AGF Manufacturing 241T TESTanDRAIN® 2 in. NPT Bronze Test and Drain Sprinkler Valve Specification
AGF Manufacturing 241T is a sectional floor control test and drain valve with pressure gauge for systems requiring pressure relief valve. It provides the test and express drain functions for wet fire sprinkler systems on multi-story installations requiring pressure relief (NFPA 13 and NFPA 13R). The 241T is available in a full range of sizes (¾” to 2”) with NPT connections (BSPT available). The 241T is shipped with relief valve and bypass drain ports plugged to expedite pressure testing.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
Model 1011T
TEST
an
DRaIn ®
Sectional Floor Control Test and Drain Valve with Pressure
Gauge for Systems Requiring Pressure Relief Valve
Sizes:
¾" 1" 1¼" 1½" 2"
The AGF Model 1011T TEST an
DRaIn ® provides the test and express drain functions for wet fire sprinkler systems on multi-story installations requiring pressure relief (NFPA
13 and NFPA 13R). The Model 1011A features a Model 7000 Pressure Relief Valve with drain pipe, 3½" Model 7500 Pressure
Gauge and 3-Way Globe Valve.
The Model 1011T is available in a full range of sizes (¾" to 2") with NPT connections
(BSPT available). The Model 7000 Pressure
Relief Valve (UL/FM) features a flushing handle and a 175 PSI factory rating (other pressure ratings available).
• Complies with NFPA 13 Requirements
• Compact, Single-Handle Ball Valve
• Tamper-Resistant Test Orifice and Sight Glasses
• 300 PSI rated.
• Specifiable orifice sizes: ³⁄
8
" (2.8K), 7 ⁄
16
" (4.2K), ½" (5.6K), 17 ⁄
32
" (8.0K), 5 ⁄
8
" (11.2K, ELO), ¾" (14.0K, ESFR), and K25
• Relieves Excess System Pressure caused by Surges or Temperature Changes
• Includes Model 7500 Pressure Gauge and UL/FM Model 7600 Globe Valve
• Shipped with Relief Valve and Bypass Drain Ports Plugged to Expedite Pressure Testing
• Locking Kit Available
Repair kits are available for all TEST an
DRaIn ® valves. Kit includes: Adapter Gasket (1), Ball (1), Valve Seats (2),
Stem Packing (1), and Stem Washer (1). Valve and orifice size must be specified when ordering.
Note: It is important to note that the pressure rating of the relief valve indicates an operating range of pressure for both opening and closing of the valve.
Standard relief valves are required to oPeN in a range of pressure between 90% and 105% of their rating. the valves are required to CLoSe at a pressure above 80% of that rating. the relief valve should be installed where it is easily accessible for maintenance. Care should be taken that the relief valve CANNot be isolated from the system when the system is operational. A relief valve should NeVeR have a shutoff valve or a plug downstream of its outlet.
Reliability, Versatility, Code Compatibility
TESTANDRAIN is a registered trademark of AGF Manufacturing Inc.
SS-M1011T_V001 · 06/13
Model 1011T
TEST
an
DRaIn ®
Model 1011T 300 PSI Bronze Ball Valve, Model 7000 Pressure Relief Valve,
Model 7500 Pressure Gauge, and Model 7600 ¼" 3-Way Globe Valve
Dimensions
SIZE
¾"
1"
1 1 ⁄
4
"
1½"
2"
A
10 1 ⁄
4
"
(256 mm)
10 1 ⁄
4
"
(256 mm)
10 1 ⁄
2
"
(263 mm)
11 1 ⁄
2
"
(288 mm)
11 1 ⁄
2
"
(288 mm)
B
3 3 ⁄
8
"
(86 mm)
3 3 ⁄
8
"
(86 mm)
3 5 ⁄
8
"
(91 mm)
3 7 ⁄
8
"
(99 mm)
3 7 ⁄
8
"
(99 mm)
C
1 13 ⁄
16
"
(46 mm)
1 13 ⁄
16
"
(46 mm)
1 15 ⁄
16
"
(51 mm)
2 5 ⁄
8
"
(67 mm)
2 5 ⁄
8
"
(67 mm)
D
4 9 ⁄
16
"
(117 mm)
4 9 ⁄
16
"
(117 mm)
5 9 ⁄
16
"
(141 mm)
8 1 ⁄
4
"
(207 mm)
8 1 ⁄
4
"
(207 mm)
E
6 3 ⁄
8
"
(162.5 mm)
6 3 ⁄
8
"
(162.5 mm)
7 1 ⁄
2
"
(192 mm)
10 7 ⁄
8
"
(274 mm)
10 7 ⁄
8
"
(274 mm)
F
8 3 ⁄
4
"
(119 mm)
8 3 ⁄
4
"
(119 mm)
9"
(225 mm)
9 11 ⁄
16
"
(242 mm)
9 11 ⁄
16
"
(242 mm)
Model 1011T - Front View
F
TO
DRAIN
E
C
D
B
INLET
A
The Model 1011T provides the following…
From the 2013 Edition of NFPA 13
Chapter 8.16.2.4.1* Provisions shall be made to properly drain all parts of the system.
Chapter 8.16.2.4.2 Drain connections, interior sectional or floor control valve(s) –
& 8.16.2.4.3 shall be provided with a drain connection having a minimum size as shown in Table 8.16.2.4.2.
Chapter 8.16.2.4.4 Drains shall discharge outside or to a drain capable of handling the flow of the drain.
Chapter A.8.17.4.2 (Wet Pipe System) test connection is permitted to terminate into a drain capable of accepting full flow… using an approved sight test connection containing a smooth bore corrosion-resistant orifice giving a flow equivalent to one sprinkler…
Chapter 8.17.4.2.2 The test connection valve shall be accessible.
Chapter 8.17.4.2.4 shall be permitted to be installed in any location… downstream of the waterflow alarm.
Chapter 8.17.4.3.1 (Dry Pipe System) a trip test connection not less than 1" in diameter, terminating in a smooth bore corrosion-resistant orifice, to provide a flow equivalent to one sprinkler…
Chapter 8.17.4.3.2 The trip test connection… with a shutoff valve and plug not less
Chapter 7.1.2 than 1", at least one of which shall be brass.
- a wet pipe system shall be provided with a listed relief valve set to operate at 175 PSI or 10 PSI in excess of the maximum system pressure, whichever is greater.
Chapter 8.16.1.2.3* A listed relief valve of not less than ½" in size shall be provided on the discharge side of the pressure-reducing valve set to operate at a pressure not exceeding rated pressure of the system.
Chapter A.8.16.1.2.3 - consideration should be given to piping the discharge from the
(pressure relief) valve
Chapter 8.16.1.2.2 Pressure gauges shall be installed on the inlet and outlet sides of each pressure reducing valve.
Orifice Sizes
3 ⁄
8
", 7 ⁄
16
", ½", 17 ⁄
32
", 5 ⁄
8
" ELO*,
¾" ESFR*, and K25**
Materials
Handle ................ Steel
Stem ................... Rod Brass
Ball ...................... C.P. Brass
Body ................... Bronze
Valve Seat ........... Impregnated Teflon ®
Indicator Plate .... Steel
Relief Valve ......... Bronze
Bypass Fittings ... Brass
Bypass Tubing .... Nylobraid
Approvals
UL and ULC Listed:
(EX4019 & EX4533)
FM Approved
NYC-BSA No. 720-87-SM
USA Patent # 4741361 and Other Patents Pending
AGF Manufacturing Inc.
100 Quaker Lane, Malvern, PA 19355
Phone: 610-240-4900
Fax: 610-240-4906 www.testandrain.com
*Available on 1¼" to 2" size units only • **Available on 1½" and 2" size units only
Job Name:__________________________________
Architect: ___________________________________
Engineer: ___________________________________
Contractor: _________________________________
advertisement
Key Features
- Complies with NFPA 13 Requirements
- Compact, Single-Handle Ball Valve
- Tamper-Resistant Test Orifice and Sight Glasses
- 300 PSI rated
- Relieves Excess System Pressure caused by Surges or Temperature Changes
- Includes Model 7500 Pressure Gauge and UL/FM Model 7600 Globe Valve