ETS-Lindgren Med-Vizion Graphic Display Panel (GDP) System Medical Shielding Accessory Owner's Manual
ETS-Lindgren Med-Vizion Graphic Display Panel (GDP) System is a virtual window to the outside world. It uses modular, illuminated panels and skylights displaying nature scenes to create a positive mood enhancement in various environments such as MRI rooms, recovery rooms, and waiting rooms. It helps reduce stress, improve health outcomes, and support pain management. The Med-Vizion GDP has a scalable system allowing for growth and expandability, available in a variety of shapes and sizes.
Advertisement
Advertisement
Med-
Vizion™ GDP Systems
Virtual Environments
Installation Manual
ETS-Lindgren L.P. reserves the right to make changes to any product described herein in order to improve function, design, or for any other reason. Nothing contained herein shall constitute ETS-Lindgren L.P. assuming any liability whatsoever arising out of the application or use of any product or circuit described herein. ETS-Lindgren L.P. does not convey any license under its patent rights or the rights of others.
© Copyright 2012 by ETS-Lindgren L.P. All Rights Reserved. No part of this document may be copied by any means without written permission from
ETS-Lindgren L.P.
Trademarks used in this document: The ETS-Lindgren logo and Med-Vizion are trademarks of ETS-Lindgren L.P.
Revision Record
MANUAL,INSTALL,MED-VIZION GDP SYSTEMS | Part #399365, Rev. A
Revision Description Date
A Initial Release October, 2012
ii
www.ets-lindgren.com
Table of Contents
Notes, Cautions, and Warnings ................................................ v
1.0 Introduction .......................................................................... 7
LED Light Panel .................................................................................. 8
ETS-Lindgren Product Information Bulletin ............................................... 10
2.0 Maintenance ....................................................................... 11
Replacement and Optional Parts .............................................................. 11
3.0 Specifications ..................................................................... 13
LED Light Panel Specifications ................................................................. 13
Electrical Specifications .................................................................... 13
Physical Specifications...................................................................... 13
Mechanical Specifications ................................................................. 14
Dimmable LED DC Magnetic Transformer Specifications.......................... 15
Transformer Specifications ............................................................... 15
Enclosure Specifications ................................................................... 15
Electrical Specifications .................................................................... 15
Other Specifications .......................................................................... 16
Print Technology ............................................................................... 16
4.0 Before You Begin Installation ........................................... 17
5.0 Power Transformer Installation ........................................ 19
Dimmer Wiring Example ........................................................................... 21
6.0 Wall Virtual Window Installation ...................................... 23
2m x 3m Wall Virtual Window Drawing ...................................................... 24
LED Light Panel and Frame Drawing ........................................................ 24
Wiring Diagram ................................................................................. 26
www.ets-lindgren.com
iii
Power Transformer Wiring ........................................................................ 27
Installing Art Panel in Virtual Window ........................................................ 28
7.0 Ceiling Skylight Installation .............................................. 29
Integrated Into Existing Grid System Ceiling ............................................. 30
Example: Skylight ~1.8 m x 3 m / Panels 60 cm x 60 cm................... 30
Wiring Example: 2.4 m x 1.8 m ................................................................. 31
Power Switch .................................................................................... 31
Appendix A: Warranty ............................................................. 35
iv
www.ets-lindgren.com
Notes, Cautions, and Warnings
Note: Denotes helpful information intended to provide tips for better use of the product.
Caution: Denotes a hazard. Failure to follow instructions could result in minor personal injury and/or property damage. Included text gives proper procedures.
Warning: Denotes a hazard. Failure to follow instructions could result in SEVERE personal injury and/or property damage. Included text gives proper procedures.
See the ETS-Lindgren Product Information Bulletin for safety, regulatory, and other product marking information. www.ets-lindgren.com
v
This page intentionally left blank.
vi
www.ets-lindgren.com
1.0 Introduction
The ETS-Lindgren
Med-
Vizion™ GDP
(Graphic Display Panel)
system is a series of modular, illuminated panels and skylights that create a virtual window to the world outside. The virtual window and skylight display an image of nature chosen from a portfolio of beautiful, pleasing images, and can be used to provide a positive mood enhancement in MRI rooms, recovery rooms, and waiting rooms, to name a few.
Research has documented that the use of nature settings in a healthcare environment can reduce stress, improve health outcomes, and support pain management.
The Med-Vizion GDP is a scalable system, allowing for growth and expandability.
It is available in a variety of shapes (square, rectangle, round, and oval) and sizes; custom shapes and sizes are available upon request. www.ets-lindgren.com Introduction
7
Standard Configuration
The Med-Vizion GDP system includes the following:
LED light panel
—see page 8 for more information
Art panel
—see page 9 for more information
LED light panel power transformer
Aluminum frame (wall virtual windows only)
LED L
IGHT
P
ANEL
The LED light panel is MRI room-compliant, comprised of non-ferrous materials, and is available in standard pure white.
8
Introduction www.ets-lindgren.com
The 8-mm thick panel is edge-lit and uses a 3D laser-engraved V-cutting system that evenly transmits light. The LED light panel is free of mercury and other hazardous materials, and consumes up to 70% less power than T5 fluorescent lamps, and up to 30% less power than CCFL. With a <1% failure rate, the patented thermal management system maximizes life expectancy.
The low-profile framing system mounts easily and conforms to ADA.
A
RT
P
ANEL
The imagery created for the art panel compliments the LED light source, is scaled for human perspective, and is a perfect balance of color, density, contrast, and saturation. Hundreds of images in a variety of categories are available: desert scenes, floral scenes, garden scenes, sky scenes, cloud scenes, and many others.
The art panels are stain, mildew, mold, and bacteria resistant, and are guaranteed not to fade, crack, or yellow for 12 years under specified normal lighting usage.
Optional Items
The power transformer should be attached to a power switch or dimmer (not included). To order a dimmer, contact the ETS-Lindgren Sales Department. www.ets-lindgren.com Introduction
9
ETS-Lindgren Product Information Bulletin
See the ETS-Lindgren Product Information Bulletin included with your shipment for the following:
Warranty information
Safety, regulatory, and other product marking information
Steps to receive your shipment
Steps to return a component for service
ETS-Lindgren calibration service
ETS-Lindgren contact information
10
Introduction www.ets-lindgren.com
2.0 Maintenance
Before performing any maintenance, follow the safety information in the
ETS-Lindgren Product Information
Bulletin included with your shipment.
WARRANTY
Use a damp cloth and mild cleaner to clean.
If you have any questions concerning maintenance, contact ETS-Lindgren
Customer Service.
Replacement and Optional Parts
ETS-Lindgren may substitute a similar part or new part number with the same functionality for another part/part number. Contact
ETS-Lindgren for questions about part numbers and ordering parts.
Following are the part numbers for ordering replacement or optional.
Part Description
Replaceable LED light panels
Additional art panels
Part Number
Contact ETS-Lindgren Sales
Department
Contact ETS-Lindgren Sales
Department
Service Procedures
For the steps to return a system or system component to ETS-Lindgren for service, see the Product Information Bulletin included with your shipment. www.ets-lindgren.com Maintenance
11
This page intentionally left blank.
12
Maintenance www.ets-lindgren.com
3.0 Specifications
LED Light Panel Specifications
E
LECTRICAL
S
PECIFICATIONS
Input Voltage:
Power Consumption:
12 Volt DC
0.25 Watts/LED
(Power consumption/wattage depends upon final size/shape)
Standard: 18
LED Configuration
(per ft/illuminated edge):
Electrical Connection:
Wiring:
Wire size: 20 AWG 2 wire
Polarity: Positive center/white line
Panels may be wired in parallel when connecting multiple panels to a single power transformer
P
HYSICAL
S
PECIFICATIONS
Minimum Size:
Maximum Size:
Thickness:
Weight:
Color Options:
Color Temperature(CCT):
Operating Temperature:
5.08 cm x 5.08 cm
2 in x 2 in
1.49 m x 2.99 m
58.625 in x 117.625 in
8 mm
1.95 lb per sq ft
Standard pure white: 5300K pure 5300K
–30 °
C to +40
°
C (
–22 °
F to +104
°
F) www.ets-lindgren.com Specifications
13
Longevity:
Luminous Efficacy (LED):
Luminous Flux:
Power Supplies:
Ratings:
More than 50,000 hours:
11 years at 12 hours per day
80 lm / W
2289 lm
110/277AVC
–12/24VDC
UL and CE
UL/CE/IP-67 ratings are available upon request
M
ECHANICAL
S
PECIFICATIONS
Tensile Strength:
Elongation:
Flexural Strength:
Flexural Modulus:
Izod Impact Strength:
Rockwell Hardness:
760 kg/cm
2
6%
1170 kg/cm
2
32000 kg/cm
2
2 kg cm/cm
95 (Mscale)
14
Specifications www.ets-lindgren.com
Dimmable LED DC Magnetic Transformer Specifications
T
RANSFORMER
S
PECIFICATIONS
Leads:
Lead Insulation:
Insulation System:
E
NCLOSURE
S
PECIFICATIONS
Input: 18 AWG
Output: 12 AWG
Primary: PVC 600V #20,
#18, #18
Secondary: PVC 300V #14,
#12, #12
105
°
C
Class B 130
°
C
Enclosure Temperature:
Wiring Compartment:
Will not exceed 70
°
C @ 40
°
C ambient
Has 2 knockouts sized for 3/4-in screw cable connectors
Removable cover is secured in place by a screw
Black powder-coated
Coating:
E
LECTRICAL
S
PECIFICATIONS
Max Load:
Input Voltage:
Output Voltage Full Load:
Input Current Full Load:
Open Circuit Volts:
Output Current Full Load:
www.ets-lindgren.com
60 W, 100 W, 150 W
120V 60Hz
11.5 VDC
540 mA, 898 mA, 1240 mA
12.5 VDC
4.8 A, 8.05 A, 12.35 A
Specifications
15
O
THER
S
PECIFICATIONS
Efficiency:
Coll Former:
Thermal Class:
Art Panel Specifications
I
MAGERY
Format:
Content:
89.20%, 87.20%, 85.20%
Double section bobbin
B 130
°
C
Panoramic photographs in both horizontal and vertical
500 MB to 1.2 GB files on analog film
P
RINT
T
ECHNOLOGY
Print Resolution:
Fire Rating:
Durability/Comprehensive
Strength:
2400 × 1200 dpi
Class A; ASTM-84 test method
ASTM-D 695 / 17,000 psi
(117 M Pa)
16
Specifications www.ets-lindgren.com
4.0 Before You Begin Installation
Before assembling, connecting, or installing any components, follow the safety information in the ETS-Lindgren Product Information
Bulletin included with your shipment.
Installation must be performed by a qualified builder and electrician. This installation manual does not replace the services of a qualified builder/electrician.
Local building conditions, codes, and materials vary. The information in this installation manual is generic. Contact a qualified builder/electrician for the conditions, codes, and materials specifically required for your location. www.ets-lindgren.com Before You Begin Installation
17
This page intentionally left blank.
18
Before You Begin Installation www.ets-lindgren.com
5.0 Power Transformer Installation
Before assembling, connecting, or installing any components, follow the safety information in the
ETS-Lindgren Product Information Bulletin included with your shipment.
WARRANTY
The LED light panel is powered by 12V/DC
(constant voltage) power transformers. Apply correct voltage required for your system or damage may occur. Warranty is void if using any other power transformers that are not approved.
Any adjusted cords from the power transformer to the LED light panel should be kept as short as possible to avoid any voltage drop to the
LED light (default is about 10 feet at #22AWG).
Never apply AC power directly to the LED light panels as this will instantly damage the LEDs.
The transformer is to be installed in accordance with Article 450 of the National Electric Code.
The transformer must be installed in a well-ventilated area free from explosive gases and vapors. Proper operation requires the free flow of air. This transformer is hardwired, and should only be installed by a qualified electrician.
www.ets-lindgren.com Power Transformer Installation
19
Prior to following the steps in this section, see Before You Begin
For more information on power transformers, see Power Transformer
1.
Check the label and verify that the transformer has the proper input voltage, output voltage, and wattage for the specific application.
Verify that the wire markings match the following wiring diagram.
20
2.
Select a suitable location capable of supporting the weight of the transformer. Use the two keyholes in the transformer case. It is recommended that the transformer be mounted vertically with the wiring compartment pointing down.
Power Transformer Installation www.ets-lindgren.com
For all wire connections use only UL listed wire nuts and connectors of suitable size and type. The transformer case must be grounded in accordance with the N.E.C.
3.
Remove the wiring compartment knockouts and install strain reliefs.
With power turned off, route the input wires through a strain relief and connect one wire to black and one wire to white.
Connect the ground wire to the transformer green wire.
4.
Bring the wires of the light fixture through the other open knockout and connect them to the transformer wires.
Positive to the red wire
Negative to the blue wire.
Dimmer Wiring Example
On the following page is a sample wiring diagram for a dimmer configuration that includes (3) 2 ft x 4 ft LED light panels. www.ets-lindgren.com Power Transformer Installation
21
22
Power Transformer Installation www.ets-lindgren.com
6.0 Wall Virtual Window Installation
Before assembling, connecting, or installing any components, follow the safety information in the ETS-Lindgren Product Information
Bulletin included with your shipment.
Enough fasteners should be used to support the weight of the wall virtual window to the wall.
Fasteners are not included in the shipment; purchase the type and quantity the will properly support to your installation.
Where possible, the cable and power transformer should be hidden from view; for example, behind or in the wall, or using a cable channel.
The power transformer should be attached to a power switch or dimmer (not included).
Prior to following the steps in this section, see Before You Begin
A 6-ft x 8-ft window is used as an example in this section. www.ets-lindgren.com Wall Virtual Window Installation
23
2m x 3m Wall Virtual Window Drawing
LED Light Panel and Frame Drawing
24
Wall Virtual Window Installation www.ets-lindgren.com
Wiring for LED Light Panel
Cables and power transformer should be hidden in the wall.
The light panel contains two rows of LEDs.
Wires from each row are brought together and connected to one wire and run to the power transformer. www.ets-lindgren.com Wall Virtual Window Installation
25
W
IRING
D
IAGRAM
26
Wall Virtual Window Installation www.ets-lindgren.com
Power Transformer Wiring
One power transformer can supply power to multiple LED light panels as long as the total wattage of the light panels is less than the total wattage of the power transformer. If multiple LED light panels are wired to a single power transformer, connect them in parallel instead of series; this will avoid a voltage drop while maximizing the light output.
C
ORRECT
www.ets-lindgren.com Wall Virtual Window Installation
27
I
NCORRECT
Installing Art Panel in Virtual Window
Handle art panels with care. DO NOT GLUE
ART PANEL TO LED LIGHT PANEL.
1.
Open the frame on all sides.
2.
Place image against the LED light panel.
3.
Place acrylic (clear plastic) sheet against the image.
4.
Close the frame on all sides to secure the image.
28
Wall Virtual Window Installation www.ets-lindgren.com
7.0 Ceiling Skylight Installation
Before assembling, connecting, or installing any components, follow the safety information in the ETS-Lindgren Product Information
Bulletin included with your shipment.
Enough cables should be used to support the weight of the skylight to the structural ceiling.
Where possible, the cable and power transformer should be hidden from view; for example, behind or in the wall, or using a cable channel.
The power transformer should be attached to a power switch or dimmer (not included).
Wiring diagram can be supplied if required when final configuration is confirmed.
Prior to following the steps in this section, see Before You Begin
A 6-ft x 10-ft skylight is used as an example in this section. www.ets-lindgren.com Ceiling Skylight Installation
29
Integrated Into Existing Grid System Ceiling
LED light panels fit into existing suspended grid ceiling, either 600 mm x 600 mm
(2 ft x 2 ft) or 600 mm x 1200 mm (2 ft x 4 ft).
E
XAMPLE
: S
KYLIGHT
~1.8
M X
3
M
/ P
ANELS
60
CM X
60
CM
30
Ceiling Skylight Installation www.ets-lindgren.com
Wiring Example: 2.4 m x 1.8 m
Cables and power transformer should be hidden. Do not coil excess wiring in the ceiling or on the ceiling grid; this could cause RF noise.
The light panel contains two rows of LEDs. Wires from each row are brought together and connected to one wire and run through the filter to the power transformer.
RF F
ILTERS
RF filters are required for panels installed in an MRI room. RF filters are not required for other types of Radiology rooms.
P
OWER
S
WITCH
The power on/off switch is typically located outside the MRI room, placed between the power transformers and the mains power. www.ets-lindgren.com Ceiling Skylight Installation
31
32
Ceiling Skylight Installation www.ets-lindgren.com
Installing Art Panel in Skylight
Image is printed on an acrylic substrate for optimum rigidity; however, always handle art panels with care.
Place art panel into suspended grid ceiling, with LED light panel resting on top of art panel. www.ets-lindgren.com Ceiling Skylight Installation
33
This page intentionally left blank.
34
Ceiling Skylight Installation www.ets-lindgren.com
Appendix A: Warranty
See the Product Information Bulletin included with your shipment for the complete ETS-Lindgren warranty for your Med-
Vizion™ GDP
(Graphic Display Panel) system.
D
URATION OF
W
ARRANTIES FOR
M
ED
-V
IZION
GDP S
YSTEM
All product warranties, except the warranty of title, and all remedies for warranty failures are limited to two years.
Product Warranted
LED Light Panel
Art Panel
Duration of Warranty Period
2 Years
12 Years www.ets-lindgren.com Warranty
35

Download
Advertisement