MK Logic Plus Technical

MK Logic Plus Technical
TD1
Logic Plus Technical
WHITE
www.mkelectric.co.uk
Switchsocket Outlets
Standards and approvals
All Logic Plus 13A socket outlets comply with
BS 1363: Part 2: 1995.
Replacement fuses to the 3 gang socket outlets
comply with BS 1362: 1973.
Technical specification
Electrical
Voltage rating:
250V a.c.
Current rating:
13A per socket outlet
(except 3 gang which is 13 amp in total)
Terminal capacity:
Live, neutral & earth
3 x 2.5mm2
3 x 4mm2
2 x 6mm2 (standard)
(Dual earth terminals on list Nos.
K781 WHI, K2657 WHI, K2737 WHI, K2746 WHI, K2757
WHI)
Physical
Ambient operating temperature:
–5°C to +40°C
(not to exceed an average of more than 25°C in any 24
hour period)
IP rating:
IP2XD
Max. installation altitude:
2000 metres
Description
A range of socket outlets designed for ease of installation and having all the advantageous design
features of the Logic Plus range. The 2 gang sockets with outboard rockers are of particular value for use
by the infirm and partially sighted.
Non-standard clean earth sockets are for use on installations where restricted access is required and will
only accept MK LN647 13A non-standard plug with T-shaped earth pin. The sockets have two
independent earth terminals so that they can also be used for ‘clean earth’ installations. K2746 CE WHI
has two independent earth terminals for ‘clean earth’ installations.
K781 WHI, K2657 WHI, K2737 WHI, K2746 WHI and K2757 WHI are fitted with two earth terminals on
a common busbar to provide a double earth facility for use when installations are to comply with Section
607 of BS 7671, IEE Wiring Regulations.
The products can be quickly installed as replacement for existing 13 amp sockets or in a new installation.
Fuse carriers
(3 gang switchsocket only)
The fuse carrier is opened by a fast-acting, screwdriver-operated, worm-drive screw for ease of
replacement.
Round pin sockets
A range of round pin sockets is also available, switched and unswitched.
BOX TYPES
For a full range of corresponding products,
see pages 20–22 in the product selector.
Flush
Flush (for extra
wiring space)
Surface Insulated
Surface Metal
1 gang
861 ZIC
866 ZIC
K2140 WHI
K2211 ALM/K2213 ALM
2 gang
862 ZIC
886 ZIC
K2142 WHI
K2212 ALM/K2214 ALM
3 gang
K863 ZIC
Not available
K2153 WHI
Not available
Logic Plus Technical
TECHNICAL HOTLINE +44 (0)1268 563720
TD2
WHITE
Switchsocket Outlets
Features
●
Moulded ‘on’ indicator flash on switches
will not rub off – totally safe
●
Additional electrical safety from neutral
‘make first’, ‘break last’ feature
●
Optional neon indicators in the switch
rockers with 175° visibility in the horizontal
and vertical planes
●
Switch contacts with silver contacts on
both surfaces for good continuity
●
●
Unique 3 pin operated safety shutter
Only one size of screwdriver required for
installation
●
Printed terminal markings on grey rear
mouldings for clearer identification
●
●
Top access, angled terminals make wiring
easier and quicker
Dual earth terminals for high integrity
earthing on list Nos. K781 WHI,
K2657 WHI, K2737 WHI, K2746 WHI,
K2757 WHI
●
3mm switch contact gap
●
Backed out and captive terminal screws
●
‘Clean earth’ sockets available
●
Non-standard ‘clean earth’ sockets
available
●
Double pole switching
●
Choice of inboard or outboard positioned
rockers
Dimensions (mm)
Installation
Logic Plus socket outlets can be wall or bench
mounted. Do not mount or use as a trailing
socket or where they may be subject to excessive
moisture or dampness.
1 gang
86
30
2 gang switchsocket – view from rear
Top-facing, angled, backed-out terminals make
wiring easier and quicker.
86
60.3
17
2 gang
146
30
86
86
120.6
Cable management
146
30
120.6
17
3 gang
Logic Plus socket outlets can be mounted in a
variety of MK trunking systems.
206
32
86
fuse
180.9
19
17
TD3
Logic Plus Technical
WHITE
www.mkelectric.co.uk
Sentrysocket RCD Protected Switchsocket Outlet
Compliance with EC Directives,
Standards and approvals
All Sentrysockets comply with the following
EC Directives and are CE marked:
Low Voltage Directive (73/23/EEC)
Electromagnetic Compatibility Directive (89/336/EEC)
Sentrysocket RCD Single Sockets also comply with
the requirements of the following standards:
BS 7288: 1990 (1993)
BS 2011 Part 2.1 Db (Damp Heat - cyclic)
BS 2011 Part 2.1 Ka (Salt mist)
BS EN 50082-1
Sentrysocket RCD Double Sockets comply with BS EN 61543:
1996
Technical specification
Description
Sentrysocket provides a high level of protection against electrocution and gives further protection when
used with appliances vulnerable to insulation damage, particularly when they are in damp environments
or outdoors. Sentrysocket is not suitable for mounting in damp environments or outdoors.
Sentrysocket, incorporating an RCD, is part of a complete range of fixed and portable wiring devices and
circuit protection devices suitable for use in domestic, commercial and industrial applications.
Electrical
Rated Voltage:
240V a.c., 50 or 60Hz
Current rating:
13A resistive
Rated tripping current
30mA and 10mA versions
Terminal capacity:
3 x 4mm2
Physical
Ambient operating temperature:
–5°C to +40°C
IP rating:
IP2XD
Max. installation altitude:
2000 metres
Sentrysockets are only suitable for use in TN-S system
where the Supply Neutral Connection is connected to the
Supply Earth.
They are not suitable for connection across two lines of a
127V line to Neutral Voltage System.
Installation
Active control circuits
Incorporate a ‘Re-set’ mechanism and are mains failure sensitive, ie they will function under all the
normal conditions expected of an RCD, but will also trip in the event of a power cut or a sudden, dramatic
reduction in mains voltage. This makes them ideal for use where it would be hazardous for equipment
to suddenly energise after return of mains power, such as use with rotating machinery and heat
developing apparatus.
Passive control circuits
Incorporate a ‘Stay-set’ mechanism and is mains failure proof, ie it will function under all the normal
conditions expected of an RCD and will not trip in the event of a power cut. This makes it suitable for use
with freezers or in inaccessible or unmanned locations.
Features
●
Suitable for most residential, commercial
and light industrial applications
●
Active and passive control circuit
applications
●
Comply fully with current Wiring
Regulations
●
Double pole switching
●
Flexible and versatile in use
●
Ideal for use with equipment subject to
wet weather or high humidity
●
Part of a complete range of MK circuit
protection devices
●
They are pulsating DC sensitive for residual
current
Dimensions (mm)
Flush mounting steel wall box
Single socket
It should be noted that some of the conduit
entries may be restricted, depending upon their
positions and the depth of box used.
Double socket
146
6
146
24
8
sentrysocket
rcd protected
Cable management
Sentrysockets can be mounted in a variety of MK
trunking systems.
T
86
see page 21 in the product selector.
rcd protected
red
on
86
on
active control
device trips with
loss of mains
tripping current
10mA
120.6
For a full range of corresponding products,
Flag below Reset (R) button.
Red : ON Black: OFF
ALWAYS TEST BEFORE USE
Press Test (T) button, Red flag should
disappear. If it does not, do not use.
Press Reset (R) after testing.
sentrysocket
test before use
press button - T
white
off
(tripped)
T
R
14
120.6
14
22
Logic Plus Technical
TECHNICAL HOTLINE +44 (0)1268 563720
TD4
WHITE
Filtered Switchsocket Outlets
Technical specification
Electrical
Current rating:
13A maximum total for 2 sockets
Voltage rating:
250V a.c. 50Hz
Earth leakage:
0.5 mA
Suppression:
150 kHz – 30 MHz (transients)
Description
A range of sockets in the Logic Plus style, designed to combat interference to or data losses on sensitive
electrical products and systems due to mains borne voltage spikes and RFI.
Maximum energy absorption:
140 Joules L – N
140 Joules L – E
Such systems include:
Terminal capacity:
K1826 and K1816, 2 x 6mm2
3 x 4mm2, 3 x 2.5mm2, 3 x 1.5mm2
●
Computer or microprocessor based equipment
●
Telecommunications systems
Physical
●
Electronic measurement equipment
Operating temperature:
–5°C to +40°C (not to exceed an average of more than
25°C in any 24 hour period)
●
Cash registers
●
Audio visual and hi-fi equipment
Thermal overload:
The K1826 filter socket incorporates a thermal overload
device in the RFI filter section. Overload current causes
temperature rise, resulting in automatic ‘trip out’. The
overload device will re-set as the temperature falls.
These products can be quickly installed as replacements for existing twin 13 amp sockets or in a new
installation.
Two earth terminals on each product enable use in installations complying with Section 607 (High
Integrity Earthing) of BS 7671 IEE Wiring Regulations.
IP rating:
IP2XD
Filter cassettes
Max. installation altitude:
2000 metres
Filter cassettes are supplied with sockets and have an LED which shows green under normal conditions
but will turn red or extinguish when a replacement cassette (K1800) is required. An alarm will also beep
at 5 second intervals to indicate replacement necessity. It can be de-activated if required.
Features
Cable management
Logic Plus socket outlets can be mounted in a
variety of MK trunking systems.
Dimensions (mm)
146
30
●
Moulded ‘on’ indicator flash on switches
will not rub off – totally safe
●
3 pin operated safety shutter
●
Printed terminal markings on grey rear
mouldings for clearer identification
●
Reduces risk of damage to equipment and
down time
●
●
86
●
120.6
17
For a full range of corresponding products,
see page 21 in the product selector.
Reduces risk of data loss
2 way filtering – into appliance and back
into mains supply
Double pole switches
●
Twin earth terminals for use in installations
complying with Section 607 of BS 7671
IEE Wiring Regulations
●
Clearly visible LED on filter cassette,
changes from green to red when
replacement required
●
Simple replacement of cassettes
●
10 year guarantee (except filter cassette)
●
3mm switch contact gap
●
Backed out and captive terminal screws
TD5
Logic Plus Technical
WHITE
www.mkelectric.co.uk
Round Pin Socket Outlets
Standards and approvals
Round pin socket outlets comply with BS 546: 1950.
Technical specification
Electrical
Voltage rating:
250V a.c.
Terminal capacities:
2 amp sockets (K770):
7 x 1mm2
4 x 1.5mm2
2 x 2.5mm2
1 x 4mm2
5 amp sockets (K771, K2891):
3 x 2.5mm2
2 x 4mm2
2 x 6mm2 (stranded)
15 amp sockets (K772, K2893, K2493):
3 x 2.5mm2
3 x 4mm2
2 x 6mm2 (stranded)
Physical
Ambient operating temperature:
–5°C to +40°C
(not to exceed an average of more than 25°C in any 24
hour period)
IP rating:
IP2XD
Max. installation altitude:
2000 metres
Installation
Description
A range of socket outlets designed for ease of installation and having all the advantages and design
features of the Logic Plus range. These products can be quickly installed as replacements for existing
socket outlets or in new installations.
Features
●
Top access terminals make wiring easier
and quicker
●
Additional electrical safety from neutral
“make first”, “break last” feature on
switched sockets
●
Integral ON indicator on switches will not
rub off – totally safe
●
Optional neon indicator on 15A switched
socket rockers with 175° visibility in the
horizontal and vertical planes
Switch contacts with silver contact points
on both surfaces for good continuity
●
5A and 15A sockets contain a unique
3 pin operated safety shutter
●
3mm switch contact gap
●
●
Double pole switching
Printed terminal markings on grey rear
mouldings for clearer identification
●
Terminal screws backed out
●
2A socket shuttered
●
Dimensions (mm)
Logic Plus socket outlets can be wall or bench
mounted – do not mount or use as a trailing
socket or where they may be subjected to
excessive moisture or dampness.
Cable management
86
86
Logic Plus socket outlets can be mounted in a
variety of MK trunking systems.
60.2
Depth
2 Amp sockets: 12mm
5 Amp sockets: 21mm
15 Amp sockets: 23mm
BOX TYPES
Flush for extra
wiring space
Surface Insulated
Surface Metal
5A and 15A 861 ZIC
866 ZIC
K2140 WHI
K2211 ALM
K2213 ALM
2A
866 ZIC
861 ZIC
K2140 WHI
K2211 ALM
K2213 ALM
Flush
For a full range of corresponding products,
see page 22 in the product selector.
3995 ZIC
Logic Plus Technical
TECHNICAL HOTLINE +44 (0)1268 563720
TD6
WHITE
NON UK Socket Outlets
Standards and approvals
15A AMERICAN
15A American sockets comply with SSA: 444: 1985
16A Universal sockets comply with BS.5733: 1995
16A 2P+E German sockets comply with IEC 60884-1: 2002
Technical specification
146
86
Electrical
9
15A American
Voltage rating:
127V a.c.
86
86
Current rating:
15A
Terminal capacity:
Live, neutral & earth
3 x 2.5mm2
2 x 4mm2
1 x 6mm2 (stranded)
All dimensions
in mm
120.6
60.3
15
BOX TYPES
Max. installation altitude:
2000 metres
Flush
Flush (for extra
wiring space)
Surface
16A Universal Socket
1 gang
861 ZIC
866 ZIC
K2140 WHI
Voltage rating
125/250V
2 gang
862 ZIC
886 ZIC
K2142 WHI
Current rating:
16A
86
16A UNIVERSAL
9
Terminal capacity
2 x 6mm2 (stranded)
3 x 4mm2 3 x 2.5mm2
86
16A 2P+E German Socket
All dimensions
in mm
Voltage rating:
250V a.c.
Current rating:
16A
Terminal capacity:
Live, neutral & earth
4 x 1.5mm2
2 x 2.5mm2
1 x 4mm2
60.3
Description
21
The universal socket does not incorporate an earth contact.
Therefore, appliances needing earth connection (class 1
equipment) must NOT be used with this socket. The socket is
intended for use with BS, USA and CEE standard plugs.
BOX TYPES
Flush
Surface
861 ZIC
K2140 WHI
Physical (all NON UK outlets)
Ambient operating temperature:
–5°C to +40°C
(not to exceed an average of more than 25°C in any 24
hour period)
16A 2P+E GERMAN
BOX TYPES
Flush
IP rating:
IP2XD
2 gang 886 ZIC K2172 WHI
Max. installation altitude:
2000 metres
146
86
9
Note: 16A 2P+E
German Outlet:
These products are
not suitable for
25mm deep boxes.
86
86
All dimensions
in mm
For a full range of corresponding products,
see pages 22–23 in the product selector.
Surface
1 gang 866 ZIC K2031 WHI
60.3
120.6
30
TD7
Logic Plus Technical
WHITE
www.mkelectric.co.uk
Three Pole Fan Isolators
Standards and approvals
Comply with BS EN 60947: 1992
Technical specification
Electrical
Voltage rating:
250V a.c. 50Hz
Current rating:
10 amps
Terminal capacity:
4 x 1mm2
4 x 1.5mm2
3 x 2.5mm2
2 x 4mm2
1 x 6mm2
Description
The MK Three Pole Fan Isolator provides a safe and simple method of isolating mechanical fan units and
is particularly useful in bathrooms, toilets, storerooms and basements where there is little or no natural
light.
Classifications
For example, timer controlled fans are often linked into the lighting circuit for energy saving and
convenience. In such an installation there is often a need for the lighting circuit to remain live to provide
light whilst the fan unit is externally isolated so that routine maintenance and repairs can be carried out
in complete safety.
Method of operation: Stored energy operation
Suitability for isolation: Suitable for isolation
The fan isolator can be used as a double pole or triple pole isolator. In addition it includes a clear on/off
indicator and the frontplate features a fan isolator symbol for easy circuit identification.
Contact gap:
3mm switch contact gap
Ratings
Utilisation category
AC23B
Rated operational voltage (Ue)
250V
Conventional free air thermal
current (Ith)
10A
Rated frequency
50Hz
Rated making capacity
100A rms
Rated breaking capacity
80A rms
Rated conditional short-circuit
current
6000A rms
(with supply side protective device GEC NIT 16
BS88: part 2: 1988 16A 550VAC utilisation
category gG 80KA breaking capacity fuse links.)
Dimensions (mm)
85
BOX TYPES
9
on
85
off
isolator
Physical
Operating temperature:
–5°C to +40°C)
IP rating:
IP4X
Max. installation altitude:
2000 metres
Features
●
Switchlock list no. K4858 is available to
allow the isolator to be locked in the
disconnected position to facilitate fan
maintenance
For a full range of corresponding products,
see page 23 in the product selector.
60.3
12
Flush
Surface
3995 ZIC
K2160 WHI
Logic Plus Technical
TECHNICAL HOTLINE +44 (0)1268 563720
Three Pole Fan Isolators
Wiring diagrams
Two pole switching for fan units without timers
N
L
TOP
Supply
L1
L1
L2
L2
N
N
To Fan Unit without Timer
(see Fan Unit Intructions)
Rear view of
Fan Isolator
N
L (switched)
N
L
TOP
Supply
L1
L1
L2
L2
N
N
To Fan Unit without Timer
(see Fan Unit Intructions)
Rear view of
Fan Isolator
N
L (switched)
Three pole switching for fan units incorporating timers
N
L
Supply
TOP
L1
L1
L2
L2
N
N
To Fan Unit with Timer
(see Fan Unit Intructions)
Rear view of
Fan Isolator
N
L (unswitched)
L (switched)
N
L
Supply
TOP
L1
L1
Rear view of
Fan Isolator
L2
L2
N
N
To Fan Unit with Timer
(see Fan Unit Intructions)
N
L (unswitched)
L (switched)
WHITE
TD8
TD9
Logic Plus Technical
WHITE
www.mkelectric.co.uk
Shaver Socket Outlets
Standards and approvals
Shaver socket outlets comply with
BS 4573: 1970 and IEC 884-1: 1994.
Plug pin apertures, and engagement face dimensions comply
with BS 4573: 1970.
Technical specification
Electrical
Voltage rating:
200-250V a.c. Input
Maximum load:
200 mA (internal thermister trip current)
Terminal capacities:
Each terminal will accommodate 1 x 4mm2,
or 2 x 2.5mm2, 3 x 1.5 solid conductors
Physical
Ambient operating temperature:
–5°C to +40°C
Description
Designed for ease of installation and having many of the advantageous features of the Logic Plus range.
The shaver socket outlet accommodates the following plugs:
British 5mm dia pins on 16.6mm pitch (230V socket) to BS 4573: 1970.
European 4mm dia pins on 17 to 19mm pitch (230V socket) to IEC 83: 1975 Standard C5.
IP rating:
IP2XD
Australian 6.5 x 1.6 flat blades each set at 30° to the vertical on a nominal pitch of 13.7mm (230V socket)
AS C112: 1964.
Max. installation altitude:
2000 metres
The fuse carrier is captive and opened by a fast acting, screwdriver operated worm drive screw for ease
of replacement.
Installation
Features
Shaver socket outlets may be wall or bench
mounted.
●
Top access terminals make wiring quicker
and easier
●
Printed terminal markings on grey rear
mouldings for clearer identification
This shaver socket must not be used in
bathrooms and washrooms. Non-isolated, fused,
shaver socket outlets must never be installed in
any location subject to splashes, condensation or
damp conditions.
●
Only one size of screwdriver required for
installation
●
Front plate fixing screws retained on rear
case moulding
●
Terminal screws supplied ‘backed out’ and
held captive within the terminal moulding
For installation in any other room where a wash
basin or shower cubicle is installed then refer to
the current IEE wiring regulations.
Dimensions (mm)
86
9
Cable management
Logic Plus socket outlets can be mounted in a
variety of MK trunking systems.
shavers only
86
200 - 250V ac
fuse
60.3
For a full range of corresponding products,
see page 23 in the product selector.
20
Logic Plus Technical
TECHNICAL HOTLINE +44 (0)1268 563720
TD10
WHITE
Shaver Supply Units
Standards and approvals
Shaver supply units comply with BS 61558-2-5: 1998
Accommodates plugs as follows:
●
British 5mm dia pins on 16.6mm pitch (230V socket) to BS
4573: 1970.
●
European 4mm dia pins on 17 to 19mm pitch (230V socket) to
IEC 83: 1975 Standard C5.
●
Australian 6.5 x 1.6 flat blades each set at 30° to the vertical
on a nominal pitch of 13.7mm (230V socket) AS C112: 1964.
●
American 6.6 x 1.6 flat horizontal blades on 12.7mm pitch
(115V socket) to ANSI C73.10.
Technical specification
Electrical
Voltage rating:
K701: 230V a.c. Input (will operate at 220-250V a.c.)
K706: 127V a.c. Input (will operate at 110-130V a.c.)
230V or 115V nominal outputs
Current rating:
K701: 200mA max. (internal thermister trip current)
K706: 400mA max. (internal thermister trip current)
Maximum load:
20VA
No load voltage < 275V
Description
Designed for ease of installation and having many of the advantageous design features of the Logic Plus
range.
May be used in bathrooms and washrooms – must only be installed in accordance with the current IEE
Wiring Regulations BS 7671: 1992: Amendment 3.
Features
Terminal capacities:
Each terminal will accommodate 1 x 4mm2 or
2 x 2.5mm2 solid conductors*
●
Top access terminals make wiring quicker
and easier
●
Terminal screws supplied ‘backed out’ and
held captive within the terminal moulding
Physical
●
Automatic primary supply switching on
insertion of plug
●
Ambient operating temperature:
–5°C to +40°C
Printed terminal markings on grey rear
mouldings for clearer identification
●
Choice of 230V or 115V output socket
positions
●
IP rating:
IP41 (In Zone 2 if fixed where direct spray from showers is
unlikely)
Front plate fixing screws retained on rear
case moulding
●
Safety interlocked shutters to prevent
insertion of two plugs simultaneously
●
Integral over current device to protect
transformer
Max. installation altitude:
2000 metres
●
Only one size of screwdriver required for
installation
*The design of this unit means that on no load the
transformer output is allowed to be as high as 275V. This
means that rechargeable shavers intended for use on the
continent may be damaged by the inrush current created
by this higher voltage. Rechargeable shavers with a wide
range of input voltage should be recharged at 115V.
Shavers manufactured for the UK are designed to be used
with a transformer unit. Loads in excess of 20VA may
cause the solid state overload to operate before shaving is
completed. This is to protect the transformer.
Installation
Dimensions (mm)
Shaver supply unit should be wall mounted.
86
Wiring
9
An installation instruction leaflet is available.
List no. 44994 PL.
115V
230V
146
shavers only
35
For a full range of corresponding products,
see page 23 in the product selector.
Logic Plus Technical
TD11
WHITE
www.mkelectric.co.uk
Connection Units, 20A Switches and Flex Outlets
Standards and approvals
All Logic Plus connection units comply with
BS 1363: Part 4: 1995.
The 20A DP switch complies with BS EN 60669-1: 2000
The flex outlet plate complies with BS 5733: 1995.
Fuses are to BS 1362.
Technical specification
Electrical
Voltage rating:
250V a.c.
Current rating:
Connection units – 13 amp
DP switches – 20 amp
Flex outlets – 20 amp
Terminal capacity:
Supply terminal:
2 x 6mm2 stranded
2 x 4mm2
3 x 2.5mm2
Description
Load terminals:
2 x 6mm2 stranded
2 x 4mm2
3 x 2.5mm2
A range of 13A fused connection units and 20A DP switches designed for the connection of refrigerators,
water heaters, central heating boilers and other fixed appliances.
Flex outlet/cord grip capacities:
Connection units:
min: 2 core, 0.5mm
max: 3 core, 1.5mm
20 amp DP switches &
flex outlet plate
min: 3 core, 1.5mm
max: 3 core, 2.5mm
Physical
Ambient operating temperature:
–5°C to +40°C
(not to exceed an average of more than 25°C in any 24
hour period)
IP rating:
With flex outlet:
IP2XD
Without flex outlet: IP4X
Max. installation altitude:
2000 metres
Installation
Logic Plus connection units and 20A cable outlets
and switches can be wall or bench mounted. Do
not use on a trailing lead.
The ranges are designed for ease of installation and have the advantageous design features of the Logic
Plus range.
Neon indicators
Neon indicators can be included in the rockers of the switched connection units. In the case of
unswitched units, they can be located centrally and uppermost on the face plate. Neon indicators are
integrally wired into the product and do not require separate connection when installing.
The design gives 175° visibility in the horizontal and vertical planes.
Fuse carriers
These are captive and are opened by a fast acting, screwdriver operated worm drive for ease of
replacement.
A tamper-proof version is also available.
Fuse carriers can be locked open using a padlock, List No. K2000.
Flex outlets
Bottom outlet types are supplied with blanking plug allowing use where the bottom outlet is not
required. Spare blanking plugs are available.
The products are equipped with very strong, push-fit nylon cord grips making installation safe, quick and
easy.
Flex outlet plate
An unfused flex outlet with cord grip plate and 3 pairs of terminals.
Wiring
Products must be installed in accordance with
current IEE Regulations.
Cable Management
Logic Plus connection units and DP switches can
be mounted in a variety of MK trunking systems.
For a full range of corresponding products,
see page 24 in the product selector.
Logic Plus Technical
TECHNICAL HOTLINE +44 (0)1268 563720
TD12
WHITE
Connection Units, 20A Switches and Flex Outlets
Features
●
Optional indicators in the switch rockers
with 175° visibility in the horizontal and
vertical planes
●
Worm-drive operated fuse carriers for
additional security (tamper-proof version
available)
●
Fuse carrier lockable in open position
●
All supply and load cables can be cut
and stripped to the same length
●
Integrally wired indicators save
installation time
●
Push-fit cord grips, for safer, quicker
installation
●
Angled, top mounted terminal screws
simplify wiring
●
Moulded ‘on’ indicator flash on switches
cannot rub off – totally safe
●
Captive fuse carrier
●
Additional electrical safety from neutral
‘make first’, ‘break last’ feature
●
Secure cable and flexible cord
connection
●
All terminal and fixing screws operated
by one-size (4mm) screwdriver
●
Backed out and captive terminal screws
Dimensions (mm)
86
15
86
86
fuse
fuse
11 dia
86
19
60.3
9
60.3
13
13
Products with front flex outlet
Products with flex outlet in base
and thick frontplate
Supply and load cable cords cut
and stripped to same length
Bottom outlet and
cord grip
Front outlet cord grip
Lockable fuse carrier
Blanking plug for
bottom outlet
Note: These switches are not recommended for
switching large banks of PCs
PLEASE NOTE THAT THE TERMINAL LAYOUT OF THE FLEX OUTLET, K1090, IS DIFFERENT
TO THAT SHOWN ABOVE. ALL OTHER PRODUCTS ARE AS INDICATED.
TD13
Logic Plus Technical
WHITE
www.mkelectric.co.uk
High Current Switches and Cooker Control Units
Standards and approvals
All DP switches in the range conform to
BS 3676: Part 1: 1989 (1994)
All Cooker Control Units in the range conform to BS 4177: 1992
(1993). ‘Specification for cooker control units’.
Cooker Connection Unit conforms to BS 5733: 1995
Technical specification
Electrical
Voltage rating:
250V a.c.
Current:
32A/45A resistive
Switch:
3mm contact gap
Double pole operation –
except socket switch on CCUs
Terminal capacity, 45A Switches and CCUs:
4 x 4mm2
3 x 6mm2
1 x 16mm2
Description
A range of switches and cooker control units harmonising with the Logic Plus style, suitable for the
switching of all domestic, commercial and industrial appliances where higher current ratings are
required, i.e. cookers, heaters, commercial refrigeration units etc. Metal units are particularly suitable for
refurbishment projects.
Terminal capacity, 32A Switch:
3 x 2.5mm2
2 x 4mm2
1 x 6mm2
BOX DEPTHS
Physical
Ambient operating temperature:
–5°C to +40°C
(not to exceed an average of more than 25°C in any 24
hour period)
List No.
Max. Cable Size
Flush
Surface
K5105 WHI
6mm2
10mm2
35mm
46mm
30mm
40mm
K5205 WHI
6mm2
10mm2
35mm
46mm
40mm
40mm
Switches
K5215 WHI
IP rating:
IP2XD (K5061, K5060, K5041, K5040, K5001, K5011)
IP4X (K5105, K215, K5205, K5215CK, K5215SH, K5230,
K5011)
6mm2
10mm2
35mm
47mm
40mm
40mm
K5230 WHI
10mm2
–
Supplied with box
K5012 WHI
2
55mm
–
Max. installation altitude:
2000 metres
Cooker control units
Features
●
Positive switch action
●
Positive double pole switching
●
Toggle action switches
●
Metal front plates available
●
Replaceable neon indicators
●
Wide product choice
10mm
K5040 WHI
10mm2
–
Supplied with box
K5041 WHI
2
10mm
–
Supplied with box
K5060 WHI
6mm2
10mm2
35mm
47mm
–
–
K5061 WHI
6mm2
10mm2
35mm
47mm
–
–
K5001 WHI
10mm2
–
Supplied with box
K5011 WHI
2
55mm
–
10mm
BOX REFERENCES
Flush
Note: These switches are not recommended for
switching large banks of PCs
Surface
Box depth
1 gang
2 gang
1 gang
2 gang
30
–
–
K2140 WHI
–
35
886 ZIC
886 ZIC
–
–
40
–
–
K2301 WHI
K2172 WHI
46
877 ZIC
–
–
–
For a full range of corresponding products,
47
–
878 ZIC
–
–
see pages 25–26 in the product selector.
55
5120 ALM (Cooker) –
–
Logic Plus Technical
TECHNICAL HOTLINE +44 (0)1268 563720
WHITE
High Current Switches and Cooker Control Units
Dimensions (mm)
12
86
13
146
off
off
86
off
86
on
on
on
cooker
socket
60.3
120.6
K5105
K5061 or K5060 (without pilot lights)
146
19
86
off
57
off
89
86
146
off
120.6
on
on
cooker
socket
on
120.6
K5041 or K5040 (without pilot lights)
K5215 or
K5205 without pilot light
K5215CK printed ‘cooker’
K5215SH printed ‘shower’
49
87
148
off
143
120.6
on
K5230
off
on
cooker
on
socket
105
K5001
19
166
off
off
on
cooker
on
socket
179
K5011
off
156
60
105
19
166
off
179
133
on
K5012
TD14
TD15
Logic Plus Technical
WHITE
www.mkelectric.co.uk
Plateswitches
Standards and approvals
All Logic Plus plateswitches comply with BS EN 60669-1: 2000 or
BS 3676: Part 1, 1989.
Technical specification
Electrical
Voltage rating:
250V a.c. 50Hz
Current rating:
10 amps – no derating when used on fluorescent
or inductive loads
20 amps – no derating when used on fluorescent
or inductive loads
Terminal capacity:
All products except K4870/71/72
4 x 1mm2
4 x 1.5mm2
3 x 2.5mm2
2 x 4mm2
1 x 6mm2
For products K4870/71/72
4 x 1mm2
4 x 1.5mm2
2 x 2.5mm2
1 x 4mm2
Description
Logic Plus plateswitches are designed to blend in with the decor, whilst complementing a wide range of
other Logic Plus accessories. They are designed for easy installation in plaster depth boxes and are
suitable for controlling lighting circuits in domestic, commercial and industrial applications.
Neon locator
Contact gap:
3mm switch contact gap
A textured, polycarbonate moulding allowing the glow of the neon to be seen at almost any angle.
Designed to complement the Logic Plus 1, 2, or 3 gang plateswitches.
Physical
It is easy to install in existing locations. For 3 gang applications using a 25mm deep box simplifies wiring.
Operating temperature:
–5°C to +40°C)
Features
IP rating:
IP2XD
●
Two way switches can be wired as one
or two way
Max. installation altitude:
2000 metres
●
All products clearly printed with
BS Nos., ratings, etc
Operational testing (all plateswitches):
tested to 100,000 operations for mechanical life
tested to 30,000 operations at 10 amp rating
tested to 10,000 operations at 20 amp rating
●
Matching Grid switches available in
10 or 20A ratings
●
3mm switch contact gap
●
Positive switch action
●
Top access, backed out and captive
terminal screws
●
Neon locator available making switch
easy to find in darkened rooms
Cable Management
Logic Plus plateswitches can be mounted in a
variety of MK trunking systems.
For a full range of corresponding products,
see pages 27–28 in the product selector.
Logic Plus Technical
TECHNICAL HOTLINE +44 (0)1268 563720
TD16
WHITE
Plateswitches
Dimensions (mm)
Wiring Diagrams
1 gang
2 gang
85
3 gang
85
One-way switching
85
Common
85
85
85
1
L
N
60.3
60.3
60.3
85
85
85
Lamp/s
12
Two-way switching – 2 wire control
Common
85
85
85
60.3
60.3
4 gang
60.3
2
1
Lamp/s
12
Dotted lines show alternative switch positions
Two-way switching plus intermediate switching
– 2 wire control
6 gang
146
2 Two-way switches
1
L
N
Common
146
Common
85
85
2
L
N
Two-way
1 switch
2
1
Common
2
Intermediate
1 switch
Two-way
switch
1
2
Lamp/s
120.6
120.6
Dotted lines show alternative switch positions
12
Two-way switching – 3 wire control
1 gang
architrave
2 gang
architrave
32
Common
32
1
146
120.6
60.3
85
L
N
Common
2 Two-way switches
1
2
SW.L
Lamp/s
Dotted lines show alternative switch positions
12
Two-way switching plus intermediate switching
– 3 wire control
12
Common
Sectional drawings show the furthest projections from the back of the
frontplate (wall surface).
L
N
1
Two-way
2 switch
2
1
2
Intermediate
1 switch
Common
1
2
Two-way
switch
SW.L
Lamp/s
Dotted lines show alternative switch positions
N.B. Terminal positions may alter. The above diagrams are to
show wiring layout.
TD17
Logic Plus Technical
WHITE
www.mkelectric.co.uk
Dimmer Switches
Standards and approvals
All CE marked Logic Plus dimmer switches comply with the EC
Low Voltage Directive: 73/23/EEC,
Electromagnetic Compatibility Directive 89/336/EEC
They also comply with BS EN 60669-2-1
and BS EN 55015
Non-UK dimmer switches conform to the relevant parts of BS
5518.
Technical specification
Description
Electrical
Mains Supply Voltage:
230V a.c. (Nominal)
220V a.c. (Nominal, Non-UK)
127V a.c. (Nominal, Non-UK)
Mains Supply Voltage Range:
216V a.c. to 253V a.c.
200V a.c. to 250V a.c
120V a.c. to 134V a.c.
Mains Supply Frequency:
50Hz ±3Hz
60Hz ±3Hz
Type of Loads:
Standard Dimmers:
Fused GLS Tungsten Filament lamps only to BS EN 60064:
1996 and BS EN 60432-1: 2000,
rated at 230/240V
Low Voltage Dimmers:
Fused GLS Tungsten Filament lamps to BS EN 60064: 1996
and BS EN 60432-1,2 rated at 230/240V. Dimmable wire
wound or electronic Low Voltage Transformers of good
quality. Can also be used with good quality mains voltage
halogen lamps incorporating GU10 bases. Please check
with lamp manufacturer to determine suitability.
Note: Transformer must be suitable for dimming using
phase delay (leading edge) and NOT only phase cut
(trailing edge) type of dimmers.
Warning: These dimmer switches are not suitable for use
with Fluorescent Lamps or Energy Saving Lamps.
Physical
MK Dimmer Switches fall into three categories:
1) Standard Dimmer Switches
2) Intelligent Dimmer Switches
3) Non-UK Dimmer Switches
Standard Dimmer Switches
Dimmer Switches belonging to this category employ simpler electronic circuitry and the CE marked
products make use of thermal switches to conform to the very stringent requirements of the Standard
BS EN60669-2-1, for overload protection. They are only suitable for use with normal tungsten filament
lamps with internal fuses, conforming to BS EN 60064: 1996 and BS EN 60432-1 Standards and do not
have any added features, e.g. soft start, ability to control dimmable transformers for low voltage, etc.
Standard Dimmer Switches are not suitable for use with transformers for Low Voltage
Lighting or Fluorescent Loads, including Energy Saving Lamps.
Intelligent Dimmer Switches
Dimmer Switches belonging to this category, employ the latest, state of the art, micro-controller based
electronic circuitry and use current sensing to compute the load conditions. These products show
progressive reaction to overload conditions, depending on the extent of overload as shown in the table
below. List numbers belonging to this category are identified by the suffix letters LV, e.g. K1501 WHI LV.
All MK Intelligent Dimmer Switches employ one pole change over switches to facilitate two way
switching.
MK Intelligent Dimmer Switches are not suitable for use with Fluorescent Loads, including
Energy Saving Lamps.
Only one Dimmer Switch can be used in a two-way switching circuit.
OVERLOAD REACTION
Case
Approximate load
on the dimmer as
a percentage of its
maximum load
Power output to load when dimmer control
is set to maximum
1
Up to 125%
Load will receive maximum power continuously.
2
>125% to 150%
Output to load will be reduced to 50% of the maximum
after a delay of approximately 20 seconds after switch on.
3
>150% to 200%
Output to load will be reduced to the minimum setting of
the dimmer after a delay of approximately 20 seconds after
switch on.
4
>200%
Output will be disabled (load will be switched off) almost
instantaneously after switch on.
Operating temperature:
0°C to +40°C)
IP rating:
IP2XD
Max. installation altitude:
2000 metres
Non-UK Dimmer Switches
For a full range of corresponding products,
see pages 28–29 in the product selector.
Dimmer switches belonging to this category only conform to the relevant parts of BS 5518, without
conforming to BS 800. Loads suitable for use with standard dimmer switches above are also suitable for
use with this category of dimmer switch.
Logic Plus Technical
TECHNICAL HOTLINE +44 (0)1268 563720
TD18
WHITE
Dimmer Switches
Features
Dimensions (mm)
Intelligent Dimmer Switches incorporate the following advanced
features
●
Suitable for dimming Low Voltage Halogen lamps via good quality,
fully dimmable electronic or wire-wound transformers
●
Can be used with good quality mains voltage halogen lamps
incorporating GU10 bases. Please check with lamp manufacturer to
determine suitability
●
Unidirectional current sensing.
While being used with wire-wound transformers for low voltage
lighting, these dimmer switches continuously monitor the drive
conditions to the transformers, which require essentially, bidirectional a.c. supply at their input terminals. If, due to some fault
condition, the supply to the wire-wound transformer is detected to
be unidirectional, which could result in over-heating and/or
damaging the transformer, the dimmer switches’ circuitry
automatically stops supplying the transformer after a few cycles of
detected unidirectional supply
●
Suitable only for use with fused GLS Tungsten Filament lamps to BS
EN 60064 and BS EN 60432-1
●
One way dimmer switches incorporate manual soft start
●
Incorporate thermal switches for protection against overload
28
19
86
16
60.3
18
INTELLIGENT DIMMER SWITCHES
Soft Start, which gradually increases the light output from the load
over 1 to 3 seconds after switch on. The Soft Start feature is also
particularly beneficial when used to dim Mains Voltage Tungsten
Halogen lamps which have inherent very high inrush current at
switch on
Standard Dimmer Switches
●
86
1 gang single
dimmer
Rating
Max No. of Transformers
(total rating of all
transformers must not
exceed maximum VA
rating of dimmer)
40-300W (LV and mains voltage
halogen rating 40-240W/VA)
4
1 gang double 2 x 40-300W (LV and mains voltage
dimmer
halogen rating 2 x 40-240W/VA)
4 per dimmer
1 gang single
dimmer
5
60-500W (LV and mains voltage
halogen 60-400W/VA)
One-way switching
L
L1
Supply 230V a.c. - 50Hz
N
L2
Load
DIMMER
C
Two-way switching
(only one dimmer can be used)
2 way switch
N
Supply 230V a.c. - 50Hz
L
Load
L1
C
L2
L1
L2
DIMMER
C
Wires must be connected to the correct dimmer terminals.
DO NOT connect earth to dimmer.
Please note the dimmer may be substituted for
any of the Two-Way switches shown on pages
27-28
Logic Plus Technical
TD19
WHITE
www.mkelectric.co.uk
Euro and LJU6C Data Frontplates
Standards and approvals
BS 5733
Technical specification
Dimensions
Height:
Width:
85.75mm
85.75mm (1G)
147mm (2G)
Depth:
Description
9mm
Aperture Dimensions
Frontplates used for mounting snapfit data modules. Euro modules are available separate or already
mounted to save on installation time.
Euro Frontplates
Height:
Width:
50mm
50mm (1G)
Dimensions (mm)
100mm (2G)
LJU6C Frontplates
LJU6C Frontplates
Euro Frontplates
Height:
37mm
Width:
22mm
Weight
1G 1 module:
32g (including fixing screws)
1G 2 module:
28g (including fixing screws)
2G 4 module:
39g (including fixing screws)
86
86
86
Colour
60.3
MK White
Features
●
1G and 2G frontplates
●
Logic Plus style
●
Colour matched to MK Logic Plus range
●
Accept industry standard (Euro) and
LJU6C snapfit modules
●
1G Euro frontplate accepts 2 Euro
modules, (50 x 50mm aperture)
●
2G Euro frontplate accepts 4 Euro
modules, (100 x 50mm aperture)
●
2G LJU6C frontplate accepts two LJU6C
modules (27 x 37mm aperture)
●
1⁄2 module (12.5 x 50mm) blank
available for Euro frontplates
For a full range of corresponding products,
see pages 30–31 in the product selector.
86
9
1 Gang
2 module
60.3
K182 WHI
K172 WHI
2 Gang
4 module
147
86
120.6
K184 WHI
9
9
Logic Plus Technical
TECHNICAL HOTLINE +44 (0)1268 563720
TD20
WHITE
Power Modules
Standards and approvals
Description
K5830: BS 1363: Part 2: 1995
A range of euro modules designed to provide a variety of power options.
K5831: IEC 60884-1: 2002
K5832: SSA.444: 1985
Technical specification
13A UK
16A German
15A American
Electrical
Electrical
Electrical
Voltage rating:
250V a.c.
Voltage rating:
250V a.c.
Voltage rating:
127V a.c.
Current rating:
13A
Current rating:
16A
Current rating:
15A
Terminal capacity:
Live, neutral & earth
3 x 2.5mm2
3 x 4mm2
2 x 6mm2 (stranded)
Terminal capacity:
Live, neutral & earth
4 x 1.5mm2
2 x 2.5mm2
1 x 4mm2
Terminal capacity:
Live, neutral & earth
3 x 2.5mm2
2 x 4mm2
1 x 6mm2 (stranded)
Physical
Physical
Physical
Ambient operating temperature:
–5°C to +40°C
(not to exceed an average of more than 25°C in any 24
hour period)
Ambient operating temperature:
–5°C to +40°C
(not to exceed an average of more than 25°C in any 24
hour period)
Ambient operating temperature:
–5°C to +40°C
(not to exceed an average of more than 25°C in any 24
hour period)
IP rating:
IP2XD
IP rating:
IP2XD
IP rating:
IP2XD
Max. installation altitude:
2000 metres
Max. installation altitude:
2000 metres
Max. installation altitude:
2000 metres
Dimensions (mm)
13A UK
16A German
15A American
50
50
50
50
50
50
K5830 WHI
K5831 WHI
25
BOX TYPES
K5832 WHI
40
25
BOX TYPES
BOX TYPES
Minimum
Extra wiring space
Minimum
Minimum
Extra wiring space
35mm
46mm
46mm
35mm
46mm
Installation
MK socket outlets can be wall or bench mounted. Do not mount or use as a trailing socket or where they
may be subject to excessive moisture or dampness.
For a full range of corresponding products,
see page 30 in the product selector.
TD21
Logic Plus Technical
WHITE
www.mkelectric.co.uk
RJ45/ISDN Data Outlets
Standards and approvals
BS EN 50173.
IEC 11801.
TIA/EIA 568A.
TIA/EIA TSB40A.
Description
Suitable for use in all LJU6C, Euro and MK Modular frontplates, available in the Logic Plus range, Cat5/5e
and ISDN modules suitable for use in structured cabling distribution systems. ISDN modules incorporate
a line terminating resistor.
Installation
●
Maximum cable length 90m.
●
Do not over tighten cable ties.
●
Cable bend radii, 40mm during installation,
20mm after installation.
●
Do not unwind the twists in the wire pairs by
more than 13mm max.
●
Maximum pull force 8.7kg.
BOX TYPES
Depth
Note
UTP
25mm
Edge/Insignia and Aspect require 32mm box depth
STP
32mm
Edge/Insignia and Aspect require 45mm box depth
DIMENSIONS
Euro
25 x 50mm
LJU6C
22 x 37mm
MK Modular:
Logic Plus
25 x 58mm
(only fit into MK modular frontplates K191/2/3/4)
Installation details and wiring
diagram illustrations
Euro and LJU6C modules are to be
wired as follows
TIA WIRING SCHEME COLOUR CODES:
Pin No. 568A
568B
1
WHITE / green
WHITE / orange
2
GREEN / white
ORANGE / white
3
WHITE / orange
WHITE/ green
4
BLUE / white
BLUE / white
5
WHITE / blue
WHITE / blue
6
ORANGE / white
GREEN / white
7
WHITE / brown
WHITE / brown
8
BROWN / white
BROWN / white
For a full range of corresponding products,
see pages 30–32 in the product selector.
P2
P3
P1
568A
P3
P4
P2
P1
568B
Pair 1 – BLUE/white & WHITE/blue
Pair 2 – ORANGE/white & WHITE/orange
Pair 3 – GREEN/white & WHITE/green
Pair 4 – BROWN/white & WHITE/brown
P4
4
6
8
7
5
3
1
2
Logic Plus Technical
TECHNICAL HOTLINE +44 (0)1268 563720
TD22
WHITE
Telephone, RJ11/12, BNC Data and Blank Modules
Standards and approvals
Telephone sockets K5820 and K5821 comply with the following:
BS 6312: 2.2, OFTEL Approval NS/G/23/L/100005.
Data sockets K5801, BS 5733:1995 (where applicable).
K5887 complies with FCC68.
Technical specification
Electrical
Cable types:
Telephone: CW1311, CW1293, CW1308, CW1316
No. of cables per termination:
Telephone: 2
RJ11/12: 1
BNC
50. impedance cable – RG58, RG141, URM43 Belden
9907
Description
BT Wiring Scheme
A range of telephone, data and blank modules to
fit Euro and LJ6UC front plates. BNC Euro
modules with a 50Ohm crimp connector suitable
for use with RG58, URM43, URM76 and Beldon
9907 type co-axial cables are also available.
1 GREEN / white
2 BLUE / white
3 ORANGE / white
4 WHITE / orange
5 WHITE / blue
6 WHITE / green
Installation (Telephone socket modules)
Note: Main wire colour is shown in capitals
Product performance, systems
compatibility
Frequency range:
BNC connector: 0 to 4GHz
Master Sockets: For use as the first socket outlet
on a direct exchange. They contain the required
surge protector (for line protection against
electrical surges) and ringing capacitor.
Impedance:
BNC Connector: 50. nominal
Termination type:
Telephone module – IDC
BNC module – Crimped connection
1
Temperature range:
Ambient air –20°C to +60°C
IP rating:
IP2XD – K5820, K5821, K5801 and K5787.
IP4X – K180, K188, K186 and K170
Max. installation altitude:
2000 metres
DIMENSIONS (mm)
5
2
3
4
Secondary Sockets: for use as extension sockets
when connected on the same line as a Master
Socket.
Physical
6
IDC
terminals
Installation tools required IDC Connectors
(telephone & RJ45 outlets)
Cable tie
Cable tie
hole
First Socket Outlet
Master
Extension Outlet
Secondary
1 2 3
4 5 6
1 2 3
4 5 6
MK insertion tool List No. 400 or 22630.
Wire pull-out force: 10.5 Newtons when
installed correctly.
Wiring regulation restrictions
RJ11/12 Wiring Scheme
Domestic Installations: The total REN (Ring
Equivalent Number) value of all telephone
equipment connected on a line must not exceed 4.
PIN
NO.
STRIPPED COLOUR
WIRE
SOLID COLOUR
WIRE
1
2
3
4
5
6
WHITE / green
WHITE / orange
BLUE / white
WHITE / blue
ORANGE / white
GREEN / white
White
Black
Red
Green
Yellow
Blue
List No.
Dimensions
K5820 / K5821 /
K5801/ K188 / K5887
25 x 50
K180
50 x 50
BOX TYPES
K186
12.5 x 50
K5820 / K5821
16mm
K5787/K170
22 x 37
K5801 / K5887 / K5787
25mm
Note: Main wire colour is shown in capitals
Features
●
Meet all relevant BS, OFTEL and cabling
standards
●
Interchangeable modules clip into
frontplates
●
Front fixing facilitates easy exchange of
modules
●
Part of a complete range of products for
telephone and data processing
requirements
●
Can be specified for all applications
●
Fit in plaster depth boxes
Data sockets
●
Latest specification for high performance
systems
●
Made to stringent quality assurance
procedures
●
Wide range of data connectors available
3
5
4
2
6
1
Telephone sockets
●
100% tested before delivery
●
Quick, simple and reliable IDC connectors
For information on TV Satellite and FM Modules see
pages TD28 – TD30
For a full range of corresponding products,
see pages 30–32 in the product selector.
TD23
Logic Plus Technical
WHITE
www.mkelectric.co.uk
MK Modular Datacoms
Standards and approvals
Logic Plus Telephone and Data sockets comply with the following:
Telephone sockets K420 and K421
BS 6312: 2.2, OFTEL Approval NS/G/23/L/100005
Data sockets K190 to K194, K501
BS 5733: 1995 (where applicable)
Data sockets K545
Cat 5e performance to EIA/TIA TSB568, BS EN 50173, IEC11801
Description
Technical specification
Electrical
Cable types:
A unique modular system in the distinctive Logic Plus style comprising a range of socket modules for Data
and Telephone use, with 4 matching frontplates capable of accepting combinations of interchangeable
modules. The ‘clip-in’ design provides a high degree of versatility, making the system ideal for use in all
commercial and industrial applications.
Telephone CW1311, CW1293, CW1308, CW1316
RJ45: 20 to 26 AWG, 100 ohm Cat 5e UPT cable
Features
No. of cables per termination (Telephone & RJ45):
●
Telephone: 2
RJ45:
1
●
Interchangeable modules clip into
frontplates
●
Front fixing facilitates easy exchange of
modules
BNC
50Ω impedance cable – RG58, RG141, URM43
Belden 9907
Frequency range:
BNC connector: 0 to 4GHz
Meet all relevant BS, OFTEL and cabling
standards
●
Part of a range of products for telephone
and data processing requirements
Telephone sockets and frontplates
Quick, simple and reliable IDC connectors
●
●
Can be specified for all applications
●
Fit in plaster depth boxes
Data sockets and frontplates
Cat 5e specification performance
●
●
Impedance:
BNC Connector: 50Ω nominal
Termination type:
RJ45& telephone module – IDC
BNC module – Crimped connection
Physical
Temperature range:
Ambient air –20°C to +60°C
IP rating:
IP2XD
Max. installation altitude:
2000 metres
Made to stringent quality assurance
procedures
BOX TYPES
Where there is more than one module in a frontplate, the depth of the
box is determined by the module with the deepest back projection.
Ref.
Min. box
depth mm
Flush box
List No.
Surface box
List No.
K420
16
3995 ZIC
K2160 & 2161 WHI
K421
16
3995 ZIC
K2160 & 2161 WHI
K190
16
3995 ZIC
K2160 & 2161 WHI
K501
16
3995 ZIC
K2160 & 2161 WHI
3995 ZIC
861 & 862 ZIC
K2160 & 2161 WHI
K2140 & 2142 WHI
K545
(min.)
16
(recommend) 25
Dimensions – Data and TV modules (mm)
25
25
13
58
58
25
21.5
11.5
58
14
For a full range of corresponding products,
see page 33 in the product selector.
K501 WHI
K420 / K421 /
K545 WHI
K190 WHI
Logic Plus Technical
TECHNICAL HOTLINE +44 (0)1268 563720
TD24
WHITE
MK Modular Datacoms
Installation (Data sockets)
Dimensions – Modular frontplates (mm)
86
RJ45 modules
146
In order to maintain Category 5e performance,
install cabling in accordance EIA/TIA or ISO
General Cabling Standards.
86
86
Installation (Telephone socket
modules)
Product performance, systems
compatibility
60.3
Master Sockets: For use as the first socket outlet
on a direct exchange. They contain the required
surge protector (for line protection against
electrical surges) and ringing capacitor.
120.6
K191 WHI
K193 WHI
86
Secondary Sockets: for use as extension sockets
when connected on the same line as a Master
Socket.
146
Installation tools required IDC Connectors
(telephone & RJ45 outlets)
86
86
MK insertion tool List No. 400 or 22630.
Wire pull-out force: 10.5 Newtons when installed
correctly.
60.3
Wiring regulation restrictions
120.6
K192 WHI
Domestic Installations: The total REN (Ring
Equivalent Number) value of all telephone
equipment connected on a line must not exceed 4.
K194 WHI
Industrial and commercial installations: MK
telephone sockets are suitable in all situations
after the PBX/PABX has been installed by a
recognised installer. For key systems and
other ‘special’ systems, the manufacturer’s
instructions should be referred to.
RJ11 Wiring Scheme
PIN
NO.
STRIPPED COLOUR
WIRE
SOLID COLOUR
WIRE
1
2
3
4
5
6
WHITE / green
WHITE / orange
BLUE / white
WHITE / blue
ORANGE / white
GREEN / white
White
Black
Red
Green
Yellow
Blue
6
1
Rear View of Terminal
Connection Block
Safety information
None of the above products should be installed
into the same fixing or mounting boxes as mains
rated equipment or cable.
Note: For BT and RJ45 wiring scheme diagrams
see pages TD26 and TD21 respectively.
Note: Main wire colour is shown in capitals
Cable management
BOT
TOM
Logic Plus Modular Data and Telephone Sockets
can be mounted in a variety of MK trunking
systems. See main catalogue for further details.
TD25
Logic Plus Technical
WHITE
www.mkelectric.co.uk
Telephone, TV/FM and Satellite Socket Outlets
Standards and approvals
Logic Plus Telephone and TV sockets comply with the following:
Telephone sockets K422 and K427
BS 6312: 2.2, BS 5733: 1995 (where applicable) and OFTEL
Approval NS/G/23/L/100005.
K4817: BS 5733: 1979 (where applicable) and FCC68.
TV sockets K3520, K3521 and K3523
BS 3041: Part 2: 1977/IEC 169-2: 1977, BS5733: 1995 (where
applicable) and IEC65, Cls 10.1, 10.3.
TV sockets K3525
BS 5733: 1995 (where applicable).
Technical specification
Electrical
Telephone sockets, cable specification:
CW1311, CW1293, CW1308, CW1316
No. of cables per termination: 2
Re-usability:
>9 reterminations (should not be reterminated with
smaller diameter wire)
TV sockets:
Cable specification: CT 100 or equivalent
Any standard low-loss TV co-axial cable:
Outside 4-8mm diameter,
inner conductor 0.5-2mm diameter
Insertion loss:
Graphs showing insertion loss available on request
‘F’ Type satellite socket (K3525), cable specification:
Co-axial cable: inner core diameter – 0.5-1.2mm
RJ11 (K4817), Cable specification:
Capable of taking 0.08 to 0.65mm2 solid or stranded cable
Physical
Ambient air:
–20°C to +60°C
IP rating:
IP2XD
Max. installation altitude:
2000 metres
For a full range of corresponding products,
see pages 34–35 in the product selector.
Description
A part of the very wide range of products in the distinctive Logic Plus style to meet the latest technical
requirements and the standards applicable to modern technology in the installation of telephone and
television equipment. The master and secondary telephone sockets K422 and K427 comply with relevant
OFTEL approvals for direct and indirect connections between a termination point of a public
telecommunications system and any piece of approved telecommunications apparatus. For applications
requiring twin or dual telephone outlets, refer to ‘Modular Data and Telephone Sockets’.
Logic Plus Telephone and TV sockets will fit in plaster depth boxes (except for RJ11).
The F-type Satellite Socket may be used for connection of CATV, MATV and satellite TV installations.
Digital TV outlets are available. See pages TD28-TD30 for details.
Features
●
Single screw termination on TV outlets
●
IDC connectors on telephone outlets
●
Protected, fully enclosed PCBs
●
●
Meet all relevant BS requirements
Part of a complete range of products for
telephone, television and data processing
requirements
●
Attractive new easy-clean Logic Plus styling
●
Angled connector on TV outlets
●
Quick, simple and reliable terminal
connection
●
Sockets fit in plaster depth boxes (except
K4817)
Logic Plus Technical
TECHNICAL HOTLINE +44 (0)1268 563720
TD26
WHITE
Telephone, TV/FM and Satellite Socket Outlets
Dimensions (mm)
Installation (Telephone sockets)
Product performance, systems compatibility
Typically 25
85
85
Master Sockets: for use as the first socket outlet on a direct exchange or
PABX line. They contain surge protector (for line protection against electrical
surges) and ringing capacitor.
14
Secondary Sockets: For use as extension sockets when connected on the
same line as a Master Socket.
85
85
Installation tools required
MK IDC insertion tool List No. 400 or 22630 (not supplied with product).
Wiring regulation restrictions
60.3
60.3
15
K3522/3523
K3520/3521
BT Wiring Scheme
Typically 25
85
85
Domestic installations: Any number of MK sockets may be installed
thereafter, with a total REN (Ring Equivalent Number) value of all telephone
equipment connected on a line not exceeding 4.
85
1 GREEN / white
2 BLUE / white
3 ORANGE / white
4 WHITE / orange
5 WHITE / blue
6 WHITE / green
14
85
Note: Main wire colour is shown in capitals
3
60.3
60.3
15
IDC
terminals
4
2
5
1
6
K3520/3521
K3525
Cable Tie
fixing point
Sectional drawings show the furthest projections from the back of the
frontplate (wall surface), including a typical coaxial connector in the case of
TV sockets. All units will fit in 16mm plaster depth boxes except for K4817
(Western Telecom socket).
Cable tie
First Socket Outlet
Master
1 2 3
BOX TYPES
1 gang
Flush
Surface
861 ZIC
K2140 WHI
4 5 6
Extension Outlet
Secondary
1 2 3
4 5 6
TD27
Logic Plus Technical
WHITE
www.mkelectric.co.uk
Telephone, TV/FM and Satellite Socket Outlets
Installation (TV sockets)
FM
TV
Product performance, systems compatibility
Isolated Outlets are intended for use where safety isolation (rated at 2000V
ac) is required to provide protection against faults occurring within any mains
powered product used on different parts of the distribution system. They are
not suitable for use in systems where DC signals are passed through the
socket, (e.g. where masthead/headend equipment is controlled by
receiver/decoder equipment).
2
Diplexer Outlets are used in distribution systems where both TV and FM band
signals are combined on a single aerial downlead. The filtering in the diplexer
separates the appropriate signals and feeds them through to the relevant
output connection port.
TV
1
TV DIST
3
3
TV
HI-FI
VID
Cable routing and use of cable clamp
Sharp bends in the cable must be avoided during installation. The single
TV/FM socket is fitted with a cable clamp that can be fixed on either side of
the termination position to facilitate this.
TV
TV
When tightening the screening braid clamps ensure that the cable is firmly
gripped and that the inner insulation is not squashed flat beyond a slight oval
shape.
Safety information
TV outlets or modules must not be installed in the same enclosure as
equipment rated in excess of 50V, (e.g. mains rated 13A sockets or switches).
3
3
VID
Method of installation of TV and FM aerial connection by using MK co-axial
socket outlet and only one down lead.
Conventional distribution system for TV and FM signals using a single aerial
downlead.
1
A standard TV/FM diplexer product is required to combine the TV and
FM signals from the separate aerials in the loft space. (Black lines in
wiring diagram).
2
The single cable feed from the diplexer then feeds to the input of a
multi way distribution amplifier, typically located in the loft or garage.
(Red line in wiring diagram).
3
Each individual output from the distribution amplifier is then fed to the
individual rooms in the house to a standard TV (single or diplexer)
outlet to which the TV/VCR and/or Hi-Fi can be connected. (Blue lines
in wiring diagram).
Logic Plus Technical
TECHNICAL HOTLINE +44 (0)1268 563720
TD28
WHITE
Digital TV and Telephone Outlets
Standards and approvals
All Logic Plus TV Outlets comply with BS 5733
and BS EN 50083 where applicable.
Also IEC 169-2, BS EN 60169-24 and BS 6312 part 2
Modular products are Euro compatible.
Technical specification
Frequency Specification
TV outlet
Single Modules: DC – 950MHz
Diplexer Modules:DC – 68.5MHz, 174 - 862MHz
Triplexer Modules: 5 – 68.5MHz, 174 - 862MHz
FM outlet
Single Modules: DC – 950MHz
Diplexer Modules: 87.5 – 108MHz
Triplexer Modules: 87.5 – 108MHz
SAT outlet
Single Modules: DC – 1.75GHz
Diplexer Modules: n/a
Triplexer Modules: DC – 200kHz: 950 – 2400MHz
Cable management
Logic Plus TV outlets can be mounted in
a variety of MK trunking systems.
Description
Diplexer modules are for connecting to a single co-axial aerial down lead carrying combined TV and FM
signals. The filtering in the diplexer splits out the appropriate signal and feeds it to the relevant output
connection. A DC control path is provided in the TV signal path through the diplexer.
Triplexer modules are for connecting to a single co-axial aerial down lead carrying combined TV, FM and
SAT signals. The filtering in the triplexer splits out the appropriate signal and feeds it to the relevant
output connection. A DC control path is provided in the SAT signal path through the triplexer.
Telephone secondary outlets are provided on some products for connection of telephone or for
interactive TV applications.
Features
●
Non Isolated
●
●
Fully screened
●
Earth terminal provided on TV modules
●
Selected products with BT secondary
outlets for interactive TV applications
Selected products with supplementary TV
outlet for back-feed for further distribution
BOX TYPES
Flush
Flush (for Extra
wiring space)
Surface Insulated
Surface Metal
1 gang
861 ZIC
866 ZIC
K2140 WHI
K2211 ALM/K2213 ALM
2 gang
862 ZIC
886 ZIC
K2142 WHI
K2212 ALM/K2214 ALM
Minimum recommended box depth 32mm
Note: Edge/Insignia mounted modular products require 45mm box
For a full range of corresponding products,
see page 34 in the product selector.
Logic Plus Technical
TD29
WHITE
www.mkelectric.co.uk
Digital TV and Telephone Outlets
Dimensions (mm)
Installation
●
When installing the TV co-axial cable ensure
that all cable bends are smooth so that the
inner insulation is not crushed or squashed,
otherwise the TV signal quality may be
affected.
●
Not suitable for loop-in loop-out installations.
●
Use CT100 cable (or equivalent).
1 gang (monobloc) dimensions (mm)
86
FM
33
TV
86
In the event that the earth terminal is required to
be used, the installer must ensure that a suitable
earth conductor is present to connect to the earth
terminal. (In the case of 2G products both TV
modules should be earthed).
In the event that the earth terminal is required to
be used, the installer must ensure that a suitable
earth conductor is present to connect to the earth
terminal. (In the case of 2G products both TV
modules should be earthed).
TV Co-axial cable stripping details
6.5 6.5
60.3
BT Wiring Scheme
2 gang (monobloc) dimensions (mm)
146
Screening braid to remain in
place over the inner insulation
33
TV
FM
Earth terminal
86
1 GREEN / white
2 BLUE / white
3 ORANGE / white
4 WHITE / orange
5 WHITE / blue
6 WHITE / green
Note: Main wire colour is shown in capitals
SAT
Cable
clamping
plate
Foil EMC
screening
gasket
120.6
Co-axial
cable
Clamping
plate fixing
screws
4
3
IDC
terminals
Earth
terminal
5
2
6
1
Cable tie
Cable tie
hole
View with cable
clamp removed
Cable clamp
Co-axial
cable
Clamping
fixing screws
BT Outlet Connection
Carefully strip 50mm of the BT cable outer sheath
to expose the inner insulated conductors. Using
the insertion tool supplied, (MK List no. 400)
carefully push each lead into the appropriate IDC
terminals according to the wiring colour code
stated in the BT Wiring Scheme diagram.
Pins 1 and 6 are frequently unused, 4 wire cable
may be used in these installations.
If an existing installation uses a different wiring
colour code system, this should be retained on
any new or extended installation.
Additional secondary extension outlets should be
wired in parallel with the existing installation via
the IDC terminals, (i.e. pin 1 to pin1, pin 2 to pin
2, etc).
First Socket Outlet
Master
1 2 3
4 5 6
Extension Outlet
Secondary
1 2 3
4 5 6
Logic Plus Technical
TECHNICAL HOTLINE +44 (0)1268 563720
TD30
WHITE
Digital TV and Telephone Outlets
Installation (Digital TV sockets)
FM
Product Performance, System Compatibility
Isolated Outlets are intended for use where safety isolation (rated at 2000V
ac) is required to provide protection against faults occurring within any mains
powered product used on different parts of the distribution system. They are
not suitable for use in systems where DC signals are passed through the
socket, (e.g. where masthead/headend equipment is controlled by
receiver/decoder equipment).
TV
1
3
TV DIST
SAT
Diplexer Outlets are used in distribution systems where both TV and FM band
signals are combined on a single aerial downlead. The filtering in the diplexer
separates the appropriate signals and feeds them through to the relevant
output connection port.
4
TV
4
TV
HI-FI
VID
Triplexer Outlets are used in distribution systems where TV, FM and Satellite
band signals are combined on a single aerial downlead. The filtering in the
triplexer separates the appropriate signals and feeds them through to the
relevant output connection port.
TV
2
Cable Routing and Use of Cable Clamp
Sharp bends in the cable must be avoided during installation. The single
TV/FM socket is fitted with a cable clamp that can be fixed on either side of
the termination position to facilitate this.
TV
4
VID
SKY/DIG
When tightening the screening braid clamps ensure that the cable is firmly
gripped and that the inner insulation is not squashed flat beyond a slight oval
shape.
Safety Information
Method of installation of TV and FM aerial connection by using MK co-axial
socket outlet and only one downlead.
TV outlets or modules must not be installed in the same enclosure as
equipment rated in excess of 50V, (e.g. mains rated 13A sockets or switches).
Conventional distribution system for TV and FM signals using a single aerial
downlead.
Distribution system for Digital TV, FM and Satellite signals using a single aerial
downlead.
1
The signals from the TV and FM aerials and the satellite dish are
combined together using two products. The first combines the TV and
FM signals and the second adds the Sky signal to the TV/FM signal and
provides a DC control path to power the LNB unit on the satellite dish.
(These products are not supplied by MK).
The single aerial down lead feeds into the triplexer of a K3563 outlet
(black lines in wiring diagram).
2
The separated satellite signal is then fed to the decoder. The decoded
satellite signal is then fed into the VCR along with the TV signal from
the Triplexer. The output signal from the VCR then feeds into the TV
and also back to the single outlet on the K3563 and onto the
distribution amplifier (black lines in wiring diagram).
3
The single cable back-feed from the K3563 then feeds back to the
input of a multi way distribution amplifier, (typically located in the loft
or garage) (red lines in wiring diagram).
4
Each individual output from the distribution amplifier is then fed to the
individual rooms in the house to a standard TV (single or diplexer)
outlet to which the TV/VCR and/or Hi-Fi can be connected (blue lines
in wiring diagram).
TD31
Logic Plus Technical
WHITE
www.mkelectric.co.uk
Grid Plus Front Plates
Standards and approvals
BS 5733: 1995
Description
Grid Plus is a comprehensive modular switching and monitoring system ideal for a variety of applications
within the commercial, public and domestic sectors.
Dimensions (mm)
86
86
86
86
1 module
K3631 WHI
86
86
2 module
K3632 WHI
4 module
K3634 WHI
3 module
K3633 WHI
146
146
146
146
146
146
146
206
6 module
K3636 WHI
8 module
K3638 WHI
12 module
K3639
For a full range of corresponding products,
see page 35 in the product selector.
Logic Plus Technical
TECHNICAL HOTLINE +44 (0)1268 563720
TD32
WHITE
Accessories
SURFACE MOUNTING BOXES
16mm
Moulded
30mm
Moulded
32*mm
Moulded
38mm
PVC
40mm
Moulded
41mm
Steel
1 gang Sockets (13A)
K2140
K2181
K2025
K2031
K2211 ALM K2213 ALM
2 gang Sockets
K2142
K2183
K2172
K2212 ALM K2214 ALM K5400
3 gang Sockets
K2153
K2185
2A Round Pin Sockets
K2140
K2181
K2211 ALM K2213 ALM
5A/15A Round Pin Sockets
K2140
K2181
K2211 ALM K2213 ALM
RCD Sockets
Filtered Sockets
Connection Units
K2140
K2181
K2025
41*mm
Steel
K2172
K2212 ALM K2214 ALM K5400
K2172
K2212 ALM K2214 ALM K5400
K2031
K2211 ALM K2213 ALM
20A DP Switches
K2140
K2181
K2025
K2031
K2211 ALM K2213 ALM
K5105 32A DP Switch
K2140
K2181
K2025
K2031
K2211 ALM K2213 ALM
K2172
K2212 ALM K2214 ALM
K5205, K5215 (CK & SH)
K5230
K5400
K5060, K5061
K2172
K700
K2140
K2181
K2025
K701
K2214 ALM
K5400
K2211 ALM K2213 ALM
K2172
1, 2 & 3 gang Switches
K2160
K2140
K2181
4 & 6 gang Switches
K2161
K2142
K2183
1 gang Architrave Switch
K2151
2 gang Architrave Switch
K2152
Dimmers using Pattress
K1501, K1511, K1531, K1532
K2160
K1521, K1534, K1533, K1535
K2160
K2140
K2181
Dimmers not using Pattress
K1501, K1511, K1531, K1532
K2025
K2025
K2031
K2211 ALM K2213 ALM
K2172
K2212 ALM K2214 ALM K5400
K2031
K1521, K1534, K1533, K1535
K2140
K2181
K2025
K2211 ALM K2213 ALM
K191, K192
K2140 ■
K2181
K2025
K2211 ALM K2213 ALM
K2142 ■
K2183
K2140
K2181
K193, K194
Data/Telecom Plates
48*mm
Steel
K2160
■ Dependent upon modules used
* With conduit entry knockouts
NOTE: the size of cable should be taken into consideration when choosing box depth
K2212 ALM K2214 ALM K5400
K2025
K2211 ALM K2213 ALM
55mm
Steel
TD33
Logic Plus Technical
WHITE
www.mkelectric.co.uk
Accessories
FLUSH MOUNTING BOXES
16mm
25mm*
27mm*
35mm*
45mm
46mm*
877 ZIC
1 gang Sockets (13A)
861 ZIC
866 ZIC
K2061
2 gang Sockets
862 ZIC
886 ZIC
K2062
3 gang Sockets
K863
861 ZIC
866 ZIC
K2061
877 ZIC
861 ZIC
866 ZIC
K2061
877 ZIC
RCD Sockets
886 ZIC
K2062
Filtered Sockets
886 ZIC
K2062
Connection Units
866 ZIC
K2061
20A DP Switches
866 ZIC
K2061
K5105 32A DP Switch
866 ZIC
K5205, K5215 (CK & SH)
886 ZIC
2A Round Pin Sockets
3995 ZIC
5A/15A Round Pin Sockets
47mm*
878 ZIC
878 ZIC
878 ZIC
877 ZIC
877 ZIC
877 ZIC
K2062
878 ZIC
K5012
K5120 ALM
K5045
K2061
K5060, K5061
886 ZIC
877 ZIC
K2061
878 ZIC
K5011
K5120 ALM
K700
861 ZIC
866 ZIC
K2061
877 ZIC
K701
1, 2 & 3 gang Switches
878 ZIC
3995 ZIC
4 & 6 gang Switches
861 ZIC
866 ZIC
K2061
862 ZIC
886 ZIC
K2062
1 gang Architrave Switch
3921 ZIC
2 gang Architrave Switch
3922 ZIC
Dimmers using Pattress
K1501, K1511, K1531, K1532
3995 ZIC
K1521, K1534, K1533, K1535
3995 ZIC
Dimmers not using Pattress
K1501, K1511, K1531, K1532
55mm
877 ZIC
878 ZIC
861 ZIC
866 ZIC
K2061
877 ZIC
K1521, K1534, K1533, K1535
861 ZIC
K2062
877 ZIC
K191 & K192
861 ZIC ■
866 ZIC ■
K2061
877 ZIC ■
K193 & K194
862 ZIC ■
886 ZIC ■
K2062
Data/Telecom Plates
861 ZIC
866 ZIC
K2061
■ Box supplied with accessory
■ Dependent upon modules used
NOTE: the size of cable should be taken into consideration when choosing box depth
878 ZIC ■
877 ZIC
* With conduit entry knockouts
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project