Eaton MTL 9493-PS-XXX Instruction manual

Eaton MTL 9493-PS-XXX Instruction manual

Eaton MTL 9493-PS-XXX is an intrinsically safe power supply designed for Zone 2 hazardous areas. It offers isolated power supply with a range of Ex ia output voltages, allowing for flexible use in various applications. The device can be mounted on DIN rails or backplanes, providing installation versatility. Additionally, the MTL 9493-PS-XXX features a Power over Ethernet (PoEx) option, enabling efficient power distribution through existing Cat5e cables. This compact and versatile power supply is ideal for powering instrumentation, sensors, and other devices in hazardous environments.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Manual
Eaton MTL 9493-PS-XXX Instruction manual | Manualzz
Instruction manual
MTL intrinsic safety solutions
February 2016
INM MTL 9493-PS-XXX rev 1
MTL 9493-PS-XXX
intrinsically safe power supply
This page left intentionally blank
ii
INM 9493-PS-XXX rev 1
CONTENTS
1 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2 DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1/2
3 DIN-RAIL INSTALLATION METHOD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.1 Protection of equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.2 DIN rail mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.2.1 Mounting power supplies on DIN rail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.2.2 Wiring up power supplies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3.2.3 Ambient temperature considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.3 Power bus - Installation and use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.4 Earth rail and tagging accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.4.1 Parts list. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.5 Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.5.1 Fitting earth rails. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.5.2 Fitting tagging strips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.5.3 Completed assemblies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4 BACKPLANE MOUNTING VARIANT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.1 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.2 Protection of equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.3 Backplane mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.3.1 Surface mounting – with kit SMS01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.3.2 T- or G-section DIN-rail mounting –with kit DMK01. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.4 Backplanes – identification and tagging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.4.1 Backplane identification labels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.4.2 Tagging strip mounting kit (TSK08). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.5 Backplanes - earth rails . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.5.1 Earth rail kit (ERK08). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.6 Backplanes – power supply connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.6.1 Single backplane. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.6.2 Interconnection of power supplies for multiple backplanes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.7 Fitting MTL 9493-PS-XXX modules to backplane. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.7.1 Installation - Figure 4.15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4.7.2 Module removal - Figure 4.16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5 ENVIRONMENTAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6 WASTE REMOVAL INFORMATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
7 APPROVALS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8 ATEX & IECEX CERTIFICATION INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17/18
9 DECLARATION OF CONFORMITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
INM 9493-PS-XXX rev 1
iii
GENERAL SAFETY INFORMATION
Safety instructions for installation and operating personnel
The operating instructions provided here contain essential safety instructions for installation personnel
and those engaged in the operation, maintenance and servicing of the equipment.
WARNING !
A ‘WARNING’ marked in this way is provided for operator and plant safety and MUST be followed.
CAUTION !
A Caution is provided to prevent damage to the instrument.
NOTE
These are used to guide the user in the operation of the instrument.
Before commencing installation or commissioning:
•
Read and understand the contents of this manual
•
Ensure installation and operating personnel have received adequate training for this task
•
Ensure that any operating instructions are fully understood by the personnel responsible.
•
Observe national and local installation and mounting regulations (e.g. IEC 60079-14).
WARNING !
These assemblies may not be used in explosion-hazard area applications if they have been used
previously in general electrical installations.
WARNING !
The responsibility for planning, installation, commissioning, operation and maintenance, particularly
with respect to applications in explosion-hazard areas, lies with the plant operator.
During operation:
•
Make the relevant instructions available at all times to the operating personnel.
•
Observe safety instructions.
•
Observe national safety and accident prevention regulations.
•
Operate the equipment within its published specification.
•
Servicing, maintenance work or repairs not described in this manual must not be performed without prior agreement with the manufacturer.
•
Any damage to this equipment may render its explosion protection null and void.
•
No changes to any of the components that might impair their explosion protection are permitted.
If any information provided here is not clear:
Contact Eaton or an authorised MTL distributor or sales office.
NOTE
Improper installation and operation of the enclosure can result in the invalidation of the guarantee.
iv
INM 9493-PS-XXX rev 1
MTL 9493-PS-XXX IS Power Supply
1FEATURES
• Isolated power supply
• Zone 2 mountable
• DIN-rail or backplane mounting
• ATEX / IECEx approvals
• Range of Ex ia output voltages available
• Power over Ethernet option (PoEx)*
• Multiple outputs achieved by ganging MTL 9493-PS-XXX modules using 24V DC
power distribution backplane
*Note – PoEx is a simple adaptation of the IEEE 802.3af Power over Ethernet (PoE)
standard to bring the benefits to the 9400 Range of Hazardous Area devices. This
allows two spare pairs in the existing Cat5e cable to distribute the power supplied
to a 9466 Ethernet Switch (Power Sourcing Equipment – PSE) to each of the devices
connected to its five ports (PD – Powered Device). This adaptation is necessary due to
restrictions for Hazardous Area use. It is not implied that the device conforms to the
802.3af (PoE) standard.
2DESCRIPTION
The MTL 9493-PS-XXX Power Supply is a general purpose intrinsically safe power supply unit. It
takes a 24v DC safe area or zone 2 supply and produces an intrinsically safe output available in a
range of different DC voltages. The MTL 9493-PS-XXX may be mounted in a safe area or zone 2
hazardous area.
The output is Ex ia certified for group I, IIA,IIB or IIC, depending on model to suit different
applications. See Figures 2.1 for connection details.
If multiple outputs are required, there is a power distribution backplane available to simplify
INM 9493-PS-XXX rev 1
1
Safe area
Hazardous area
Zone 0
Figure 2.1
Zone 0
Ex ia IIB
application
Terminal
1
2
3
13
14
Terminal
Table 2.2
Backplane
mounting
connnections
1
2
3
7, 8 & 9
10, 11 & 12
Table 2.1
DIN-rail
mounting
connections
Function
x ia output +ve
E
n.c.
E x ia output –ve
Supply –ve (Vs–)
Supply +ve (Vs+)
Function
x ia output +ve
E
n.c.
E x ia output –ve
Supply –ve (Vs–)
Supply +ve (Vs+)
the 24VDC input connection to the modules, or alternatively a number of them can be DIN-rail
mounted with a convenient “Powerbus” input.
The MTL 9493-PS-XXX module has LED power indication for both input and output (see Figure
2.2) along with internal current limiting and electronic auto-reset circuit breaker action to protect
the module in the event of its output being short circuited or overloaded. This also minimises
the power dissipation during the fault to a negligible level, thus improving reliability.
3
Figure 2.2
MTL 9493-PS-XXX
top label and
LED indicators
2
DIN-RAIL INSTALLATION METHOD
9493-PS-C5 5VDC POWER
SUPPLY
INM 9493-PS-XXX rev 1
This section deals with mounting the individual MTL 9493-PS-XXX power supplies on DIN rail,
for backplane mounting see Section 4.
WARNING !
If this module is to be connected to intrinsically safe apparatus, it must be installed, operated
and maintained only be trained competent personnel and in accordance with all appropriate
international, national and local standard codes of practice and site regulation and in accordance
with the instructions contained here.
3.1
Protection of equipment
When the power supply is mounted in a safe area ensure that the local environment is clean
and free of dirt and dust and note the ambient temperature considerations given in Section 5.
WARNING !
When mounted in a Zone 2 hazardous area the module must be protected by a suitably
certified enclosure. See the Special Conditions for Safe Use provided in the ATEX Safety
Instructions at the end of this manual for further details of operation in
Zone 2 hazardous areas.
3.2
DIN rail mounting
Mount the MTL 9493-PS-XXX power supplies on low-profile (7mm) or high-profile (15mm) type
T35 (top-hat) DIN-rail to EN50022, BS5584, DIN46277; this is available from MTL, in 1 metre
lengths (THR2 DIN rail). It is recommended that, in normal practice, the DIN rail is earthed to ensure
personnel safety in the event of mains being put accidentally on the rail.
See Figure 3.1 for power supply dimensions.
Figure 3.1
MTL 9493-PS-XXX
package
dimensions
& connections
INM 9493-PS-XXX rev 1
3
3.2.1
Mounting power supplies on DIN rail
Clip power supplies onto type T35 DIN rail as shown in Figure 3.2, with the blue signal plugs facing
towards the hazardous-area wiring. To remove an power supply from the rail, insert a screwdriver
blade into the clip as shown and lever the clip gently outwards; pivot the power suppy off the rail.
Allow a maximum mounting pitch of 16.2mm for each unit.
Figure 3.2
DIN rail mounting
and removal
of module
3.2.2 Wiring up power supplies
Depending on the installation, it may be easier to wire up power supplies with power plugs either
in place or removed. Either way, allow sufficient free cable to permit plugs to be removed easily for
future maintenance and/or replacement purposes.
Power conductors
The removable power plugs are fitted with screw clamp terminals. Note that the conductors should
be between 14 and 24 AWG (1.6 and 0.5mm dia) in size. Plugs, located on top of the modules, are
mechanically keyed to fit in only one position. The input power plug slots into the socket at terminals
13 and 14 on the safe-area side of each module.
Figure 3.2
Removable
power plugs
Making connections
a)
Trim back the insulation of conductors by 12mm.
b)
Check the terminal assignments shown in section 6 or on the side label of the unit.
c)
Insert conductors according to the terminal assignments and tighten screws.
If the wires are to be fitted with crimp ferrules, 10–12mm is the recommended length of the metal tube.
If longer ones are used, they must be trimmed to 12mm before fitting.
4
INM 9493-PS-XXX rev 1
Finishing
Wire up individual power supplies in accordance with wiring schedules. Daisy-chain power supply
connections between individual power plugs or use the power bus (see section 4.1).
Segregate hazardous- and safe-area wiring into separate trunking or looms wherever possible to
avoid errors and maintain a tidy installation.
3.2.3 Ambient temperature considerations
Ambient temperature limits for unenclosed power supplies are from -40°C to +70°C with units closepacked.
3.3
Power bus - Installation and use
A PB-8T power bus kit enables power supply terminals (13 and 14) of up to 8 installed MTL 9493-PSXXX power supplies to be linked to a standard 24V power supply. The bus consists of a chain of
power plugs and different lengths are available to suit various numbers of modules as follows.
1. Check to make sure the bus length is correct for the number of modules involved.
2. If the number of modules is less than the maximum number the chain will support,
cut off the surplus power plugs at the tail end of the chain - leaving sufficient cable to
attach further power plugs if it becomes necessary later.
3. Insert power plugs into the power terminals on the safe- area side of each module in
sequence.
4. Connect the power supply source to the tail end of the chain (using the insulation
displacement connectors [Scotchloks] provided if required).
Notes:
1. To avoid excessive voltage drop or over-current, DO NOT connect power buses in series.
2. Surplus sections can be used (and, if required) connected together provided the cut
ends are safely terminated and/or connected together. Use single ferrules with a crimp tool
or insulation displacement connectors (Scotchloks). Suitable ferrules and connectors are
provided with the kits.
– +
x2
Optional insulation
displacement
connectors
Figure 3.3
Power bus
wiring, joining
and terminating
INM 9493-PS-XXX rev 1
5
3.4
Earth rail and tagging accessories
This section explains how to specify and assemble earth rail and tagging strip accessories for the
MTL 9493-PS-XXX power supplies. The accessories consist of mounting brackets, earth rails, tagging
strips and associated parts. They provide facilities for earthing, terminating cable screens and tagging
(identifying) the positions of individual units.
3.4.1
Parts list
IMB57 Insulating mounting block (Figures 3.4, 3.5 & 3.6)
One required at each end of a tagging strip/earth rail. Suitable for low-profile (7.5mm) and highprofile (15mm) symmetrical DIN rail.
ERB57S Earth-rail bracket, straight (figure 3.10)
Nickel-plated bus bar; supplied with two push fasteners, one earth-rail clamp (14mm, 35mm2) and
one earth cable clamp (10mm, 16mm2).
Note: ERB57S is the preferred choice of earth-rail bracket. It is usually fitted in the upper slot
on insulating mounting block IMB57.
Where the earth rail is required to be positioned at a lower height and to allow access to the
IMB57 mounting screws, the straight earth-rail bracket ERB57S can be inserted in the lower
slot, but only after insulating mounting blocks IMB57 are clamped to the DIN rail. This may not
be possible if, for example, trunking is fitted. In this case, fit offset earth-rail bracket ERB570
(see figure 3.4 & 3.10) in the upper slot: the mounting blocks can then be fitted in a restricted
space with this bracket already fitted.
ERB570 Earth-rail bracket, offset (figure 3.10)
Nickel-plated bus bar; supplied with two push fasteners, one earth-rail clamp (14mm, 35mm2)
and one earth cable clamp (10mm, 16mm2).
ERL7
Earth rail, 1m length (figure 3.10)
Nickel-plated bus bar; may be cut to length.
TAG57
Tagging strip, 1m length (figure 3.10)
Cut to size. Supplied with tagging strip label.
TGL57
Tagging strip labels, set of 10 x 0.5m
Spares replacement, for use with TAG57 tagging strip.
MS010 DIN rail module spacer, 10mm, pack of 5 (figure 3.8)
Grey spacer; one required between each MTL 9493-PS-XXX and any adjacent module on a DIN rail,
to provide 10mm air-circulation space between modules.
ETM7
Earth terminal, bag of 50 (figure 3.9)
For terminating cable screens and 0V returns on the ERL7 earth rail. For cables ≤ 4mm2.
TH5000 Tag holder
Spares replacement.
Connectors
Spares replacement: HAZ1-3, HAZ4-6, HAZ-CJC, PWR5000, SAF7-9, SAF10-12 (SAF1-3 and SAF4-6
grey connectors, also available for use in safe-area applications).
6
INM 9493-PS-XXX rev 1






Figure 3.4: Assembly drawing showing part numbers
Figure 3.5: Mounting details
Figure 3.6: IMB57 Insulating mounting block
Figure 3.7: TAG57 Tagging strip,1m length
Figure 3.8: MS010 DIN rail module spacers
Figure 3.10: Earth rails and clamps
Figure 3.9: ETM7 Earth terminals
INM 9493-PS-XXX rev 1
7
3.5Assembly
3.5.1
Fitting earth rails
a) In upper position
Before fitting insulating mounting blocks IMB57, check that the swing nuts in the base of
each unit are turned back into the moulding. Locate the mounting blocks on the DIN rail in the
chosen position and tighten the screws (see figure 3.11). Check that the swing nuts rotate
correctly to locate underneath the flanges of the DIN rail.
Figure 3.11:
Fitting IMB57
Slide a straight earth-rail bracket ERB57S into the upper slot in each mounting block. Push two
plastic push fasteners into each bracket to locate the brackets in the mounting blocks.
Cut earth rail ERL7 to the length needed. Slide the required number of ETM7 earth terminals
(5mm or 7mm wide) onto the rail. Clamp each end of the earth rail to earth-rail brackets ERB57S
using the terminal clamps (14mm, 35mm2) supplied. Fit an earth clamp (10mm, 16mm2) to the
free end of each earth-rail bracket.
Note: For lengths of earth-rail greater than 500mm, provide additional support by installing a
third IMB57 mounting block and earth-rail bracket, mid-way between the end mounting blocks.
Snap out the perforated extension between the lugs on this mounting block if a continuous
tagging strip is to be fitted (see figure 3.4).
b) In lower position, where at least 150mm clearance exists on one side, measured from
the edge of the mounting block.
As for a), but slide earth-rail brackets ERB57S into the lower slots in each mounting block.
c) In lower position, where there is insufficient clearance to fit earth-rail brackets ERB57S.
As for a), but slide offset earth-rail brackets ERB57O into the upper slot in each mounting
block before assembling the mounting blocks to the DIN rail. ERB57S brackets cannot be used
because they obscure the mounting blocks' fixing screws.
3.5.2 Fitting tagging strips
Assemble mounting blocks IMB57 to the DIN rail as above. Cut TAG57 tagging strip and label to the
length needed, and insert label so that the appropriate side is visible. Clip the strip onto the lugs on
the mounting blocks. Hinge up the strip to provide access to the tops of the power supplies.
Note: If necessary, provide additional support for long lengths of tagging strip by installing an
extra IMB57 mounting block mid-way between the end mounting blocks. Snap out the perforated
extension between the lugs on this mounting block.
8
INM 9493-PS-XXX rev 1
3.5.3 Completed assemblies
Figure 3.12 illustrates a complete assembly of MTL 9493-PS-XXX power supplies using the
accessories mentioned above.
The broken-line boxes either side of the assembly represent cable trunking, and the accompanying
dimensions represent the minimum spacing between trunking and assemblies.
Figure 3.12:
MTL 9493-PS-XXX
power suppliescomplete assembly
INM 9493-PS-XXX rev 1
9
4
BACKPLANE MOUNTING VARIANT
PLEASE NOTE: The backplane mounting variant is only available by prior special arrangement.
Please contact MTL product line to discuss.
The alternative to DIN-rail mounting is to use a standard MTL backplane that accommodates 8
modules with 24V dc dual redundant power supplies. In applications where a number of backplanes
are installed, the power supply can be interconnected. Optional earth-rail and tagging-strip kits are
available for the backplanes.
WARNING !
If this module is to be connected to intrinsically safe apparatus, it must be installed, operated
and maintained only be trained competent personnel and in accordance with all appropriate
international, national and local standard codes of practice and site regulation and in accordance
with the instructions contained here.
4.1Accessories
Accessories are available that enable the user to mount the backplanes. These include surfacemounting kits, T-section and G-section DIN-rail mounting kits and end stops.
MOUNTING KITS
ACCESSORIES
DIN-rail
19-inch
Earth-rail
Tagging
Spare
Surface
(T or G)
rack
kit
strip kit
fuse pack
SMS01
DMK01
–
ERK08–
TSK08
FUS08
4.2
Protection of equipment
When the power supply is mounted in a safe area ensure that the local environment is clean
and free of dirt and dust and note the ambient temperature considerations given in Section 5.
WARNING !
When mounted in a Zone 2 hazardous area the module must be protected by a suitably
certified enclosure. See the Special Conditions for Safe Use provided in the ATEX Safety
Instructions at the end of this manual for further details of operation in Zone 2 hazardous areas.
4.3
Backplane mounting
See the table for details of the kits and accessories applicable to the mounting methods and Figure
4.1 for dimensions and mounting centres.
Note: Before mounting a MTL 9493-PS-XXX on a backplane two minor modifications must be made.
1. Remove the DIN-rail mounting clip by compressing the small spring inside the clip with a
screwdriver and then removing it; the clip may then be removed easily from its mounting.
2. Remove the power supply plug located in the side of the unit, then fit the small plastic plate
supplied to cover the hole in the module case.
Figure 4.1:
CPS08 backplane
for MTL 9492-PS-PLUS
modules
10
INM 9493-PS-XXX rev 1
Fixing Screws
T-section G-section
(13)
(12)
G-section
(13)
End stop
(11)
T-section
(12)
OR


Figure 4.2: Surface mounting procedure
Figure 4.5: Mounting end stops onto DIN rail

Figure 4.3: T-section and G-section DIN-rail attachment

Figure 4.6: Backplane layout showing locations for labels and
attachment of accessories


 ­€
‚ƒ
„
€ ­†



 ­€
‚ƒ
„
…€ ­†
Figure 4.4: Mounting a backplane onto DIN rail
INM 9493-PS-XXX rev 1
Figure 4.7: Mounting a tagging-strip post
11
4.3.1
Surface mounting – with kit SMS01
See Figures 4.1 and 4.2.
a) Select four M4 x 20mm screws.
b) P
repare holes in the surface at centres A, tapping these if retaining nuts are not
required (Figure 4.1).
c) Place a locking washer (2) and a plain washer (3) over each M4 x 20mm screw (1) (Figure 4.2).
d) Insert the screws through the backplane at each mounting centre A (Figures 4.1
and 4.2).
e) Fit M4 x 10mm spacers (5), retaining them with retaining washers (6) (Figure 4.2).­
f)
ttach the assemblies into the pre-drilled surface holes at centres A, retaining the
A
screws with a suitable nut if the holes are not tapped.
4.3.2T- or G-section DIN-rail mounting –with kit DMK01
See Figures 4.1, 4.3, 4.4 and 4.5.
a) Select two pieces of T- or G-section DIN-rail of the appropriate length.
b) Mount the two lengths of DIN-rail side-by-side at centres A, 113mm apart (Figure 4.1).
c) Clip four mounting feet (7) to the DIN rail (8) at centres A (Figure 4.4).
d) Select the appropriate number of No. 6 x 1/2-inch screws.
e) Place a locking washer (2) and a plain washer (3) onto each No. 6 x 1/2-inch screw (1)
(Figure 4.4).
f)
Insert the assemblies through the mounting holes A on the backplane (Figures 4.1
and 4.4).
g) Fit spacers (5), retaining them with the washers (6) (Figure 4.4).
h) Locate the assemblies over the mounting feet and attach the screws (1) to the feet (Figure 4.4).
i)
For backplanes that are mounted in a vertical orientation, attach one end stop (11) to
the lower end of each DIN-rail supporting a column of backplanes by clipping the stops
into place and tightening the appropriate screw [(12) for T-section and (13) for
G-section DIN-rails] (Figure 4.5).
j)
Additional end stops should be attached between backplanes to increase the stability
of tall columns of backplanes.
4.4Backplanes – identification and tagging
Marked areas are provided for identifying backplanes. Mounting holes for earth-rail and tagging-strip
attachments are similarly marked.
4.4.1
Backplane identification labels
a) Attach a suitably marked label to the area marked BACKPLANE IDENT. to identify an
individual backplane. See Figure 4.6.
4.4.2 Tagging strip mounting kit (TSK08)
See Figures 4.1, 4.9, 4.10 and 4.11.
12
a)
Locate the tagging strip mounting posts (1) at backplane centres B (Figure 4.1).
b)
Attach each mounting post (1) to the backplane with two M3 x 12mm mounting
screws (2) and washers (3) (Figure 4.7).
c)
Slide the tag label (5) into the plastic holder (6) and retain with a plastic rivet
(9) (Figure 4.7).
d)
Attach the plastic retaining tie (7) with two plastic rivets (8) (Figure 4.7).
e)
Clip the tag strip holder (6) onto the mounting posts (1) by pushing it downwards
(Figure 4.8).
f)
If required, swivel the tagging strip vertically (Figure 4.9)
INM 9493-PS-XXX rev 1
Figure 4.11: Power supply connections
Figure 4.8: Attaching and swivelling a tagging-strip

PSU

Figure 4.9: Attaching an earth-rail post
A secondary
supply can
be connected
in the same
configuration
to PWR2
connector
Figure 4.10: Attaching earth rail terminals and rivets
INM 9493-PS-XXX rev 1
Figure 4.12: “Ring” wiring multiple backplanes
13
4.5
Backplanes - earth rails
Optional earth rails are available for backplanes (kit ERK08). Cable screens from hazardous-area
circuits, or spare pairs from a multicore cable, are connected to the terminals on the earth rails,
which are mounted on the backplane at about the same height as the front of the modules, close to
the hazardous-area connectors. Earth rails are attached using the following procedure:–
4.5.1
Earth rail kit (ERK08)
See Figures 4.1, 4.9 and 4.10.
a) Locate the earth rail mounting posts (1) at backplane centres C (Figures 4.1 and 4.9).
b) Attach the mounting posts (1) with M3 x 12 screws (3) and washers (4) (Figure 4.9).
c) Slide the earth rail (5) through the slots in the of the mounting posts (1) (Figure 4.10).
d) Fit the earth terminal(s) (6) on the rail (5) (Figure 4.10).
e) Attach plastic retaining rivets (7) to each end of the earth rail (5) (Figure 4.10).
4.6
Backplanes – power supply connections
4.6.1
Single backplane
Dual 24V power supplies, to provide redundancy, are routed to the backplane by plug-in connectors
and then bussed by the backplane to individual power supply modules. LEDs on the backplane
indicate that the two supplies are operational. A diode circuit between the two ensures that the
highest voltage supply is the one in use at any given moment, so providing automatic switchover of
supplies if the primary source fails. The procedure for connecting power supplies is:–
a) Connect each of the two 21V to 35V dc power supply connectors to the independent
supply sources according to the terminal assignments shown in Figure 4.11. The
maximum permissible wire size is 2.5mm2 (14 AWG).
b) Plug the power supply connectors into the base connectors on the backplanes.
c) The rating for the fuse located between the two supply connectors on the
backplanes is 1A.
4.6.2 Interconnection of power supplies for multiple backplanes
Power supplies for backplanes can be interconnected in the form of a ring. This will reduce wiring
and also permit individual backplanes to be taken out of service without affecting supplies to other
backplanes. More than one backplane can be removed, provided that they are neighbours and do
not leave any other backplanes without an active supply.
a) Make the connections shown in Figure 4.12.
Wire sizes up to 2.5mm2 (14 AWG) can be used and should be chosen according to load
and voltage drop.
4.7
Fitting MTL 9493-PS-XXX modules to backplane
WARNING !
When installing MTL 9492-PS-PLUS power supply modules it is essential to make sure that
intrinsically safe and non-intrinsically safe wiring is segregated as required by a nationally accepted
authority or as described in BS EN 60079-14, ISA RP 12.6 or DIN VDE-165.
4.7.1
Installation - Figure 4.15
a) Trim insulation to suit bare or ferrule wire end (Figure 4.13)
b) Terminate IS power wiring on blue connector(s).
c) Mount interface unit on the backplane.
d) Locate input bulk power connector(s) on backplane safe-area/power supply connector(s).
4.7.2
Module removal - Figure 4.16
a) Unclip the latch nearest the CE mark on the module label.
b) Rotate the module away from this latch.
c) When the module is unplugged from the power connector, move the module clear of
the other latch and remove.
14
INM 9493-PS-XXX rev 1
Figure 4.13: Wiring hazardous-area power output plugs
Figure 4.15: Fitting power supplies to backplane
Hazardous area
power connectors
Haz 1-3 ia output
0ther models
available
Figure 4.14: Key elements of the MTL 9493-PS-XXX power supply
INM 9493-PS-XXX rev 1
Figure 4.16: Removing power supplies from backplane
15
5ENVIRONMENTAL
Operating Temperature
-40°C…+70°C
Storage Temperature
–40°C…+70°C
Humidity
5…95% RH, non condensing
6
WASTE REMOVAL INFORMATION
The electronic equipment within must not be treated as general waste. By
ensuring that this product is disposed of correctly you will be helping to prevent
potentially negative consequences for the environment and human health,
which could otherwise be caused by incorrect waste handling of this product.
For more detailed information about the take-back and recycling contact MTL.
7APPROVALS
The operating parameters must not exceed those as detailed on the certificate.
•
2004/108/EC EMC Directive
•
2006/95/EC Low Voltage Directive
Region
Europe (ATEX)
International IECEx
Authority
CML
CML
Standard
EN 60079-0:2012
EN 60079-11:2012
EN 60079-26:2006
Approved
for
II (1) GD,
[Ex ia Ga] IIA, or
[Ex ia Ga] IIB, or
[Ex ia Ga] IIC, as applicable
[Ex ia Da] IIIC
I (M1)
[Ex ia Ma] I
Ta = -40°C to +70°C
IEC 60079-0:2011
IEC 60079-11:2011
IEC 60079-26:2006*
[Ex ia Ga] IIA, or
[Ex ia Ga] IIB, or
[Ex ia Ga] IIC, as applicable
[Ex ia Da] IIIC
[Ex ia Ma] I
Ta = -40°C to +70°C
Cert. no.
CML 15ATEX2071X
IECEx CML 15.0034X
Standard
EN 60079-0:2012
EN 60079-15:2010
Approved
for
II 3 G, 3(1)G
Ex nA IIA T4 Gc, or
Ex nA IIB T4 Gc, or
Ex nA IIC T4 Gc, as applicable
(Ta = -40°C to +70°C)
CML 15ATEX4072X
IEC 60079-0:2011
IEC 60079-15:2010
Ex nA IIA T4 Gc, or
Ex nA IIB T4 Gc, or
Ex nA IIC T4 Gc, as applicable
(Ta = -40°C to +70°C)
Cert. no.
IECEx CML 15.0034X
* (for guidance on marking)
Notes
1.
8
16
Terminals 1 and 3
ATEX & IECEx CERTIFICATION INFORMATION
INM 9493-PS-XXX rev 1
The following information is in accordance with the Essential Health and Safety Requirements
(Annex II) of the EU Directive 94/9/EC [the ATEX Directive - safety of apparatus] and is provided
for those locations where the ATEX Directive is applicable.
General
a)
This equipment must only be installed, operated and maintained by competent
personnel. Such personnel shall have undergone training, which included instruction on
the various types of protection and installation practices, the relevant rules and
regulations, and on the general principles of area classification. Appropriate refresher
training shall be given on a regular basis. [See clause 4.2 of EN 60079-17].
b)
This equipment has been designed to provide protection against all the relevant
additional hazards referred to in Annex II of the directive, such as those in clause
1.2.7.
This equipment has been designed to meet the requirements of intrinsically safe
electrical apparatus in accordance with EN 60079-0, EN 60079-11, EN 60079-15 and
EN 60079-26.
Installation
a)
reference to the IEC code of practice IEC 60079-14. In addition, particular industries
or end users may have specific requirements relating to the safety of their installations
and these requirements should also be met. For the majority of installations the
Directive 1999/92/EC [the ATEX Directive - safety of installations] is also applicable.
b)
Unless already protected by design, this equipment must be protected by a suitable
enclosure against:
i) mechanical and thermal stresses in excess of those noted in the certification
documentation and the product specification.
ii) aggressive substances, excessive dust, moisture and other contaminants.
c)
This apparatus is intrinsically safe electrical apparatus and is normally mounted in
a safe area. When mounted in a Zone 2 location the apparatus must be provided
with an enclosure, which offers an additional degree of protection appropriate to the
area classification.
Special conditions for safe use (when mounted in a Zone 2 hazardous area)
a) If the equipment is installed in a zone 2 hazardous area, it shall be housed in an
enclosure that is coded Ex nA, Ex e, Ex d or Ex p, suitable for operating temperatures
of -40°C to +135°C and providing an ingress protection of IP54 minimum. For some
types of enclosure, additional certification will be required to permit the installation of
the module within the enclosure. Reference should be made to the enclosure
certificate. The installer shall ensure that the maximum ambient temperature of the
module when installed is not exceeded.
b) When the device is mounted in a zoned area, connection and disconnection of the
modules input supply voltage while live is only permitted if the potentially explosive
atmosphere is shown to be absent.
Inspection and maintenance
a)
Inspection and maintenance should be carried out in accordance with European,
national and local regulations which may refer to the IEC standard IEC 60079-17. In
addition specific industries or end users may have specific requirements which should
also be met.
b) Access to the internal circuitry must not be made during operation.
Repair
This product cannot be repaired by the user and must be replaced with an equivalent
certified product.
Marking
continued on next page
INM 9493-PS-XXX rev 1
17
Each device is marked in accordance with the Directive and CE marked with the
Notified Body Identification Number.
This information applies to products manufactured during or after the year 2010.
Figure 8.1
MTL 9493-PS-XXX
product label
18
INM 9493-PS-XXX rev 1
9
INM 9493-PS-XXX rev 1
APPENDIX A - DECLARATION OF CONFORMITY
19
DECLARATION OF CONFORMITY -
20
continued
INM 9493-PS-XXX rev 1
This page left intentionally blank
INM 9493-PS-XXX rev 1
21
This page left intentionally blank
22
INM 9493-PS-XXX rev 1
This page left intentionally blank
INM 9493-PS-XXX rev 1
23
NORWAY
Norex AS
Fekjan 7c, Postboks 147,
N-1378 Nesbru, Norway
AUSTRALIA
MTL Instruments Pty Ltd,
10 Kent Road, Mascot, New South Wales, 2020, Australia
Tel: +61 1300 308 374 Fax: +61 1300 308 463
E-mail: [email protected]
Tel: +47 66 77 43 80 Fax: +47 66 84 55 33
E-mail: [email protected]
BeNeLux
MTL Instruments BV
Terheijdenseweg 465, 4825 BK Breda
The Netherlands
RUSSIA
Cooper Industries Russia LLC
Elektrozavodskaya Str 33
Building 4
Moscow 107076, Russia
Tel: +31 (0) 76 7505360 Fax: +31 (0) 76 7505370
E-mail: [email protected]
Tel: +7 (495) 981 3770 Fax: +7 (495) 981 3771
E-mail: [email protected]
CHINA
Cooper Electric (Shanghai) Co. Ltd
955 Shengli Road, Heqing Industrial Park
Pudong New Area, Shanghai 201201
SINGAPORE
Cooper Crouse-Hinds Pte Ltd
No 2 Serangoon North Avenue 5, #06-01 Fu Yu Building
Singapore 554911
Tel: +86 21 2899 3817 Fax: +86 21 2899 3992
E-mail: [email protected]
Tel: +65 6 645 9888 Fax: +65 6 487 7997
E-mail: [email protected]
FRANCE
MTL Instruments sarl,
7 rue des Rosiéristes, 69410 Champagne au Mont d’Or
France
SOUTH KOREA
Cooper Crouse-Hinds Korea
7F. Parkland Building 237-11 Nonhyun-dong Gangnam-gu,
Seoul 135-546, South Korea.
Tel: +33 (0)4 37 46 16 53 Fax: +33 (0)4 37 46 17 20
E-mail: [email protected]
Tel: +82 6380 4805 Fax: +82 6380 4839
E-mail: [email protected]
GERMANY
MTL Instruments GmbH,
Heinrich-Hertz-Str. 12, 50170 Kerpen, Germany
UNITED ARAB EMIRATES
Cooper Industries/Eaton Corporation
Office 205/206, 2nd Floor SJ Towers, off. Old Airport Road,
Abu Dhabi, United Arab Emirates
Tel: +49 (0)22 73 98 12 - 0 Fax: +49 (0)22 73 98 12 - 2 00
E-mail: [email protected]
Tel: +971 2 44 66 840 Fax: +971 2 44 66 841
E-mail: [email protected]
INDIA
MTL India,
No.36, Nehru Street, Off Old Mahabalipuram Road
Sholinganallur, Chennai - 600 119, India
Tel: +91 (0) 44 24501660 /24501857 Fax: +91 (0) 44 24501463
E-mail: [email protected]
ITALY
MTL Italia srl,
Via San Bovio, 3, 20090 Segrate, Milano, Italy
Tel: +39 02 959501 Fax: +39 02 95950759
E-mail: [email protected]
JAPAN
Cooper Crouse-Hinds Japan KK,
MT Building 3F, 2-7-5 Shiba Daimon, Minato-ku,
Tokyo, Japan 105-0012
UNITED KINGDOM
Measurement Technology Limited,
Great Marlings, Butterfield, Luton
Beds LU2 8DL
Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
E-mail: [email protected]
AMERICAS
Cooper Crouse-Hinds MTL Inc.
3413 N. Sam Houston Parkway W.
Suite 200, Houston TX 77086, USA
Tel: +1 281-571-8065 Fax: +1 281-571-8069
E-mail: [email protected]
Tel: +81 (0)3 6430 3128 Fax: +81 (0)3 6430 3129
E-mail: [email protected]
Measurement Technology Limited,
Great Marlings, Butterfield, Luton
Beds, LU2 8DL, UK.
Tel: + 44 (0)1582 723633 Fax: + 44 (0)1582 422283
E-mail: [email protected]
www.mtl-inst.com
© 2016 MTL
All Rights Reserved
Publication No. INM 9493-PS-XXX 030216
February 2016
EUROPE (EMEA):
+44 (0)1582 723633
[email protected]
THE AMERICAS:
+1 800 835 7075
[email protected]
ASIA-PACIFIC:
+65 6 645 9888
[email protected]
The given data is only intended as a product
description and should not be regarded as a legal
warranty of properties or guarantee. In the interest
of further technical developments, we reserve the
right to make design changes.

advertisement

Related manuals

Download PDF

advertisement