64

Coil version

AC/DC

AC/DC

AC/DC

AC/DC

A

4

4

1 - 4

1 - 4

B C

3 - 4 - 5 2 - 4

3 - 6 - 7 2 - 4

3 - 6 - 7 1

3 - 6 - 7 1

D

0

0

0

0

Options

Auto-On-Off selector + mechanical indicator + LED (xx40 option)

Type 22.32 / 22.34

1

1

Options

Selector

The three-position manual selector has the following functions:

• ON position - the contacts are latched in the operated state

(NO contacts - closed and NC contacts - open), the mechanical indicator is visible in its window, the LED is not illuminated.

2

3

2

• AUTO position - the state of contacts, mechanical indicator and LED follow the coil supply voltage.

• OFF position - even if terminals A1 - A2 are supplied with rated voltage, the coil is not energized, and so the contacts remain in the non-operated state, the mechanical indicator is not visible and the LED is not illuminated.

LED

Type 22.44 / 22.64

3

1

Mechanical indicator

Options

Mechanical indicator

1

4

22 Series - Modular contactors 25 - 40 - 63 A

Technical data

Insulation

Rated insulation voltage

Pollution degree

Insulation between coil and contact set

V AC 250

3 *

22.32 / 22.34

440

2

Type of insulation

Overvoltage category

Rated impulse voltage

Dielectric strength

Insulation between adjacent contacts

Type of insulation kV (1.2/50 μs)

Reinforced

III

6

V AC 4,000

Overvoltage category

Rated impulse voltage

Dielectric strength

Insulation between open contacts

Basic

III kV (1.2/50 μs) 4

V AC 2,500

NO contact

Contact gap

Overvoltage category

Rated impulse voltage mm 3

III kV (1.2/50 μs) 4

NC contact

1.5

II

2.5

Dielectric strength V AC/kV (1.2/50 μs) 2,500/4 2,000/3

* Only for versions without Auto-On-Off selector. For versions with Auto-On-Off selector pollution degree 2 applies.

Conducted disturbance immunity Reference standard

Fast transients (burst 5/50 ns, 5 kHz) at coil terminals EN 61000-4-4

Voltage pulses (surge 1.2/50 μs) at supply terminals (differential mode) EN 61000-4-5

Short circuit protection

Rated conditional short circuit current

Back-up fuse

Terminals

Max. wire size – contact terminals

Max. wire size – coil terminals kA

A

22.32 / 22.34

3

32 (gL/gG type) mm 2

22.32 / 22.34

mm 2 1 x 6 / 2 x 4

AWG 1 x 10 / 2 x 12

1 x 4 / 2 x 2.5

Level 4 (4 kV)

Level 4 (4 kV)

22.44

3

63

Solid and stranded cable

440

3

Reinforced

III

4

2,000

Basic

III

4

2,000

NO/NC contacts

3

III

4

2,000/3

Level 2 (2 kV)

Level 2 (2 kV)

22.64

3

80

22.44 / 22.64

22.44 / 22.64

1x25 (solid) - 1x16 (stranded)

1x4 (solid) - 1x6 (stranded)

1x2.5

Min. wire size – contact and coil terminals

Screw torque

Wire strip length

Power lost to the environment

AWG 1 x 12 / 2 x 14 mm 2 1 x 0.2

AWG 1 x 24

Nm 0.8

mm 9

22.32

without contact current W 2 with rated current W 4.8

22.34

2

6.3

1x14

1x1 (coil) - 1x1.5 (contacts)

1x18 (coil) - 1x16 (contacts)

1.2 (coil terminals) - 3.5 (contact terminals)

10

22.44

5

17

22.64

5

37

NOTE

22.32/22.34: It is suggested an air gap of 9 mm between adjacent relays for installations and working conditions close to the limit (that is, ambient temperature > 40 °C, coil operated for a prolonged period of time, all contacts loaded with current > 20 A).

22.44/22.64: The maximum ambient temperature with 3 adjacent contactors is + 40 °C; when more than 3 contactors are installed, it is necessary an air gap of 9 mm.

With 2 adjacent contactors the maximum ambient temperature is + 55 °C; when more than 2 contactors are installed, it is necessary an air gap of 9 mm.

22

SERIES

5

22

SERIES

22 Series - Modular contactors 25 - 40 - 63 A

Contact specification

Ratings and utilization categories according to EN 61095: 2009

Type

AC-7a

Rated current Rated electrical

(A) life (Cycles)

22.32….1xx0 (AgNi contacts)

22.32….4xx0 (AgSnO

2

22.34….1xx0 (AgNi contacts)

22.34….4xx0 (AgSnO

2

22.44….4xx0

22.64….4xx0

contacts) contacts)

25

25

25

25

40

63

70·10 3 (NO)

30·10 3 (NC)

30·10 3

150·10 3

100·10 3

(NO)

(NC)

30·10 3

100·10 3

100·10 3

Utilization category

AC-7b AC-7c

Rated current Rated electrical Rated current Rated electrical

(A) life (Cycles) (A) life (Cycles)

10

10

10

10

22

30

Utilization category: AC-7a = Slightly inductive loads (cos ϕ=0.8)

AC-7b = Motor loads; (cos ϕ=0.45, I making

= 6xI breaking

)

AC-7c = Compensated electric discharge lamps (cos ϕ=0.9, C= 10 mF/A)

30·10 3

30·10 3

30·10 3

30·10 3

150·10 3

150·10 3

10

10

30·10 3

30·10 3

H 22 - Maximum DC1 breaking capacity - Type 22.32 / 22.34

H 22 - Maximum DC1 breaking capacity - Type 22.44 / 22.64

type 22.64

type 22.44

DC voltage (V) DC voltage (V)

When switching a resistive load (DC1) having voltage and current values under the curve, an electrical life of ≥ 100·10

3 can be expected.

In the case of DC13 loads, the connection of a diode in parallel with the load will permit a similar electrical life as for a DC1 load.

Note: the release time for the load will be increased.

Coil specifications

AC/DC version data (type 22.32)

Nominal voltage

U

N

V

12

24

48

60

120

(110...125)

230

(230...240 AC)

(220 DC)

Coil code

0.012

0.024

0.048

0.060

0.120

0.230

Operating range

U min

V

9.6

19.2

38.4

48

88

184 (AC)

176 (DC)

U max

V

13.2

26.4

52.8

66

138

264 (AC)

242 (DC)

Rated coil consumption

I

N at U

N

(AC) mA

165

83

42

33

16.5

8.7

AC/DC version data (type 22.44 / 22.64)

Nominal voltage

U

N

V

12

24

120

Coil code

0.012

0.024

0.120

Operating range

U min

V

10.2

20.4

102

U max

V

13.2

26.4

138

(110...125)

230

(230...240 AC)

0.230

196

264 (AC)

(220 DC)

242 (DC)

I

Rated coil consumption

N at U

N

(AC) mA

417

208

41

21

AC/DC version data (type 22.34)

Nominal voltage

U

N

V

12

24

48

60

120

(110...125)

230

(230...240 AC)

(220 DC)

Coil code

0.012

0.024

0.048

0.060

0.120

0.230

Operating range

U min

V

9.6

19.2

38.4

48

88

184 (AC)

176 (DC)

U max

V

13.2

26.4

52.8

66

138

264 (AC)

242 (DC)

R 22 - Coil operating range v ambient temperature

Rated coil consumption

I

N at U

N

(AC) mA

165

83

42

33

16.5

8.7

1 - Max. permitted coil voltage.

2 - Min. pick-up voltage with coil at ambient temperature.

6

Wiring diagrams

22 Series - Modular contactors 25 - 40 - 63 A

22

SERIES

Line and neutral switched Line only switched

Type 22.32

Line and neutral switched

Type 22.34

Type 22.34

Line only switched

Type 22.44 / 22.64

Type 22.44 / 22.64

7

22

SERIES

Outline drawings

Type 22.32

Screw terminal

22 Series - Modular contactors 25 - 40 - 63 A

Type 22.32 + 022.33 / 022.35

Screw terminal

Type 22.34

Screw terminal

Type 22.34 + 022.33 / 022.35

Screw terminal

Type 022.33 / 022.35

Screw terminal

Type 22.44 / 22.64

Screw terminal

8

22 Series - Modular contactors 25 - 40 - 63 A

Auxiliary module 022.33 / 022.35 for 22.32 and 22.34 only

022.33

022.35

22

SERIES

22.32 + 022.33 / 022.35

22.34 + 022.33 / 022.35

Contact specification

Contact configuration 2 NO

Conventional free air thermal current I th

Rated current AC15 (230 V)

A 6

VA 700

Electrical life at rated load cycles 30 x 10 3

Contact material AgNi

Short circuit protection

Rated conditional short circuit current kA 1

Back-up fuse

Terminals

Max. wire size

A 6 (gL/gG type)

Solid and stranded cable

Min. wire size mm 2 1 x 4 / 2 x 2.5

AWG 1 x 12 / 2 x 14 mm 2 1 x 0.2

Screw torque

Wire strip length

Power lost to the environment

without contact current with rated current

AWG 1 x 24

Nm 0.8

mm 9

W

W

0.5

Approvals (according to type)

NOTE: it is not possible to assembly the auxiliary module on 22.32.0.xxx.x4x0 (2 NC versions).

1 NO + 1 NC

6

700

30 x 10 3

AgNi

9

22

SERIES

Accessories

22 Series - Modular contactors 25 - 40 - 63 A

Adaptor for panel mounting (for 22.32 type), plastic, 17.5 mm wide

020.01

020.01

Adaptor for panel mounting (for 22.34 type), plastic, 35 mm wide

011.01

011.01

Sheet of marker tags, plastic, 72 tags, 6x12 mm 060.72

060.72

019.01

Identification tag, plastic, 1 tag, 17x25.5 mm

019.01

Separator for rail mounting, plastic, 3 mm wide

020.03

020.03

022.18

U

RO

P A

AN

P E A N

T E

PE

N T

RO

8-way jumper link for types 22.32, 17.5 mm wide

Rated values

022.18 (blue)

10 A - 250 V

022.26

U

RO

P E A N

P A

AN

T E

PE

N T

RO

6-way jumper link for types 22.34, 35 mm wide

Rated values

022.26 (blue)

10 A - 250 V

10

advertisement

Key Features

  • Continuous duty for the coil and contacts
  • AC/DC silent coil (with varistor protection)
  • Protective separation (reinforced insulation) between coil and contacts
  • Mechanical and LED indicators as standard
  • Auto-On-Off selector version available
  • AgNi and AgSnO2 contact versions available
  • Auxiliary contact module available, quick-assembly with the main contactor
  • 35 mm rail (EN 60715) mount
  • Compliant with EN 61095: 2009 and with EN 60947-4-1: 2009

Frequently Answers and Questions

What are the contact materials available for these contactors?
The contact materials available are AgNi and AgSnO2. AgNi contacts are intended for resistive and slightly inductive loads as well as for motor loads, while AgSnO2 contacts are intended for lamp loads and for high inrush current loads.
What are the different types of contact configurations available?
The contact configurations available include 2NO, 1NO + 1NC, 2NC, 4NO, 3NO + 1NC, and 2NO + 2NC.
What is the rated current for these contactors?
The rated current for these contactors varies depending on the model. The 22.32 contactors are rated for 25A, the 22.34 contactors are rated for 25A, the 22.44 contactors are rated for 40A, and the 22.64 contactors are rated for 63A.

Related manuals

Download PDF

advertisement