Bard WPV 30B, WPV 36B, WPV 53B, WPV 62B water source heat pump Installation instructions
Below you will find brief information for water source heat pump WPV 30B, water source heat pump WPV 36B, water source heat pump WPV 53B, water source heat pump WPV 62B. This installation instructions document provides guidance on installing and setting up these heat pumps.
PDF
Download
Document
Advertisement
Advertisement
INSTALLATION INSTRUCTIONS HIGH EFFICIENCY WATER SOURCE PACKAGED HEAT PUMPS MODELS WPV30B WPV36B WPV53B WPV62B Ground Water Temperatures 45 - 75 Earth Loop Fluid Temperatures 30 - 110 F MANUAL 2100-155 REV. E SUPERSEDES REV. D FILE VOL. I, TAB 8 COPYRIGHT FEBRUARY, 1989 BARD MANUFACTURING COMPANY BRYAN, OHIO II. 111. IV. VI. VII. VIII. IX. INDEX General Installation . . . BTUH Capacity Selection . Site Selection . Ductwork Filter Electrical Wiring . A. Main Power Un с) NO >= Condensate Drain . . . Piping Access To The Unit ‚ Water Connections . Well Pump Sizing LO COP o Sequence Of Operation . . 1. Cooling With Or Without Duct ‘Heaters 2. Single Stage Heat Without Duct Heaters 3. Two Stage Heat With Duct Heaters 4. Emergency Heat ea System Start Up Procedure . Water Corrosion . Remedies Of Water Problems Lake and Pond Installations . Earth Coupled Ground Loop Applications Add-On Heat Recovery Hot Water Heater . Installation . Start-Up, Check-Out Maintenance . Heat Pump Service . coe. B. Control Circuit--Low Voltage Wiring ) Ca Où UT UT U1 UT Æ> La fa LD (5) La) LC dd Sd] co 10 10 12 13 13 15 Figure Figure Figure Figure Figure Figure Figure Figure Figure Table Table Table Table Table Table Table Table Table Table Table LD 00 4 Ji UN La 6) РО = fi ja — с = * Table 12 . VO 00 1 0% UT Je LY NO = INDEX OF FIGURES AND TABLES a = = 8 4 вто ово обо = * ® 2 т 4% ®» a ай # a a = Ti » = = # + MLS AMOLS SIONES Y NI ANO NOLLYTWISNI OL L3NI@V) SIHL MAI) AYH S3007 NOELY TIWISNI 399I719dY “0351 SI 1900 DIV NOML3Y ON 41 :310N ( ONISY) D 3015 149183 NO al NADHS SY 031015NI 38 AY) 1NYd $539 SNIdId 7 NI d31YA — JAVA NOISNVdXT — IND d31YA — Lead 3) A03S NOLITS —— HILTAS . RIMSSI HH JAVA Ad ——7 Y ENvd DINO] — IB — / ——— USO) 130d IAT —— JOI¥HISIO HL IAS — 38d AM ASSY JA TVA — MADR LYH didlS IWNIWJIL Are . à * L À | \ х08 №1 М JOY L10A HOIH NOTLYOO 1 1u1N0) HOLLIVdYI N HOSSJUdN0) ra | [rm IV du 18338 AY Y 10000) Figure ] Alr Flow WATER SOURCE HEAT PUMP Tharmostatic Vapor Indoor COOLING CYCLE E slon Valve Lina Coll Suction Sarvice Port Extarnal Equalizer a Comprassor Tube Olscharge Line Reversing u] High Pressure Vapor Valve Low Prassura Vapor E-] Low Pressura Liquid D'scharge Servica Port HE High Prassura Liquid Water Qut GHDirectional Thermosistic Expansion Valve Water In Strainer Air Flow WATER SOURCE HEAT PUMP HEATING CYCLE Thermostatic Vapor Indoor Valve Line / Coil & Capillary _ — fit Suction Service Port External Equalizer Compressar Tube Discharge Lina Reveriing u] High Pressure Vapor Valve Low Pressure Vapor E- 3 Low Pressure Liquid Discharge ” Service Port SN High Pressura Liquid ny Water Qui Bi-Directionsl Thermostallc Expansion Valve -— — Water In = тэ Ef Strainer Figure Z I. GENERAL Units are shipped completely assembled and internally wired, requiring only duct connections, thermostat wiring, 230-208 volt AC power wiring, and water piping. The equipment covered in this manual is to be installed by trained, experienced service and installation technicians. Any heat pump is more critical of proper refrigerant charge and an adequate duct system than a cooling only air conditioning unit, These instructions and any instructions packaged with any separate equipment required to make up the entire heat pump system should be carefully read before beginning the installation, Note particularly any tags and/or labels attached to the equipment. While these instructions are intended as a general recommended quide, they do not in any way supersede any national and/or local codes. Authorities having jurisdiction should be consulted before the installation is made. Unpacking Upon receipt of the equipment, the carton should be checked for external signs of shipping damage. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier's agent. II. INSTALLATION 1. BTUH Capacity Selection Capacity of the unit for a proposed installation should be based on heat loss calculations made in accordance with methods of the Air Conditioning Contractors of America, formerly National Warm Air Heating and Air Conditioning Association. The air duct system should be sized and installed in accordance with Standards of the National Fire Protection Association For The Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No. 90A, and Residence Type Warm Air Heating and Air Conditioning Systems, NFPA No. 90B, 2. Site Selection The unit may be installed in a basement, closet or utility room provided adequate service access is insured. Ideally, three sides of the unit should have a minimum access clearance of two feet but the unit can be adequately serviced if two or only one side has the minimum two feet clearance. The unit should be located in the conditioned space to prevent freezing of the water lines. Clearance to combustible materials is Ô inches for the heat pump. If an optional duct heater is installed, follow the instructions packed with the duct heater for specifications regarding clearance to combustible naterial. Before setting the unit, consider ease of piping, drain and electrical connections for the unit. Also, for units which will be used with a field installed heat recovery unit, consider the proximity of the unit to the vater heater or storage tank, Place the unit on a solid base, preferably concrete, to minimize undesirable noise and vibration, DO NOT elevate the base pan on rubber or cork vibration eliminator pads as this will permit the unit base to act like a drum, transmitting objectionable noise, 3. Ductwork If the unit is to be installed in a closet or utility room which does not have a floor drain, a secondary drain pan under the entire unit is highly recommended. DO NOT install the unit in such a way that a direct path exists between any return grille and the unit. Rather, insure that the air entering the return grille will make at least one Lurn before entering the unit air coil. This will reduce possible objectionable compressor and air noise from entering the occupied space. Design the ductwork according to methods given by the National Warm Air Heating and Air Conditioning Association, When duct runs through unconditioned spaces, it should be insulated with vapor barrier. It is recommended that flexible connections be used to connect the ductwork to the unit in order to keep the noise transmission to a minimum, 4, Filter This unit must not be operated without a filter. It comes equipped with a disposable filter which should be checked often and replaced if dirty. Insufficient air flow due to undersized duct systems or dirty filters can result in nuisance tripping of the high or low pressure control, Refer to Table 2 & 3 for correct air flow and static pressure requirements. See Figure 3. FIGURE 3 A = \J All electrical connections are made through the top of the unit. High voltage connections are made with wire nuts to the {actory-provided pigtail leads in the junction box, Low voltage connections are made to the terminal strip mounted on the top of the unit, Refer to the wiring diagram for connecting the terminals. 5. Electrical Wiring A. Main Power Refer to the unit serial plate for wire sizing information and correct overcurrent protection size. Each unit is marked with a "Minimum Circuit Ampacity.” This means that field wiring connectors must be sized to carry that amount of current. Each unit and/or wiring diagram is also marked "Use Copper Conductors Only,” meaning the leads provided are not suitable for aluminum wiring. Refer to the National Electric Code for complete current-carrying capacity data on the various grades of wiring material. The unit rating plate lists "Maximum Overcurrent Prolective Device” Lhat 15 to be used wilh the equipment. This device may be a time delay fuse or HACR type circuit breaker. The correct size overcurrent protective device must be used to provide for proper circuit protection and to avoid nuisance trips due Lo the momentary high starting current of the compressor motor. В. Control Circuit--Low Voltage Wiring A 24 volt terminal strip is mounted on top of the unit, Two types of thermostats are available: 1) Single stage heat, single stage cool to cperate the heat pump alone--without backup duct style electric heaters. This thermostat is equipped with a signal light to indicate when the unit is "locked out” because of the low or high pressure control. Refer to the wiring diagrams at the end of this manual for correct connection of the terminals. 2) Two stage heat, single stage cool to operate the heat pump or duct heaters on heating or the heat pump on cooling. This thermostat is also equipped with a signal light to indicate when the unit is "locked out” because of operation of the low or high pressure control, In addition, a second signal light tells when the unit has been placed in Emergency Heat. Refer to the wiring diagram at the end of this manual and to the wiring diagram packed with the duct heater for correct connection of the low voltage terminals. 6. Condensate Drain Determine where the drain line will run. This drain line contains cold water and must be insulated to avoid droplets of water from condensing on the pipe and dropping on finished floors or the ceiling under the unit, A trap MUST BE installed in the drain line and the trap filled with water prior to start up. The use of plugged tees in place of elbows to facilitate cleaning is highly recommended. Drain lines must be installed according to local plumbing codes. It is not recommended that any condensate drain line be connected to a sewer main. The drain line enters the unit through the water access panel, ((3) Figure 4) and connects to the FPT coupling under the condensate drain pan. 7. Piping Access To The Unit Water piping to and from the unit enters the unit casing through the water access panel. Piping connections are made directly to the heat exchanger coil and are 3/4" or 1" FPT. The access panel can be installed on any one of three sides (any side of the casing except the air coil side). It is highly recommended that the piping fron the water coil to the outside of the casing be installed while the unit is completely accessible and before it is finally set in position. 8. Water Connections It is very important that an adequate supply of clean, non-corrosive water at the proper pressure be provided before the installation is made. Insufficient water, in the heating mode for example, will cause the low pressure control to trip, shutting down the heat pump. In assessing the capacity of the water system, it is advisable that the complete water system be evaluated to prevent possible lack of water or water pressure at various household fixtures whenever the heat pump turns on. All plumbing to and from the unit is to be installed in accordance with local plumbing codes. The use of plastic pipe, where permissible, is recommended to prevent electrolytic corrosion of the water pipe. Because of the relatively cold temperatures encountered with well water, it is strongly recommended that the water lines connecting the unit be insulated to prevent vater droplets from condensing on the pipe surface. Refer to Piping, Figure 4. Slow closing Solenoid Valve (6) with a 24V coil provides on/off control of the water flow to the unit, Refer to the wiring diagram for correct hookup of the valve solenoid coil. Constant Flow Valve (7) provides correct flow of water to the unit regardless of variations in water pressure. Observe the water flow direction indicated by the arrow on the side of the valve body. Following is a table showing which valve is to be installed with vhich heat pump. Constant Reat Pump Flow Flow Yalve Model Rate Part Number | "РУЗОВ 4 GPM 8603-010 WPY36B 5 GPM 8603-011 NPY53B 6 GPM 8603-007 WPYG2B 8 GEM 8603-008 Strainer (5) installed upstream of constant flow valve (7) to collect foreign material which would clog the flow valve orifice. The figure shows the use of shut-off valves (9) and (11), on the in and out water lines to permit isolation of the unit from the plumbing system should future service work require this. Clobe valves should not be used as shutoff valves because of the excessive pressure drop inherent in the valve design. Instead use gate or ball valves as shut-offs so as to minimize pressure drop. Drain cock (8) and (10), and tees have been included to permit acid cleaning the refrigerant-to-water coil should such cleaning be required. See WATER CORROSION. Drain Cock (12)provides access to the system to check water flow through the constant [low valve to insure adequate water flow through the unit. A water meter 1-10 GPM (8603-013) is used to check the water [low rate, FIGURE 4 9. Well Pump Sizing Strictly speaking, sizing the well pump is the responsibility of the well drilling contractor. It is important, however, that the HYAC contractor be familiar with the factors that determine what size pump will be required. Rule of thumb estimates will invariably lead to under or oversized well pumps. Undersizing the pump will result in inadequate water to the whole plumbing system but with especially bad results to the heat pump--NO HEAT/NO COOL calls will result. Oversized pumps will short cycle and could cause premature pump motor or switch failures. The well pump must be capable of supplying enough water and at an adequate pressure to meet competing demands of water fixtures. The well pump must be sized in such a way that three requirements are net: 1. Adequate flow rate in GPM. д. Adequate pressure at the fixture. 3. Able to meet the above from the depth of the well-feet of lift. The pressure requirements put on the pump are directly affected by the diameter of pipe being used as well as by the water flow rate through the pipe. The worksheet included in manual 2100-078 should quarantee that the well pump has enough capacity. It should also ensure that the piping is not undersized which would create too nuch pressure due to friction loss. High pressure losses due to undersized pipe will reduce efficiency and require larger pumps and could also create water noise problems. ITI. SEQUENCE OF OPERATION 1. Cooling With Or Without Duct Heaters Whenever the system lever is moved to COOL, thermostat system switch completes a circuit R to 0, energizing the reversing valve solenoid. On a call for cooling, the cooling bulb completes a circuit from R to G, energizing the blower relay coil. The blower relay contacts complete a 230 volt circuit to the blower motor and the blower operates. R to Y circuit is completed at the same time as the fan circuit and current flows from Y to terninal 4 at the lockout relay. Terminal 4 of the lockout relay provides two paths for current flow. 1. Through the lockout relay coil which offers the resistance of the lockout relay coil. 2. Through the normally closed contacte of the lockout relay to terminal 5 of the lockout relay and then through the high and low pressure switches to the compressor contactor coil, If the high and low pressure switches remain closed (refrigerant pressure remains normal), the path of least resistance is through these safety controls to the compressor contactor coil, The contacts of the compressor contactor complete a 230 volt circuit to the compressor and the compressor runs. If discharge (suction) pressure reaches the set point of the high (low) pressure control, the normally closed contacts of the high (low) pressure control open and current no longer flows to the compressor contactor coil--the coil drops out. Current now can take the path of least resistance through the lockout relay coil, energizing the lockout relay coil and opening terminals 4 and 5 of the lockout relay. The lockout relay will remain energized as long as a circuit is completed between R and Y at the thermostat. In the meantime, since the compressor is not operating, refrigerant pressure will equalize and the high (low) pressure switch will automatically reset. However, the circuit to the compressor contactor will not be complete until the lockout relay is de-energized by moving the thermostat system switch to OFF, breaking the circuit from R to Y dropping out the lockout relay coil and permitting terminalis 4 and 5 to make, When Lhe high (low) pressure switch closes, a circuit is conplete to L at the thermostat, energizing the signal light to indicate a malfunction, When the system switch is moved from OFF to COOL, the cycle is repeated. 2. Single Stage Heat Without Duct Heaters Compressor circuit R to Ÿ including lockout relay and pressure controls is the same as cooling, Blower circuit R to G is the same as cooling. With system switch set to HEAT, no circuit is completed between R and O and reversing valve solenoid is not energized. 3. Two Stage Heat With Duct Heaters First stage heat is the same as single heating without duct heater. When the second stage thermostat bulb nakes, a circuit is completed from C to W2, energizing the duct heater heat contactor, through the heating element and manual reset limit. C to W2 also simultaneously energizes the 24 voit coil on the interlock relay, closing the contacts, which in turn energize the low voltage coil on the blower relay to close the high voltage contacts and power the blower motor. The elements and blower remain energized as long as C to W2 are made. The following is a verbal description of the proper procedure for connecting the low voltage hookups for the duct heater. 1. Black wire from duct heater to C on the 24 volt terminal block. 2. Green wire from duct heater to green wire from thermostat, These wires must be wire nutted and isolated from the terminal block. Failure to do so will result in improper heater operation, 3. Connect green with tracer from heater to the G terminal on the 24 volt terminal block. 4. Connect the white wire from the heater to W2 on 24 volt terminal block. A. For the 15 and 20kw duct heaters, connect the white and white with black tracer wires to W2. 4. Emergency Heat When the system switch is moved to EMER, the compressor circuit R to Y is disconnected, Control of the electric heaters is fron C to W2 and W3 through the thermostat second stage heating bulb. Blower opération is controlled by the second stage heating bulb. Operation is the same as above, "Two Stage Heat With Duct Heaters." IV. SYSTEM START UP PROCEDURE |. Be sure main power to the unit is OFF at disconnect. 2. Set thermostat system switch to OFF, fan switch to AUTO, 3. Move main power disconnect to ON. Power should be on to unit for a minimum of four hours or sixty minutes per pound of refrigerant. This allows the crankcase heater to drive any refrigerant liquid out of the conpressor sump. This procedure should be followed whenever the power has been off for twelve hours or longer. Except as required for safety while servicing--NO NOT OPEN THE UNIT DISCONNECT SWITCH. 4, Check system air flow for obstructions. A. Move thermostat fan switch to ON. Blower runs. В, Be sure all registers and grilles are open. C. Move thermostat fan switch to AUTO. Blower should stop. 5. Fully open the manual inlet and outlet valves. 6. Check water flow. A. Connect a water flow meter to the drain cock (12, Figure 4) between the constant flow valve and the solenoid valve. Run a hose from the flow meter to a drain or sink. Open the drain cock. B. Check the water flow rate through constant flow valve to be sure it is the same as the unit is rated for. (Example 4 GPM for a WPY30) | С. When water flow is okay, close drain cock and remove the water flow meter. The unit is now ready to start, 7. Start the unit in cooling mode. By moving the thermostat switch to cool, fan should be set for AUTO. A. Check to see the solenoid valve opened, 8. Check the system refrigerant pressures against the cooling refrigerant pressure Table 11, Page 19 in the Installation Manual for rated water flow and entering water temperatures. If the refrigerant pressures do not match, check for air [low problem then refrigeration system problen. 9. Switch the unit to the heating mode. By moving the thermostat switch to heat, fan should be set for AUTO. A. Check to see the solenoid valve opened again. 10. Check the refrigerant system pressures against the heating refrigerant pressure Table 12, Page 20 in Installation Manual. Once again, if they do not match, check for air flow problems and then refrigeration. system problems, NOTE: If a charge problem is determined (high or low}: Check for possible refrigerant leaks. Discharge all remaining refrigerant from unit. Evacuate unit down to 29 inches of vacuum, Recharge the unit with refrigerant by weight. This is the only way to insure a proper charge. Кр a OF све V. WATER CORROSION Two concerns will immediately come to light when considering a water source heat pump, whether for ground water or for a closed loop application: Will there be enough water? And, how will the water quality affect the system? Water quantity is an important consideration and one which is easily determined. The well driller must perform a pump down test on the well according to methods described by the National Well Water Association. This test, if performed correctly, will provide information on the rale of [low and on the capacity of the well, It is important to consider the overall capacity of the well when thinking about a water source heat pump because the heat pump may be required to run for extended periods of time, The second concern, about water quality, is equally important. Generally speaking, if the water is not offensive for drinking purposes, it should pose no problem for the heat pump. The well driller or local water softening company can perform tests which will determine the chemical properties of the well water. Water quality problems will show up in the heat pump in one or more of the following ways: 1. Decrease in water flow through the unit. 2. Decreased heat transfer of the water coil (entering to leaving water temperature difference is less). There are four main water quality problems associated with ground water. These are: 1. Biological Growth, This is the growth of microscopic organisms in the water and will show up as a slimy deposit throughout the water system. Shock treatment of the well is usually required and this is best left up to the well driller. The treatment consists of injecting chlorine into the well casing and flushing the system until all growth is removed. 2. Suspended Particles In The Water, Filtering will usually remove most suspended particles (fine sand, small gravel) from the water. The problem with suspended particles in the water is that it will erode metal parts, pumps, heat transfer coils, etc, So long as the filter is cleaned and periodically maintained, suspended particles should pose no serious problem. Consult with your well driller. 3. Corrosion Of Metal. Corrosion of metal parts results (from either highly corrosive water (acid water, generally not the case with ground water) or galvanic reaction between dissimilar metals in the presence of water. By using plastic plumbing or dielectric unions galvanic reaction is eliminated. The use of corrosion resistant materials (such as the Cupro Nickel coil) through the water system will reduce corrosion problems significantly. 4. Scale Formation. Of ail the water problems, the formation of scale by ground water is by far the most common. Usually this scale is due to the formation of calcium carbonate but magnesium carbonate or calcium sul{ate may also be present. Carbon dioxide gas (CO2), the carbonate of calcium and magnesium carbonate, is very soluble in water. It will remain dissolved in the water until some outside factor upsets the balance. This outside influence may be a large change in water temperature or pressure, When this happens, enough carbon dioxide gas combines with dissolved calcium or magnesium in the water and falls out of solution until a new balance is reached, The change in temperature that this heat pump produces is usually not high enough to cause the dissolved gas to fall out of solution. Likewise if pressure drops are kept to a reasonable level, no precipitation of carbon dioxide should occur. VI. REMEDIES OF WATER PROBLEMS Water Treatment. Water treatment can usually be economically justified for closed loop systems. Rowever, because of the large amounts of water involved with a ground water heat pump, water treatment is generally too expensive, Acid Cleaning The Water Coil Or Heat Recovery Unit. If scaling of the coil is strongly suspected, the coil can be cleaned up with a solution of Phosphoric Acid (food grade acid). Follow the manufacturer's directions for nixing, use, etc. Refer to the "Cleaning Water Coil”, Figure 5. The acid solution can be introduced into the heat pump coll through the hose bib (Part 8 of Figure 5), Be sure the isolation valves (Parts 9 and 11 of Figure 5) are closed to prevent contamination of the rest of the system by the coil. The acid should be pumped from a bucket into the hose bib (Part 8, Figure 5) and returned to the bucket through the other hose bib (Part 10, Figure 5). Follow the manufacturer's directions for the product used as to how long the solution is to be circulated, but it is usually circulated for a period of several hours. FIGURE 5 po DEF ACID SOLUTION <> (See Text) VII. LAKE AND POND INSTALLATIONS Lakes and ponds can provide a low cost source of water for heating and cooling with a ground water heal pump. Direct usage of the water without some filtration is nol recommended as algae and turbid water can foul the water to freon heat exchanger. Instead, there have been very good results using a dry well dug next to the water line or edge. Normal procedure in installing a dry well is to backhoe a 15 to 20 foot hole adjacent to the body of water (set backhoe as close to the water's edge ns possible). Once excavated, a perforated plastic 10 casing should be installed with gravel backfill placed around the casing. The gravel bed should provide adequate filtration of the water to allow good performance of Lhe ground water heat pump. The following is a list of recommendations to follow when installing this type of systen: A. A lake or pond should be at least 1 acre (40,000 square feet) in surface area for each 50,000 BTUs of ground water heat pump capacity or have 2 times the cubic feet size of the dwelling that you are trying to heat (includes basement if heated). The average water depth should be at least 5 feet and Lhere should be an area where the water depth is at least 12 to 15 feet deep. If possible, use a submersible pump suspended in the dry well casing. Jet pumps and other types of suction pumps normally consume more electrical energy than similarly sized submersible pumps. Pipe the unit the same as a water well system. Size the pump to provide necessary GPM for the ground water heat pump. A 12 GPM or greater water flow rate is required on all modes when used on this type system, A pressure tank should be installed in the dwelling to be heated adjacent to the ground water heat pump. A pressure switch should be installed at the tank for pump control. Ail plumbing should be carefully sized to compensate for friction losses, etc., particularly if the pond or lake is over 200 feet from the dwelling to be heated or cooled. Keep all water lines below low water level and below the frost line. Most installers use 4-inch field tile (rigid plastic or corrugated) for water return to the lake or pond. The drain line discharge should be located at least 100 feet from the dry well location. The drain line should be installed with a slope of 2 inches per 10 feet of run to provide complete drainage of the line when the ground water heat pump is not operating. This gradient should also help prevent freezing of the discharge where the pipe terminates above the frost line, locate the discharge high enough above high water level so the water will not back up and freeze inside the drain pipe. Where the local conditions prevent the use of a gravity drainage system to a lake or pond, you can instead run standard plastic piping out into the pond below the frost and low water level, WARNING THIN ICE MAY RESULT IN THE VICINITY OF THE DISCHARGE LINE. 11 For complete information on water well systems and lake and pond applications, refer to Manual 2100-0788 (or later edition), available from your distributor, VIII. EARTH COUPLED GROUND LOOP APPLICATIONS This unit is also designed to work on earth coupled ground loop systems, however these systems operate at entering water (without antifreeze) temperature well below the temperature normally experienced in water well system. Therefore, when this unit is connected to an earth coupled ground Icop, an optional thermostat kit, 8620-002, is required. The kit consists of a SPST thermostat to sense refrigerant temperature and shut off compressor should extremely low antifreeze temperatures or loss of flow occur. See Installation Instructions for thermostat kit packed with the thermostat. When used on these systems, Item 5 strainer, Item 6 solenoid valve, and Item 7 constant flow valve (refer to Figure 4) are not needed. An external circulating pump must be used. For information on earth coupled loop design, piping connections to heat pump and installation refer to Manual 2100-099G, "Earth Coupled Loop System Design Manual," available from your distributor. FIGURE 6 We!l Cap Y Y Y Y VY y ¥ LAKE AND POND APPLICATIONS | Electrical Line Fithezss Adaptar Те Preysmra Tank > AD e A ou % E Sh = aati ep + EMRE Spb SEE See TTT fri E A E о NE A RR EE, Te rea = ПН SR RE à a. fr Sis: к PE Ro A nes e at, re TN TA "ES Ea ih, y at р dec d 4; en ee e Ocio ia TE EN e e Ч mew Ve eR 1e IX. ADD-ON HEAT RECOVERY HOT WATER HEATER NOTE: This section applies only if a water heating recovery device is added. GENERAL This high efficiency water source heat pump series was designed for easy field installation of a heat recovery device for hot water heating commonly known as a desuperheater water heater. The amount of annual hot water supplied and thus additional energy cost savings will depend on the amount of hot water your family uses and the number of hours your heat pump operates. We recommended that a U.L. recognized heat recovery device be used, This device must be suitable for potable water. Installation 1. Fellow all local, state and national codes applicable to the installation of heat recovery devices. 2. Follow the installation procedures you receive with the heat recovery device. 3, Connect the refrigerant lines between the heat recovery device and the heat recovery valves in the heat pump using the inlet and exit panel on the lower left side of the unit as shown in Figure 7. Keep dirt and moisture out of the inter-connecting tubing using good refrigeration service procedures. (See Figure 7). Use refrigeration grade (type L) copper tubing. The tube diameter should be the same as the valve for lengths up to 15 feet each way. For lengths between 15 and 25 feet, increase the diameter 1/8". Avoid placing the heat recovery device over 25 feet from the heat pump. This tubing should be insulated with Armaflex insulation. Tubing should be protected from abrasion and damage. FIGURE 7 _- >. ` — O, oo \ - 50 ” CONNECTION BETWEEN OUTLET OF 0 - HEAT RECOVERY DEVICE AND п DISCHARGE LINE TO REVERSING VALVE CONNECTION FROM COMPRESSOR DISCHARGE TUBE TO INLET OF HEAT RECOVERY DEVICE REFIRIGERANT FLOW 13 “ Evacuate the heat recovery device inter-connecting tubing and heat exchanger through the process service ports A or B shown in Figure 8 and pressurize with Refrigerant 22 and perform a leak check. Release the charge used for pressurization, leak check and re-evacuate. Add 1 ounce of refrigerant for each 10 feet of additional interconnecting tubing to the total system charge. Replace the caps and tighten. FIGURE 8 PROCESS SERVICE PORT *g* TD REVERSING YALVE LP Cas GEL N x N PINCH DISCHARGE TUBE CLOSED AS SHOWN, USING A REFRIGERATION PINCH OFF TOOL WITH SMOOTH ROUNO - pe PROCESS \ PLUNGER EDOES. DO NOT USE PLIERS (R SIMILAR SERVICE cap gr TOOL WITH SHARP EDGES THAT COULD DAMAGE THE COPPER TUBING AND REDUCE [TS STRENGTH. FROM COMPRESSOR DISCHARGE 14 5. Tighten the plunger caps "C" and "D" shown in Figure 8. This forces down a plunger which shears a frangible plug and moves it out of the refrigerant flow path (see Figure 9). This now permits the discharge refrigerant from the compressor to flow through valve at plunger "C" (Figure 8) to the heat recovery coll heat exchanger and back through the valve at plunger "D" and then to the condenser inlet, FIGURE NN ZANT N SS e аа TTT: Matal:Lo-Metal Seal ZAS AE ER НЕ Y AN ZAHN ANN LEN ALS NY J N O-Ring ASE O-Ring HS | NN IH ——0-Rine Plunger N JE Plunger Plunger | _~Frangible Plug Ц В нЕ! . UH \ — frangible Plug (JT Relining Cup a Retaining Cup When the plunger cap is tightened, The O-Ring seal the plunger shears the frangible plug forcing it into the retaining cup. This opens the valve for Frangitle Plug Retaining Cup on Lhe plunger ~ Tightening the plunger cap 1/4 prevents leakage while the valve turn after it bottoms results in a is being opened. netal-to-netal seal. 6. Wire the heat recovery device per the diagram supplied with the heat recovery unit, Turn power to the air conditioner off prior to wiring the heat recovery unit, DO NO in any way alter any factory or safety circuits on the air conditioner. Start-Up, Check-Out Maintenance Follow the procedures supplied with the heat recovery unit, Heat Pump Service While performing any heat pump service analysis, turn water pump switch to off as it could affect the refrigerant pressures and be misleading. 15 TABLE | _ ACCESSORY ITEMS--DUCT HEATER (See drawing below) Minimum | Wire Size | Max. Dimensions > Part No. PH | Volts | KW | Ampacity | CU AL | Fuse | AL BIC IDIELE 8604-080 1 240 5 21 #10 48 30 8 110 | 4 } 7j 7112 8604-081 1 | 240 {9.8 52 #6 #41 55 | 8 [10 | 4 | 7 | 7 [16 - AD 240 [14.7 78 #4 #1 | 8 |15 {18 | 4 | 1 | 9 |18 8604-0832) 1 240 [19.2 100 #2 #0 | 100 1125 118 | 4 [11 | 9118 > Use wire suitable for a least 75 degree E, 2) Fused units (over 48 anperes). TABLE 2 [NDOOR BLOWER PERFORMANCE CEM--DRY COIL WITH FILTER (1) Mode] WPY30B WPY53B, WPY628 With WPY53B, WPV62B Without WPY3GB Ontional Cwá45 Installed Ontional Cw45 Installed E.S.P. In.| High ¡Mediun| Low | High | Medium | Low High Medium WC. 0 1400 | 1270 | 1210 | 1920 | 1780 | 1600 1920 1750 ‚10 1345 | 1230 | 1170 | 1880 | 1750 | 1580 1880 1710 .20 1280 | 1180 | 1130 | 1830 | 1720 | 1550 1830 1670 ‚ 30 1210 | 1110 | 1090 { 1810 1680 1540 1750 1630 ‚ 40 1130 | 1070 | 1040 | 1750 | 1630 | 1500 1700 1570 .50 1050 | 1000 | 980 | 1650 | 1570 | 1440 1610 1520 ‚ 60 970 | 890 | 900 | 1580 { 1500 | 1400 1550 1450 (1) For wet coil CFM multiply by .96 TABLE 3 TABLE 4 Rated Recommended CONSTANT FLOW VALVES Model CFM Air Flow Range--CFM Min. Available Flow Rate HPY3OR 1000 900 - 1090 Part No. Pressure PSIG СРМ WPY36B | 1200 1070 - 1345 8603-007 На 6 WPY53B | 1550 1400 - 1700 8603-008 15 8 - WPV62B 1700 1530 - 1830 8603-010 15 4 | _8603-011 15 0 5 TABLE 5 (D The pressure drop through the constant WATER COIL PRESSURE DROP flow valve will vary depending on the Моде! | WPY30B | WPV36B | WPVS3B | WEYOZB available pressure ahead of the valve, GEM PSIG PSIG PSIG PSIG Unless a minimum of 15 psig is available 4 2.0 1.9 -- -- innediately ahead of the valve no vater 5 3.0 2.0 -- -- will flow 6 4,2 2.4 2.5 2.5 7 5.7 3.0 3.2 3.5 8 7.5 3.9 4,0 4,5 9 9.5 5.5 5.2 5.6 10 12.0 7.6 6.5 6.7 11 14.8 10.4 7.7 8.0 12 17.6 15.3 9.0 9.3 13 20.3 20.6 10.5 10.7 14 > -- 12.0 12.3 15 -- -- 13.9 15.5 16 -- ~~ 15.8 18.3 TABLE 6 FLOW RATES REQUIRED TO MAINTAIN RATED CAPACITY WPY3OB | WEV36B| WPY53B/ NPY62B Flow rate required CPM vater 4 5 6 8 Flow rate required GPM 15% propylene glycol | 5.2 | 6.5 | 7.8 | 10.4 | e Flow rate required GPM 30% propylene glycol | 6.4 | 8.0 | 9.6 | 12.8 LT Air Flow 16 uotjnjos azaalz-tjue salrmnbey © Atuo tun (1) 00194 [007Ez | COL0E [72,758 0096€ [00122 | 0060€ | L9/08 00/95 00$ 12 100952 |29/51|0°2|0`$) 01 00567 10027 10066 |21158 00807 |0OTEZ | OO9TE | 29/08 7°8 100685100%27 100912 |29/5110°210°5) 001 ГОГ (0052# 100552 [00996 121/58 96 [002% [0012100926 | 19/08 Z'6 10080%|00F€7|00967|79/SL|0*7|0*S) 06 61 [0065$ 100592 [0001521758 9`0Г 100857 100252 |00Т$5| (9/08 00% 1006651005991 04| ©’0г 100(2% (0052 1009 15 \29/5110°210'5| 08 6°0Г 100105 100118 100965 | 21/58 121 [00759 |00%92 [00096 | 19/08 64° 166915 100023| 04| (’1Г [00597100958 100855 129/51 |0°210°5| OL 9 FI 10036 100062 10052 | 21/58 ¿“EL 10087 100912 1005851 19/08 9’ 1006921008451 04 || ©°6Т [00215100892 |00Т9Е| 29/54 10°2|0°$| 09 9°9Г 10095500506 [00159 | 21/58 9°9{ 10010500682 10001$ | 19/08 LE E |009EZ|009€€| OL|| TSI 1001751000821 00585 | 29/51 |0`219°9| OS {`81 [00169 [00116 0008? | 21/58 9°1{ (00925 00205 |001#$ 1 (9/08 26 100002 100505) 041] L°LU 0068} 100562 100013 29/54 10`210°5| (207 217 100227 1001661001 15| 21/58 6°61 [0055 |009 16 0097$ | 19/08 50° |O06PTIOOELZI OL/| €’6T 10026% 100905 1000551 79/5110°710°5| (© = OU MD Y dl o co (Odoof vAL | 81 [iva}|(Œusa| dus | IS | OL | IVA CAMINO) IMS ONILVAH ON1T000 Wi) 0071 8 JICAdM SONILVA NOIZVOITddŸ AONSIOIMAA ONY AZIOYdVO 8 Ze (197eM JO SaUOUT) alnssald 317e]S [eulaixg = 459 (CIF C YX S13ea 10m (2107) * Gutzeay (2701--anuewiojIad 10 1491213320) » 009 18/19 Uotjd10sqe jo 7eay [ejo[ = VAL 19/19 Áyroedeo bureay rego] = Hl s97eA jrUm (210) * Burfooo [ejoj--o1Jel Aoustorzje Abreug = YIY 1p/n39 101323131 JO 1edy reja[ = MAL ON3931 UOTIN{OS 37931]-T7Ue SarTNDAy ÂTuo 310 $8 T00ZSE [00981100657 121/58 2'9 (000ZE|00LL{|009Z7 119/08 6'L lootoe[oozit[o0ztziz9/sL{0 e|0 +] oft S'6 |0095€|00¥61]00652]2L/58 0°6 — 10052510026 100562 | (9/08 8'9 [0050600081 100122 29/50 1075109] 001 8'OT |0029€100207|00TL2124/58 Гог [0062510026 1100092 | 19/08 1°6 10060600481 |00Т62 | 29/51 |0°610`#| 06 0°2т [0015100012 100592 |20/58 E*IT [00/55 |00102 100652 119/08 52% (00152100675) 91| 601 1090115100561 |00572 129/51 10°510°91 08 SEL [00L8€|00612|0010€| 76/98 L°ZT |006¥€|00602]00¥LZ{L9/08 16€ 00672000051 011! 6°21 10082500502 |00852|29/5110°5|0'91 OL 2 SI [10016610082 [0002$ [21/58 с'#Т. 100196 [00912 [00162 | (9/08 [9°6 |00%61|00892| 04| 6`61 100666 |00ТГ2 100942129/5110°610°# 211 [00917 100852 100Т6 | 24/98 [9T |009LE|00LZZ|000TE|L9/08 EFE lO00LTI00R€Z| OL|| 9*ST {00€ESE|000ZZ [00162 {Z9/SL|07E 1077 5°61 |00ZEF [00877 100796 (ZL/S8 BEL |O0E6E |OOLEZ |OOTEE | L9/08 21€ [ooret{oo6t| o.|| L'ET (00696 100622 |OOTIE! 29/52 (0°€ 1077] (207 [22 100559 100657 |0068€ | 71/58 ('02 100213 10092 [0075$ | 19/08 79°7 [00% 100951) OL) | 1°0Z |005 00852 00655 129751075 |0° |0 3 3 (Daoo| vas | 81 |ival/(Duaa| MHL | OS | O1 | IVE [OdM|NO| IMA ОКТОМЯН ONI1000 KJ0 O00I à JOLAdM SONTLVA NOIIVOITAdAŸ AONSTOIAAE ONV ALIOVAYO (а, 19/0138 Ayroedes barjoos arqisues = 25 1/019 Ajtoedes Burtooo [E70] = IL (qq 32a/q{ng AJp) J dInjerades) Je DUriaUE = [13 your alenDs/spumod--dorp ainssald I127egW = dde anutu Jad suo[[eb--ajel AO[} I3leM = KIO (afgeorrdde Jt sinjeiadme; pny} lo) +3 alnjeladua] lajea butiajug « Lug 0 17 / ) 124 000” 19npap 'uorjejado agoz 104 (7) “139 009 39mpap “uoriezado ABOZ 101 (TD) -amjeladway Ite buriaqua qq a2163p 0/ LO paseg Ájroedeo butieag ‘gInjeladus; 11e burlajua qu aalbap ¿9 dq '1 aa1Dap 08 uo paseq Ajroedes БЫТ [00) ‘butdund 133ea 10] 30UEMO[[E 3384 sapniour yocus ’,sdumg Jeog aosnos 13384 punolg 10} piepuels, ‘q7¢ pIepuels [YY {ILA aJUEPIOIE UT Paleya © © 171 0002510°¢] 00069[S ZI] 00049107011 00065! 8 [32 /00LT]EZ9AdH OE! o05FF|E"E) ONOLS|+ ETÍ O009SÍ8'OL| ODOLS) 9 [OF /0SST{GESAM O"El o0%€€|F'E| OD0Z7%|L"ET| ODOTF|8'OL) OD09E! S |97' /007T|AJEAdM 0°с| 00952151 00005 18"601| 0001610 11| 00021 Y {0G /000T{90EAIM 100/uH/018|d0)/ME/NLE] N9S|NE/NI0| VIT|UB/0MIS| WdD| 453 [2PON IAT d 05 |IM3 4 OL|IMd 1 05 1 JME "3 OL /RAD yONLIVEH «ЭКТ1000 SONIIVY INVITA ОЯТА12330 ТАМ 8°9 100551 100% (5 [00665 | 21/58 $`9 |00989 100895 00067 | {9/08 £'9 |00$#9100855 100197 | 29/5 |0°510°8| oOIT Ге 10041100486 100(95 [21/58 9°; 10090: 100045 100519 | 9/08 61 100699 100095 09997 | 29/51 [0`9 108! 001 76 1004656100007 [00238 [21/58 8°8 [0092 100285 | 00095 119/08 99 100289 10015100805 129/51 10`910`8| 06 L OTIOOTZ8 |00€TF | 00779 | 71/58 66 |009FL|00F6€]0099) L9708 65°с 100$55 [00991] 04]| 86 10010100585 00255 | 29/54 10°9 1081 08 0°71|00598 100927 00639121758 71110099; | 0090$ | 00065 | 9/08 62€ l000671/000£91 OL!| 6'01 |000 100766 | 00555129791 104 |10`8| OL 9 EL |00598 | 006€F | DOLL] 21/58 1° 2110098: 100819 | 00519 | 19/08 617€ [00925 100565! 04|] 62110066: 10090 {0581512951 10`910`8} 09 [SI |00L98 | 00757 |O0FOL | 71/58 ['+1|00908|000€F | 000F9) L9 /08 OE looeselonoza! aL|! L'ET|OO8SLICALTF|ONZTO9|79/GL|0'+|0'8) OS $ 91100606 | 0059 10025 121/58 6°51|00928 | 0023 1005991 {9/08 59°2 10000510059] 041] `51100001 100625 109529 129/51 1051081205 1 11100165 00803100651 | 21/58 5`9[ | 009#8 100355 100069 | 19/08 04° [00962100045] 0(!| 6°51!0096 [0004 100659 | 29754105 10`8 | 206 (Ddo| val | AL |iva)|(Dyazj XAL | 3S | OL | LVA [Odk|WdO| LME ONTIVEN ON 11009 H47 001 8 q79AdN SONTLYA NOILN)T dd ADNAIJ1449 ONY ALIOVAVD Of 3T4Vl Z0°1 [90° 1] 56 [201 8 20'T |SO'T] 96 |20 3 LOT [EOL] 26 [TOI у 00°C [10°C] 86 100% 7 Wd9--snId SLIVM [ANIA|SLIVM|HNI@[AOTZ PAIE SOIT OT | 56° Uma aTarsuaS N 11009 NIVEL Zo OT [9670 qnag Tejoi SMOTA YELVM JUNIO LV ANVINORIZA OT+|pa3eyf OT- [MOTA ITV payey Jo X Yod SYOLOVA NOILIDGO SUOLVA USITAILIMA ALIOYAYI gor3njos azaalJ-rUe salrnbay © Aquo 310 $`8 [00299 100/26 100555121 /58 I 9°L [00109]00TTE|00Z1¥{L9/08 y". 100999 [00206100886 | 29/51 10°210°9| 011 26 [00919 [00665 [00089 | 21/58 #8 [00519 |004 16 | 009591 (9/08 28 [0085 00806 100013 |29/51|0°210`9| 001 [`О1|00169 [90145 100/05 | 21.758 $`6 100829 [0025 [00199 | 19/08 $6 100165 | 00516 [00655 | 79/51 10°2|0`9! 06 6 11100100095 [00455 | 217/58 5° 0100259 100265 [00587 | L9 /08 WE [00989 |00659| 04| 6`0Г|00%09 [00026 | 58959 | 29/51 |0°2|0°9| AB [2110022 100/56 [00195 21/58 6° 11 | 00959 100035 [00015 | 19/08 59°6 10062100045} 04|| 9`11|00419 100566 100643 |29/94|0`210`9| OL 791 [0086100995 100885 | 21/98 661 | 00079 100635 100555 | 19/08 s#°¢ 1006151008051 04|| 6°21|00059 100855 100205 |29/54|0`210°9| OY 0`9Т [0095 100915 100919 21/58 051 [00589 100855 100095 | 19/08 97'€ [00916 |00594| 04|] 5’91 [0049 100/55 100925 | 79/54 10°2|0'9] OS 6 ° (1100041 100985 100999 [21/58 ' 9110000} [0089$ | 00585 19/08 90° 10009200685] 04] 1*91]00959 0095$ | 00059 | 29/5110°20`9 (207 070710098 [00007 [0029 121/58 (°81 100511. 0085 100019 | {9/08 98°2 100502 |0002е} 04| 6` 11 00219 [00596 | 004 5129/5072 |0°9 |()0$ | (Ddoo| var | на |2м3 || Мая) MBI | 35 | 2 | 1 |04М|на9 | JAI ONTIVZE ON 11009 N30 05ST 8 GESAJM SONÍLVA NOILVOITddV ANMNAI)I139 (NV ALllovavo — 6 S8YL 18 IT qu9vL 6521 9871 9071 5971 €SZ | 247 | O£7 | EIZ | LOZ | 961 | FBI | ELL | Tou | OST | BET Y dat} SIT | eprs UDIN | EM "bap ZL| 0011 BL BL | LL LL ol | 96 | SL | SE | + FL EL | El ZL | U it | 1L | OL | apis 407 | #0 ‘Dep 58| HID Paley 9971 LLZI 9971 552] 9927 | e£Z | 222 | LIZ | 007 | EST | SLT | (91 [ 991 | SEL | REL | $21 | ZIT | SPIS UTA | EM *D9P ¿(09 MAI 32% et | EL | 2L | ZL | |E | OL | OL 69 69 99 | 89 19 | 19 | 99 | 99 | 59 | apts mo | &0 ‘бер 08| MOLI paley 187] OLZI 097) 6521 gez | L7Z | LIZ | 907 | Gel | 381 | FLI | ET | Zst | TFT | Tel | 0211 60€ | aprs UDTH | dM ‘DD 79 EZOAdM 69 | 69 | 99 | 89129 | LS | 99 | 99 | <9 59 ¥ | #9 | $59 | & | 79 | 29 [9 | apts mol | &0 ‘бэр 5; 6161 9061 #62] 1821 997 | 597 1 Ez | OEZ | LIZ | voz | Z61 | 6460| 991 | 991 | ET | BEL | SIT | aprs UDIE | de "DAP ZL} — OSSI 06 | 68 | 98 | 98 | |» ¡es |1s | os | ez | 8 | 94 | SL | ye | € | EL | OL | APIS MOT | 40 ‘бер 58] Ma paley DIET B6Z| SBL| ELZ| 09 | BFZ | SEZ | €ZZ | OZ | GEL | set | ELL | OY | ep | SEL | EST | OTT | APIS YDIH | dM *DIP (91079 MAI 9388 78 118 | 08 | 6018. [LL |94 |SL | Y | El U IL | OL | 69 | 89 | 19 | 99 | apis so7 ! #0 ‘бэр 08] AOI Paley EOS T67| 6LZ| 992| 797 | 772 1 0€ez | LIZ | soz | soz | 661 | 891 | 991 | 190 Е ZEN | EGIT f LOT | SPIS Ybiy | dM “Dep 79 dESAdH tt | 9L | SL | 36 | ZL | ZL | IL | OL 69 | 99 (9 99 $99 | 99 | €9 | 29 [9 | apts acy | qa “Dep SL 9621 587] 5021 1921 692 | (52 | 987 | #12 | 207 | 061 | 641 | £91 | SSI | Gi] zer | Ze | 801 | eprs ubrg | qu ‘bep ZL] 0021 08 | 6L | 6L | BL 1 LL ¡ 9. |9L ¡SL | FL | EL EL | Z tw] oo | OL | 69 | 99 | apts AOT | dq 'Dap 58: —WáAj pajeg Bz] €9Z| €97| TSZ| Ore | 677 | 817 | 907 | 561 | #81 | E€LT | 191 [~OSU | 661 | OZE | 911 | 901 | PIS UDIH | A ‘Dep L9(|0'G WAI 9724 с Перт Пер ТЕ бро Тб | 89 29 L9 ag ! ey ! ey | 59 | 59 | 351$ 807 ! dq “Dan cg! MOLI 0918} 8001 [921 9521 5901 960 | 502 | 000 | 109 | 061] 6LL | ©91 | ¿ST | 9FI | 091 | KIT EI | EOT | abIS UBIH | am ‘Bap 29 J9EAdM IL |0t|0t|6 |8 | {49 [99 | 9 | #9 9 | € | 29 [9 19 | 09 | 65 | apts 407 ) #0 ‘бэр GL 8601 9821 9021 2921 052 | 852 | 922 | riz | zog | OSI | BLE | 991 | $51 | 291 | 051 | 801 | 90Г | spits ubtH | da “Bap ZL| oool 59 | 8 158148 | # | # | # | В £8 ce £8 ze 28 78 78 [8 [8 apis MOT | gM ‘Dp 58| HI) pare LB | 9LZ| 921 eST| hz LOZ | BIZ | 107 | 561 | 381 | zLt | I9T | EPT | 861 | 9ZT | SIT | €OT | êptS YDIH | 90 ‘DEP 9107 Hd9 27% 64 | 66 164 Е 84 | 84 [| 84 184 | LL LL LL tL | 9L | 9 | 9 | 9 | SL | SL | apIS MOT | 90 "Sep og| mOTI paled 087 | 6921 BS7/ 9FZ| sez | 522 | 516 | TOZ | OBI | 641 | So! | IST | SEL | MIT EZ | TIT | OOT | APIS UDTH ( NM “Dep 79 JOCAdM HL | FL IBLICL EL JEL | EL ! 7 4) А ZU i IL TL IL | OL | OL | epIS MOT | 90 "Sap SL altssalg ¡aInjeladwa[ [9PON OL! SOL| COLI SE ! 0% | SE | 08! SL | OL | 9 | 09 | 55 | 05 | SP | OF | SE | ® 11y uIny O 0 O 0 O 0 O 0 0 0 O O 0 1 291690 110) 192eM DUTIJIUY 9107eIQAMI] PINTJ IN 11009 19 97 1 96 0'8 | 7'9 TODATD auaTAdOId 70€ wd paltnbal 33el MOT $01 {8'L | 99 | 79 | TO9ATÓ auarádod YT Hi9 paltnbal ayel mory 8 9 G у 19384 gd paitnbal ajel mOTJ I29AdM | SESAdA | SICA | SOEADM 07 Gojrxs dumd 12784 UINI *SuOLIRITITIds ajefd ferias 07 pablegoal pue ‘pajenoraa Wass ‘раложел 2q prnogs abileyo AW) ‘u93s4s ayy ur buraq abieyo BurIeiodo 1291100 07 se IqNOp Aue 51 91993 11 “[TO9 lajea 347 UBROIYY 33el MOT] IWJLA pajel pUE [TO9 Jo7elodeas 303 ssol9e (MOTJILE) ИД) payes uodn paseg ale serge] 918d $ + amasald apts ybig 9154 7 + amsseid apIs A07 ‘somnasaid quetsbrires burmmseau a10Jaq „JJO, ‘Jabueyoxa jeay 1032M joy этазЭтор ceuorado ve Áofdas yorya sirun Go ION 80€ 1567 1812 1692 1867 |557 |812 1502 1881 1601 [891 | эрт$ ЧБТЕ OOLE 42 pajey 0°8 Я49 99P Lt 120 |119 129 115 125 147 175 (LE [ZE [Lz | opis MOT | ээлбер 0 107] paley 479AdM 692 109% 1152 |299 [#62 |522 {917 [£07 [661 |061 |[Т9Г Г aDIS UBIH OSSI Wd9 peley 0°9 Wd9 3724 84 |£L 189 |659 les 176 [67 | [OF 196 105 | OPIS №07 | aazbep o, MOTA pajey dESAdM $97 [997 [657 1797 |567 |122 1027 |ETZ 1907 |961 [161 | apES UPTH 0021 Mao pejey 0'S №49 9204 18 [96 [TL [99 129 [LS 125 |1% 16% 19€ [66 | aprs №07 | @aibep qf MOTA pajey J9EAdH $67 1L77 (1072 |612 [102 1002 1661 1981 [081 [6/1 [901 | aprs ubrg 000T W3D Paley 0"? Hd9 pare €8 (LL (ZL 119 1729 (95 |149 19% [17 [SE [05 | apts №07 | зэлбэр 0, MOT pare JOEAdH amssalg |3.InjeITadwsy TSPOR 08 | SL | OL | 59 | 09 | SS | OS | S+ | Or | SE | 5 ITY uIn3ay e 0 O О 0 0 0 0 O 0 0 1 [T0) 19724 Burzajuy ainjelódua] 137ey 0 ci d'IGVL ON TIVHH 20 = ———— ———— SULEMOIO VALYE PART | 8603-006 РКА TD CONTROL CIAQUIT WIRING OH CONTROL PEL HEAT АННАН A) FACTORY FIELD USE COPPER vt RING VO CONDUCTORS ONLY High VoIt0e. come oe oe oe =m COVER AMD INSTALLATION INSTRUCTIONS FOR HOOK-LP frond CHECK LIGHT "(A FOR ELA LAVE 3 OF OPTIONAL UCT HEATER a МНН LL THERMOSTAT IMS ION CAAMACASE HEATER i “us N. |! POV Q_ 900 187731110539) 088 DOY SOTO] 187481 129/0674. 1181 | Lo 14 | \ De [1 | | | | ДЭ 8 4110 | OOOHOMOOGDOOV®Q@ h Jd 24V TERM. BLOCK | МАСТИ Ш - TT - ( SEE MITE ) - o — FESR CIO DA ! — (HO) 24 и OLO EMERGENCY HEAT INANSFORER ELN nan CLON) REY. VALVE SOLENDIO — LOCA Lou! BROW E NT MOTOR BELAY | 7 y € OS foi} © BLOVER [NC | A RELAY LOV PRESSURE of : Тон 3 1 HIGH PRESSE | po GREEN 7 SWITCH ACTION OX 1 Sse] a E и pr в A 1 CAPACITOR RATINGS | гб г ДА а млн ное пб я MODEL | COMPRESSOR | BLOWER 11 40 A Fire \РУЗОВ 40/470 5/370 миомы (Е VIRUS RTE FOR USE № МЕС. УРУЗБВ 40/370 тя 20/20 - 60 - 1 404-110 I ru Jm) Qe — — 210/208 = 60 = | z 1H END , о ОНОООННО ЧОАННЩННИЙ Press | 12 se) CONTACTOR ) CAPACITOR | И LI | CRARKCASE HEATER | -2VV0 5 | BLOYER 230 | oo Ip CAPACITOR = еее: 611118 © HW HIGH PRESS, — CO MESS. | o Ho oA ro — REV, VALVE MODELS РВ РЗ 23 MEFEA 10 COMTIVIL CIMCULT WERING Cpt CONTROL PANEL CNCA ANT INSTALLATION INSTRUCTIONS FOR HAOK-UP (F OPTIMHAL, OUCT HEATER IMERSION CANMCASE HEATER ne SILENTID YAL PANT 4 ET ET MEAT AMTICIDAJOS AT DEC LIGHT 4% FÜR EITHER TE OF ( MAX, 64.) ; Wi, VALL THERMOSTAT Zh | [DO © _®OD| 187F311 1052811089 a” DODVODO ROO] 164A 29/067 1181 Maa a и \ (1 1 100 | Po a ID oo | po | OOOOOOO@OOL®®) VL {HL 20Y TERA, LUCA ] C 0-0 (OHH и OD TRANSFER ir RED ox CLOS) AX x REY. VALVE EE NL 51.9010 uN —— e) wo пол EN — UPACITR WIR eur 3 4 4 5 oH 15.2 æ od — GS 1 SITO {| —_ | le = im pia ASCTION BOX — | joe Na CAPACITOR RATINGS || ara А паж ое DE MOVIE + [FO0EL | comnesson | BLOWER \ | \ ; A UE VDE MATE FO IE IN NEC WPVS38 40/440 1.57370 an - © + | УРУБ2В 45/440 7.57370 FACTORY FIELD USE COPPER Lo Voltage WIRING YIRING CONDUCTORS ONLY High Voltege — ——— om am ov = 0-111 С. — | — 230/208 - 69 - 1 11+— 60 > COMPRESSOR CONTACTO CAPACITOR | Tl LI | CRANKCASE HEATER | ANAND | | BLOWER TIN 08 TAP CAPACITOR = ТЕНИ - ——&YYYTY C + м © (1) _ HIGH PRESS. OY PRESS. ) © ( ) COMPRESSOR (13) (5) OLCYER (1)— A o REY. VALVE MODELS ER - YPV628 , 24 | 4054-806 T87F5111/0539.41089 MÍ $ £1 Anticipator Cool sueno | O : ml [эт ® Cou! En. Ht. > haticionter y ©---© Cook 1 À Mat da X G)-- © Check Lite 1 = T874R1129/0674L1181 A © Zysten switch zhown is cout position, A System switch shown ta "Naat* moxition, Are suitch shqua ta aute position. AN fan switch shown in “Muto” positien, This wiring diagram is for use with the units listed below and the following duct heaters: 8604-080,8604-081,8604-082,48604-083. - € Field Jumper Factory Field Optional Field Wiring Wiring, Wiring 1F92-1 © — E— — — y —UOo (0465-027) ROPE PROOY | CHE 3 т a Do Nat hook up LE ZN 000 Optional Duct Heater o К "© pbracieComon | T87F3111/ + | | Q539A1006 | © 9 of ® © | г © | cree I r= G/T=Green w/ Tracer anne (© 00808800) ME ме Solenoid т | ) * | W/TeWhíte w/ Trace В ER FELIPE S T87F3111/ Q539J1089 * Wewhite ma — ® т - — CO —— ++ © U 8 800 69 6) ve ed Heat Anticipator Setting a and 10Kw “Set heat anticipator . at .45A for either type ASI VEZ A Ses paragraph of wall thermostat. , "Two stage heat Wal? Thermostat/Optional Duct Heater Field Wiring Connections d h 4054-804 Г | A Not used on the 25 1100 ¥3lvm wl 31 S150) INILVEIH0 JAISSIIXI 5 430 VIM0IO “071 NO 1VIN "XAY = = ms a „= "hy ™ ™ =8 na E JOYA VILA JAISS3373 SAMY VOSSIULMOS MOTH SHIDI 30 SWILSOW 1107 ‘071 LUYLS 108 TIIR ЗАЛЫ 0°) MOT COL 55334 МОТ кЭ1и 001 TUNSSIVd MOTIINS MOT 001 38553784 OVIN B WIN OOL TUNSSITU4 OY = ASION 05529802 © a. = с.) E Га) a OYOTU3A0 50 $3121) VOSSINANI © NOILIONO) Wi3190Ud У 3SNVI TVKOISVII0 SILONII 3SNV) NOWAOI SILONAI GIONAOS 1109 YO JAŸVA 3A3191430 35V) 371915504 Mm — FLA INT WA 3055 24007 1103817 0803 A MILSAS NVIDIA 1083708 LEIS, 1107 Y 40404 07 YI YA #IMOTE HOOONT №0113 diiNd 1V3H HIV O01 H31VM HOd LHVHO DONILOOHS-379N0HL 3ONIUIATH MIND DATE OF INSTALLATION PERFORMANCE CHECK WATER SOURCE HEAT PUMPS Instalier Please Fill Out and Retain With Unit MODEL NO(S). SERIAL NO(S). ITEM COOLING HEATING JOB NUMBER HEAD PRESSURE NAME OF INSTALLER SUCTION PRESSURE NAME OF OWNER WATER TEMP. (IN) ADDRESS WATER TEMP. (OUT) CITY STATE . WATER PRESSURE CIN) FIELD COMMENTS: | 6. WATER PRESSURE (OUT) WATER FLOW (GPM) AMPERES (BLOWER) AMPERES (COMPRESSOR) LINE YOLTAGE (COMPRESSOR RUNNING) 11. AIR TEMP. (IN) D.B. W.B. 12, AIR TEMP. (OUT) D.B. N.B. This PERFORMANCE CHECK SIEET should be filled out by installer and retained with unit. 27 ">
![](http://s2.manualzz.com/store/data/008150427_3-3ae6506ed7d19da956c2879668bb52e6-210x147.png)
Advertisement
Key features
- High efficiency water source heat pumps
- Ground water temperature range: 45-75F
- Earth loop fluid temperature range: 30-110F
- Complete assembly and internal wiring
- Duct connections, electrical wiring, and water piping required
- Requires trained service and installation technicians
- Critical of proper refrigerant charge and adequate duct system
- Optional duct heater
- Heat recovery device for hot water heating
Frequently asked questions
The temperature range for ground water is 45-75F.
The temperature range for earth loop fluid is 30-110F.
Trained, experienced service and installation technicians are required.
Proper refrigerant charge and an adequate duct system are critical for the efficient operation of the heat pump.
Duct connections, thermostat wiring, 230-208 volt AC power wiring, and water piping are required.