Manual_RF_Touch_en
USER'S MANUAL
WIRELESS TOUCH
CONTROL UNIT
RF Touch user manual
We want to thank you for your purchase of the RF Touch control unit, which is an element of
wireless RF Control system.
RF Touch allows:
you to control many devices trough touch screen
- heating control
- dimming lights
- switching of electrical appliances and equipment
- blinds
- a combination of detectors
- function timers
- Group control of electrical equipment
everything with clear visualization
wireless communication without the need for cabling
2
RF Touch user manual
Contents:
Before you start ....................... 3
Overview of wireless devices ... 4
Characteristics of RF Touch ..... 7
Technical specifications ........... 8
Installation of RF-Touch W ....... 9
RF Touch Installation-B ............ 10
Description of Control icons .... 11
Basic Steps ............................... 12
Settings
- Default setting ......................... 13
- Menu(creating and naming) ... 14
- Programming ........................... 16
- Assign a new receivers ....... 17
- Assigned receiver ............... 18
- Detectors ............................ 21
- Quick Control ..................... 23
- Display ..................................... 24
- Other ........................................ 24
Control
- Temperature regulation .......... 26
- Switching ................................. 30
- Dimming .................................. 33
- Blinds ....................................... 36
- Detectors ................................. 38
- Quick control............................ 39
What to do if ............................ 40
Installation Form ..................... 42
E
N
Before you start
The instruction manual is intended for installation and use of the equipment. Instructions are always included in the product packaging.
Installation and connection can only make personnel with appropriate qualifications, in compliance with all applicable laws, who are
perfectly familiar with this instructions and functions. Trouble free function is also dependent on transportation, storage and handling.
In case of any signs of damage, deformation, malfunction or missing parts, do not install this product and return it to the seller.
Product and its parts must be at the end of its lifetime handled as electronic waste. Before installation, make sure that all wires, connected
parts or terminals are not live. During the installation and maintenance is necessary to follow safety regulations, standards, guidelines
and special provisions for working with electrical equipment.
3
Overview of wireless RF Control devices
RF Control system
All actuators of the RF Control
System can be controlled by
wireless central unit and all
transmitters of the system
simultaneously.
CENTRAL WIRELESS UNIT
CONTROLLER
RF Touch-W
RF Touch-B
RF Pilot
for surface mounting
100 - 230V AC or
adapter (external)
12 V DC
for mounting
in the installation
box
100 - 230V AC
remote controller,
colours: white,
anthracite
BLIND ACTUATORS
TRANSMITTERS
RF KEY
RFWB-20/G
RFWB-40/G
RFJA-12B/230V
4-channel remote
controller - key pendant
2-channel wireless
switch in the design
LOGUS90
4-channel Wireless
switch in the design
LOGUS90
blind actuator
2 x 8A switching
relay protection
230V AC
RFIM-20B
RFIM-40B
RFSG-1M
RFJA-12B/24V DC
universal transmitter module
under the switch or button
wall box installation
universal transmitter module
under the switch or button
wall box installation
Transmitting module
1-module
230 V AC
blind actuator
contactless switching
12-24V DC
ANALOGUE ACTUATOR
4
DETECTORS
RFDAC-71B
Dimmable ballast
Thermo-control
actuator with analog
output 0 (1) - 10 V
1 x switch contact 16 A
7 functions, 230V AC
for dimming of fluorescent
lamps
supplied on request
with the product RFDAC-71B
of heating valves
supplied on request
with the product RFDAC-71B
JA-80P
JA-81M
JA-82M
Overview of wireless RF Control devices
SWITCHING ACTUATORS
RFSA-11B
RFSA-61B
RFSAI-61B
RFSA-62B
single channel
single function
switching actuator
1 x switching
contact 16 A
230V AC
single channel
multifunction
switching actuator
1 x switching
contact 16A
230V AC
single-channel
multi-function
switching actuator
with option of
connecting an
external wired
controller
2 channel
multifunction
switching actuator
2 x 8A switching
contact
6 functions
230V AC
RFSC-11
RFSC-61
RFUS-11
RFUS-61
RFSC-11 singlechannel, singlefunction switched
socket
1 x switching 16A
230V AC
single-channel,
multifunction
switched socket
6 functions
1 x switching 16A
230V AC
single-channel
single-function
switching actuator
1 x switching 16A
230V AC,
protection IP65
single-channel
multi-function
switching actuator
1 x switching 16A
230V AC,
protection IP65
RFSA-61M
RFSA-66M
Angle antenna
Angle Antenna
single channel
Multifunction
switching actuator
1x changeover
contact 16 A
6 functions
230V AC
six-channel
Multifunction
switching actuator
3 x 8 AND NO
3 x changeover
contact 8A
6 functions 230V AC
for plastic
switchboards
supplied as standard
for RFSA-61M,
FSA-66M, RFSG-1M
for metal
switchboard
can be ordered for
RFSA-61M,
RFSA-66M, RFSG-1M
E
N
5
Overview of wireless RF Control devices
TEMPERATURE ACTUATOR
RFSTI-11B
RFSTI-11/G
RFTI-10B
RFTC-10/G
wireless switching actuator
with temperature sensor
in design to installation box,
230V AC
wireless switching actuator
with temperature sensor
with manual
control buttons directly
on the unit, 230V AC
wireless temperature sensor
1 x CR 2477 3V battery
digital temperature
controller
2 x 1.5V AAA batteries
DIMMING ACTUATORS
RFATV-1
RFDA-11B
RFDA-71B
single function
dimming actuator
1 light scene,
function OFF, 230V AC
multifunctional dimming actuator
7 functions,
AC 230V / 250V
RFDSC-11
single-function dimmed
socket
1 lighting scene
function OFF, 230V AC
6
RFDSC-71
multifunction dimmed socket
7 functions,
230 V AC / 250VA
measures the temperature in
the given zone and provides
wireless control of the radiator
(heater) valve
RFDEL-71B
RFDA-73M/RGB
multifunction dimming
actuator
7 functions, 230 V AC /
250VA
Dimmed load: R, L, C,
LED, ESL
used to dim LED strips and
RGB LED strips, possible
other LED loads
Characteristics of RF Touch
Control Unit of the wireless system RF Control - RF Touch provides intelligent control of the RF units.
It can be used for:
Central control of all units from one place
Complete overview (visualization) of the current status of units (appliances / equipment)
Features:
sends command to temperature, switching, dimming and shutter actuators
accepts commands from the transmitters, actuators, temperature sensors and detectors
processing programs for heating and regulation
Design:
RF Touch-B fits in the round installation box with a supply voltage of 100 - 230 V AC
RF Touch-W for surface mounting with power supply from the back side: 100 - 230 V AC or from the side (via jack):
E
N
12 V DC
3.5 inch color touch screen - no mechanical buttons
RF Touch frames in the base plastic (white, black) or luxurious design Logus90 (glass, metal)
Color of the interframes - white, ivory, ice, mother of pearl, aluminum, silver
Colors of the boxes (only for RF touch-W) - white, ivory, dark gray, light gray
Backup time in case of power failure is 48 hours
40 actuators and 30 OASIS detectors can be assigned to each RF Touch unit
RF Touch can be combined with units of RF Control marked as Oasis & Touch Compatible
7
Technical specifications
Technical parameters
RF Touch-B
RF Touch-W
Display
Type:
color TFT LCD
Resolution:
320 x 240 pixels / 262,144 colors
Aspect ratio:
3:4
Visible area:
52.5 x 70 mm
Backlight:
Touch screen:
active (white LED)
resistive 4-wire
3.5”
Control:
Touch sensitive
Power supply
Power consumption:
Power supply connector:
Minimal range
RF Touch – actuator:
Frequency:
8
RF Touch-W
push-in
screwless terminal
push-in or jack
2.1 mm
Max. cross section of wires:
max. 2.5 mm2 / 1.5 mm2 with socket
Operating temperature:
0 ... +50°C
Storage temperature:
- 20 ... +70°C
Protection:
IP 20
Overvoltage category:
III.
Pollution degree:
2
Operating position:
from the back side
100 - 230 V AC
from the side 12 DC *
100 - 230 V AC
arbitrary
Installation:
installatin a box
wall box installation
Dimensions:
94 x 94 x 12 mm
94 x 94 x 24 mm
127 g
175 g
max. 5 W
Weight **:
A1 - A2
Standards:
Control
Range up to:
RF Touch-B
Operating conditions
Display:
Voltage /
specific current:
Technical parameters
Connection
* adapter is included for RF Touch-W
100 m
1m
868 MHz
** weight with plastic frame
EN 60730-1
RF Touch-W
POWER SUPPLY OVER TERMINALS
POWER SUPPLY OVER ADAPTER
A1
100 - 230V AC
A2
E
N
FITTING ON THE SURFACE
adapter included with RFTouch-W
9
RF Touch-B
POWER SUPPLY OVER TERMINALS
A2
AC 230V
A1
10
FITTING TO THE INSTALLATION BOX
Description of Control Icons
Basic
Main menu
Dimming
RF Touch version Information
and number of assigned units
Temperature regulation
settings
Switching
back to the home screen
Dimming
switch ON
dimming
step back
Blinds
switch OFF
light inclination
Detectors
impuls
light declination
Quick kontrol
button
OK
time function
- delayed switch on
- delayed switch off
Blinds
Setup Menu
scroll up
scroll down
OK
Heating
confirm
dot
yes/selected
abc
letters
no/not selected
A/a
small/capital letters
add
_
edit/remove
a/1
name/adressof the actor(s)
OK
delete
C
switch OFF
Switching
Keyboard
.
switch ON
temperature
0-10V
regulation
confirm
E
N
rise blinds
lower blinds
space
switch - the letters / numbers
confirm
erase previous
11
Basic Steps for Successful Programming
1st Step – Placing of the RF Touch and RF units
2nd Step - Fill Installation Form
Keep in mind that the radio signal range of RF installation
depends ON building construction, materials and placing of all
units.
- device name that you want to manage (to create a menu)
- the names of units (for the correct classification of the
group, for example: RFSA-61B)- addresses of units (to
identify the actuator, for example: 577515)
Installation form can be found at the end of this manual.
Transmission of radio-frequency signals through various materials.
Name
Wooden structures
with plasterboard
plates
E.g. RFSA-61B
standard glass
80-90 %
80-95 %
brick wall
reinforced concrete
60-90 %
20-60 %
Adress
E.g. 577515
metal plates
3nd Step - Set menus (create names)
0-10 %

Create a list of names of the controlled device in the
Settings / Menu (create name).






12

4rd Step – Programming
Programming of the RF units with RF Touch is carried out in
the Settings / Programming menu.
SETUP
fi 1
fig.
Initial setup
When the RF Touch is switched on for the first time, you will be automatically redirected to the display calibration screen. Touch screen can be controlled by the light touch (of about0.5-1s) in the desired location. On the
screen (Fig. 1) then appears cross in each corner of the screen, which need to be pressed twice. This will calibrate
the device. The display then shows the RF logo icon and then touch icon signalizing scanning of the actuators.
fi 2
fig.
Content of the main screen
date
time (touch in the upper right corner of the display will switch between analog
- digital clocks (Figure 2 - Figure 3)
display at the bottom of the screen is customable, eg: heating mode, a often used device ...
Touch the clock area to enter the Main menu. If you want to get to the main menu from
sleep mode, you need to touch the screen anywhere.
Main Menu / Settings
Language
Date and time
The settings menu can be openedd by touch
to
in the upper
right corner screen on the symbol
and insertion of
password (it´s setting from production – 1111) (fig. 4-6),
which you can change everywhen.
Selection of required
Language - Figure 6.
Save setting by
pressing OK .
Settings (Fig.7-8):
Date and Time
automatic
transition between
winter / summer
time (for time
Zone GTM +01:00)
Format settings
hours (12h / 24h
mode)
To save Settings
press OK .
fig.
fi 4
fi
fig. 2
fi 5
fig.
fi 6
fig.
fi 3
fig.
E
N
fig.
fi 7
fi 8
fig.
13
SETUP
Menu (create name)
Menu (create name) is used to add, edit or remove the names of the controlled device. In this menu (Figure 1) you need to first
create your own device names for the sections you want to control.
Creating names is important for successful programming of the RF Touch. For each actuator, which is involved in the installation
you have to create unique name.
The content of this menu is not set at the factory.
Menu (create name) / Add
Press the
Add icon (Fig. 2) to show a selection of sections (Fig. 3):
Temperature regulation
Dimming
Blinds
Switching
Control
Speed
Choose the section where you want to add the device name and type your own text (max. 20 characters).
Detectors
Example 1: If you want to control the blinds - Place the name to the section of the blinds (Fig.3-5).
Example 2: If you want to control a group of blinds together, first create all the blinds names in the blinds section and then create new name for group control in Quick
control section.
fi 1
fig.
fi 2
fig.
fig.
fi 3
fig.
fi 4
fi
fig. 5
Note: Actuator RFTI-10B can be connected with two temperature sensors. For each sensor, you can create your own name.
14
SETUP
Menu (create name) / Edit
Menu (create name) / Remove
Edit button is used to change or modify the name in the created menu.
Press the Edit icon
(Fig.1), a menu appears, select the section in which you want to edit created name (Fig. 2). Mark
selected name by touching it (Fig. 3) and then edit with displayed keyboard.
Press OK to confirm (Fig. 4). The modified name is stored.
Remove button can delete unit name.
Press the Remove icon (Fig. 5) following menu appears, select the section from which you want to remove the name (Fig.
6). Pick the device you want to delete by touching it.(Fig. 7) .
to confirm the selection (Fig. 8). Selected name
Press
will be deleted from menu.
fig.
fi 1
E
N
fig. 5
fi 2
fig.
fi 6
fig.
fi
fig. 3
fi 7
fig.
fi 4
fig.
fig.
fi 8
15
SETUP
Programming
Programming is used to assign or remove the actuators / detectors to menu you created.
The Programming Menu can be entered by entering a password (default - 1111).
Actuators are divided into sections for which they are intended. According to the actuator's type you have to select appropriate
section - see table (eg programming actuator RFSTI-11B - find it in the Temperature regulation section).
RF Control actuators divisions
Temperature
regulation
Switching
Dimming
Blinds
Detectors
RFSTI-11B/G
RFSA-11B
RFDA-11B
RFJA-12B/230V
JA-81M
M / 82M
M
RFSA-6x*
RFDA-71B
RFJA-12B/24V DC
JA-80P
0P
RFTI-10B IN
x
xx
RFTI-10B OUT
RFDAC-71B
RFDAC-71B
RFTC-10/G
RFSAI-61B
RFDEL-71B
RFATV-1
RFUS-11
RFDSC-11
RFUS-61
RFDSC-71
RFSC-11
fi 1
fig.
x
internal sensor
external sensor
* RFSA-61B, RFSA-62B,RFSA-61M and RFSA-66M
xx
16
fi 3
fig.
SETUP
Programming / Assign new
It is used to assign a name to the actuator in the menu. In the required section (heating, dimming ...) select Assign new (Fig. 1). A
list of selected sections actuators will be shown. (Fig. 2). Select the name of the actuator which you want to associate with the
RF Touch. Enter the address of actuator you want to assign( Figure 3) as indicated on the actuator. Confirm with OK . From the
menu you created, select the name to which the actuator will be assigned (Fig. 4).
- Only one name can be assigned for each actuator.
- When programming, actuator must be connected with the installation.
Communication test (Fig. 6) is used to detect and display the current status of the RF signal between the RF Touch and programmed actuator.
- Press Start (Fig. 7) to initiate the test, the current status of the signal is displayed in percentage.
- Press Return to Programming to get back to main menu of programming.
fig. 1
fi
fig. 2
fi
fig. 3
fig.
fi 4
E
N
fi 5
fig.
fi 6
fig.
fi 7
fig.
Programming / Temperature regulation / Assign New / RFTI-10B and RFTC-10/G
These two units are temperature sensors, communication test is not executed during programming.
Note: The actuator RFTI-10B is able to be connected with two temperature sensors, each sensor may have its
own name. Address of the actuator is the same for both sensors.
17
SETUP
fi 7
fig.
Programming / Associated Receivers
It serves to control or remove the actuator from the name of the menu you created.
In the selected section (Figure 1 - Temperature regulation, dimming ...) select Assigned receivers
(Fig. 2) a list of names specified in this section will be shown(Fig. 3). Touching on the name you will
assign it to the actuator (Fig. 4).
By pressing arrows you can check the name and address assigned to the actuator (Fig. 4, 5).
By touching the name or address of the actuator, you can Remove the actuator (Image 7), Change
the address (Image 8), or perform a Communications test (Image 9) and Pair with ....switching
actuators, or internal relays (Image 10).
obr.
b 8
fi
fig. 9
fi 1
fig.
fi 2
fig.
fig.
fi 3
fi 4
fig.
fi 5
fig.
fi 6
fig.
obr.
b 10
obr.
b 11
Correction table for offset settings inRFSTI-11 /G device
Due to warming of internal relay contact in the product RFSTI-11 /G, which are caused by current flow to the connected load, it is highly
recommended to use the offset settings according to the following correction table, according to the value of controllable power. Offset
settings are done in RF Touch device, for a given heating circuit, to which the device RFSTI-11/G is assigned.
18
Connected power
0 VA
250 VA
500 VA
1000 VA
1500 VA
2000 VA
Offset in RF Touch settings
-5 °C
-3,5 °C
-2 °C
-1,5 °C
-0,5 °C
0
SETUP
Programming / Temperature regulation / Assigned receivers / RFTI-10B, RFTC-10/G and RFATV-1
Function Assigned receivers in Temperature reg. - RFTI-10B, RFTC-10/G and RFATV-1 are used to pair or remove temperature units from the actuator.
In the Temperature regulation section, press the screen to select Assigned receivers; the list of names assigned in this section will be
displayed Press the name to display the assigned actuator. Select the name to which the RFTI-10B, RFTI-10/G or RFATV-1 is assigned
(Fig. 1-3). Use arrows to check the name and address of the assigned actuator (Fig. 4-5).
Touch the name or address of the actuator to display the menu (Fig. 6):
Remove
Pair with...
Paired with...
Programming / Temperature regulation / Assigned receivers / RFTI-10B, RFTC-10/G and RFATV-1/ Remove
Serves to cancel the link between the temperature unit and the name from the menu Temperature regulation.
fi 1
fig.
fi 2
fig.
fi 3
fig.
E
N
fig.
fi 4
fi 6
fig.
fig.
fi 5
19
SETUP
Programming / Temperature regulation / Assigned receivers / RFTI-10B, RFTC-10/G and RFATV-1/ Pair with...
Serves to combine the RFTI-10B, RFTC-10/G or RFATV-1 temperature unit with the RFSA-61M or RFSA-61B or RFDAC-71B multifunction
actuator, where the temperature unit measures the current temperature and the multifunction actuator switches on the Temperature
regulation based on the measured temperature. The multifunction actuator switches based on the set temperatures in the RF Touch.
Note: the attached actuator RFTI-10B can be used in two ways:
For temperature measurement (without pairing with a switching actuator)
When paired with the multifunction switching actuator it can switch heating equipment on the basis of the measured temperature.
Programming / Temperature regulation / Assigned receivers / RFTI-10B, RFTC-10/G and RFATV-1/ Paired with....
Shows multifunction switching actuator, which is paired with a temperature actuator. By touching the name of the actuator you
can remove a paired actuator.
Note: Battery indication on the display (Fig. 1) informs of low battery in one of the temperature units. Press the battery to display the unit name. Use arrows
o switch between the name and the address of the unit (Fig. 2-3).
fi 1
fig.
20
fi
fig. 2
fi 3
fig.
SETUP
Programming / Detectors
Section detectors (Fig. 1) is intended for assign or remove OASIS detectors to menu.
Select Assign detector (Fig. 2). The list of detectors will be shown. Select the detector you want assign to the RF Touch unit (Fig. 3).
RF Unit Touch will enable search (Fig. 4) searching icon is shown (the shortest distance to assign a detector is 1.5m). RF Touch
will recognize new detector when batteries are inserted into the detector. Confirm the assignment by pressing
(Fig. 5).
Choose a name to which the detector will be assigned (Fig. 6). Each detector may be assigned only to one name.
Pressing arrows
can display the name or address associated with the detector (Fig. 7, 8).
When you touch on the name or address of the detector following options appear (Fig. 9):
Remove…
Pair with ...
Paired with ...
E
N
fig.
fi 1
fi
fig. 2
fi 3
fig.
fi
fig. 5
fi 8
fig.
fig.
fi 6
fi
fig. 4
fi
fig. 7
fi 9
fig.
21
SETUP
fig.
fi 1
Programming / Detectors / Remove
Used for deleting link between the detector and the name given in the detector menu (Fig. 1).
Note: Two state JA-81M and JA-82M can be used in two ways:
information about the status (open / close) - eg window is open(without pairing with a switching actuator)
pairing with the multifunction switching actuator, which responds to the detector status (open / close)
- eg light is switched on when you open the door.
Single state detectors (JA-80P) must always be paired with multi-function actuator.
fi 2
fig.
Programming / Detectors / Pair with ...
Paired detector can be paired with the multifunction switching actuator from switching
menu, (eg, motion detector with entrance light, Fig. 2-3).
One detector can be paired with up to 30 multifunction switching actuators.
If the detector is paired with a switching actuator function of delayed off feature is automatically activated. When detector switch on, actuator switches connected device for preset
time (2s - 60min). Time delay can be set in the main Menu / Control of the paired actuators
(see page 26).
The above method can be used to assign additional detectors. The RF Touch can be
programmed with up to 30 detectors.
Note: The minimum distance between the detector and RF Touch is 1.5 meters.
Programming / Detectors / Paired with ...
This menu will lists switching actuators, which are paired with the detectors. By touching the
name you can remove paired actuator (Fig. 4-5).
22
fig.
fi 3
fi 4
fig.
fig.
fi 5
SETUP
Programming / Quick Control
Quick control is used for creating a group command, where one-touch control multiple actuators.
For each name of group command you can assign a combination of up to 20 different actors.
Note: Quick control can be set only when all actuators are programmed in different sections of switching, dimming and blind control.
In the Quick Menu control(Fig. 1)choose name from list for the group command (Fig.2).
Select Assign new (Fig. 3) it will show group of units (switching, dimming and blind control). Select the section you want to assign for desired command name (Fig. 4). You can create a menu for your device names created in the desired section.
Select the name (Fig. 5) and further define the function (Fig. 6).
The unit will returns to display groups of units (switching, dimming and blind - fig.7), where you can continue with programming.
When you select assigned receiver (Fig. 8) you can go to the menu to remove (Fig. 10) or change the device name
fig.
fi 1
fi
fig. 2
fi
fig. 3
fi 4
fig.
fi 5
fig.
fi
fig. 8
fi 9
fig.
fi 10
fig.
fig.
fi 6
E
N
fi 7
fig.
Note: The Remove function removes
a group command name from the
RF Touch unit memory. The actuators will remain in the memory.
23
SETUP
fi 1
fig.
Setup / Display (fig. 1-2)
Background: select the type of screen background color (black, blue, green, purple).
Screensaver: the desired brightness (25%, 50%, 75%, 100%) will be activated after
preset time since the last touch (15s, 30s, 1min, 3min).
Sleep mode: set the time after which RF Touch screen unit goes to sleep - the screen
goes dark (0min, 10min, 15min, 20min).
Calibrating the display: cross appear in every corner of the screen, which need to be
pressed twice. Calibration will be performed. Display calibration can also be
started by resetting the unit or disconnecting the supply voltage from the unit;
after connecting again, the RF Touch logo will appear on the display - hold the
logo for more than 3s to activate calibration – touch logo longer than 3 seconds
and calibration will be activated. After calibration, the display shows Home screen.
fig.
fi 2
Setup / Others (fig. 3-4)
Change Password: Changes the password for Setup menu. Enter password - Figure 5 (default password 1111)
will start the the screen to select a new password - where you type and confirm new password. Touch OK to save the
new password (Fig. 6).
Reset the device: To reset the password use 1234 (Fig. 7). This password cannot be changed. Password, and confirmation
YES (Fig. 8) to return the RF Touch unit to the factory settings. RF Touch restarts without entering the password confirmation
OK. (Settings remain unchanged)
fig.
fi 3
24
fi
fig. 4
fi 5
fig.
fi 6
fig.
fi
fig. 7
fig.
fi 8
SETUP
fig.
fi 1
Setup / Others (fig. 1)
Keyboard lock: activation serves to prevent accidental or unwanted control of RF Touch (Fig. 2). For
unlocking locked Home screen press the lock icon twice (Figure 3).
View menu: you can set to display only those sections that you want to see in the main menu.
(eg: only Dimming, Switching and Detectors - fig.4-5).
If you select all the default sections , you will only see menu that you created without division into
sections - Figure 6, this view is useful if you programmed max. 7 actuators).
Temperature regulation: (Fig. 7) displayed units (° C / ° F). settings for Hysteresis heating: upper and lower
margins in a range of 0.5 - 5°C (image 8), set Offset (fix inaccuracies in temperature measurements) in the
range from -5 to +5 °C, Selection of function for temperature control: Heating / Cooling
Main screen: possibility to personalize Home screen (Figure 9 -10). Left (1st choice), middle (2nd choice)
and right field (3rd choice) is used to set the most common controled devices directly from the Home
screen.
fig.
fi 2
fi 4
fig.
Note: Offset is set
directly on the RFTC-10/G unit.
E
N
fi 9
fig.
fi 7
fig.
fi
fig. 5
fi 3
fig.
fi
fig. 6
fi 8
fig.
fig.
fi 10
25
CONTROL / TEMPERATURE REGULATION
fi 1
fig.
Control / Temperature regulation
Temperature regulation Menu (Fig.1) is designed for setting controls over heating equipment.
Touch the heating you enter the menu of additional circuits (image 2).
Standard mode
Economic mode
Party mode
Anti-freezing mode
These modes offer a preset temperature, which you can adjust as you need for individual
heated rooms (circuits). By activation of Standard, Economic, Party or Anti-freezing mode, the
Temperature Regulation adjusts the set temperature. By touching one of the icons, you activate
the chosen mode for the selected room (heating circuit).
The Anti-freeze mode is designed to maintain the minimum required temperature in a
range of 5 - 15°C.
Heating program can be used to set the heating regime for the whole week.
Holiday mode is used for temporary interruption of the heating program or other heating mode.
fi 2
fig.
AUTO
Note: Setting Units ° C / ° F and hysteresis for heating is done in the Settings / Other / Heating
Temperature regulation / Changing heating modes to Economy,Normal and Party modes
To edit the mode, first select the settings button
(image 3), then the relevant mode to modify (Fig. 4) - Standard, Economic,
Party or Anti-freezing mode. The current temperature and the set temperature for Switching on the selected mode is displayed at
the
icon. Touch Settings icon (Fig. 5) for adjusting the temperature. Arrows
/
can set the desired temperature (longer
OK
pressed arrow will accelerate changing of numbers) Touch
to save the set temperature (Fig. 6).
fig.
fi 3
26
fi 4
fig.
fi 5
fig.
fi 6
fig.
CONTROL / TEMPERATURE REGULATION
Temperature regulation / Heating program
By touching the Setting, you go into editing mode of a certain heating circuit or program (Fig. 1). Chose
Heating Program for
which you can set the time program and temperature (Fig. 2). Touch-hour time interval (or minutes) to indicate the information
you want to change (Fig. 3). Arrows
/
set time for switching - On and Off . Arrows can adjust desired temperature.
AUTO

Note: longer push of arrows will accelerate changing of figures.
Touch of Sun-Sat activate the heating program for desired day of the week.
- active for the day,
- disabled for the day.
Confirmation of the selected program - OK . If you want to set additional heating program to continue with programming.
Note: For one day you can create up to 5 heating programs. Times of programs may not overlap (Fig. 5). Setting of program until midnight and over midnight - see
page 37.
Daily overview (Fig. 4) – arrows
will choose between selected time program or temperature (Figure 5-6). To remove single
time schedule mark time / temperature bar and (Fig. 6) then press basket symbol - bin icon . If you not choose any heating
program bar you will delete all programmed schedules for given day.
Weekly overview (Figure 7-8) - touch the basket symbol
to erase all programmed heating programs.
fig.
fi 1
fi
fig. 4
E
N
fi 7
fig.
fi 2
fig.
fi 5
fig.
fi 3
fig.
fi 8
fig.
fig.
fi 6
27
CONTROL / TEMPERATURE REGULATION
Temperature regulation / holiday mode
Holiday mode is used for temporary interruption of the heating program.
Touch holiday mode (Fig. 1) to open Switch ON screen where you set the date, month and year when your holiday mode should
start. Confirm with OK (Fig. 2). Switch Off screen appears where you set the day month and year for the end of holiday mode.
Confirm with OK .
If you touch Overview icon(Fig. 3) you can check list of holiday programs.
Note: Up to 5 Holiday modes can be assigned up to 5 time intervals. Times of programs may not overlap. During the holiday Economy mode is active.
Individual deletion of Holiday Mode is selected by touching bar belonging to the program(Fig. 4), then touch the bin icon
program will be erased. If you do not mark any bar you can touch the bin icon
to remove all holiday arrangements.
and
fi 1
fig.
fi 2
fig.
fi 3
fig.
fi
fig. 4
The precedence of the heating modes
Anti-freezing
freeezin
fr
ng mode
Holiday
olliid
oli
da
da
ayy m
mode
o
AUTO
Economic
mode
Heating
t ng p
ting
program
prog
rog
Standard
d d mode
Party
mode
Note: The required temperature can be set manually on the RF Touch unit. The adjustment after activation is valid until the first subsequent change of the Heating programme or the Vacation mode. The required temperature may be set manually on the RFTC-10/G unit. This adjustment is valid until the subsequent
change of the heating programme in RF Touch.
28
CONTROL / TEMPERATURE REGULATION
Temperature regulation / RFATV-1
To edit the mode, first select the setting button
(image 1) and then the applicable mode to be modified (image 2) - Standard,
Energy-saving, Party or Antifreeze mode.
The open window detection function (image 4) monitors a sharp drop in temperature in the event of an open window and closes
the thermo-valve to a preset period. You can choose 3 levels of open window detection sensitivity, or switch the function off.
- Low sensitivity - drop in temperature by over 1.2°C /min.
- Medium sensitivity - drop in temperature by over 0.8°C /min.
- High sensitivity - drop in temperature by over 0.4°C /min.
Window detection (image 5) - a green dot displays the ongoing stoppage of heating during the set time of inactivity if an open
window has been detected.
Status (image 5) - Status 0 means the thermo-valve is functioning correctly, during constant display of different value, contact
the manufacturer.
Inactive period (image 6) - here you set the period during which heating is shut off once an open window has been detected.
fi 1
fig.
fi 2
fig.
fi 3
fig.
fi
fig. 4
fi 5
fig.
E
N
fi 6
fig.
Note: If there are more thermo-valves RFATV-1 in one installation and there are paired to one switching actuator through RF Touch unit, the RF Touch sends the
command “to turn off the heating ” after the desired temperature is recorded by all thermo-valves.
29
CONTROL / SWITCHING
Main menu / Switching
Switching menu is for all the devices you want to switch. Touch Switching (Fig. 1) displays the names of your choice created
in menu. Red / Green LED indicates contact status:
green -ON,
red switched - off.
switch on
switch off.
Touch the desired name (Fig. 2) to show basic functions:
Switching / Function

Press the Next functions button (Fig. 3) will show a selection of switching functions (Fig. 4). Other functions can be used only in
combination with multifunction switch actuators - RFSA-61B, RFSA-62B, RFSA-61M and RFSA-66M.
Impulse –first touch
switch on, second one to switch off.
Button – It is on as long as long you are holding button .
Delayed switch on - touch
will begin to count preset time, after which the actuator switch on.
Delayed switch off -touch
will start to count preset time after which the actuator will switch off.
In the section Time settings all times for Delay on and Delay off can be set.
Time delay can be set in the range from 2 to 60 minutes. Touch-hour time interval (or minutes) to indicate the information you
want then change it (Fig. 5) with Arrows
/
.
Note: longer press of arrows will accelerate shifting of figures. Confirm time setting by pressing OK .
fig.
fi 1
fi 2
fig.
fi 3
fig.
30
fi 4
fig.
fig.
fi 5
CONTROL / SWITCHING
Main menu / Switch on / RFDAC-71B
Upon selecting the Switching on menu to which the RFDAC-71B actuator is assigned, the basic function are displayed:
Switch on
Switch off .
Press shortly the arrows
/
fig.
fi 1
at the Regulation icon
fig.
fi 2
0-10V
to set the desired value (Fig. 3). Touch
OK
to perform the command.
fig.
fi 3
E
N
Note: For efficient regulation of Temperature regulation, it is recommended to pair the RFDAC-71B actor with the RFTC-10/G or RFTI-10B temperature unit.
31
CONTROL / SWITCHING
Switching / Weekly Program
Weekly program provides weekly settings for the automatic mode switching.
Touch Weekly program icon (Fig. 1), setup menu will appear. Touch-hour time interval (or minutes) to mark information you want to
/
will set the time of switch On and switch Off.
change. Arrows
Note: longer press of arrow is accelerate shift of figures.
Touch the Sun-Sat icon will activate the program on a given day of the week (Fig. 2). - active for the day, - disabled for the day.
To confirm of selected programs touch OK . If you want to configure other Switching program continue programming.
Note: For one day you can create up to 5 switching programs. Programs must not overleap. Setting of program until midnight and over midnight - see page 37.
Daily / Weekly Overview shows the daily / weekly overview of switching programs.
To delete a program in the Daily overview (Fig. 3) indicate bar you want to delete (Fig. 4) at then press the bin icon
not select any of programed bars and press bin icon , you will remove all schedules in the day.
Weekly overview (Figure 5-6) touch the bin icon to clear all programs.
to delete it. If you
fi 11a
fig.
fi 3
fig.
fi 5
fig.
fi 2
fig.
fi 1b
fig.
32
fig.
fi 4
fi
fig. 6
CONTROL / DIMMING
Main menu / Dimming
Dimming Menu is for all the lights where you want to control the brightness (load R L, C - 250V). Touch-Dimming
display a selection of names you created in menu (Fig. 2).
Red / Green LED indicates contact status:
green- On
red -Off.
(Fig. 1)to
Dimming/Functions
E
N

Touch the desired name to displays basic functions:
switch on
switch off. A short touch on the arrows
/
beside icon
OK
Dimming
will set the desired brightness (Fig. 3). Touch
to confirm. In the case displayed icon
- level has been set by
other controler (Fig. 4).
Further functions (Fig. 5) can be used only in combination with multifunctional dimming actuators - RFDA-71B and analog
actuator RFDAC-71B.
Smooth start - touch
will start smooth start-up for preset time.
Smooth stop – touch
will start smooth run down for preset time.
In the Setting you can set time for smooth start and smooth stop. Time can be set from 2s to 30 minutes. Touch the time interval hours (or minutes) to indicate the information you want to change (Fig. 6). Arrows
/
will set time. Confirm setting by
OK
pressing
.
Note: longer press of arrows will accelerate shifting of figures.
fi 1
fig.
fi 3
fig.
fi 5
fig.
fi 6
fig.
fi
fig. 2
fi
fig. 4
33
CONTROL / DIMMING
DIMMING/ RFDA-73M, RF RGB LED-550
The control screen RGB comprises of several elements and buttons.
Long pressing (touch) of button ON/OFF controls the central setting of RGB elements and the light brightness - on/off
The buttons
in the screen upper part include the light brightness setting function from 0-100% in step 5% (see the indicator
of adjustable brightness %).
Buttons
in the screen lower half include the colour comfort setting function and accelerated control of RGB light. The
buttons include the arresting function. Upon pressing button
„white light on“, the analogue inputs are automatically set
to the maximum value of individual colour elements which is indicated in the RGB light source output by means of mixing the
elements with resulting white colour. Then we can regulate only the brightness intensity on the output. Upon pressing (touch)
button
„light on with colour as per RGB“ the button
„white light on“ is automatically blocked, and button „light on with
colour as per RGB“ is arrested. Now reset the analogue inputs values of individual RGB colour elements as per the preset cursor
in the colour wheel of RGB scale on screen RF Touch.
obr.
fi 11
fig.
fi
fig. 22
obr.
obr.33
fi
fig.
34
E
N
35
CONTROL / BLINDS
Main Menu / Blinds
Blinds Menu is designed to control all shutters, blinds, awnings, gates and garage doors that have a built-end switch.
Touch the Louvre
(Fig. 1)to display selection of names you created in menu (Fig. 2).
Red / Green LED indicates device status:
green- closed blinds
red – open blinds.
Blinds / Functions

Touch the desired description / name of the device to display features:
Open
Close
First you need to measure time "t" which your device needs to fully open / close.
for more than 3 seconds to put (Fig. 3) device into the end position. Then touch close icon
longer than
Touch open icon
3 seconds to retract indicate the device while in motion, measure time "t" - a period during which the equipment is in motion.
/
set meUnder Settings you touch on a time interval of hours (minutes) mark information you want to change. Arrows
asured by time "t " + 2s Pulling into the field and the same time and in the field of load (Fig. 4). Confirm the time by pressing OK .
Note: longer pressing the arrow is accelerated shift to the figures.
A short touch on
end position.
Up /
Down can control the devices in the desired direction. Touch longer than 3 devices place the desired
fi 1
fig.
fi 2
fig.
fi 3
fig.
fi
fig. 4
t+2s
36
CONTROL / BLINDS
Blinds / Weekly program
Weekly program can adjust automatic weekly mode.
Touch Weekly program icon (Fig. 1), setup menu will appear. Touch-hour time interval (or minutes) to mark information you
/
will set the time of switch On
and switch Off .
want to change. Arrows
Note: longer press of arrow is accelerate shift of figures.
Touch the Sun-Sat icon will activate the program on a given day of the week (Fig. 2).
- active for the day,
- disabled for the
day.
Confirmation of the selected program - OK . If you want to set additional blinds program to continue with programming.
Note: For one day you can create up to 5 blinds programs. Programs must not overleap (Fig. 5). Setting of program until midnight and over midnight - see page 37.
Daily / Weekly Overview shows the daily / weekly overview of switching programs.
To delete a program in the Daily overview (Fig. 3) indicate bar you want to delete
(Fig. 4) at then press the bin icon to delete it.
If you not select any of programed bars and press bin icon , you will remove all schedules in the day.
to clear all programs.
Weekly overview (Figure 5-6) touch the bin icon
fig.
fi 1
fi
fig. 3
fi 2
fig.
Note: Setting the Inversion function: touch
/
in the Weekly
programme to set the initial movement of the roll-up blinds (Fig. 7).
fig.
fi 5
fig.
fi 4
E
N
fi
fig. 6
fig.
fi 7
37
CONTROL / DETECTORS
Main Menu / Detectors
fi 1
fig.
fig.
fi 2
The menu Detectors is used for thee visualisation
v
and switching of devices using detectors.
By touching the option Detectors (Fig. 1) you will display the list of names on the detector
menu that you have created (Fig. 2).
Double State Detectors
Double state detectors (JA-81M - doors; JA-82M - windows) feature state visualisation:
Green – Off state
Red - On state.
JA-81M and JA-82M detectors may be used in two ways:
Information regarding the state (On/Off ) - e.g. open window (without pairing with the
switching actuator)
Pairing with the multifunctional switching actuator (On/ Off ) - e.g. light switched on when
door opened. By touching the name of the detector you will display the name of the
switching devices with which the detector is paired. By pressing the name of the
switching device you will display the selection (Fig. 4):
On state (neutral):
Off state (alarm):
Switch off - switched off without delay.
Delayed run out – switches off after the time period set in the switching settings.
Switch on - switches on without delay.
Delayed onset – switches on after the time period set in the switching settings.
Confirm by pressing OK (Fig. 4).
fi 3
fig.
fig.
fi 4
Note: The time delay is set for the paired actuator.
Single State Detectors
Single state motion detectors JA-80P do not feature state visualization and they are designed for pairing with the multifunctional switching actuator. By touching the name of the detector you will display the name of the switching actuator with which the
detector is paired. Note: The function of Delayed Switch Off is automatically allocated to the detector. The time delay is set for the paired actuator.
38
CONTROL / QUICK CONTROL
Main Menu / Quick control
Quick control menu serves to the group control of devices.
Touch Quick controll
options (Fig. 3):
to display the name selection of your custom menu (Fig. 2). Touch the name to display the following
Activate - displays set scenes.
Deactivate - the OFF function will be executed on all active actuators.
E
N
fi
fig. 1
fi 2
fig.
fi 3
fig.
39
What to do when ...
RF Touch Unit Warnings
Warning is displayed in case of incorrect or incomplete entry.
Warning
40
Procedure
Up to 40 rooms may be defined.
no more than 40 device names may be entered
Saving failed.
repeat entry
Delete failed.
repeat entry
No unit allocated.
allocate the requested actuator
Two time programmes overlap within a single day.
enter new settings
No time programme available within a single day.
no other programme can be entered
No day selected.
enter new settings
Switch on time may not exceed the switch off time.
enter new settings
Unit already allocated to the room. Select another room.
only one actuator can be allocated to one name of device (outside Quick
Control)
This room has already been defined in the group.
enter a new name
The address has already been selected in the unit list. Choose another
address.
enter correct information
The address information must be complete.
enter correct information
xxx displayed instead of temperature.
actuator not programmed,
actuator/sensor defect,
communication failure
Up to 40 units may be defined.
no more than 40 units may be entered
The switch on date must be different from the switch off date.
enter new settings
The switch on date must not exceed the switch off date.
enter new settings
All 5 programmes are engaged.
no other programme can be entered
What to do when ...
RF Touch Unit Warnings
Warning
No unit allocated to the room.
Procedure
allocate actuator
This group has already been allocated.
enter new settings
Display incomplete - control impossible.
calibrate the device
(disconnect the power supply, after reconnecting hold the logo RF Touch,
finish the calibration by touching twice the cross signs that appear in each
corner of the screen)
EPROM memory error!
contact the manufacturer
RTC circuit error!
contact the manufacturer
AT45 circuit error!
contact the manufacturer
Setting of program until midnight and over midnight - at the time of 00:00
there isn´t any action on the actuator.
- setting of time over midnight : set the required "switch ON" time and set
the required "switch OFF" time on 00:00, next day set the switch ON" time
on 00:00 and set the required "switch OFF" time.
E
N
- setting of time until midnight: set the required "switch ON" time and set
the required "switch OFF" time on 23:59
Have you lost the password?
please ask the manufacturer for information about further steps
General Information
With consideration to the transmission of the RF signal ensure that RF components are suitably located in the building where the device is to be installed. The RF Control system must only
be installed in indoor areas. The device has not been designed for outdoor use or use in moist environment, it must not be installed in metal distribution boxes and plastic distribution boxes
with metal doors as this would prevent the transmission of the radio frequency signal. RF Control is not recommended for the control of devices providing for vital life functions or for the
control of risk devices such as pumps, electrical heaters without heat regulators, lifts, pulleys etc. - radio frequency transmission could be hampered with an obstacle, interfered with, the
transmitter battery may become depleted etc. thus disabling the remote control. Not suitable for use in industrial environment.
Do not expose to extreme temperature changes. In case of extreme temperature changes allow approx. 2 hours prior to installation for the RF Touch to adjust to the temperature of the
installation location. This will prevent condensation of moisture in the device and the occurrence of a potential short circuit.
Keep flammable materials away from the device.
The graphic indication of the contact / device status (red/green LED) is only for information and may be influenced by the amount of processed information or the combination of more RF
Touch and RF Pilot control units.
Safety functions in RFSTI-11B and RFSTI-11G actuators: the actuators disconnect the output in case of an accidental communication failure exceeding 25 minutes.
41
Installation Form
Serial no.:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
42
Description /
Name of the controlled device
Actuator name
Actuator address
Installation Form
Serial no.:
Description /
Name of the controlled device
Actuator name
Actuator address
21.
22.
23.
24.
25.
26.
27.
E
N
28.
29.
30.
31.
32.
33.
34.
35.
36.
37.
38.
39.
40
43
ELKO EP, s.r.o.
Palackého 493 | 769 01 Holešov | Všetuly,CZ, tel.: +420 573 514 211 | fax: +420 573 514 227
[email protected] | www.elkoep.com
rev.2
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement