Features
Allows normal building video message displays to
be controlled by a Simplex® 4100ES, 4010ES, or
4100U fire alarm control panel:
 When an emergency condition is reported to the host fire
alarm control panel, normal building video message
communications are switched to provide emergency
communications
 ECDI Software resides in an on-site computer and
monitors the computer port protocol output from the host
control panel
 Upon receipt of an emergency condition, the information
provided to the ECDI Computer allows it to abort
normal building messages and switch to the programmed
emergency message
 Standard messages are listed on page 4; custom
messages or images can be prepared, or the output can
be connected to a pre-selected URL
 Operation includes control of the video feed using a
separate VGA switch, or providing an RSS message feed
to enable the desired action at the receiving controls, or
both can be provided
 Operation requires Microsoft Windows XP or
Windows 7 (32-bit) operating systems; computers
require a serial port for control panel communications
and a second serial port for VGA Switch control; RSS
feed is via Ethernet port
Link panel point activity to a website:
 Panel trigger points can be programmed to connect the
ECDI Computer to a specific website URL to send to the
building displays to view activity or take action (view
web cameras, broadcast messages, etc.)
VGA message control:
 Building display communications are connected through
a dual input, single output VGA Switch (see page 2)
 When an emergency is detected at the host control panel,
point information is sent to the ECDI Computer allowing
it to control the VGA Switch output to feed to its video
output for the duration of the message(s)
 When the emergency is clear, communications revert
back to the standard controller
RSS message control:
 For compatible building display controllers, the ECDI
Computer functions as a web server to provide an RSS
feed via LAN/WAN connection, sending out the
programmed text associated to the selected panel
activity; an Internet browser with functionality equal to
Internet Explorer 7 or above is required
 For RSS feed only, ECDI software can reside on a
Simplex TrueSite Workstation computer if there is an
available Ethernet port and an available RS-232 port to
connect to the host control panel
 The RSS feed may also be compatible with other
building communications equipment such as power over
Ethernet (POE) message display products
Normal building messages on video displays
VGA Switch
Message Control
System
Computer with
ECDI Software
Shelter In Place
An emergency condition has been
reported. Secure your windows and
doors and remain in the building.
Unsafe conditions may exist outside.
You will be notified when further
information is available.
Cafeteria is open until 2PM today
Today's luncheon special is pepperoni
and onion pizza
10:17:35 am
Wednesday July 25, 2012
57°partly cloudy
Shelter In Place
An emergency condition has been
reported. Secure your windows and
doors and remain in the building.
Unsafe conditions may exist outside.
You will be notified when further
information is available.
Emergency Message
from the ECDI Computer
Fire alarm panel controlled Emergency
Communications message display
Fire Alarm Control
Panel (4100ES shown)
Control Building Communications Video Displays to
Deliver Custom Emergency Communications Messages
Description
Fire Alarm Systems. Fire alarm systems normally
communicate information to their connected fire alarm
notification appliances to advise building occupants of
emergency conditions and of the directed response.
However, many buildings also have non-emergency,
non-fire alarm display equipment in place to advise of
normal conditions such as daily events, weather,
announcing special visitors, or maybe just the daily menu.
Using the Fire Alarm System to Control other
Systems. ECDI Software allows the information displays
used for normal building communications to distribute
emergency information under the control of a Simplex
4100ES, 4010ES, or 4100U fire alarm control panel. The
software resides on a separate computer and controls the
building information equipment by either controlling a
VGA switch, or by sending RSS communications, or both
may be supplied.
Applications Note. ECDI Software provides a variety
of system connection options. Contact your local Simplex
product representative to have your specific building
requirements reviewed by our Solutions team.
For more information, refer to Installation Instructions
579-952
– This product was not agency listed as of document revision date.
S4190-0019-2 9/2012
ECDI Software Video Switch Connection Reference
Normal building message display system (by others)
Video output as selected
by the ECDI Software
Cafeteria is open until 2PM today
Today's luncheon special is pepperoni
and onion pizza
10:17:35 am
Wednesday July 25, 2012
57°partly cloudy
Normal building message on video displays
Video
Multiplexer
(by others)
Normal video feed
RS-232 control for input
selection; this connection
is supervised by the
ECDI Software (use USB
to RS-232 adapter if
needed, not supplied)
ECDI Software
Computer
(ordered
separately)
Black Box VGA Switch Model
AC505A (ordered separately)
Emergency VGA feed; use
HDMI/DVI output to VGA
converter cable if needed
(ordered separately)
SHELTER IN PLACE
An emergency condition has been
reported. Secure your windows and
doors and remain in the building.
Unsafe conditions may exist outside.
You will be notified when further
information is available.
Op
ti
on
al
o
ECDI Software loaded on PC; images,
and point mapping/programming
reside here, requires connection of
Security Service dongle (supplied)*
utp
ut
Cafeteria is open until 2PM today
Cafeteria is open until 2PM today
Today's luncheon special is pepperoni
and onion pizza
Today's luncheon special is pepperoni
and onion pizza
10:17:35 am
Wednesday July 25, 2012
57°partly cloudy
10:17:35 am
Wednesday July 25, 2012
57°partly cloudy
Shelter In Place
Shelter In Place
An emergency condition has been
reported. Secure your windows and
doors and remain in the building.
Unsafe conditions may exist outside.
You will be notified when further
information is available.
An emergency condition has been
reported. Secure your windows and
doors and remain in the building.
Unsafe conditions may exist outside.
You will be notified when further
information is available.
When the ECDI Computer receives a point status from
the fire alarm control panel that matches a programmed
trigger point, it controls the VGA Switch to feed the
ECDI Computer screen to the connected displays;
ECDI programming determines which message screen,
image, or URL is displayed per point or point type
Example screen for automatic
website linking*
RS-232 serial port, Computer Port
Protocol output to ECDI Software
Computer RS-232 serial port input
* Note: Run the ECDI program full
screen. Do not select a screen
saver. Set display and computer
timeout to never. (When the
ECDI computer takes control, its
monitor screen becomes the
screen shown on the building
message displays)
Fire Alarm
Network
Connection
IDNet communications and power wiring from control panel
Host Fire Alarm Control Panel,
4100ES, 4010ES, or 4100U
Fire alarm panel controlled Emergency Communications
message displays (with scrolling messages)
2
S4190-0019-2 9/2012
ECDI Software RSS Feed Connection Reference
Normal building message display control equipment (by others)
Video
Multiplexer
(by others)
Cafeteria is open until 2PM today
Today's luncheon special is pepperoni
and onion pizza
10:17:35 am
Wednesday July 25, 2012
57°partly cloudy
Cafeteria is open until 2PM today
Cafeteria is open until 2PM today
Today's luncheon special is pepperoni
and onion pizza
Today's luncheon special is pepperoni
and onion pizza
10:17:35 am
Wednesday July 25, 2012
57°partly cloudy
10:17:35 am
Wednesday July 25, 2012
57°partly cloudy
RSS compatible devices,
including other building
system display controllers
LAN/WAN
Fire Alarm Network
Connection
Alternate
RSS feed
Severe Weather
Alert
Severe Weather
Alert
A severe weather warning has been
issued. Proceed to the designated
shelter area and wait for further
instructions.
A severe weather warning has been
issued. Proceed to the designated
shelter area and wait for further
instructions.
During an emergency, the standard message is changed to
display the appropriate Emergency Communications message
(standard emergency screen is shown for reference)
Note: The desired emergency display is determined by the
controller receiving the RSS feed, not by the ECDI computer
TrueSite Workstation
Alternate Hardware Connection
TrueSite Workstation Server or Remote
Client PC with ECDI Software
Note: For RSS operation only, ECDI
Software can be located on a Simplex
TrueSite Workstation Server or Remote
Client PC; requires non-captive TrueSite
Workstation operation, one available
RS-232 port, and one available Ethernet
port
The RSS feed provides a time stamp, and Title and
Description as determined by ECDI programming
ECDI Software PC
(by others)
OR
ECDI Software loaded on PC and set to create RSS feed,
requires connection of Security Service dongle (supplied)
RS-232 serial port, Computer Port Protocol
output to ECDI Software PC
To fire alarm control panel
controlled message displays
Fire Alarm
Network
Connection
IDNet communications
and power wiring from
control panel
Host Fire Alarm Control Panel,
4100ES, 4010ES, or 4100U
3
S4190-0019-2 9/2012
Black Box VGA Switch Reference
Manufacturer
Model Number
For additional information
Black Box Network Services
AC505A
www.blackbox.com
Specification Summary
Size
1 ¼” H x 4 ¼” W x 2 ½” D (32 mm x 108 mm x 64 mm)
Power Requirements
120 VAC, 60 Hz to power converter (supplied)
Converter output is 6 VDC, 300 mA (center positive) to VGA switch
Resolution
Video Level
Video Bandwidth
1600 x 1200 maximum
0 to 0.7 V p-p
250 MHz
Video and Control
Connections
Video input: (2) HD15F
Video cable is by others per system distance requirements
Video output: (1) HD15F
Serial input: (1) 3.5 mm F (RS-232), cable included
Distance
150 ft (45.7 m) maximum at XGA resolution
ECDI Software Pre-Programmed Messages
The following standard message screens are provided to coordinate with the standard Simplex LED Reader Board
messages. Custom messages can easily be created for local content. These messages require mapping to the selected
trigger points from the connected fire alarm control panel at the ECDI Computer.
Message Title
Screen Color
(with black text)
Bomb Threat
Orange
Bomb Threat
An emergency has been reported in the building. Please proceed to the nearest exit
and vacate the building.
Hostile Intruder
Orange
Hostile Intruder
An emergency has been reported in the building. Please secure your area and wait for
further instructions.
Shelter in Place
Orange
Shelter In Place
An emergency condition has been reported. Secure your windows and doors and
remain in the building. Unsafe conditions may exist outside. You will be notified when
further information is available.
Alternate Exit
Red
Severe Weather
Alert
Yellow
Weather Alert
A severe weather warning has been issued. Proceed to the designated shelter area
and wait for further instructions.
All Clear
Green
All Clear
Attention please, the emergency condition has been cleared. You may return to your
normal activities
Evacuate
Red
Evacuate
A fire has been reported in the building. Proceed to the nearest exit and vacate the
building. Report to your designated assembly place outside the building.
Alert
Yellow
Alert
An emergency condition has been detected in another part of the building. Please
remain in your area. You will be notified if further action is required.
Live Voice
Red
Displayed Message
Evacuate-Alternate
An emergency condition has been discovered in the building. Proceed to your
alternate exit and vacate the building.
Live Voice
A live voice announcement is currently being broadcast
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. Microsoft, and Windows are
trademarks of Microsoft Corporation in the United States and/or other countries. Black Box is a trademark of Black Box Corporation.
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA
www.simplexgrinnell.com
S4190-0019-2 9/2012
© 2012 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement