OPERATOR ADAPTER GEC
Installation Instructions for General Electric Flexible Cable Operating Mechanisms
(For parts list, see Page 2)
)RUIORRUPRXQWHGHQFORVXUHVZLWK
WKHGLVFRQQHFWRQWKHULJKWIODQJH
0DVWHU
'RRU
)RURQHWKURXJKVL[GRRUIUHHVWDQGLQJHQFORVXUHV
ZLWKWKHGLVFRQQHFWWKHWKHULJKWIODQJH
0DVWHU
'RRU
)RUIORRUPRXQWHGHQFORVXUHVZLWK
WKHGLVFRQQHFWRQWKHFHQWHUSRVW
0DVWHU
'RRU
Rev. B
© 2018 Hoffman Enclosures Inc.
PH 763 422 2211 • nVent.com/HOFFMAN
P/N 89114664
89115503
The functions, fits and clearances of the installation described hereon are calculated from information supplied
by the manufacturers of the equipment to be installed. Be certain to check the function, fits and clearances
of all equipment both before and after installation to assure that it operates properly and safely and meets all
applicable codes, standards and regulations.
In the event the completed installation does not function properly or fails to meet any such codes, standards or
regulations, do not attempt to make alterations or operate the equipment. Report such facts immediately to:
Hoffman Customer Service
2100 Hoffman Way
Anoka, MN 55303
763.422.2211
http://hoffman.nvent.com/contact-us
Parts List
Operator Adapter, Catalog Number GEC, for General Electric Disconnects
Item No.
1
-2-
Description
Part No.
Qty.
ADAPTER PLATE, CABLE OPERATOR
27206002
1
2
PLATE GASKET
89109613
1
3
SCREW, 1/4-20X1/2 PAN HEAD
99401031
4
4
SLIDE ARM
26250001
1
5
SHOULDER COLLAR
26149001
1
6
SCREW, 1/4-20X7/8, HEX HEAD
99401030
1
7
LOCKWASHER, 1/4 SPRING
99401318
1
8
WASHER, FLAT
22101003
2
9
LOCKWASHER, 1/4 INTERNAL TEETH
99401300
2
10
NUT, 1/4-20 HEX
99401406
2
11
DOOR CATCH
23101002
1
12
SCREW, 10-32X3/8 PAN HEAD
99401007
2
13
LOCKWASHER, #10 INTERNAL TEETH
99401307
2
14
NYLON WASHER
26132003
4
15
INSTALLATION INSTRUCTIONS
89114664
1
© 2018 Hoffman Enclosures Inc.
PH 763 422 2211 • nVent.com/HOFFMAN
89115503
INTRODUCTION
This installation instruction is for General Electric SCH cable operating mechanisms. These mechanisms are for circuit breakers
mounted in Hoffman disconnect enclosures.
INSTALLATION STEPS
Step 1
Install operating plate (item1) and plate gasket (item 2) on the inside of the enclosure, behind the rectangular opening provided.
Gasket side with PSA should be attached to the adapter plate. Secure in place with four screws (item 3) and four nylon washers
(item 14).
Step 2
Assemble the General Electric SCH operating handle and cable adapter to the mounting plate which was installed in the enclosure
in step 1. Omit cap screw and lockwasher which fits into bottom hole of G.E. operating andle. Also omit G.E. stiffening bracket
which is not required.
Step 3
Install the slide arm (item 4) over the interlock part of the G.E. operating handle as shown. Note the the notch in the slide arm
is positioned toward the door opening. Place the smaller diameter end of the shoulder collar (item 5) through the oval slot in
the slide arm. Install long cap screw (item 6) with lockwasher (item 7) through shoulder collar into the bottom mounting hole
of the G.E. operating handle and tighten. The slide arm should move up and down smoothly. Install G.E. interlock blade per G.E.
instructions.
Step 4
Attach the bottom of the slide arm (item 4) to the offset arm of the lock release mechanism. Use two flat washer (item 8), two
lockwashers (item 9), and two hex nuts (item 10). Do not tighten until parts are adjusted (see step 5B).
Step 5
The handle safety lock release mechanism is adjustable.
(A) Check the adjustment of the factory installed roller bracket on enclosures with disconnect on right flange. The door
latch should hit against the latch stop portion of the roller bracket when the door is closed and latched. Adjust up or down
if necessary. The attached mechanism will then provide the necessary up−down motion required to operate the release
mechanism.
(B) Adjust the length of the slide arm assembly. With proper adjustment of the slide arm, the safety lock (on G.E. handle
operator) should release just before the master door is fully latched. Lengthen slide arm if safety lock releases too soon.
Shorten slide arm if safety lock releases too late.
Step 6
Attach the door catch (item 11), provided by Hoffman, to the tapped spacer on the door using the bottom set of mounting
holes. Use two screws (item 12) and lockwashers (item 13). The door catch prevents the door from being opened when the G.E.
operating handle is in the “ON” position.
Step 7
Drill and tap holes in panel per General Electric instructions. See General Electric instructions for locating holes within range of
cable length being used.
Step 8
Install panel in enclosure.
Step 9
Mount circuit breaker and cable operating mechanism on panel using General Electric instructions and parts.
89115503
© 2018 Hoffman Enclosures Inc.
PH 763 422 2211 • nVent.com/HOFFMAN
-3-
For Floor-Mounted, Two-Door Enclosures with Disconnect on Right Flange
For Floor-Mounted, Two-Door Enclosures with Disconnect on Centerpost
For One- Through Six-Door, Free-Standing Enclosures with Disconnect on Right Flange
+$1'/(5(7851635,1*
/2&.,1*/(9(5(;7(16,21
*(1(5$/(/(&75,&
&$%/($'$37(5
$66(0%/<
2))6(7$50
52//(5%5$&.(7
52//(5%5$&.(7/$7&+6723
/2&.5(/($6(0(&+$1,60
3$5762)5(/($6(0(&+$1,6021(1&/2685(:,7+',6&211(&7215,*+7)/$1*(
-4-
© 2018 Hoffman Enclosures Inc.
PH 763 422 2211 • nVent.com/HOFFMAN
89115503
">