Chromalox CX224 User manual

Chromalox CX224 User manual
CX224
12-Channel Temperature Monitor
Installation and Operating Instructions
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
This page left blank intentionally.
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
2
Table Of Contents
1.
Introduction
2.
Pre-Installation
3.
Installation
4.
A.
Mounting
B.
Wiring
1.)
Controller Power
2.)
Inputs
3.)
Outputs
4.)
Serial Communications
Programming Configuration
A.
Using the CX224
1.)
5.
6.
Chromalox
Modes / Buttons
B.
Entering the Program Settings
C.
Setup Worksheet
Communications
A.
Function Codes
B.
Memory Map
Specifications
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
3
1.
Introduction
The CX224 is a universal 12-channel monitor capable of monitoring inputs for any combination of
RTDs, Thermocouples, and 4-20mA loop inputs. The CX224 has 5 outputs, 4 of the outputs can be
used for warning or shutdown signals, the other output is dedicated to signaling alarm conditions.
One internal audible alarm is also present. RS485 or RS232 Serial Communications is also included
on the CX224 and allows use of the Modbus Protocol to communicate data with another device.
Chromalox CX224 Software is also provided to allow easy communication with the CX224 by using a
computer.
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
4
2.
Pre-Installation
The first step before installing the CX224 is to determine the input types that will be used. If analog
4-20mA signals will be used as inputs, jumpers under the rear cover will need to be changed. When
received, the jumpers are set to allow RTD and thermocouple inputs on all input channels. Analog
inputs require that the jumpers be moved to the 4-20mA setting. Follow the simple steps below to
allow 4-20mA loop inputs:
1.
2.
3.
4.
Remove the 4 screws that hold the rear cover on. (Do not remove the other 4 screws
that go directly through the board.)
Set the rear cover aside.
Look at the top of the CX224. There is one jumper for each channel located next to the
corresponding channels terminal block. For all of the channels that will be used for 420mA inputs, set the jumper to the position away from the dot. Figure 1 shows a
jumper in the position to allow 4-20mA loops. Leave the jumpers for the other
channels that will be used for RTDs and thermocouples in the dot position. Figure 2
shows a jumper in the position for RTD and Thermocouple inputs.
Replace the rear cover and screws.
The CX224 is now ready to accept 4-20mA inputs on the channels that are set like the jumper shown
in Figure 1.
Figure 1 – Switches in position for 4-20mA Inputs
Figure 2 – Switches in position for RTD or Thermocouple Inputs
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
5
3.
Installation
A.
Mounting
Make a rectangular cut out in the panel where the CX224 will be located. The cutout should
be made according to Figure 3.
Figure 3 – Panel Cutout
Slide the CX224 into the cut out, drill holes for the screws or bolts that will fasten the unit to
the panel. Be sure that the gasket around the CX224 is compressed between the front cover
and the panel so that liquid and debris cannot get behind and inside of the panel.
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
6
B.
Wiring
The locations of the connections on the CX224 are shown in Figure 4. The rear cover of the
CX224 also shows the connections for each terminal. More detail for each of the connections
is given in the following sections.
Figure 4 – Wiring Connection Locations
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
7
1.
Controller Power
The CX224 Power connections will vary depending on which type of power is use.
AC
On AC models, the Line and Neutral will be connected to the terminal block in the lower right
hand corner on the rear of the CX224. See Figure 5. The lower terminal on the terminal block
is used for ground. It is important to connect earth ground to the lower terminal if shielded
cable is used for sensors. This connection is how a grounding connection is made to the
shields of the RTDs. Connecting to earth ground also provides a path for current to flow in
the event of an electrical failure and helps to protect the operator from possible electrocution
in such an event.
Fuse
Fuse
Figure 5 – AC Power Connections
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
8
DC
On DC models, the DC voltage is connected to the upper terminals and the terminal block in
the lower right corner on the rear of the CX224. See Figure 6. The upper terminal on the
control power terminal block is connected to the positive supply voltage, between 18 and
36Vdc. The lower terminal on the terminal block is used for ground. It is important to
connect earth ground to the lower terminal if shielded cable is used for sensors. This
connection is how a grounding connection is made to the shields of the RTDs. Connecting to
earth ground also provides a path for current to flow in the event of an electrical failure and
helps to protect the operator from possible electrocution in such an event.
Fuse
Fuse
Figure 6 – DC Power Connections
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
9
2.
Inputs
The CX224 can accept any combination of the input types specified in Section 6 at the end of
this document. These may include RTDs, thermocouples, and 4-20mA transmitter loops.
However, some care must be taken when using multiple inputs so that a safe environment is
created for personnel and equipment. For instance, a CX224 should monitor sensors from
only one piece of equipment, especially if high voltage is present. Using this approach,
damage to other devices is greatly reduced, if a circuit fault should occur.
The CX224 does not have channel to channel isolation. This means that grounded
thermocouples cannot be used directly with the CX224. Ungrounded thermocouples may be
used. If grounded thermocouples are used, a device such as the Minco Model TI241 can be
utilized as a means to break ground loops and provide proper inputs to the CX224.
Another consideration due to not having channel to channel isolation is that when using 420mA inputs, all loops will share the same return path. Keep this in mind when planning the
system to ensure that it is safe to wire all loops together. It is the system designer’s
responsibility to ensure that good safety measures are used. If unsure about the safety
aspects of a system, call Chromalox for assistance.
Each input channel has 3 input terminals and a common earth ground terminal. The
terminals are labeled as A, B, C and D. Terminal D is connected to earth ground, when earth
ground is connected to the terminal block as described in Section 1, Controller Power. Input
wiring for the different input types is shown in Figures 7, 8, 9, and 10.
RTDs - RTDs Use three terminals per channel. Care should be taken to not exceed 30 ohms of
lead wire resistance. Chart 1 shows maximum lead wire length per lead of an RTD so as not to
exceed the 30 ohms maximum lead wire resistance. Leadwire for RTDs should be twisted and
shielded, this will reduce fluctuations in the readings due to noise.
Leadwire
(AWG)
18
20
22
24
26
28
Ohms/Foot at
25ºC
.0065
.0103
.0165
.0262
.0418
.0666
Maximum Length for
30 ohms of
Resistance
4615
2912
1818
1145
717
450
Chart 1 – Leadwire Resistance per lead
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
10
3-wire RTD: The odd colored wire must be connected to terminal A of the input channel.
The other two wires can be placed in either order in B and C. If the RTD has a shield, place it
into terminal D. When adding leadwire to the RTD, be sure to use the same length and gauge
for each lead. The CX224 is able to provide very good compensation for leadwire resistance
as long as each lead has the same resistance. Recommended Extension Leadwire: Belden
1031A or any other wire that is twisted and shielded is a good choice.
Figure 7 – 3-Wire RTD Wiring
2-wire RTD: One of the leads should be placed in terminal A for the input channel. The
other lead should be placed in either B or C. A jumper wire must be placed between B and C
in order to complete the input circuit. If the RTD has a shield, connect it to terminal D.
Recommended Extension Leadwire: Belden 1030A or any other wire that is twisted and
shielded is a good choice.
The 2-wire RTD will exhibit some error due to the inability to compensate for lead wire
resistance. This can be partially compensated by using the Zone Offset feature as shown later
in the manual under the Programming Configuration section. Chart 2 shows lead wire
resistance based on wire gauge. The desired offset value can be calculated using the chart,
length of leadwire, and by visiting www.chromalox.com and using the “Sensor Calc” program
to determine the affect of the leadwire. By using this information it is possible to reduce the
leadwire error by adjusting the offset.
Figure 8 – 2-Wire RTD Wiring
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
11
Thermocouples – Thermocouples use terminals B and C. The positive lead on the
thermocouple should be connected to the B terminal and the negative lead to the C terminal.
On a thermocouple the red lead is usually negative (–) and the other lead is usually positive
(+). Figure 9 shows how to wire the Thermocouple to the CX224.
Figure 9 – Thermocouple Wiring
4-20mA – 4-20mA inputs use terminals B and C. The loop positive should be connected to
the B terminal and the loop negative should be connected the C terminal. When configuring
the CX224 for 4-20mA loops, you must set the DIP switch on the PCB toward the top of the
CX224. This is shown in Figure 1 in the Pre-Installation Instruction section.
Figure 10 – 4-20mA Wiring Diagram
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
12
3.
Outputs
Two types of outputs are available on the CX224, relays or logic. The output type is
determined by the options that were ordered.
There are three terminals for each output. All three terminals are used when relays are the
output type. When logic outputs are installed, only two of the terminals are used. The
terminals are labeled as A, B, C. Caution: The terminal positions are A, B, C on the left side of
the unit reading from top to bottom, but they are labeled as C, B, A on the right side of the
unit.
The CX224 has 5 outputs. Four of the outputs are used for signals and can be configured to
trip and untrip in several different ways. The different methods are covered in section
4. Program Configuration part B) Entering The Program Settings. The Alarm Output
differs from the other 4 outputs in several ways. The Alarm Output will use the hysteresis
value for the channel that caused it to trip as it’s untrip value. If the alarm is configured to
sound with a channel that is set to latch another output on a trip, the alarm will continue to
sound until a key is pressed. The Alarm Output cannot be configured for reverse acting, it is
always direct acting.
Relay outputs: Relays are SPDT, they have terminals for both normally open (NO) and
normally closed (NC) contacts. The NO contact is between terminals B and C and the NC
contacts are between terminals A and B.
Logic outputs: Logic outputs use terminals A and B, with B as the reference ground. Logic
outputs are not isolated from the controller supply. Caution must be taken when using logic
outputs since several devices may be sharing the same reference ground when they are
connected.
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
13
4.
Serial Communications
Modbus protocol is used to communicate between the CX224 and other device (PC or PLC).
Two physical interface options are available for serial communications. They are RS232 and
RS485. The CX224 is always a slave device.
RS485
RS485 allows for multiple devices to be connected to one network. Up to 128 CX224 can be
connected to a network. The RS485 standard allows up to 32 nodes to be connected on a
half-duplex network. However, each CX224 accounts for only ¼ of a node, so 128 CX224 can
be connected to the network when RS485 is used as the medium.
The connections on the CX224 are labeled as A, B, and S. The two signal wires are A and B.
The A terminal should be connected to the A terminal on the RS232 to RS485 converter. The
B terminal should be connected to the B terminal on the RS232 to RS485 converter. The S
terminal should be connected to the shield. The shield wire should be connected to ground
in one location only, to avoid ground loops, which can cause erratic communications. Refer
to Figure 11 for a wiring diagram.
RS232
Terminal A is the Transmit Data (TD) connection, terminal B is the Receive Data (RD)
connection, and terminal S is the Signal Ground (SG) connection on the CX224. RS232 devices
require Terminal A connected to Receive Data from the master device, Terminal B to Transmit
Data from the master device, and terminal S to Signal Ground. For a 9-pin D-Sub connector
on a PC, connect A to pin2, B to pin 3, and S to pin 5. Caution should be taken when using
RS232, as it is not isolated. This could cause ground loops through devices, which could
cause damage to the CX224 and / or other devices. Refer to Figure 11 for a wiring diagram.
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
14
RS485
RS232
Figure 11 – Wiring diagrams for RS232 and RS485
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
15
Connecting Multiple CX224
A network of CX224’s should be wired so that the CX224’s are in a chain. However, only
devices using RS485 can be connected in this manner. RS232 will only allow one (1) device to
be connected to a port, so RS232 devices cannot be used in a network. A star or ring
configuration is not appropriate for RS485. Each CX224 should only be connected to at most
2 other CX224. Figure 12 shows the basic wiring for a chain configuration. Like terminals on
the CX224’s should be connected together in the chain, A to A, B to B, S to S.
Figure 12 – Master Slave Chain
End devices (Master and last Slave) on an RS485 network should be terminated to achieve
error-free communications. The termination should match the characteristic impedance of
the network. Normally this value is about 120ohms. Figure 13 shows how to easily apply a
termination resistor to the last CX224 in a chain. Do not use more than 2 termination resistors
on the network. There are many other methods for terminating an RS485 network. If
interested in trying a different termination approach, consult the Internet for various other
configurations. In most applications, terminating with 120ohm resistors will provide errorfree communications.
Figure 13 – Termination of RS485 Network
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
16
4. Program Configuration
A.
Using the CX224
The CX224 has two main modes of operation, Monitoring Mode and Menu Mode. When the
CX224 is powered up it will enter Monitoring Mode. Initially the message “Initializing Inputs”
will be shown on the display. The CX224 is evaluating the inputs and initializing the outputs
based on the program configuration that has been stored in the device. After a few seconds
the screen will change and display an input reading.
1.
Modes / Buttons
The CX224 has 4 buttons. The user interface has been designed to offer quick modifications
to many parameters in an easy to use manner. Buttons have different purposes depending on
the Mode of the CX224.
Monitoring Mode
Most of the time the unit will be in Monitoring Mode. In Monitoring Mode, all zones
that are configured for input (including the Cold Junction Compensation value), are
scanned and the program settings are used to adjust the outputs.
When in Monitoring Mode, the Back and Right arrow buttons display the next lower
input zone while the Enter and Up arrow buttons move to the next higher input zone.
When customized zone names are used, they will be displayed. The name given to
input zone 1 will be displayed in place of the default name “ZONE 1”. Entering a
custom zone name can be done by entering Menu Mode, selecting Options, Rename
Zones.
Menu Mode
To enter Menu Mode from Monitoring Mode, press and hold any key for 3 seconds. A
beep will sound and the main menu will be shown. There are many different menus
that can be accessed in the Menu Mode. While in Menu Mode, the inputs are not read
and outputs are not adjusted. A 60-second countdown is started each time a key is
pressed when in Menu Mode. If 60 seconds passes without pressing a key, the CX224
will reset and enter Monitoring Mode and continue to evaluate inputs and outputs.
The buttons in Menu Mode are used for different purposes based on which area is
entered. The Back and Right arrow buttons move the cursor up one line and the Enter
and Up arrow move the cursor down one line when making a selection from a list.
When a selection is made which prompts the user for input, then the buttons take on
different tasks. When prompted to enter a value, the Up arrow is used to change the
value of the character or the selection where the cursor is located. Once the desired
character has been set at the current cursor position, pressing the right arrow will
move the cursor to the next position and the Up arrow can be used to adjust that
character. Pressing Enter will accept (and save) the current setting and advance to the
next step in the configuration process. The Back button is used to move back to the
previous step in the configuration process or exit the section that is currently being
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
17
modified. To quickly exit an area where configuration is being done, hold the Enter
Key for 3 seconds and the mode will be exited. All parameters that were modified and
saved by pressing Enter will be saved.
The first menu shown when Menu Mode is entered is the Main Menu. It allows the
following choices:
1.
Monitor Zones
2.
Setup
3.
Manual Reset
4.
Options
1. Monitor Zones
Select this option to return to Monitoring Mode to read and evaluate the inputs and
outputs.
2. Setup Menu
The Configuration Menu may require a password to enter, by default no password is
required. The Configuration Menu contains the following options.
1.
Change Passwords
2.
Change Settings
3.
Modify Offsets
4.
Comm Settings
1.
Change Passwords - Select the password to change. A message asking
if you would like to change a password will be shown. Choose ‘Yes’ to change a
password or ‘No’ to exit the Change Passwords option. By setting a password
to 0000, the password will be deactivated. The valid range for a password is
0000 to 9999. If a password is already entered, the user will be required to
enter the existing password in order to change it. If you forget your password,
the master password can be used, it is found on the last page of this manual.
Available selections are:
1.
Program Password
2.
Unlatch Password
1.
2.
Program Password – Changes the password that is used to
protect the Change Program option.
Unlatch Password – Changes the password that is used to
protect Manual Reset of the Outputs.
2.
Change Settings - This section is used to configure all inputs and
outputs. (May be password protected.) When this section is exited, either due
to the 60-second timeout or exited by the user, the CX224 will automatically
reset and start scanning with the new program settings. The CX224 will also
reset when program settings are changed via the communications link using
Chromalox’s CX224 Software. This is the main section of the CX224
configuration process and has a full section below covering its use. See section
4B, Entering the Program Settings, for more information.
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
18
3.
Modify Offsets - Adjust the offset for each input zone. The offsets are
used to improve accuracy of the readings. This could be useful if a 2-wire RTD
is used or a particular value is crucial in a process. The offset can be used so
that less error is present. The units for the offset are Tenths. So, if the reading
is off by -1 degree (or 1 unit in any other measurement), the number that
should be entered for the offset value is 10, because this will raise the value by
10 tenths or +1 degree.
4.
Comm Settings – This selection steps through setting the monitor
address and the baud rate for the serial communications. The settings chosen
must match the settings selected by the master device that will be
communicating with the CX224. The first screen requests the user to enter the
Modbus address. The valid range of addresses is from 1 to 247. If 0 is selected,
the CX224 will not monitor the communication lines. Each CX224 is factory set
to a default Modbus address of 1. If communications are not used, it is
acceptable to leave the default address at 1. If multiple CX224 are to be used,
the addresses should be changed to prevent communication errors. The next
screen will request setting the baud rate. Valid baud rates are: 600, 1200, 2400,
4800, 9600, and 19200.
3. Manual Reset - Use this option to reset the outputs if a trip has occurred and
Manual Reset Only was selected when configuring the outputs. (May be password
protected.)
4. Options – Options Menu allows the user to personalize the zone names and
exercise the relays.
1.
Rename Zones
2.
Exercise Relays
3.
Freeze Outputs
1.
Rename Zones – This option is used to personalize the display. Up to
16 characters can be entered to describe the input location. Capital letters (AZ), numbers (0-9), and spaces are allowed.
2.
Exercise Relays – This option can be used to trip the outputs for test
purposes. This can be helpful to verify that wiring is correct and that
connections are secure. When selected and relays are in tripped condition, the
unit will keep the outputs tripped until another key is pressed.
3.
Freeze Outputs – Selecting this option will disable the program from
changing the state of any output. The message “Outputs are Frozen” is
displayed on the screen when this selection is active and the CX224 is in
Monitor Mode. To unfreeze the outputs, choose this option again and the
Freeze Outputs option will be disabled.
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
19
B) Entering the Program Settings
The first step to take when configuring the CX224 is to decide how you would like the device
configured. Configuration is best performed using Chromalox CX224 Software. If you do not
have a computer available for configuration you may also use the keypad on the CX224 to
enter the settings. If using the keypad to configure the CX224, use the Setup Worksheet to
speed up the process and reduce errors. Due to the 60-second timeout in the CX224, it is best
to fill out the Setup Worksheet before configuring the unit. This will also allow you to have
record of the settings that are programmed into the unit for future reference.
A description for each of the configuration options is give on the following pages.
Reverse acting outputs? - Choose the outputs you would like to configure for reverse action.
N – Relay: Normally Open (NO) contact will be open and the Normally Closed (NC)
contact will be closed.
Logic: Output will be low (0V) in untripped state.
Y – Relay: NO contact will be closed and the NC contact will be open in the untripped
state. The Logic: Output will be high (+5V) in untripped state.
Temperature Scale: Choose the temperature scale that the CX224 should use. RTDs and
thermocouples will use this temperature scale for display. Options are F, Fahrenheit and C,
Celsius.
Zone to be displayed during normal operation: Choose how the input readings should be
displayed.
The user can always adjust the displayed reading by pressing keys, after 5 seconds the CX224
will resume it’s process of displaying the High, Low or Scanning through inputs.
High – Highest input reading is displayed, regardless of input type.
Low – Lowest input reading is displayed, regardless of input type.
Any – Display will stay on the zone that the user has set it to.
Minutes of alarm silence when a key is pressed: Set the amount of time to wait until the
alarm will resound, if the alarm condition is still present. Valid range is 1 to 100 minutes or
Stays Off. This setting only resounds the alarm, it will not re-trip an output. It is designed to
remind personnel that there is still a trip condition in affect.
If an input fails: This setting allows the user to determine what action the CX224
should take if a broken sensor is detected.
Sound alarm – Alarm will sound if input fails. Alarm will resound according to the
“Minutes of alarm silence when a key is pressed” set in the previous step.
Trip output(s) associated with failed input – All outputs configured to trip on the
channel that has a failed input will trip.
Ignore – Continue operating like the input is still functioning properly.
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
20
Choose input type: Select the input type for this zone. Options are:
RTD Inputs
Material
Platinum (PA)
Platinum (PB)
Platinum (PD or PE)
Platinum (PF)
Nickel (NA)
Copper (CA)
Resistance
at 0ºC in ohms
100
100
100
1000
120
9.035 (10 Ω at 25°C)
TCR
.00392
.00391
.00385
.00385
.00672
.00427
Sensor Range
-200 to 700ºC (-328 to 1292ºF)
-200 to 700ºC (-328 to 1292ºF)
-200 to 850ºC (-328 to 1562ºF)
-200 to 600ºC (-328 to 1112ºF)
-80 to 260ºC (-112 to 500ºF)
-100 to 260ºC (-148 to 500ºF)
Thermocouple Inputs
Type
Sensor Range
E
-270 to 1000ºC (-454 to 1832ºF)
J
-200 to 1200ºC (-328 to 2192ºF)
K
-270 to 1150ºC (-454 to 2102ºF)
T
-270 to 400ºC (-454 to 752ºF)
4-20mA Transmitters: Output proportional to process variable for Pressure PSI, Pressure Bar,
% Relative Humidity, Process Variable mA, Process Variable Vdc, Vibration G, Temperature ºC,
Temperature ºF.
Enter Low End of Transmitter Range: This setting will only be displayed if a 4-20mA input is
selected in the previous step. All ranges for RTDs and thermocouples are fixed. The valid
input range is between -999 and 9999.
Enter High End of Transmitter Range: This setting is also only available when a 4-20mA
input is selected. The valid input range is between –999 and 9999. The high end of the
transmitter range must be higher than the low end.
Zone X Trip 1: Set the trip value for this zone. When Trip 2 is displayed it will correspond to
the second trip value for the zone. Valid temperature ranges are shown in the charts found
under “Choose input type:”. If a value not within the range for the sensor is entered, a
warning will be displayed and a new, valid setting should be entered.
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
21
Trip Over or Under? – This setting determines when the outputs will trip.
Over – Outputs for the zone will trip when the reading is higher than the trip value.
Under – Outputs for the zone will trip when the reading is lower than the trip value.
Sound Alarm on Trip? –Yes will cause the alarm to sound and alarm output to trip when the
reading passes the trip value. Selecting No will not sound the alarm when the outputs are
tripped.
Outputs to trip:
Output1__ Output2__
Output3__ Output4__ - A Y after the output indicates to trip the output when the reading
passed the trip value. An N after the output indicates the output should not be tripped.
Untrip Outputs by: - This setting will determine how the outputs associated with this trip will
be untripped.
Manual Reset Only – This setting causes the outputs to latch. The outputs can only
be reset by entering the Main Menu and selecting Manual Reset. (A password may be
necessary to reset the relays.)
Pressing Enter – The outputs will untrip when Enter is pressed.
Using Hysteresis – The outputs will untrip when the input value exits the hysteresis
(deadband) limit.
Note: The order of precedence for the methods of untrip is Manual Reset Only,
Pressing Enter, and then Using Hysteresis. This means that if at any time an output is
tripped and configured by an zone to untrip using Manual Reset Only, the only way to
untrip that zone is using the Manual Reset.
Note: When any zone causes a trip for an output, all zones that have caused a trip on
that output will be refreshed. This means that if an output has been tripped and then
cleared by pressing Enter and another zone causes that output to retrip, the output
will act as though both trips have reoccurred at the same time to cause the output to
trip. So, if the second trip were to reset by dropping below the programmed
hysteresis value, the output will still be tripped, due to the first zone, which caused the
trip. To reset the output again, Enter would need to be pressed.
Set Hysteresis: - Hysteresis is the amount that the reading must move past the trip value
before the outputs will reset. For example, the system is configured to trip at 100ºF, has a
10ºF hysteresis and will trip Output 1 on an over temperature reading. The reading increases
to 100ºF, so Output 1 trips. The reading will need to go below 90ºF before Output 1 will reset.
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
22
C.
Setup Worksheet
Prompt
Reverse acting
outputs?
Temperature Scale:
Zone to be
displayed during
normal operation:
Minutes of alarm
silence when a key
is pressed:
If an input fails:
Description
Choose which outputs should be
in an active state, before a trip
condition occurs.
Choose the temperature scale to
which the CX224 should be
configured.
Choose how input readings
should be displayed.
Selection
Output 1__ Output 2__
Output 3__ Output 4__
Degrees _____
High
Low
Set the amount of time that
should pass before the alarm will
resound due to an alarm
condition.
Choose action to take if input fails.
Any
________ Minutes
Sound Alarm
Trip Output(s)
Zone X Trip 1:
Choose input type:
Zone X Trip 1:
Enter Low End of
Transmitter Range:
Chromalox
Choose the type of input that is
attached.
For 4-20mA current loops, enter
the low end of the range of the
input. These settings will not be
used for RTD and Thermocouple
inputs. The range for RTD and
Thermocouples are not
changeable. See Specifications in
the rear of the manual for the
range of RTD and Thermocouples.
Ignore
Zone 1 _____
Zone 6_____
Zone 2 _____
Zone 7_____
Zone 3 _____
Zone 8_____
Zone 4 _____
Zone 9_____
Zone 5 _____
Zone 10_____
Zone 6 _____
Zone 11_____
Zone 7 _____
Zone 1 _____
Zone 12_____
Zone 6_____
Zone 2 _____
Zone 7_____
Zone 3 _____
Zone 8_____
Zone 4 _____
Zone 9_____
Zone 5 _____
Zone 10_____
Zone 6 _____
Zone 11_____
Zone 7 _____
Zone 12_____
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
23
Prompt
Zone X Trip 1:
Enter High End of
Transmitter Range:
Zone X Trip 1:
Zone X Trip 1:
Trip Over or Under?
Zone X Trip 1:
Sound Alarm on
Trip?
Chromalox
Description
For 4-20mA current loops, enter
the high end of the range of the
input.
Set the trip value.
Set the input condition for when
the output(s) should trip.
Set to alarm when an output is
tripped.
Selection
Zone 1 _____
Zone 6_____
Zone 2 _____
Zone 7_____
Zone 3 _____
Zone 8_____
Zone 4 _____
Zone 9_____
Zone 5 _____
Zone 10_____
Zone 6 _____
Zone 11_____
Zone 7 _____
Zone 12_____
Zone 1 _____
Zone 6_____
Zone 2 _____
Zone 7_____
Zone 3 _____
Zone 8_____
Zone 4 _____
Zone 9_____
Zone 5 _____
Zone 10_____
Zone 6 _____
Zone 11_____
Zone 7 _____
Zone 1 _____
Zone 12_____
Zone 6_____
Zone 2 _____
Zone 7_____
Zone 3 _____
Zone 8_____
Zone 4 _____
Zone 9_____
Zone 5 _____
Zone 10_____
Zone 6 _____
Zone 11_____
Zone 7 _____
Zone 1 _____
Zone 12_____
Zone 6_____
Zone 2 _____
Zone 7_____
Zone 3 _____
Zone 8_____
Zone 4 _____
Zone 9_____
Zone 5 _____
Zone 10_____
Zone 6 _____
Zone 11_____
Zone 7 _____
Zone 12_____
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
24
Prompt
Zone X Trip 1:
Outputs to trip:
Output1__
Output2__
Output3__
Output4__
Description
Choose outputs to trip when trip
value is observed.
Selection
Zone 1 Trip 1:
Zone 7 Trip 1:
Output1__ Output2__ Output1__ Output2__
Output3__ Output4__ Output3__ Output4__
Zone 2 Trip 1:
Zone 8 Trip 1:
Output1__ Output2__ Output1__ Output2__
Output3__ Output4__ Output3__ Output4__
Zone 3 Trip 1:
Zone 9 Trip 1:
Output1__ Output2__ Output1__ Output2__
Output3__ Output4__ Output3__ Output4__
Zone 4 Trip 1:
Zone 10 Trip 1:
Output1__ Output2__ Output1__ Output2__
Output3__ Output4__ Output3__ Output4__
Zone 5 Trip 1:
Zone 11 Trip 1:
Output1__ Output2__ Output1__ Output2__
Output3__ Output4__ Output3__ Output4__
Zone X Trip 1:
Untrip Outputs by:
Zone X Trip 1:
Set Hysteresis:
Chromalox
Choose the preferred method to
untrip the outputs.
Set the hysteresis (deadband)
value. Hysteresis is the amount
that the input value must pass
beyond the trip value before the
output will untrip.
Zone 6 Trip 1:
Zone 12 Trip 1:
Output1__ Output2__ Output1__ Output2__
Output3__ Output4__ Output3__ Output4__
Zone 1 _____
Zone 6_____
Zone 2 _____
Zone 7_____
Zone 3 _____
Zone 8_____
Zone 4 _____
Zone 9_____
Zone 5 _____
Zone 10_____
Zone 6 _____
Zone 11_____
Zone 7 _____
Zone 1 _____
Zone 12_____
Zone 6_____
Zone 2 _____
Zone 7_____
Zone 3 _____
Zone 8_____
Zone 4 _____
Zone 9_____
Zone 5 _____
Zone 10_____
Zone 6 _____
Zone 11_____
Zone 7 _____
Zone 12_____
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
25
Prompt
Zone X Trip 2:
Choose input type:
Zone X Trip 2:
Enter Low End of
Transmitter Range:
Description
Choose the type of input that is
attached.
Enter the low end of the range of
the input.
(4-20mA inputs
only, if another
input type is
selected, this option
will not be
displayed.)
Zone X Trip 2:
Enter High End of
Transmitter Range:
Enter the high end of the range of
the input.
(4-20mA inputs
only, if another
input type is
selected, this option
will not be
displayed.)
Zone X Trip 2:
Chromalox
Set the trip value.
Selection
Zone 1 _____
Zone 6_____
Zone 2 _____
Zone 7_____
Zone 3 _____
Zone 8_____
Zone 4 _____
Zone 9_____
Zone 5 _____
Zone 10_____
Zone 6 _____
Zone 11_____
Zone 7 _____
Zone 1 _____
Zone 12_____
Zone 6_____
Zone 2 _____
Zone 7_____
Zone 3 _____
Zone 8_____
Zone 4 _____
Zone 9_____
Zone 5 _____
Zone 10_____
Zone 6 _____
Zone 11_____
Zone 7 _____
Zone 1 _____
Zone 12_____
Zone 6_____
Zone 2 _____
Zone 7_____
Zone 3 _____
Zone 8_____
Zone 4 _____
Zone 9_____
Zone 5 _____
Zone 10_____
Zone 6 _____
Zone 11_____
Zone 7 _____
Zone 1 _____
Zone 12_____
Zone 6_____
Zone 2 _____
Zone 7_____
Zone 3 _____
Zone 8_____
Zone 4 _____
Zone 9_____
Zone 5 _____
Zone 10_____
Zone 6 _____
Zone 11_____
Zone 7 _____
Zone 12_____
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
26
Prompt
Zone X Trip 2:
Trip Over or Under?
Zone X Trip 2:
Sound Alarm on
Trip?
Zone X Trip 2:
Outputs to trip:
Output1__
Output2__
Output3__
Output4__
Description
Set the condition when the
outputs should trip.
Set to alarm when an output is
tripped.
Choose outputs to trip when trip
value is observed.
Selection
Zone 1 _____
Zone 6_____
Zone 2 _____
Zone 7_____
Zone 3 _____
Zone 8_____
Zone 4 _____
Zone 9_____
Zone 5 _____
Zone 10_____
Zone 6 _____
Zone 11_____
Zone 7 _____
Zone 1 _____
Zone 12_____
Zone 6_____
Zone 2 _____
Zone 7_____
Zone 3 _____
Zone 8_____
Zone 4 _____
Zone 9_____
Zone 5 _____
Zone 10_____
Zone 6 _____
Zone 11_____
Zone 7 _____
Zone 12_____
Zone 1 Trip 1:
Zone 7 Trip 1:
Output1__ Output2__ Output1__ Output2__
Output3__ Output4__ Output3__ Output4__
Zone 2 Trip 1:
Zone 8 Trip 1:
Output1__ Output2__ Output1__ Output2__
Output3__ Output4__ Output3__ Output4__
Zone 3 Trip 1:
Zone 9 Trip 1:
Output1__ Output2__ Output1__ Output2__
Output3__ Output4__ Output3__ Output4__
Zone 4 Trip 1:
Zone 10 Trip 1:
Output1__ Output2__ Output1__ Output2__
Output3__ Output4__ Output3__ Output4__
Zone 5 Trip 1:
Zone 11 Trip 1:
Output1__ Output2__ Output1__ Output2__
Output3__ Output4__ Output3__ Output4__
Zone 6 Trip 1:
Zone 12 Trip 1:
Output1__ Output2__ Output1__ Output2__
Output3__ Output4__ Output3__ Output4__
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
27
Prompt
Zone X Trip 2:
Untrip Outputs by:
Zone X Trip 2:
Set Hysteresis:
Chromalox
Description
Choose the preferred method to
untrip the outputs.
Set the hysteresis (deadband)
value. Hysteresis is the amount
that the input value must pass
beyond the trip value before the
output will untrip.
Selection
Zone 1 _____
Zone 6_____
Zone 2 _____
Zone 7_____
Zone 3 _____
Zone 8_____
Zone 4 _____
Zone 9_____
Zone 5 _____
Zone 10_____
Zone 6 _____
Zone 11_____
Zone 7 _____
Zone 1 _____
Zone 12_____
Zone 6_____
Zone 2 _____
Zone 7_____
Zone 3 _____
Zone 8_____
Zone 4 _____
Zone 9_____
Zone 5 _____
Zone 10_____
Zone 6 _____
Zone 11_____
Zone 7 _____
Zone 12_____
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
28
5.
Communications
The CX224 uses Modbus protocol to communicate over an RS485 bus. RTU transmission
mode is supported by the CX224. ASCII transmission mode is not supported. Data transfer
must adhere to the following data format: 1 start bit, 8 data bits and 1 stop bit. Supported
data rates are: 600, 1200, 2400, 4800, 9600, and 19200 baud. Supported function codes are
03, 04, 06 and 10. These instructions allow the program settings to be read and modified and
access to the input readings on the monitor. The communications are limited to 41
characters per transmission, including header information and checksum. A character is
defined as hexadecimal 0 … 9, A … F. Modbus addresses are allowed in the range from 1 to
247. If the CX224 is set to a Modbus address of 0, the unit will ignore all signals on the
communication inputs.
The CX224 supports half-duplex operation. This means that only two signal wires are
required to send and receive signals. Using half-duplex operation helps to minimize wiring
and still provides the long distance communications allowed while using RS485. Wire lengths
up to 4000 ft. are allowed with RS485 as compared to only 50 ft. using RS232.
Using a PC for RS485 Communications
Minco offers an accessory package (AC102734) that contains an isolated RS232 to RS485
converter, power supply to power the converter, and a DB25 to DB9 adapter. These parts
have been thoroughly tested and have been found to work properly with the CX224 and
Chromalox CX224 software. Chromalox CX224 software is configured to use a converter that
requires DTR to be active all of the time and RTS to be active when transmitting and inactive
when receiving. Other converters that have the same requirements will work with the
Chromalox CX224 software. More information about CX224 Communications can be found in
the Chromalox CX224 Software Manual. Chromalox does not guarantee that any other RS232
to RS485 converter will work with the CX224.
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
29
A)
Function Codes
Function Code 03 – Read program settings
The 03 function code is used to read the program settings in the CX224. Program settings are
shown in the memory map later in this section. The maximum number of data bytes that can
be sent from the CX224 is 32. This is due to the 41 byte limit set for communications.
Therefore, the maximum value that can be used as the number of memory locations to read is
0x16.
To request data from 3 memory locations starting at location 0x20, the proper data string to
use, assuming the monitor address is 1, would be:
0103002000030104
01
03
00
20
00
03
0104
Monitor Address
Function Code
High byte of starting memory location
Low byte of starting memory location
High byte of the number of memory locations to read
Low byte of the number of memory locations to read
The checksum for the string that is being sent
The response from the CX224 would look like the following:
01030600010002000374FD
01
03
06
000100020003
74FD
Chromalox
Monitor Address
Function Code
Number of data bytes returned
Data bytes returned starting at memory location 0x20
The checksum for the string that was sent
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
30
Function Code 04 – Read current inputs
The 04 function code is used to retrieve the current input readings.
To request data from 3 memory locations starting at location 0x20, the proper data string to
use, assuming the monitor address is 1, would be:
010400100003CEB1
01
04
00
10
00
03
CEB1
Monitor Address
Function Code
High byte of starting memory location
Low byte of starting memory location
High byte of the number of memory locations to read
Low byte of the number of memory locations to read
The checksum for the string that was sent
The response from the CX224 would look something like the following: (Returned data bytes
will obviously vary, depending on the values at those locations.)
01040600010002000392BC
01
04
06
000100020003
92BC
Chromalox
Monitor Address
Function Code
Number of data bytes returned
Data returned, 3 – 16 bit words
The checksum for the string that was sent
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
31
Function Code 16 – Write program settings
The 16 function code is used to write program settings to the CX224. When sending the Write
Program Settings command, the hexadecimal number 10 will be used. Program settings are
shown in the memory map later in this section. The maximum number of data bytes that can
be sent to the CX224 is 32. This is due to the 41 byte limit set for communications. Therefore,
the maximum value that can be used as the number of memory locations to write is 0x16.
To store settings to 3 memory locations starting at location 0x20, the proper data string to
use, assuming the monitor address is 1, would be:
011000200003AABBCCDDEEFF5B39
01
10
00
20
00
03
AABB
CCDD
EEFF
5B39
Monitor Address
Function Code
High byte of starting memory location
Low byte of starting memory location
High byte of the number of memory locations to write
Low byte of the number of memory locations to write
First word of data to send
Second word of data to send
Third word of data to send
The checksum for the string that was sent
The response from the CX224 would look something like the following:
011006C2AD
01
10
06
C2AD
Chromalox
Monitor Address
Function Code
Number of data bytes received
The checksum for the string that was sent
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
32
B)
Memory Map
Explanation of the Value Format can be found after the chart Current Values for Inputs and
Outputs.
Program Settings are stored according to the chart below:
Register Address
Value Format
0000
Reverse Acting Relays / Temperature Scale
A
0001
Zone to be displayed
B
0002
Length of Silence
C
0003
Action to take on failed input
D
0004
Zone 1 Trip 1 – Input Type
E
0005
- Low end of input range
F
0006
- High end of input range
G
0007
- Trip Value
H
0008
- Trip Over or Under
I
0009
- Sound Alarm / Outputs to trip
J
000A
- Output Reset / Hysteresis Value
K
000B
Zone 1 Trip 2 – Trip Value
H
000C
- Trip Over or Under
I
000D
- Sound Alarm / Outputs to trip
J
000E
- Output Reset / Hysteresis Value
K
000F
Zone 2 Trip 1 – Input Type
E
0010
- Low end of input range
F
0011
- High end of input range
G
0012
- Trip Value
H
0013
- Trip Over or Under
I
0014
- Sound Alarm / Outputs to trip
J
0015
- Output Reset / Hysteresis Value
K
0016
Zone 2 Trip 2 – Trip Value
H
0017
- Trip Over or Under
I
0018
- Sound Alarm / Outputs to trip
J
0019
- Output Reset / Hysteresis Value
K
001A
Chromalox
Description
Zone 3 Trip 1 – Input Type
E
001B
- Low end of input range
F
001C
- High end of input range
G
001D
- Trip Value
H
001E
- Trip Over or Under
I
001F
- Sound Alarm / Outputs to trip
J
0020
- Output Reset / Hysteresis Value
K
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
33
0021
H
0022
- Trip Over or Under
I
0023
- Sound Alarm / Outputs to trip
J
0024
- Output Reset / Hysteresis Value
K
0025
Zone 4 Trip 1 – Input Type
E
0026
- Low end of input range
F
0027
- High end of input range
G
0028
- Trip Value
H
0029
- Trip Over or Under
I
002A
- Sound Alarm / Outputs to trip
J
002B
- Output Reset / Hysteresis Value
K
002C
Zone 4 Trip 2 – Trip Value
H
002D
- Trip Over or Under
I
002E
- Sound Alarm / Outputs to trip
J
002F
- Output Reset / Hysteresis Value
K
0030
Zone 5 Trip 1 – Input Type
E
0031
- Low end of input range
F
0032
- High end of input range
G
0033
- Trip Value
H
0034
- Trip Over or Under
I
0035
- Sound Alarm / Outputs to trip
J
0036
- Output Reset / Hysteresis Value
K
0037
Zone 5 Trip 2 – Trip Value
H
0038
- Trip Over or Under
I
0039
- Sound Alarm / Outputs to trip
J
003A
- Output Reset / Hysteresis Value
K
003B
Zone 6 Trip 1 – Input Type
E
003C
- Low end of input range
F
003D
- High end of input range
G
003E
- Trip Value
H
003F
- Trip Over or Under
I
0040
- Sound Alarm / Outputs to trip
J
0041
- Output Reset / Hysteresis Value
K
0042
Zone 6 Trip 2 – Trip Value
H
0043
- Trip Over or Under
I
0044
- Sound Alarm / Outputs to trip
J
0045
- Output Reset / Hysteresis Value
K
0046
Chromalox
Zone 3 Trip 2 – Trip Value
Zone 7 Trip 1 – Input Type
E
0047
- Low end of input range
F
0048
- High end of input range
G
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
34
0049
- Trip Value
H
004A
- Trip Over or Under
I
004B
- Sound Alarm / Outputs to trip
J
004C
- Output Reset / Hysteresis Value
K
004D
H
004E
- Trip Over or Under
I
004F
- Sound Alarm / Outputs to trip
J
0050
- Output Reset / Hysteresis Value
K
0051
Zone 8 Trip 1 – Input Type
E
0052
- Low end of input range
F
0053
- High end of input range
G
0054
- Trip Value
H
0055
- Trip Over or Under
I
0056
- Sound Alarm / Outputs to trip
J
0057
- Output Reset / Hysteresis Value
K
0058
Zone 8 Trip 2 – Trip Value
H
0059
- Trip Over or Under
I
005A
- Sound Alarm / Outputs to trip
J
005B
- Output Reset / Hysteresis Value
K
005C
Zone 9 Trip 1 – Input Type
E
005D
- Low end of input range
F
005E
- High end of input range
G
005F
- Trip Value
H
0060
- Trip Over or Under
I
0061
- Sound Alarm / Outputs to trip
J
0062
- Output Reset / Hysteresis Value
K
0063
Zone 9 Trip 2 – Trip Value
H
0064
- Trip Over or Under
I
0065
- Sound Alarm / Outputs to trip
J
0066
- Output Reset / Hysteresis Value
K
0067
Zone 10 Trip 1 – Input Type
E
0068
- Low end of input range
F
0069
- High end of input range
G
006A
- Trip Value
H
006B
- Trip Over or Under
I
006C
- Sound Alarm / Outputs to trip
J
006D
- Output Reset / Hysteresis Value
K
006E
Chromalox
Zone 7 Trip 2 – Trip Value
Zone 10 Trip 2 – Trip Value
H
006F
- Trip Over or Under
I
0070
- Sound Alarm / Outputs to trip
J
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
35
0071
0072
Zone 11 Trip 1 – Input Type
K
E
0073
- Low end of input range
F
0074
- High end of input range
G
0075
- Trip Value
H
0076
- Trip Over or Under
I
0077
- Sound Alarm / Outputs to trip
J
0078
- Output Reset / Hysteresis Value
K
0079
Zone 11 Trip 2 – Trip Value
H
007A
- Trip Over or Under
I
007B
- Sound Alarm / Outputs to trip
J
007C
- Output Reset / Hysteresis Value
K
007D
Zone 12 Trip 1 – Input Type
E
007E
- Low end of input range
F
007F
- High end of input range
G
0080
- Trip Value
H
0081
- Trip Over or Under
I
0082
- Sound Alarm / Outputs to trip
J
0083
- Output Reset / Hysteresis Value
K
0084
Chromalox
- Output Reset / Hysteresis Value
Zone 12 Trip 2 – Trip Value
H
0085
- Trip Over or Under
I
0086
- Sound Alarm / Outputs to trip
J
0087
- Output Reset / Hysteresis Value
K
0088
Input Offset – Zone 1
L
0089
- Zone 2
L
008A
- Zone 3
L
008B
- Zone 4
L
008C
- Zone 5
L
008D
- Zone 6
L
008E
- Zone 7
L
008F
- Zone 8
L
0090
- Zone 9
L
0091
- Zone 10
L
0092
- Zone 11
L
0093
- Zone 12
L
0094
Reserved
0095
Reserved
0096
Reserved
0097
Reserved
0098
Zone 1 Name - Characters 1, 2
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
M
36
0099
- Characters 3, 4
M
009A
- Characters 5, 6
M
009B
- Characters 7, 8
M
009C
- Characters 9, 10
M
009D
- Characters 11, 12
M
009E
- Characters 13, 14
M
009F
- Characters 15, 16
M
00A0
Zone 2 Name - Characters 1, 2
M
00A1
- Characters 3, 4
M
00A2
- Characters 5, 6
M
00A3
- Characters 7, 8
M
00A4
- Characters 9, 10
M
00A5
- Characters 11, 12
M
00A6
- Characters 13, 14
M
00A7
- Characters 15, 16
M
00A8
Zone 3 Name - Characters 1, 2
M
00A9
- Characters 3, 4
M
00AA
- Characters 5, 6
M
00AB
- Characters 7, 8
M
00AC
- Characters 9, 10
M
00AD
- Characters 11, 12
M
00AE
- Characters 13, 14
M
00AF
- Characters 15, 16
M
00B0
Zone 4 Name - Characters 1, 2
M
00B1
- Characters 3, 4
M
00B2
- Characters 5, 6
M
00B3
- Characters 7, 8
M
00B4
- Characters 9, 10
M
00B5
- Characters 11, 12
M
00B6
- Characters 13, 14
M
00B7
- Characters 15, 16
M
00B8
Zone 5 Name - Characters 1, 2
M
00B9
- Characters 3, 4
M
00BA
- Characters 5, 6
M
00BB
- Characters 7, 8
M
00BC
- Characters 9, 10
M
00BD
- Characters 11, 12
M
00BE
- Characters 13, 14
M
00BF
- Characters 15, 16
M
00C0
Chromalox
Zone 6 Name - Characters 1, 2
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
M
37
00C1
- Characters 3, 4
M
00C2
- Characters 5, 6
M
00C3
- Characters 7, 8
M
00C4
- Characters 9, 10
M
00C5
- Characters 11, 12
M
00C6
- Characters 13, 14
M
00C7
- Characters 15, 16
M
00C8
Zone 7 Name - Characters 1, 2
M
00C9
- Characters 3, 4
M
00CA
- Characters 5, 6
M
00CB
- Characters 7, 8
M
00CC
- Characters 9, 10
M
00CD
- Characters 11, 12
M
00CE
- Characters 13, 14
M
00CF
- Characters 15, 16
M
00D0
Zone 8 Name - Characters 1, 2
M
00D1
- Characters 3, 4
M
00D2
- Characters 5, 6
M
00D3
- Characters 7, 8
M
00D4
- Characters 9, 10
M
00D5
- Characters 11, 12
M
00D6
- Characters 13, 14
M
00D7
- Characters 15, 16
M
00D8
Zone 9 Name - Characters 1, 2
M
00D9
- Characters 3, 4
M
00DA
- Characters 5, 6
M
00DB
- Characters 7, 8
M
00DC
- Characters 9, 10
M
00DD
- Characters 11, 12
M
00DE
- Characters 13, 14
M
00DF
- Characters 15, 16
M
00E0
M
00E1
- Characters 3, 4
M
00E2
- Characters 5, 6
M
00E3
- Characters 7, 8
M
00E4
- Characters 9, 10
M
00E5
- Characters 11, 12
M
00E6
- Characters 13, 14
M
00E7
- Characters 15, 16
M
00E8
Chromalox
Zone 10 Name - Characters 1, 2
Zone 11 Name - Characters 1, 2
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
M
38
00E9
- Characters 3, 4
M
00EA
- Characters 5, 6
M
00EB
- Characters 7, 8
M
00EC
- Characters 9, 10
M
00ED
- Characters 11, 12
M
00EE
- Characters 13, 14
M
00EF
- Characters 15, 16
M
00F0
Chromalox
Zone 12 Name - Characters 1, 2
M
00F1
- Characters 3, 4
M
00F2
- Characters 5, 6
M
00F3
- Characters 7, 8
M
00F4
- Characters 9, 10
M
00F5
- Characters 11, 12
M
00F6
- Characters 13, 14
M
00F7
- Characters 15, 16
M
00F8
Modbus Address
N
00F9
Baud Rate Indicator
O
00FA
Reserved
00FB
Reserved
00FC
Simulation Mode / Wait Mode / Reset
P
00FD
Password for entering programming menu
Q
00FE
Password for allowing manual reset
R
00FF
Reserved
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
39
Current Values for Inputs and Outputs:
Register Address
0000
0001
0002
0003
0004
0005
0006
0007
0008
0009
000A
000B
000C
000D
000E
000F
0010
0011
0012
0013
0014
0015
0016
0017
0018
0019
001A
Chromalox
Description
Input Reading for Zone 1 – Upper 16 bits
– Lower 16 bits
Input Reading for Zone 2 – Upper 16 bits
– Lower 16 bits
Input Reading for Zone 3 – Upper 16 bits
– Lower 16 bits
Input Reading for Zone 4 – Upper 16 bits
– Lower 16 bits
Input Reading for Zone 5 – Upper 16 bits
– Lower 16 bits
Input Reading for Zone 6 – Upper 16 bits
– Lower 16 bits
Input Reading for Zone 7 – Upper 16 bits
– Lower 16 bits
Input Reading for Zone 8 – Upper 16 bits
– Lower 16 bits
Input Reading for Zone 9 – Upper 16 bits
– Lower 16 bits
Input Reading for Zone 10 – Upper 16 bits
– Lower 16 bits
Input Reading for Zone 11 – Upper 16 bits
– Lower 16 bits
Input Reading for Zone 12 – Upper 16 bits
– Lower 16 bits
Input Reading for CJC – Upper 16 bits
– Lower 16 bits
Output Status
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
Value Format
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
T
40
Value Format Chart:
Value
Format
A
Explanation
This 16 bit word is used for two parameters. The upper 8 bits set which
outputs are used as reverse acting or direct acting. The lower 8 bits set the
temperature scale.
Reverse or Direct acting outputs:
A 0 indicates Normal output operation and a 1 indicates Reverse acting. The
format is as follows: 0000 4321, where bit location 4 represents output 4, bit
location 3 represents output 3, etc.
Temperature Scale:
0 indicates using degrees C and a 1 indicates using degrees F
The format is as follows: 0000 000X, where X will be a 0 or 1 indicating the
scale
Example:
Set Output 1 and 2 as reverse acting and the temperature scale to F:
The 16 bits to send would be: 0000 0011 0000 0001 = 0x0301
B
This 16 bit word sets the zone to be displayed.
0000 0000 0000 00XX, where XX is 00 for High zone, 01 for Low zone, or 10 for
‘Any’. The ‘Any’ option will stay on the zone that was last viewed by the user.
Example:
Set option ‘Any’:
The 16 bits to send would be: 0000 0000 0000 0010 = 0x0002
C
This 16 bit word sets the length of silence before the alarm will resound if a
trip condition still exists after the alarm has been silenced. To set the alarm so
that it will not resound, a value greater than 100 should be.
Example:
Set the silence time to 5 minutes:
The 16 bits to send would be: 0000 0000 0000 0101 = 0x0005
To disable the alarm from resounding, set the value to 101:
The 16 bits to send would be: 0000 0000 01101 0101 = 0x0065 (101 decimal)
D
This 16 bit word sets the zone to be displayed.
0000 0000 0000 00XX, where XX is 00 for Sound Alarm, 01 for Trip Outputs, or
10 for Ignore.
Example:
Set option Trip Outputs:
The 16 bits to send would be: 0000 0000 0000 0001 = 0x0001
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
41
E
This 16 bit word sets the input type.
0000 0000 000X XXXX, where X XXXX is assigned in the chart below.
Hex value
0x00
0x01
0x02
0x03
0x04
0x05
0x06
0x07
0x08
0x09
0x0A
0x0B
0x0C
0x0D
0x0E
0x0F
0x10
0x11
0x12
Input Type
Input Off
PA
PB
PD or PE
PF
NA
CA
E Thermocouple
J Thermocouple
K Thermocouple
T Thermocouple
4-20mA Pressure, PSI
4-20mA Pressure, Bar
4-20mA % Humidity
4-20mA Process Variable, mA
4-20mA Process Variable, Vdc
4-20mA Vibration, G
4-20mA Temperature, C
4-20mA Temperature, F
Example:
Set the input to a PF (1000 ohm platinum) RTD.
The 16 bits to send would be: 0000 0000 0000 0100 = 0x0004
F
This 16 bit word sets the low end of the input range. The valid input range is
between -999 and 9999. If using a temperature input, the low end of the
range is shown in the following chart, choose the low end for °F, if the
temperature scale is set to °F or choose the low end for °C, if the temperature
scale is set to °C. The low and high end of the range must be entered for the
given sensor input or errant operation may result. The low end of the range
must also be lower than the high end of the range.
Input Type
PA
PB
PD or PE
PF
NA
CA
E Thermocouple
J Thermocouple
K Thermocouple
T Thermocouple
4-20mA (All)
Chromalox
Low End , °F
-328
-328
-328
-328
-112
-148
-470
-346
-454
-454
-999 to 9999
Low End, °C
-200
-200
-200
-200
-80
-100
-279
-210
-270
-270
-999 to 9999
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
42
Example:
Set the low end of the range for a PF sensor when the temperature scale is set
to F.
The 16 bits to send would be: 1111 1110 1011 1000 = 0xFEB8 (-328 decimal)
G
This 16 bit word sets the high end of the input range. The valid input range is
between -999 and 9999. If using a temperature input, the low end of the
range is shown in the following chart, choose the low end for °F, if the
temperature scale is set to °F or choose the low end for °C, if the temperature
scale is set to °C. The low and high end of the range must be entered for the
given sensor input or errant operation may result. The high end of the range
must also be higher than the low end of the range.
Input Type
PA
PB
PD or PE
PF
NA
CA
E Thermocouple
J Thermocouple
K Thermocouple
T Thermocouple
4-20mA (All)
High End , °F
1292
1292
1562
1166
500
500
1832
2192
2500
752
-999 to 9999
High End, °C
700
700
850
630
260
260
1000
1200
1370
400
-999 to 9999
Example:
Set the high end of the range for a PF sensor when the temperature scale is
set to F.
The 16 bits to send would be: 0000 0100 1000 1110 = 0x048E (1166 decimal)
H
This 16 bit word sets the Trip Value. The value must be set between the low
and high end of the range for proper operation. If the value is set higher that
the high end of the range, the input will be turned Off. If the second trip point
is used for an input, the first trip point must also be used. The second trip
point cannot be set and used without setting the first trip point, it will be
ignored.
Example:
Set the Trip Value to 100.
The 16 bits to send would be: 0000 0000 0110 0100 = 0x0064 (100 decimal)
Set the input to Off for an input using a PF sensor with temperature scale set
to F.
The 16 bits to send would be: 0000 0100 1000 1111 = 0x048F (1167 decimal)
I
This 16 bit word sets whether to trip on an input reading that is Over or Under
the trip point.
0000 0000 0000 000X, where X is 0 for Over or 1 for Under.
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
43
Example:
Set the outputs to trip on an Over reading:
The 16 bits to send would be: 0000 0000 0000 0000 = 0x0000
J
This 16 bit word is used for two parameters. The upper 8 bits set whether to
trip the alarm output and sound the alarm. The lower 8 bits set the outputs to
trip.
Trip alarm output and sound alarm:
A 0 indicates that the alarm output and alarm buzzer will not be activated
when a trip condition occurs on the specified input. A 1 indicates that the
alarm output and alarm buzzer will be activated when a trip condition occurs
on the specified input.
The format is as follows: 0000 000X, where X will be a 0 or 1
Outputs to Trip:
A 0 indicates not to trip and a 1 indicates to trip when a trip condition occurs.
The format is as follows: 0000 4321, where bit location 4 represents output 4,
bit location 3 represents output 3, etc.
Example:
Set the alarm to trip when a trip condition occurs and trip output 2 and 3:
The 16 bits to send would be: 0000 0001 0000 0110 = 0x0106
K
This 16 bit word is used for two parameters. The upper 8 bits set the type of
action that will be taken to untrip the output(s) when a trip has occurred. The
lower 8 bits set the hysteresis value that will be used, if applicable.
Action to take to untrip the output(s):
0 indicates that a Manual Reset will be used to untrip the output(s). 1
indicates that Hysteresis will be used to untrip the output(s). 2 indicates that
the output(s) can be untripped by pressing Enter.
The format is as follows: 0000 00XX, where XX will be a 00, 01, or 10
Hysteresis:
Hysteresis can be any value between 0 and 20. The units for the hysteresis are
determined by the units used for the input type.
Example:
Set the output(s) to untrip using Manual Reset:
The 16 bits to send would be: 0000 0000 0000 0000 = 0x0000
L
Chromalox
Se the output(s) top untrip using the hysteresis value. Set the hysteresis value
to 10.
The 16 bits to send would be: 0000 0001 0000 1010 = 0x010A
This 16 bit word is used to set the offset to add to the input reading to
compensate for some error in the sensor input. The offset is .1 x value. This
means that if the decimal number 10 is stored for the offset, the actual offset
is 1 unit (units are the same as the unit for the input type for the given input).
The valid range for offsets is -999 to 9999.
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
44
Example:
Set the offset to 1.2 units.
The 16 bits to send would be: 0000 0000 0000 1100 = 0x000C (12 decimal)
M
This 16 bit word holds 2 ASCII character codes. The characters are used in the
name for the input.
The ASCII character code chart for characters understood by the CX224 is
shown below.
Hex
Code
0x20
0x30
0x31
0x32
0x33
0x34
0x35
0x36
0x37
0x38
0x39
0x41
0x42
0x43
0x44
0x45
0x46
0x47
0x48
0x49
0x4A
0x4B
0x4C
0x4D
0x4E
0x4F
0x50
0x51
0x52
0x53
0x54
0x55
0x56
0x57
0x58
0x59
0x5A
Chromalox
ASCII
Character
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
45
Example:
Set two characters to be ‘R5’ in the name for a zone.
The 16 bits to send would be: 0101 0010 0011 0101 = 0x5235
N
This 16 bit word sets the Modbus Address for the controller. The valid range
for addresses is 1 to 247.
Example:
Set the address to 20:
The 16 bits to send would be: 0000 0000 0001 0100 = 0x0014 (20 decimal)
O
This 16 bit word sets the Baud Rate for the CX224 according to the chart
below.
Hex Code
0
1
2
3
4
5
Baud Rate
600
1200
2400
4800
9600
19200
Example:
Set the Baud Rate to 4800:
The 16 bits to send would be: 0000 0000 0000 0011 = 0x0003
P
This 16 bit word sets the mode of operation for the CX224.
0x0000 - Normal Operation. The CX224 will have 0x0000 in this location when
it is operating in a normal fashion.
0x0001 – Reset. If 0x0001 is placed in this register, the CX224 will reset itself.
0x0505 – Wait Mode. If 0x0505 is placed into this register, the CX224 will not
read any inputs and will not trip any outputs. It is recommended that Wait
Mode be entered before updating any program settings. This will prevent
erratic trips caused by only partially configured inputs. If Wait Mode is not
existed within 2 minutes, the CX224 will automatically exit Wait Mode and
return to Normal Operation. Wait Mode is normally exited by writing 0x0001
(Reset) to the register. This will cause the CX224 to reset and begin using the
new settings.
Example:
Unit is reading inputs and updating the outputs (operating in Normal Mode).
Update the program settings and return to normal operation.
The first step should be to enter Wait Mode. Do this by sending 0x0505 to the
register. Then, update the settings that are to be updated. After updates
have been made, send 0x0001 to the register. The CX224 will reset and clear
any trips that may have been in place due to the old settings. The CX224 will
monitor inputs after reset and use the new settings.
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
46
Q
This 16 bit word is used to store the password needed to enter the
Configuration Menu. Valid range for inputs is from 0 to 9999. 0 is used to
disable the password.
Example:
Set the password for entering the Configuration Menu to 3456.
The 16 bits to send would be: 0000 1101 1000 0000 = 0x0D80 (3456 decimal)
R
This 16 bit word is used to store the password needed to Manual Reset the
CX224. Valid range for inputs is from 0 to 9999. 0 is used to disable the
password.
Example:
Set the password for entering the Configuration Menu to 1234.
The 16 bits to send would be: 0000 0100 1101 0010 = 0x04D2 (1234 decimal)
S
This 16 bit word contains part of an input reading. The Input Reading is
comprised of 2, 16 bit words. When the upper and lower words are combined
into one 32 bit word, the result will yield the true reading for the input x .1 .
This means that if the input reads 1234, the true input reading is 123.4 .
If the upper 16 bit word is 0x7FFF, this indicates that the input is Off.
If the upper 16 bit word is 0x0001, this indicates that the input has Failed.
The valid range for inputs is determined by the low and high input ranges.
Example:
If the full 32 bit reading is 0x00000800, the true input is 204.8
If the full 32 bit reading is 0xFFFFFFF0, the true input is -1.6
If the full 32 bit reading is 0x7FFFFFFF, the input is Off
If the full 32 bit reading is 0x000186A0 (100,000 decimal), the input has Failed.
T
This 16 bit word contains the current status of the outputs. The upper 8 bits
hold the status of the outputs. The lower 8 bits are undetermined.
The upper 8 bits have the format 00054321. Where bit number 5 indicates the
status of the alarm, 0 not tripped or 1 tripped. Bit number 4 indicates the
status of output 4, 0 not tripped or 1 tripped. Bit number 3 indicates the
status for bit 3, etc.
Example:
The 16 bit value read in was 0000 0101 1000 1000
The lower 8 bits can be discarded. Use the upper 8 bits 0000 0101. 1’s
indicate that outputs 1 and 3 are tripped and 0’s indicate that outputs 2, 4 and
the alarm output are not tripped.
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
47
Important Message Regarding Communications:
The memory in the CX224 should
not be used in a way that parameters are being changed often. All settings are stored in
EEPROM. Repeated programming of EEPROM will cause the memory to fail. Under normal
use, reprogramming of memory will not be a problem. However, if an automated routine is
used to constantly change the settings, the limit of programming cycles can be quickly
overcome.
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
48
Specifications:
Input:
Input Scan Rate:
Outputs
Display:
Keyboard:
Accuracy:
Power Supply:
Replacement Fuses:
Communication Interface:
Enclosure:
Ambient Temperature Rating:
Connections:
Dimensions:
Mounting:
Weight:
Approvals:
1 to 12 RTDs (2 or 3-wire), Thermocouples, or 4-20 mA current loop.
Standard Input Types:
RTD:
-200 to 700°C: PA (100 Ω/0.00392 Ω/Ω/°C)
-200 to 700°C: PB (100 Ω/0.00391 Ω/Ω/°C)
-200 to 850°C: PD/PE (100 Ω/0.00385 Ω/Ω/°C)
-200 to 600°C: PF (1000 Ω/0.00385 Ω/Ω/°C)
-80 to 260°C: NA (120 Ω/0.00672 Ω/Ω/°C)
-100 to 260°C: CA (10 Ω/0.00427 Ω/Ω/°C)
Thermocouple: (Ungrounded only)
-270 to 1000°C: Type E
-200 to 1200°C: Type J
-270 to 1150°C: Type K
-270 to 400°C: Type T
4-20 mA current loop:
Pressure (PSI, Bar), Humidity (%), Temperature (°F, °C),
Process Variable (mA, Vdc), and Vibration G. Must be linear
with respect to process variable to be measured.
Less than 1.5 seconds.
Relays: Form C, SPDT 10 A @250 VAC/24 VDC resistive load; 10 A
make current; 2500 VA breaking capacity, ¼ HP at 120 VAC
motor load.
Logic: 5V DC output, 20 mA.
20x4 line backlit LCD. 0.1°F or 0.1°C.
4 membrane type keys with audible and tactile feedback.
2°C (3°F) in 0 to 60°C (32 to 158°F) ambient, over entire input range.
Option A: 85 to 240 VAC @ 50/60 Hz. Or 110 to 250 VDC, 5 Watts
max.
Option B: 18 to 36 VDC, 6 Watts max.
5x20mm, 250V, 500 mA.
RS485 or RS232 (Modbus protocol).
Steel case; NEMA 4 front panel.
0 to 60°C (32 to 158°F).
Terminal blocks at rear accept wires to AWG 12.
7.5” x 11.5” x 2”.
Panel mount enclosure. See cutout drawing.
3.8 lbs.
UL 508, CSA C22.2 No. 14-M91
UL File No: E252736
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
49
This page left blank intentionally.
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
50
This page left blank intentionally.
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
51
How to Order
CX224
Model Number: CX224
A Power Supply:
A= 85-240 VAC @ 50/60 HZ / 110-250 VDC
B = 18-36 VDC
1 Output:
1 = Relays
2 = Logic (5V)
A Communication Interface:
A = RS232
B = RS485
CX224A1A ← Sample Part Number
CX224 Master Password is: 9821
1382 Heil Quaker Blvd.
LAVERGNE, TN 37086
Phone: 615-793-3900
Fax: 615-793-3563
www.chromalox.com
Chromalox
Tel: 615-793-3900 • Fax: 615-793-3563 • www.chromalox.com
52