5714V103_UK
5714
Programmable
LED Indicator
No. 5714V103-UK
From serial number:
121496001 (A+B)
131077001 (C+D)
DK
PR electronics A/S tilbyder et bredt program af analoge og digitale
signalbehandlingsmoduler til industriel automation. Programmet
består af Isolatorer, Displays, Ex-barrierer, Temperaturtransmittere,
Universaltransmittere mfl. Vi har modulerne, du kan stole på i selv
barske miljøer med elektrisk støj, vibrationer og temperaturudsving,
og alle produkter opfylder de strengeste internationale standarder.
Vores motto »Signals the Best« er indbegrebet af denne filosofi – og
din garanti for kvalitet.
UK
PR electronics A/S offers a wide range of analog and digital
signal conditioning devices for industrial automation. The product
range includes Isolators, Displays, Ex Interfaces, Temperature
Transmitters, and Universal Devices. You can trust our products in
the most extreme environments with electrical noise, vibrations and
temperature fluctuations, and all products comply with the most
exacting international standards. »Signals the Best« is the epitome
of our philosophy – and your guarantee for quality.
FR
PR electronics A/S offre une large gamme de produits pour le
traite­
ment des signaux analogiques et numériques dans tous
les domaines industriels. La gamme de produits s’étend des
transmetteurs de température aux afficheurs, des isolateurs aux
interfaces SI, jusqu’aux modules universels. Vous pouvez compter
sur nos produits même dans les conditions d’utilisation sévères,
p.ex. bruit électrique, vibrations et fluctuations de température.
Tous nos produits sont conformes aux normes internationales les
plus strictes. Notre devise »SIGNALS the BEST« c’est notre ligne
de conduite - et pour vous l’assurance de la meilleure qualité.
DE
PR electronics A/S verfügt über ein breites Produktprogramm
an analogen und digitalen Signalverarbeitungsgeräte für die in­
dustrielle Automatisierung. Dieses Programm umfasst Displays,
Temperaturtransmitter, Ex- und galvanische Signaltrenner, und
Universalgeräte. Sie können unsere Geräte auch unter extremen
Einsatzbedingungen wie elektrisches Rauschen, Erschütterungen
und Temperaturschwingungen vertrauen, und alle Produkte von
PR electronics werden in Überein­stimmung mit den strengsten
internationalen Normen produziert. »Signals the Best« ist Ihre
Garantie für Qualität!
1508
Programmable LED indicator
PReview 5714
Table of contents
Warning........................................................................................................
Symbol identification.............................................................................
Safety instructions..................................................................................
Front and back layout............................................................................
Application..................................................................................................
Technical characteristics.......................................................................
Mounting.....................................................................................................
Applications...............................................................................................
Order: 5714................................................................................................
Electrical specifications........................................................................
Sensor error detection /
sensor error detection outside range..........................................
Connections...............................................................................................
Block diagram............................................................................................
Routing diagram.......................................................................................
Scrolling help text...................................................................................
Configuration / operating the function keys................................
Graphic depiction of the relay function setpoint.......................
2
2
3
5
6
6
6
7
8
8
12
14
15
17
18
20
21
5714V103-UK1
Warning
GENERaL
This device is designed for connection to hazardous electric voltages. Ignoring this warning can result in severe personal injury
or mechanical damage. To avoid the risk of electric shock and fire,
the safety instructions of this manual must be observed and the
guidelines followed. The specifications must not be exceeded,
and the device must only be applied as described in the following. Prior to the commissioning of the device, this manual must
be examined carefully. Only qualified personnel (technicians)
should install this device.
If the equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be
impaired.
WARNING
HAzARD­OUS
VOLTAGE
Until the device is fixed, do not connect hazardous voltages to
the device.
The following operations should only be carried out on a disconnected device and under ESD safe conditions:
Troubleshooting the device.
Repair of the device must be done by PR electronics A/S only.
Symbol identification
Triangle with an exclamation mark: Warning / demand. Potentially
lethal situations.
The CE mark proves the compliance of the device with the essential requirements of the directives.
25714V103-UK
Safety instructions
Definitions:
Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and 50
to 1000 Volt AC.
Technicians are qualified persons educated or trained to mount, operate, and also
troubleshoot technically correct and in accordance with safety regulations.
Operators, being familiar with the contents of this manual, adjust and operate the
knobs or potentiometers during normal operation.
Receipt and unpacking:
Unpack the device without damaging it. The packing should always follow the
device until this has been permanently mounted. Check at the receipt of the
device whether the type corresponds to the one ordered.
Environment:
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock,
as well as rain and heavy moisture. If necessary, heating in excess of the stated
limits for ambient temperatures should be avoided by way of ventilation.
All devices fall under Installation Category II, Pollution Degree 1, and Insulation
Class II.
Mounting:
Only technicians who are familiar with the technical terms, warnings, and instructions in the manual and who are able to follow these should connect the device.
Should there be any doubt as to the correct handling of the device, please contact your local distributor or, alternatively,
PR electronics A/S
www.prelectronics.com.
Mounting and connection of the device should comply with national legislation
for mounting of electric materials, i.a. wire cross section, protective fuse, and
location. Descriptions of Input / Output and supply connections are shown in the
block diagram and side label.
5714V103-UK3
The following apply to fixed hazardous voltages-connected devices:
The max. size of the protective fuse is 10 A and, together with a power
switch, it should be easily accessible and close to the device. The power
switch should be marked with a label telling it will switch off the voltage to the device.
UL installation requirements:
For use on a flat surface of a type 1 enclosure
Use 60/75°C copper conducters only
Enclosure rating (face only)........................... Type 4X, UL50E
Max. ambient temperature.............................60°C
Max. wire size, pins 41...46............................ AWG 30-16
Max. wire size, others....................................... AWG 30-12
UL file number.....................................................E248256
Calibration and Adjustment:
During calibration and adjustment, the measuring and connection of external
voltages must be carried out according to the specifications of this manual. The
technician must use tools and instruments that are safe to use.
Normal operation:
Operators are only allowed to adjust and operate devices that are safely fixed in
panels, etc., thus avoiding the danger of personal injury and damage. This means
there is no electrical shock hazard, and the device is easily accessible.
Cleaning:
When disconnected, the device may be cleaned with a cloth moistened with
distilled water.
Liability:
To the extent the instructions in this manual are not strictly observed, the
custom­er cannot advance a demand against PR electronics A/S that would otherwise exist according to the concluded sales agreement.
45714V103-UK
Front and back layout
Picture 1: Front of PReview 5714.
Picture 2: Back of PReview 5714.
5714V103-UK5
Programmable LED indicator
PReview 5714
•
•
•
•
•
4-digit 14-segment LED indicator
Input for mA, V, potentiometer, Ohm, RTD and TC
2 relays and analogue output
Universal voltage supply
Front key programmable
Application
• Display for digital readout of current, voltage, resistance, temperature or
potentiometer signals.
• Process control with 2 pairs of potential-free relays and / or analogue output.
• For local readout in extremely wet atmospheres with a specially designed
splash-proof cover.
Technical characteristics
• 4-digit LED indicator with 13.8 mm 14-segment characters. Max. display read­
out -1999...9999 with programmable decimal point, relay ON / OFF indication.
• All operational parameters can be adjusted to any application by use of the
front keys.
• PReview 5714 is available fully-configured acc. to specifications ready for
process control and visualisation.
• Help texts in eight languages can be selected via a menu item.
• In versions with relay outputs the user can minimise the installation test time
by activating / deactivating each relay independently of the input signal.
Mounting
• To be mounted in front panel. The included rubber packing must be mounted
between the panel cutout hole and the display front to obtain a protection
degree of IP65 (type 4X). For extra protection in extreme environments,
PReview 5714 can be delivered with a speially designed splash-proof cover as
accessory.
65714V103-UK
Applications
Input signals:
Current
46
+
-
2-wire transmitter
RTD & Lin R Potentio­meter connection, wires
432
+
45
44
TC
Voltage
-
+
+
-
-
43
1
2
42
41
Output signals:
26
25
24
1
23
12
2
+
22
-
21
11
Analogue, 0/4...20 mA
2 change over relays
Supply:
32
21.6...253 VAC
or
19.2...300 VDC
1
2
31
5714V103-UK7
Order: 5714
Type
Version
5714
Standard . . . . . . . . . . . . . . . . . . . . . . . : A
2 relays . . . . . . . . . . . . . . . . . . . . . . . . : B
Analogue output . . . . . . . . . . . . . . . : C
Analogue output and 2 relys . . . . : D
NB! Please order the splash-proof cover seperately. Order No. 8335.
Electrical specifications
Specifications range:
-20°C to +60°C
Common specifications:
Supply voltage, universal...................................... 21.6...253 VAC, 50...60 Hz or
19.2...300 VDC
Consumption
Type
Internal consumption
Max. consumption
5714A
2.2 W
2.5 W
5714B/C
2.7 W
3.0 W
5714D
3.2 W
3.5W
Isolation voltage, test / operation.................... 2.3 kVAC / 250 VAC
Signal- / noise ratio................................................. Min. 60 dB (0...100 kHz)
Response time (0...90 %, 100...10 %), programmable:
Temperature input........................................... 1...60 s
Current / voltage input.................................. 0.4...60 s
Calibration temperature........................................ 20...28°C
Accuracy, the greater of general and basic values:
General values
Input type
Absolute
accuracy
Temperature
coefficient
All
≤ ±0.1% of reading
≤ ±0.01% of reading / °C
85714V103-UK
Basic values
Basic
accuracy
≤ ±4 µA
≤ ±20 µV
≤ ±0.2°C
≤ ±0.1 Ω
≤ ±0.1 Ω
Input
type
mA
Volt
Pt100
Linear resistance
Potentiometer
TC type:
E, J, K, L, N, T, U
TC type: R, S, W3,
W5, LR
TC type: B
85...200°C
TC type: B
200...1820°C
Temperature
coefficient
≤ ±0.4 µA / °C
≤ ±2 µV / °C
≤ ±0.01°C / °C
≤ ±0.01 Ω / °C
≤ ±0.01 Ω / °C
≤ ±1°C
≤ ±0.05°C / °C
≤ ±2°C
≤ ±0.2°C / °C
≤ ±4°C
≤ ±0.4°C / °C
≤ ±2°C
≤ ±0.2°C / °C
EMC immunity influence..................................... < ±0.5% of readout
Auxiliary supply:
2 wire supply, pin 46...45.............................. 25...15 VDC / 0...20 mA
Vibration....................................................................... IEC 60068-2-6 Test FC
2...25 Hz................................................................ ±1.6 mm
25...100 Hz.......................................................... ±4 g
Wire size, pin 41...46 max. ................................... 1 x 1.5 mm2 stranded wire
Wire size, others max. ............................................ 1 x 2.5 mm2 stranded wire
Relative humidity..................................................... < 95% RH (non cond.)
Dimensions (HxWxD)............................................... 48 x 96 x 120 mm
Cutout dimensions................................................... 44.5 x 91.5 mm
Protection degree (mounted in panel)............. IP65 / Type 4X, UL50E
Weight........................................................................... 230 g
RTD, linear resistance and potentiometer input:
Input
type
Min.
value
Max.
value
Standard
Pt10...Pt1000
Ni50...Ni1000
Cu10...Cu100
Lin. R
Potentiometer
-200°C
-60°C
-200°C
0Ω
10 Ω
+850°C
+250°C
+260°C
10000 Ω
100 kΩ
IEC 60751
DIN 43760
α = 0.00427
-
5714V103-UK9
Input for RTD types:
Pt10, Pt20, Pt50, Pt100, Pt200, PT250, Pt300, Pt400, Pt500, Pt1000
Ni50, Ni100, Ni120, Ni1000, Cu10, Cu20, Cu50, Cu100
Cable resistance pr. wire, RTD (max.)............... 50 Ω
Sensor current, RTD................................................. Nom. 0.2 mA
Effect of sensor cable resistance
(3- / 4-wire), RTD...................................................... < 0.002 Ω / Ω
Sensor error detection, RTD................................. Yes
Short curcuit detection, RTD................................ < 15 Ω
TC input:
Type
B
E
J
K
L
N
R
S
T
U
W3
W5
LR
Min.
value
0°C
-100°C
-100°C
-180°C
-200°C
-180°C
-50°C
-50°C
-200°C
-200°C
0°C
0°C
-200°C
Max.
value
Standard
+1820°C
+1000°C
+1200°C
+1372°C
+900°C
+1300°C
+1760°C
+1760°C
+400°C
+600°C
+2300°C
+2300°C
+800°C
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
ASTM E988-90
ASTM E988-90
GOST 3044-84
Cold junction compensation (CJC)
via internal sensor............................................ ±(2.0°C + 0.4°C * Δt)
Δt = internal temperature - ambient temperature
Sensor error detection, all TC types................. Yes
Sensor error detection............................................ Yes
Sensor error current:
when detecting.................................................. Nom. 2 μA
else.......................................................................... 0 μA
Current input:
Measurement range................................................. 0...20 mA
Programmable measurement ranges................ 0...20 and 4...20 mA
Input resistance........................................................ Nom. 20 Ω + PTC 25 Ω
Sensor error detection:
loop break 4...20 mA........................................ Yes
105714V103-UK
Voltage input:
Measurement range................................................. 0...12 VDC
Programmable measurement ranges................ 0...1 / 0.2...1 /
0...10 / 2...10 VDC
Input resistance........................................................ Nom. 10 MΩ
Outputs:
Display:
Display readout.........................................................
Decimal point..............................................................
Digit height.................................................................
Display updating.......................................................
Input outside input range is
indicated by................................................................
Current output:
Signal range (span)..................................................
Programmable signal ranges................................
Load (max.)..................................................................
Load stability..............................................................
Sensor error detection............................................
NAMUR NE 43 up / downscale............................
Output limitation:
on 4...20 and 20...4 mA signals...................
on 0...20 and 20...0 mA signals...................
Current limit................................................................
Relay outputs:
Relay function............................................................
Hysteresis....................................................................
On and Off delay.......................................................
Sensor error detection............................................
Max. voltage...............................................................
Max. current................................................................
Max. AC power...........................................................
Max. current at 24 VDC..........................................
Marine approval:
Det Norske Veritas, Ships & Offshore..............
Observed authority requirements:
EMC 2004/108/EC...................................................
LVD 2006/95/EC.......................................................
UL, Standard for Safety..........................................
EAC TR-CU 020/2011.............................................
-1999...9999 (4 digits)
Programmable
13.8 mm
2.2 times / s
Explanatory text
0...20 mA
0...20 / 4...20 /
20...0 / 20...4 mA
20 mA / 800 Ω / 16 VDC
≤ 0.01% of span / 100 Ω
0 / 3.5 / 23 mA / none &
23 mA / 3.5 mA
3,8...20.5 mA
0...20.5 mA
≤ 28 mA
Setpoint
0...100%
0...3600 s
Make / Break / Hold
250 VRMS
2 A / AC
500 VA
1A
Standard for Certification No. 2.4
Standard:
EN 61326-1
EN 61010-1
UL 508
EN 61326-1
5714V103-UK11
Sensor error detection / sensor error detection outside range
Sensor error check in 5714 variants
Variant:
5714A
5714B
5714C
5714D
Input
VOLT
CURR
POTM
TEMP
LIN R
Configuration
Always:
ERR1=NONE, ERR2=NONE:
else:
O.ERR=NONE:
else:
ERR1=NONE, ERR2=NONE, O.ERR=NONE:
else:
Sensor error detection:
ON
OFF
ON
OFF
ON
OFF
ON
Outside range readout (IN.LO, IN.HI):
If the valid range of the A/D converter or the polynomial is exceeded
Range
Readout
Limit
IN.LO
< -25 mV
0...1 V / 0,2...1 V
IN.HI
> 1,2 V
IN.LO
< -25 mV
0...10 V / 2...10 V
IN.HI
> 12 V
IN.LO
< -1,05 mA
0...20 mA / 4...20 mA
IN.HI
> 25,05 mA
IN.LO
< -0,5%
IN.HI
> 100,5%
IN.LO
< temperature range -2°C
TC / RTD
IN.HI
> temperature range +2°C
IN.LO
< 0 ohm
0...800 ohm
IN.HI
> 1 kohm
IN.LO
< 0 ohm
0...10 kohm
IN.HI
> 15 kohm
Sensor error detection (SE.BR, SE.SH):
Input
CURR
Range
Loop break (4..20mA)
TC
TEMP
RTD, 2-, 3- & 4-wire
No SE.SH for Cuxx, Pt10, Pt20 & Pt50
LIN R
0...800 ohm
0...10 kohm
Readout
SE.BR
SE.BR
SE.BR
SE.SH
SE.BR
SE.BR
Limit
<= 3,6 mA; > = 21 mA
> ca. 750 kohm / (1,25 V)
> 12 kohm
< 15 ohm
> 875 ohm
> 12 kohm
Display readout below min. / above max. (-1.9.9.9, 9.9.9.9):
Input
Range
CURR
VOLT
All
LIN R
All
POTM
-
125714V103-UK
Readout
-1.9.9.9
9.9.9.9
-1.9.9.9
9.9.9.9
-1.9.9.9
9.9.9.9
Limit
Display readout <-1999
Display readout >9999
Display readout <-1999
Display readout >9999
Display readout <-1999
Display readout >9999
Readout at hardware error
Error search
Test of internal communication uC / ADC
Test of internal CJC sensor
Check-sum test of the configuration in RAM
Check-sum test of the configuration in EEPROM
Readout
HW.ER
CJ.ER
RA.ER
EE.ER
Error cause
Permanent error in ADC
CJC sensor defect
Error in RAM
Error in EEPROM
! Error indications in the display blink once a second. The help text explains the error.
5714V103-UK13
Connections
Inputs:
RTD & Lin R, 2-wire
41 42 43 44 45 46
RTD & Lin R, 3-wire
RTD & Lin R, 4-wire
41 42 43 44 45 46
41 42 43 44 45 46
TC
2-wire transmitter
Current
41 42 43 44 45 46
41 42 43 44 45 46
41 42 43 44 45 46
-
+
-
+
Tx
Voltage
Potentiometer
41 42 43 44 45 46
41 42 43 44 45 46
-
-
+
+
Output:
Supply:
Current
Relays
31 32
11 12
21 22 23 24 25 26
-
mA
+
145714V103-UK
R1
R2
1
3
2
Potm.
4
3
2
RTD & Lin R,
wires
+
+V
Tx
+
Input gnd.
+
Input +,
mA
2-wire supply
> 15 VDC
41
42
Int.
CJC
43
44
45
46
20 W
PTC
AD
5714
EEPROM
CPU
Version D
1
2
3
4
R2
R1
26
24
25
23
21
22
11
12
31
32
mA
Relay 2 N.C.
Common
Relay 2 N.O.
Relay 1 N.C.
Common
Relay 1 N.O.
I
Output
I+
Supply
21.6...253 VAC
or
19.2...300 VDC
Supply
Block diagram
5714V103-UK15
Power up
1.2
F.SET
1 2
1 2
REL1
REL2
50.0
1.3
3
SETP
1 2
-1999
9999
/OFF
3
1.0
3
Fast setpoint adjustment
and relay test
1 Increase setpoint
2 Decrease setpoint
3 Save and exit the menu
1 and 2 simultaneously = change relay state
1.1
1.4
PASS
1 2
0000
9999
IN
ADV
3
1 2
NO
YES
DEC.P
1 2
1111
1.1.1.1
1 2
3
DI.LO
1 2
a999
9999
3
PERC
DI.HI
1 2
a999
9999
3
3
1 2
PERC
DISP
3
YES
ADV.SET
3
POTM
CURR 3 RANG
1 2
0-20 4-20
3
VOLT 3 RANG
1 2
0-1 0.2-1
0-10 2-10
1.0 = Default state
1.1 = Only if passwordprotected
1.2 = Only is FastSet is enabled
1.3 = FastSet and relay test disabled at password 5000...9999.
1.4 = No relay outputs
1.5 = Not valid for these input
signals: Potentiometer, 0...20
mA and voltage
1.6 = No analogue output
1.7 = Only if input signal is
temperature
1.8 = In default state press and
hold 1 or 2 to change
display intensity between
damped and full
(7 = full intensity).
1.6
3
LIN.R 3 LR.LO
LR.HI
1.4
CONN
1 2 3 1 2 3 1 2
3
0-9998
1-9999 2W 3W 4W
TEMP 3 TYPE
1 2
PT
3
NI
3
TC
3 TC.TY
CU
PT.TY
CONN
1 2 3 1 2
10-1000 2W 3W 4W
NI.TY
3
CONN
1 2 3 1 2
50-1000 2W 3W 4W
3
3
1 2
TC.B-E-J-K-L-N-R
S-T-U-W3-W5-LR
3
CU.TY
1 2
10-100
1 2
1111
111.1
CONN
1 2
2W 3W 4W
3
165714V103-UK
DEC.P
3
UNIT
3
1 2
'C
'F
3
Routing diagram
If no keys are activated for 2 minutes the display returns to default state
1.0 without saving configuration changes..
1 Increase value / choose next parameter
2 Decrease value / choose previous parameter
3 Accept the chosen parameter and go to the next menu
Hold 3 Back to previous menu / return to menu 1.0 without saving
REL.1
3
SETP
1 2
SET
SKIP
OFF
3
REL.2
3
1 2
0.0
100.0
ACT1
3
SETP
1 2
SET
SKIP
OFF
3
1 2
0.0
100.0
1 2
INCR
DECR
HYS1
1 2
0.0
100.0
3
ACT2
3
1 2
INCR
DECR
HYS2
1 2
0.0
100.0
3
1.5
3
1.5
3
ERR1
ON.DE
1 2
HOLD
ACTI
DEAC
NONE
3
ERR2
1 2
0000
3600
OF.DE
1 2
0000
3600
3
ON.DE
1 2
HOLD
ACTI
DEAC
NONE
3
1 2
0000
3600
3
OF.DE
1 2
0000
3600
3
3
1.6
1.6
1.4
A.OUT
1.7
1 2
4-20
0-20
20-4
20-0
3
ADV.SET
O.LO
1 2
a999
9999
1.7
3
O.HI
1 2
a999
9999
DE
ES
IT
UK
LANG
DISP
CAL
12
1.5
3
O.ERR
1 2
0/3.5mA
23mA
NONE
DK
FR
SE
CZ
RESP
3
1 2
0.0
60.0
E.PAS
3
1 2
YES
NO
N.PAS
1 2
0000
9999
3
3
NO
To default state 1.0
----
12
LANG 3
UK
3
HLP.T
1...7
12
1.8 DISP
3
7
3
LIGH
100.0
0.0
12
YES NO
12
CAL 3 YES 3
CA.LO
NO
2.0
VAL.L
100.0
0.0
12
YES NO
12
YES NO
12
3 YES 3 90.0 3 YES 3
CA.HI
VAL.H
USE.C
NO
5714V103-UK17
Scrolling help text
Display in default state xxxx, hardware error:
SE.BR --> SENSOR WIRE BREAKAGE
SE.SH --> SENSOR SHORT CIRCUIT
IN.HI --> INPUT OVERRANGE
IN.LO --> INPUT UNDERRANGE
9.9.9.9--> DISPLAY OVERRANGE
-1.9.9.9
-->DISPLAY UNDERRANGE
HW.ER --> HARDWARE ERROR
EE.ER --> EEPROM ERROR CHECK CONFIGURATION
RA.ER --> RAM MEMORY ERROR
CJ.ER --> CJC SENSOR ERROR
Fastset (Enabled):
F.SET
REL1 --> FAST SET MENU REL2 --> SELECT RELAY
SETP
xxxx --> RELAY SETPOINT - PRESS OK TO SAVE
Fastset (Disabled):
SETP
xxxx --> RELAY SETPOINT - READ ONLY
Configuration menus:
ADV
YES
--> ENTER ADVANCED SETUP MENU?
NO
PASS
xxxx --> SET CORRECT PASSWORD
IN
C.LIN* --> TEXT ENTERED BY USER IN PRESET
CURR --> CURRENT INPUT
VOLT --> VOLTAGE INPUT
POTM --> POTENTIOMETER INPUT
LIN.R --> LINEAR RESISTANCE INPUT
TEMP --> TEMPERATURE SENSOR INPUT
RANGWhen current selected:
0-20 --> INPUT RANGE IN mA
4-20 --> INPUT RANGE IN mA
RANGWhen voltage selected:
0-10 --> INPUT RANGE IN VOLT
2-10 --> INPUT RANGE IN VOLT
0.0-1 --> INPUT RANGE IN VOLT
0.2-1 --> INPUT RANGE IN VOLT
DEC.P
1111 --> DECIMAL POINT POSITION
111.1 --> DECIMAL POINT POSITION
11.11 --> DECIMAL POINT POSITION
1.111 --> DECIMAL POINT POSITION
LR.LO
xxxx --> SET RESISTANCE VALUE LOW
LR.HI
xxxx --> SET RESISTANCE VALUE HIGH
REL.U
PERC --> SET RELAY IN PERCENTAGE
DISP --> SET RELAY IN DISPLAY UNITS
TYPE
CU
--> SELECT CU SENSOR TYPE
PT
--> SELECT PT SENSOR TYPE
NI
--> SELECT NI SENSOR TYPE
TC
--> SELECT TC SENSOR TYPE
CU.TY
10
--> SELECT CU SENSOR TYPE
20
--> SELECT CU SENSOR TYPE
50
--> SELECT CU SENSOR TYPE
100
--> SELECT CU SENSOR TYPE
PT.TY
10
--> SELECT PT SENSOR TYPE
20
--> SELECT PT SENSOR TYPE
50
--> SELECT PT SENSOR TYPE
100
--> SELECT PT SENSOR TYPE
200
--> SELECT PT SENSOR TYPE
250
--> SELECT PT SENSOR TYPE
300
--> SELECT PT SENSOR TYPE
400
--> SELECT PT SENSOR TYPE
500
--> SELECT PT SENSOR TYPE
1000 --> SELECT PT SENSOR TYPE
NI.TY
50
--> SELECT NI SENSOR TYPE
100
--> SELECT NI SENSOR TYPE
120
--> SELECT NI SENSOR TYPE
1000 --> SELECT NI SENSOR TYPE
CONN When Cu, Pt and Ni sensor is selected
2W
--> SELECT 2-WIRE SENSOR CONNECTION
3W
--> SELECT 3-WIRE SENSOR CONNECTION
4W
--> SELECT 4-WIRE SENSOR CONNECTION
TC.TY
TC. B --> SELECT TC SENSOR TYPE
TC. E --> SELECT TC SENSOR TYPE
TC. J
--> SELECT TC SENSOR TYPE
TC. K --> SELECT TC SENSOR TYPE
TC. L --> SELECT TC SENSOR TYPE
TC. N --> SELECT TC SENSOR TYPE
TC. R --> SELECT TC SENSOR TYPE
TC. S --> SELECT TC SENSOR TYPE
TC. T --> SELECT TC SENSOR TYPE
TC. U --> SELECT TC SENSOR TYPE
TC.W3 --> SELECT TC SENSOR TYPE
TC.W5 --> SELECT TC SENSOR TYPE
TC.LR --> SELECT TC SENSOR TYPE
DEC.P When temperature selected
1111 --> DECIMAL POINT POSITION
111.1 --> DECIMAL POINT POSITION
UNIT
°C
--> DISPLAY AND RELAY SETUP IN CELSIUS
°F
--> DISPLAY AND RELAY SETUP IN
FAHRENHEIT
DI.LO
xxxx --> DISPLAY READOUT LOW
DI.HI
xxxx
--> DISPLAY READOUT HIGH
185714V103-UK
REL1
SET
--> ENTER RELAY 1 SETUP
SKIP --> SKIP RELAY 1 SETUP
OFF
--> RELAY 1 DISABLED
SETP
xxxx --> RELAY SETPOINT
ACT1
INCR --> ACTIVATE AT INCREASING SIGNAL
DECR --> ACTIVATE AT DECREASING SIGNALL
HYS1
xxxx --> RELAY HYSTERESIS
ERR1
HOLD --> HOLD RELAY AT ERROR
ACTI --> ACTIVATE RELAY AT ERROR
DEAC --> DEACTIVATE RELAY AT ERROR
NONE --> UNDEFINED STATUS AT ERROR
ON.DE
xxxx --> RELAY ON-DELAY IN SECONDS
OF.DE
xxxx --> RELAY OFF-DELAY IN SECONDS
REL2
SET
--> ENTER RELAY 2 SETUP
SKIP --> SKIP RELAY 2 SETUP
OFF
--> RELAY 2 DISABLED
SETP
xxxx --> RELAY SETPOINT
ACT2
INCR --> ACTIVATE AT INCREASING SIGNAL
DECR --> ACTIVATE AT DECREASING SIGNAL
HYS2
xxxx --> RELAY HYSTERESIS
ERR2
HOLD --> HOLD RELAY AT ERROR
ACTI --> ACTIVATE RELAY AT ERROR
DEAC --> DEACTIVATE RELAY AT ERROR
NONE --> UNDEFINED STATUS AT ERROR
ON.DE
xxxx --> RELAY ON-DELAY IN SECONDS
OF.DE
xxxx --> RELAY OFF-DELAY IN SECONDS
A.OUT
0-20 --> OUTPUT RANGE IN mA
4-20 --> OUTPUT RANGE IN mA
20-0 --> OUTPUT RANGE IN mA
20-4 --> OUTPUT RANGE IN mA
O.LO
xxxx --> DISPLAY VALUE FOR OUTPUT LOW
O.HI
xxxx --> DISPLAY VALUE FOR OUTPUT HIGH
O.ERR
23 mA --> NAMUR NE43 UPSCALE AT ERROR
3,5 mA --> NAMUR NE43 DOWNSCALE AT ERROR
0mA --> DOWNSCALE AT ERROR
NONE --> UNDEFINED OUTPUT AT ERROR
RESP
xxx.x --> ANALOGUE OUTPUT RESPONSE TIME
IN SECONDS
E.PAS
NO
--> ENABLE PASSWORD PROTECTION
YES
N.PAS
xxxx --> SELECT NEW PASSWORD
ADV MENU:
LANG --> ENTER LANGUAGE SETUP
DISP --> ENTER DISPLAY SETUP
CAL
--> PERFORM PROCESS CALIBRATION
HLP.T
DE
-->
DK
-->
ES
-->
FR
-->
IT
-->
SE
-->
UK
-->
CZ
-->
LIGH
xxxx
DE - WAEHLE DEUTSCHEN HILFETEXT
DK - VAELG DANSK HJAELPETEKST
ES - SELECCIONAR TEXTO DE
AYUDA EN ESPANOL
FR - SELECTION TEXTE D’AIDE
EN FRANCAIS
IT - SELEZIONARE TESTI DI
AIUTO ITALIANI
SE - VALJ SVENSK HJALPTEXT
UK - SELECT ENGLISH HELPTEXT
CZ - VYBER CESKOU NAPOVEDU
--> ADJUST DISPLAY LIGHT INTENSITY
CA.LO
YES
--> CALIBRATE INPUT LOW TO PROCESS
VALUE?
NO
CA.HI
YES
--> CALIBRATE INPUT HIGH TO PROCESS
VALUE?
NO
VAL.L
xxxx --> SET VALUE FOR LOW CALIBRATION
POINT
VAL.H
xxxx --> SET VALUE FOR HIGH CALIBRATION
POINT
USE.C
YES
--> USE PROCESS CALIBRATED VALUES?
NO
5714V103-UK19
Configuration / operating the
function keys
Documentation for routing diagram.
In general:
When configuring the display you are guided through all parameters, you can
choose the settings which fit the application. For each menu there is a scrolling help text which is automatically shown in the display, this starts after 5
seconds if no key has been activated.
Configuration is carried out by using the 3 function keys.


3
will increase the numerical value or choose the next parameter.
will decrease the numerical value or choose the previous parameter.
will accept the chosen value and end the menu.
If a function does not exist in the display all parameters are skipped to make the
configuration as simple as possible.
Once the configuration has been entered the display will show “----”.
Pressing and holding 3 will return to the previous menu or return to the default
state (1.0) without saving the changed values or parameters.
If no key is activated for 2 minutes, the display will return to the default state
(1.0) without saving the changed values or parameters.
Further explanations:
Fast setpoint adjustment and relay test: These menus allow you to change the
set point quickly and to check the operation of the relays.
Pressing 1 and 2 at the same time will change the state of the relay – this change
is indicated by the diodes on the display. Pressing 3 will save the set point
change.
Holding down 3 for more than 0.5 seconds will return the unit to the default state without changing the set point.
Password protection:
Using a password will stop access to the menu and parameters. There are two
levels of password protection. Passwords between 0000…4999 allow access to
the fast set point adjustment and relay test. (Using this password stops access
to all other parts of the menu). Passwords between 5000…9999 stop access
to all parts of the menu, fast set point and relay test. (Current set point is still
shown). By using the master password 2008, all configuration menus are available.
205714V103-UK
Graphic depiction of the relay function setpoint
100
100
Relay units
90
90
80
80
70
70
60
Relay units
60
50
40
Hysteresis = 10
50
Setpoint = 50
Setpoint = 50
40
Hysteresis = 10
30
30
20
Off N.O.
On N.O.
Off N.O.
10
On N.C.
Off N.C.
On N.C.
t
0 10203040506070 8090100
Relay action: Increasing
20
Off N.O.
On N.O.
Off N.O.
10
On N.C.
Off N.C.
On N.C.
t
0 10203040506070 8090100
Relay action: Decreasing
5714V103-UK21
Displays
Programmable displays with a wide selection of
inputs and outputs for display of temperature, volume and weight,
etc. Feature linearization, scaling, and difference measurement
functions for programming via PReset software.
Interfaces for analog and digital signals as well
Ex interfaces
as HART® signals between sensors / I/P converters / frequency
signals and control systems in Ex zone 0, 1 & 2 and for some
devices in zone 20, 21 & 22.
Galvanic isolators for analog and digital signals
Isolation
as well as HART® signals. A wide product range with both looppowered and universal isolators featuring linearization, inversion,
and scaling of output signals.
Temperature
A wide selection of transmitters for DIN form
B mounting and DIN rail devices with analog and digital bus
communication ranging from application-specific to universal
transmitters.
Universal
PC or front programmable devices with
universal options for input, output and supply. This range offers
a number of advanced features such as process calibration,
linearization and auto-diagnosis.
www.prelectronics.fr
[email protected]
www.prelectronics.de
[email protected]
www.prelectronics.es
[email protected]
www.prelectronics.it
[email protected]
www.prelectronics.se
[email protected]
www.prelectronics.com
[email protected]
www.prelectronics.com
[email protected]
www.prelectronics.cn
[email protected]
www.prelectronics.be
[email protected]
Head office
Denmarkwww.prelectronics.com
PR electronics A/S
Lerbakken 10
DK-8410 Rønde
[email protected]
tel. +45 86 37 26 77
fax +45 86 37 30 85
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement