Fire-Lite Alarms MS 5012 fire alarm panel, ADM 12 annunciator module, RZA 5F remote annunciator Installation, Operation and Programming Manual
Below you will find brief information for fire alarm panel MS 5012, annunciator module ADM 12, remote annunciator RZA 5F. The MS-5012 is a combination control panel and digital communicator all on one circuit board. It is a five-zone panel which uses conventional input devices. The panel accepts waterflow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally open contact devices. Outputs include bell circuit, alarm, trouble, supervisory and communicator failure relay drivers. The integral communicator transmits system status (alarms, troubles, AC loss, etc.) to a UL recognized Central Station via the public switched telephone network. The control panel has a built in programmer and may also serve as a slave communicator to a host panel. It also supervises all wiring, AC voltage, telephone line input voltage and battery level. The ADM-12 Annunciator Driver Module supports the RZA-5F Remote Annunciator module. Annunciator wiring is supervised for open conditions by this module.
MS-5012
Control Communicator
Installation, Operation and
Programming Manual
12 Clintonville Road, Northford, CT 06472
ECN 97-227
F
P/N 15465:F
© 1997 Fire•Lite Alarms, Inc.
Installation Precautions
- Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or encountered.
CAUTION - System Reacceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72-
1993 Chapter 7 after any programming operation or change in site-specific software.
Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
Disconnect AC power and batteries prior to removing or inserting circuit boards.
Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
Do not tighten screw terminals more than 9 in-lbs. Over tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system meets NFPA requirements for operation at 0-49 O and at a relative humidity of 85% RH (non-condensing) at 30
O
C/32-120
C/86
O
F.
O F
However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a nominal room temperature of 15-27
O
F.
C/60-80
O
Verify that wire sizes are adequate for all initiating and indicating device loops.
Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals.
These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Fire Alarm System Limitations
While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance!
An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability can provide early warning of a developing fire.
Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire. Furthermore, all types of smoke detectors - both ionization and photoelectric types, have sensing limitations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time.
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist.
Equipment used in the system may not be technically compatible with the control.
It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled.
The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection and testing should be scheduled monthly or as required by National and/or local fire codes. Adequate written records of all inspections should be kept.
FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC
Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the
Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
Technical Publishing Document PRECAULG.P65 12/31/96
1.0
2.0
3.0
4.0
5.0
6.0
Appendix A
NFPA Standards, UL Documents
Product Description
1.1 Product Features
1.2 Circuits
1.3 Front Panel Switches
1.4 Displays
1.5 Digital Communicator
1.6 Optional Boards
1.7 Remote Annunciator
1.8 Specifications
Control Panel Operation
2.1 Switches
2.2 Displays
2.3 Operation
2.4 Digital Communicator
Table 2.4-1: Format Selection Addresses
Table 2.4-2: Compatible UL Listed Receivers
Installation
3.1 Cabinet
Figure 3.1-1: The MS-5012
3.2 Input Circuits
Figure 3.2-1: Cabinet Dimensions
Figure 3.2-1: Initiating Device Circuits
3.3 Output Circuits
Figure 3.3-1: Output Circuits
Figure 3.3-2: Relays
3.4 UL Power-limited Wiring Requirements
Figure 3.4-1: Typical Wiring for UL Power-limiting
3.5 Digital Communicator
Figure 3.5-1: Wiring RJ31X
3.6 Operating Power
Figure 3.6-1: Power Connections
Figure 3.6-2: Optional AC Terminal Block Installation
3.7 Optional Modules
Figure 3.7-1: Installing the Annunciator
Figure 3.7-2: Wiring the RZA-5F/ADM-12
Programming Instructions
4.1 Entering Programming
4.2 Switch Functions
4.3 Programming
Servicing
5.1 Walk Test Mode
5.2 History Mode
5.3 Troubleshooting Mode
Figure 5.3-1: Handset Connection
5.4 Lamp Test
Programming Reference Sheet
Factory Default Settings
Slave Communicator Configuration
Figure 6.0-1: Slave Communicator Connections
Power Calculations
Index
4
33
34
35
35
30
31
31
32
32
27
28
28
29
30
25
25
25
25
26
36
36
37
37
14
14
15
17
20
21
24
9
10
8
8
10
7
7
8
11
57
58
59
62
48
48
48
51
52
52
53
54
15465 Rev F 5/2/97 P/N 15465:F
3
This control panel has been designed to comply with standards set forth by the following regulatory agencies:
✔
Underwriters Laboratories Standard UL 864
✔
NFPA Standard 72-1993 Local, Remote Station Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards, NFPA 72-1993 National Fire Alarm Code:
Installation, Maintenance, and Use of Central Station Fire Alarm Systems
Local Fire Alarm Systems
Use of Proprietary Fire Alarm Systems
Automatic Fire Detectors
Installation, Maintenance, and Use of Notification Appliances for Fire Alarm Systems
Testing Procedures for Fire Alarm Systems
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers—Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
ADA Americans with Disabilities Act
** Applicable Local and State Building Codes
** Requirements of the Local Authority Having Jurisdiction
4
15465 Rev F 5/2/97 P/N 15465:F
15465 Rev F 5/2/97 P/N 15465:F
5
The MS-5012 Panel
Primary & Secondary
Phone Lines
Slot for Annunciator
Driver Module
Piezo
85dB
4-Digit LED
Display
Keypad
5 Input
Zones
4 Open
Collector
Outputs
6
Holds up to 7AH Batteries
Up to 60 Hrs. of Standby
15465 Rev F 5/2/97 P/N 15465:F
1.0 Product Description
The MS-5012 is a combination control panel and digital communicator all on one circuit board. It is a five-zone panel which uses conventional input devices. The panel accepts waterflow devices, twowire smoke detectors, four-wire smoke detectors, pull stations and other normally open contact devices. Outputs include bell circuit, alarm, trouble, supervisory and communicator failure relay drivers.
The integral communicator transmits system status (alarms, troubles, AC loss, etc.) to a UL recognized Central Station via the public switched telephone network. The control panel has a built in programmer and may also serve as a slave communicator to a host panel. It also supervises all wiring, AC voltage, telephone line input voltage and battery level.
1.1 Product Features
❏
Fire Control Panel
❏ Slave Fire Communicator
❏ 12 Volt Operation
❏ Real Time Clock
❏ Telephone Line Active Indicators
❏ Trouble Reminder
❏ One Style D (Class A) Zone
❏ Four Style B (Class B) Zones
❏ Programmable Zone ID
❏ Alarm Verification
❏ RZA-5F Remote Annunciator
(requires ADM-12 Annunciator Driver Module)
❏ Annunciator Type (LEDs) or (RZA-5F)
❏ Small Size (14.5" x 12.5" x 2.875")
❏ Event History Storage
❏ Silence Inhibit
❏ Auto-Silence
❏ Programmable Event Codes (all formats)
❏ Touchtone/Rotary Dialing
❏ Programmable Make/Break Ratio
❏ Communication Confirmation (Kissoff) LED
❏ Fuseless
❏ AC loss report meets 1993 UL 864 req.
❏ Number of dial attempts (5 min, 10 max)
❏ Programmable Channel ID (slave)
Optional DP-5012 Dead Front dress panel
❏ Programmable Zone Delay (waterflow only)
❏ Four Open Collector Outputs
❏ Disable report by event
❏ Low AC Voltage Sense
❏ Walk Test
❏ Built in Voltmeter
❏ Built-in Programmer
❏ One NFPA Style Y Notification Appliance (bell) Circuit
❏ Optional Dead Front cover available
15465 Rev F 5/2/97 P/N 15465:F
7
8
1.2 Circuits
Input Circuits
Initiating Device Circuit 1 (Style B) N.O. contact devices only.
Initiating Device Circuit 2 (Style B) N.O. contact devices, 2-wire smoke detectors.
Initiating Device Circuit 3 (Style B/D) N.O. contact devices, 2-wire smoke detectors, waterflow devices. (2-wire detectors use Style B only)
Initiating Device Circuit 4 (Style B) N.O. contact devices only.
Initiating Device Circuit 5 (Style B) N.O. contact devices only.
Output Circuits
❏ Notification Appliance Circuit
❏ Resettable Power Circuit
❏ Non-Resettable Power Circuit
❏ Relay Driver Output - Alarm
❏ Relay Driver Output - Trouble
❏ Relay Driver Output - Supervisory
❏ Relay Driver Output - Communicator Failure
❏ Primary Telephone Line
❏ Secondary Telephone Line
❏ 12 Volt Battery Charger
1.3 Front Panel
Switches
Reset
Silence
Mode
Up Arrow
Down Arrow
1st Event
Enter Store
E
F
C
D
Digits 0-9
A
B u v w
123f q'
456e r
789d s a0bc t
1.4 Displays
❏ Alarm - red LED
❏ Trouble - yellow LED
❏ Supervisory - yellow LED
❏ AC Power - green LED
❏ Four, Seven Segment Displays - red
❏ Primary Phone Line Active - red LED
❏ Secondary Phone Line Active - red LED
❏ "Kissoff" Signal from Central Station - green LED
❏ Silence - yellow LED
15465 Rev F 5/2/97 P/N 15465:F
1.5 Digital
Communicator
Digital Communicator
The integral digital communicator provides the following functions:
❏ Line Seizure - takes control of the phone lines disconnecting any
premises phones.
❏ Off/On Hook - perform on and off-hook status to the phone lines.
❏ Listen for dial tone - 440 hertz tone typical in most networks.
❏ Dialing the Central Station(s) number - default is Touch-Tone®,
programmable to rotary.
❏ Discern proper “Ack” and “Kiss-off” tone(s) - The frequency and
time duration of the tone(s) varies with the transmission format.
The control panel will adjust accordingly.
❏ Communicate in the following formats:
12 Tone Burst Types: 20 pps
(3+1, 4+1, 4+2, 3+1 Exp., 4+1 Exp., 4+2 Exp.)
15465 Rev F 5/2/97 P/N 15465:F
9
10
1.6 Optional
Boards
ADM-12 Annunciator Driver Module
The ADM-12 Annunciator Driver Module supports the RZA-5F Remote
Annunciator module. Annunciator wiring is supervised for open conditions by this module. The Annunciator Driver Module mounts to the main board, occupying one of the two option connectors.
TB1
J1
J3
ALARM
TROUBLE
SUPERVISORY
RESET
SILENCE
MODE
TB2
11
12
13
7
8
9
10
3
4
1
2
5
6
14
Connect ADM-12 to main board at
J3. Use nylon spacer here
(supplied.)
Note: Make connections with system power off.
TB3
3
4
1
2
5
6
7
1 2
1.7 Remote
Annunciator
The RZA-5F Remote Annunciator mounts on a standard single-gang box, and provides LED indication of the following:
Alarm Zone 1 (red)
Alarm Zone 2 (red)
Alarm Zone 3 (red)
Alarm Zone 4 (red)
Alarm Zone 5 (red)
System Trouble (yellow)
A Local Trouble Sounder and
Tone Silence Switch are also provided. All LED wiring is supervised for open conditions.
Any open condition will cause the
System Trouble LED to illuminate. Slide in paper labels permit an easy change of zone information.
NOTE: The Remote Annunciator requires the use of the ADM-12
Annunciator Driver Module .
RZA-5F
15465 Rev F 5/2/97 P/N 15465:F
1.8 Specifications
AC Power Primary TB1 Terminals 1-2
120VAC, 50/60 Hz, 0.32 A
15.0 VAC, 50/60 Hz, 2.0 amps, 25 VA
Battery (sealed lead acid only) Connector J1
Maximum Charging Capacity: 14.3V, 0.80A
Maximum Battery Capacity: 7AH
Initiating Device Circuits TB2 Terminals 1-2, 9-10, 11-12
N.O. Contact Zones 1, 4, 5
Power-Limited Circuitry
Operation: NFPA Style B
Normal Operating Voltage: 13.8VDC (ripple = 100mV max)
Short Circuit Current: 4.46 mA maximum
Maximum Loop Resistance: 100 ohms
End-of Line Resistor: 2.2K, 1/2-Watt (part # 27070 UL listed)
Standby Current: 2.66 mA
Initiating Device Circuits TB2 Terminals 3-4, 5-8
Detector Zones 2, 3
Power-Limited Circuitry
Operation: Zone 2 (NFPA Style B), Zone 3 (NFPA Style B, D)
Connecting 2-wire detectors on Zone 3 requires NFPA Style B only.
Normal Operating Voltage: 13.8VDC (ripple = 100mV max)
Alarm Current: 12 mA
Short Circuit Current: 24 mA maximum
Maximum Detector Current in Standby: 2 mA
Maximum Loop Resistance: 30 ohms
End-of-Line Resistor: 2.2K, 1/2-Watt (part # 27070 UL listed)
Detector Loop Current is sufficient to ensure operation of one alarmed detector per zone.
Standby Current: 5.17 mA (including ELR)
Notification Appliance Circuit TB3 Terminals 1-2
Power-Limited Circuitry
Operating Voltage Range: 8.5 to 17.16 VDC
Requires minimum of 300 mA load
Total current available to external devices: 1A
End-of-Line Resistor: 2.2K, 1/2-Watt (part # 27070 UL listed)
Auxiliary Outputs TB3 Terminals 4-7
Power-limited Circuitry
Type: Open Collector
Rating: 40 mA each.
TB3-4 Alarm Relay Driver. Normally high, Active low. Sinks up to 40 mA.
TB3-5 Trouble Relay Driver. Normally low, Active high. Sinks up to 40 mA.
TB3-6 Supervisory Relay Driver. Normally high, Active low. Sinks up to 40 mA.
TB3-7 Communicator Failure. Normally high, active low. Sinks up to 40 mA.
15465 Rev F 5/2/97 P/N 15465:F
11
12
Four-wire Smoke Detector Power TB2 Terminals 13(+), 14(-)
Power-limited Circuitry
Up to 200 mA is available for powering 4-wire smoke detectors.
Maximum ripple voltage: 100 mV max.
Normal Operating Voltage = 13.8 VDC
Non-Resettable Power TB3 Terminal 3(+) and TB2 Terminal 14 (-)
Available Current: 185 mA. Power-limited Circuitry
Maximum ripple voltage: 100 mV max.
Normal Operating Voltage = 13.8 VDC
Telephone Circuitry:
Ringer Equivalence Number (REN) = 0.0B
AC Impedance 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ-31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive REN's on the telephone line may result in the devices not ringing in response to an incoming call.
In most, but not all areas, the sum of the REN's should not exceed five
(5.0). To be certain of the number of devices that may be connected to the line, as determined by the total REN's, contact the telephone company to determine the maximum REN for the calling area.
Digital Communicator:
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. The following information is provided if required by the local telephone company :
Manufacturer : Fire·Lite Alarms Inc.
12 Clintonville Rd.
Northford, CT 06492
Product Model Number: MS-5012
FCC Registration Number: 1W6USA-74525-AL-E
Ringer Equivalence 0.0B
Piezo Sounder
An on-board piezo sounder will emit three distinctly different audible tones depending on system activity. Steady on for alarms, one second on, one second off, for trouble, and 1/2 second on, 1/2 second off for supervisory.
Bell Circuit Fault: The NFPA Style Y circuit configuration allows for connection of polarized bells, strobes and horns. The wiring to these notification appliances is monitored for opens and shorts.
15465 Rev F 5/2/97 P/N 15465:F
Telephone Company Rights and Warnings:
The telephone company under certain circumstances may temporarily discontinue services and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE,
GROUND START, OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The control panel must be connected to the public switched telephone network upstream of any private telephone system at the protected premises.
An FCC compliant telephone cord must be used with this equipment.
This equipment is designed to be connected to the telephone network or premises wiring using a compatible RJ31X male modular plug which is
Part 68 compliant.
15465 Rev F 5/2/97 P/N 15465:F
13
2.0 Control Panel Operation
14
Normal Mode
The MS-5012 has six Modes of operation; Normal, Program, Walk Test,
Lamp Test, Troubleshoot, and History. Upon initial power up, the
system will be in Normal Mode. This section discusses operation of the
control panel in the Normal Mode. Programming is discussed in
Section 4. Walk Test, History and Troubleshoot Modes are discussed in
Section 5.
2.1 Switches
u
Below is a description of the function switches in Normal Mode:
The Reset Switch resets the system and any smoke detectors. If the
Reset Switch is pressed, the control panel will:
✔ Clear the display and status LEDs
✔ Turn off the Notification Appliance Circuit
✔ Reset all zones by temporarily removing power
✔ Silence the on board piezo sounder
✔ Store “reset” message in the History file (see Section 5.2)
✔ Clear all relay driver outputs
✔ Temporarily remove power from the resettable power output
TB1 terminals 13 + 14.
Any alarm, supervisory or trouble condition that exists after a system reset, will resound the system, reactivating normal system activity.
Upon release of the reset switch, the display will read reS
for six seconds.
15465 Rev F 5/2/97 P/N 15465:F
v
If the Silence Switch is pressed:
✔ The bell circuit will be turned OFF.
✔ The silence LED will be turned ON.
✔ The piezo sounder will be shut OFF.
✔ “System Silenced” message will be stored in the History file.
Upon occurrence of a subsequent event (alarm or trouble), System
Silence is overridden and the control panel will respond to the new event.
The System Silence switch will be ignored for waterflow type alarms.
w
Pressing the Mode Switch followed by a valid 4-digit numerical code selects one of the five modes of operation.
☛ To enter normal mode from any other mode press
w then
6676
[ENTER/STORE]
.
6676 spells NORM on a Touch-Tone® phone.
s
=
This switch along with the up arrow and down arrow, is used to display any presently active alarm and/or fault conditions present in the system.
Press the 1st Event switch at any time to display the 1st event (alarm and/ or trouble) that occurred.
r
Down arrow - Use the down arrow switch to view other events
(older) that have occurred and are active - not cleared yet.
q
Up arrow - Use the up arrow switch to view other events (newer), that have occurred and are active - not cleared yet.
t
2.2 Displays
Enter/Store - Not used in Normal Mode.
A 1
A 2
A 3
A 4
A 5
F 1
F 2
F 3
F 4
F 5
F A
Four 7-segment red LED characters provide visual annunciation of status, events and messages. A list of messages that may appear on the display in normal mode is shown below:
Alarm Zone 1
Alarm Zone 2
Alarm Zone 3
Alarm Zone 4
Alarm Zone 5
Trouble Zone 1
Trouble Zone 2
Trouble Zone 3
Trouble Zone 4
Trouble Zone 5
Annunciator Fault
F E
Lo b no b
PH 1
PH 2 bELL no 1 no 2
5UP4
AC rES
Earth Fault
Low Battery
No Battery
Primary Number Communication Fault
Secondary Number Communication Fault
Bell Fault
Primary Phone Line Fault
Secondary Phone Line Fault
Supervisory Alarm
AC Power Loss
Reset
15
15465 Rev F 5/2/97 P/N 15465:F
16
Individual LEDs are provided for:
System Alarm—A red LED that lights when an alarm condition is detected.
System Trouble—This yellow LED indicates that a fault or abnormal condition exists and that the fire alarm system may be inoperative.
AC Power On—A green LED that remains on while the A.C. power supply is operating. If this indicator fails to light under normal conditions, service the system immediately.
Supervisory—A yellow LED that indicates need for action in connection with the supervision or maintenance of sprinklers, extinguishing systems or other protective systems.
System Silence—A yellow LED that indicates an Alarm or Trouble is being silenced.
Primary Line Active—A red LED that indicates the primary phone line is active.
Secondary Line Active—A red LED that indicates the secondary phone line is active.
Kiss-Off—A green LED on the board that indicates the Central Station has acknowledged receipt of transmitted message.
Primary
Line
Secondary
Line
Secondary
Active LED
Primary Active
15465 Rev F 5/2/97 P/N 15465:F
Kiss-Off
LED
2.3 Operation
Normal mode is the standard mode of operation. In this mode, the panel continuously monitors system status. When no alarm or fault conditions exist, the display will be blank and all LEDs will be off
(except the AC Power LED). The Notification Appliance Circuit will be off, all relay drivers are deactivated and the on-board piezo sounder will be off. (The communicator is not active, primary and secondary active LEDs are off).
All alarm conditions and fault conditions are annunciated on the control panel's display. The control panel will maintain an “active event list”(as shown in the preceding table) This list will consist of all alarms, supervisory alarms and faults currently active, and not cleared, requiring immediate service. When the system is cleared and restored to normal, the display will be blank. All alarms and faults are stored in a history file and may be recalled at any time. (See History Mode,
Section 5.2).
Higher priority events take precedence over lower priority events.
Display of System Activity is done on a priority basis. Priorities are, from highest to lowest:
1. Alarms
2. Supervisory alarms
3. Faults (troubles)
The highest priority event will be communicated to the central station first. It also is displayed, overriding any other displayed event. (only one is displayed at a time) Whenever multiple events occur, an authorized user may view each event by operating the “up” and “down arrow” switches. At any time the user may press the “1st Event” switch to display the first event that occurred. (That is, the first event that occurred after the panel was last reset, cleared of all active events and placed into normal mode.)
If the events to be displayed are alarms only (no troubles), the control panel will scroll them on the display. Pressing the 1st Event key will stop the scrolling and cause display of the First alarm that occurred.
Operation of the “up” and “down arrow” keys will display all remaining alarms in sequence.
15465 Rev F 5/2/97 P/N 15465:F
17
18
Alarm Response
The MS-5012 will upon detection of an alarm condition:
✔ Turn the alarm LED on.
✔ Activate the alarm relay driver. (TB3-4)
✔ Display an alarm message as follows:
A 1
Alarm on zone 1
A 2
Alarm on zone 2
A 3
Alarm on zone 3
A 5
Alarm on zone 5
Note that when Zone 4 is programmed as a supervisory zone, it will not be processed in the same manner as a conventional alarm zone. See
System Supervisory Condition later in this section.
✔ Communicate the alarm to the central station.
✔ Store the alarm in the History file.
✔ Turn the Notification Appliance Circuit on.
✔ Turn the Piezo Sounder on.
Alarm Restoral
The control panel only returns to normal after all alarms have been cleared and the Reset switch has been pressed (pull stations reset, smoke detectors reset and no smoke is present, waterflow has stopped). The control panel will perform the following upon restoral of all active alarms:
✔ Turn off the alarm LED.
✔ Deactivate the alarm relay driver. (TB3-4)
✔ Clear the 4-character display .
✔ Send all "Zone Restoral" messages to the central station.
✔ Turn off the Notification Appliance Circuit.
✔ Turn off the Piezo Sounder.
System Supervisory Condition
Zone 4 is factory programmed as a supervisory zone. This zone is primarily used in applications where a waterflow sensing device has been employed and the wiring to the waterflow valve and/or a tamper switch is monitored. If the wiring is cut, a trouble condition will occur.
If the Normally Open tamper switch is activated, a supervisory condition will occur.
15465 Rev F 5/2/97 P/N 15465:F
When a supervisory condition occurs, the control panel will:
✔ Turn on the supervisory LED.
✔ Activate the supervisory relay driver. (TB3-6)
✔ Display the following message: (
5UP4
).
✔ Communicate the supervisory condition to the central station.
✔ Store "supervisory" message in History file.
✔ Pulse the piezo sounder at 0.5 sec on 0.5 sec off rate.
When the supervisory condition has been cleared (condition is restored and the reset switch has been pressed) the MS-5012 will perform the following:
✔ Turn off the supervisory LED .
✔ Deactivate the supervisory relay driver. (TB3-6)
✔ Clear the display of the SUP4 message .
✔ Communicate the "supervisory restoral" message to the central station.
✔ Shut off the piezo sounder.
Trouble Conditions
The control panel will perform the following upon detection of a trouble condition:
✔ Turn on the trouble LED.
✔ Activate the trouble relay driver. (TB3-5)
✔ The appropriate trouble message will be displayed. Below are the
trouble messages shown in priority fashion from the highest priority to the lowest:
AC
F 1
F 3
F 2
F 5
F 4
F E
L b no b no 1 no 2 bELL
PH 1
PH 2
F A rES
AC Loss (Must press up, down, or first event to view)
Trouble on zone 1
Trouble on zone 3
Trouble on zone 2
Trouble on zone 5
Trouble on zone 4
Ground fault
Low battery
No battery
Primary Phone Line Fault
Secondary Phone Line Fault
Bell circuit fault
Primary Number Communication Fault
Secondary Number Communications Fault
Annunciator Fault
Reset
15465 Rev F 5/2/97 P/N 15465:F
19
✔ Communicate the trouble condition to the central station.
✔ Store the trouble condition in the History file.
✔ Sound the piezo sounder one second on, one second off.
Note: When AC Brownout occurs the AC LED is off, and the Trouble
LED is on. Should the brownout condition remain, it will be transmitted to the central station after a delay (see Program Address number 55
Section 4.3.)
Trouble Condition Restoral
The control panel performs the following upon restoral of a trouble condition:
✔ The trouble LED turns OFF.
✔ The trouble relay driver deactivates. (TB3-5)
✔ If the Trouble was loss of AC power, the control panel will turn
on the AC LED upon restoral.
✔ Clear the display of the trouble message.
✔ Communicate the restored trouble condition to the central sta-
tion.
OFF Normal Reporting
Removing the panel from Normal Mode and placing it into any other mode causes a transmission of an "off normal" fault message. Returning the panel to Normal Mode causes a transmission of a "return to normal" restoral message.
20
2.4 Digital
Communicator
The MS-5012 transmits zone and system status reports to a Central
Station via the public switched telephone network. Two supervised telephone line connections are made to interface the control panel to the telephone lines. Two optional 7-foot telephone cords are available for this purpose. See Figure 3.5-1 for proper wiring diagram.
The control panel supervises both telephone lines for proper voltage. A delay of two minutes will occur before a fault in either phone line connection is reported as a trouble. When a fault is detected, an audible trouble signal will sound, the yellow trouble LED will turn on, the 4 character display will show either no 1 or no 2 (depending upon which telephone line has the fault. no 1 = Primary Line, no 2 = Secondary
Line) and the trouble condition will be reported to the Central Station over the remaining "good" phone line.
The control panel comes with line seizure capability provided to both the primary and secondary telephone line interfaces. Any time that the control panel needs to make a call to the Central Station, line seizure will disconnect any local premises phones sharing the same telephone line.
All transmission to the Central Station will be sent over the Primary phone line. In the event of noisy phone lines, transmissions will be sent over the backup Secondary phone line.
15465 Rev F 5/2/97 P/N 15465:F
Two phone numbers must be programmed (see Section 4.0), the primary phone number and the secondary phone number. All system reports will be transmitted to the primary phone number. Reports will automatically be sent to the secondary phone number if attempts to transmit to the primary phone number are unsuccessful. If 10 attempts to communicate are unsuccessful, the Communicator Failure output will be turned on
(TB3, terminal 7). Note that as an option, all reports may be sent to the secondary phone number.
The MS-5012 meets NFPA 72-1993 for Central Station Signaling
Service and for Remote Station Protective Signaling Service reporting requirements for: (a) the type of signal (b) condition (c) location of the reporting premises. The general priority reporting structure is:
1. Zone Alarms and Restores
2. Zone Troubles and Restores
3. System Troubles and Restores
4. 24-hour test
The control panel is capable of reporting detailed messages depending upon the format in use. Tables 4.3-1 through 4.3-4 list these messages.
The table below shows the reporting structure for all of the tone burst type formats.
Table 2.4-1: Format Selection Addresses (16+42)
Report
Alarm
Alarm Restore
Zone Trouble
(Zone Open)
Zone Trouble
Restore
System Trouble
System Trouble
Restore
Low Battery
Low Battery
Restore
AC Loss
AC Loss Restore
Supervisory
Condition
Supervisory
Condition
Restore
Test Reprot
Format #
2, 4, 6, 8
Format #
3, 5, 7, 9
3+1/4+1 Standard 3+1/4+1/ Expanded
SSS(S) A
SSS(S) RA
SSS(S) A
AAA(A) Z
SSS(S) RA
RARARA(RA) Z
SSS(S) TZ SSS(S) TZ
SSS(S) RTZ
SSS(S) TS
SSS(S) RTS
SSS(S) L
Format #
A, C
4+2/Standard
SSSS AA2
SSSS RARA2
SSSS TZTZ2
SSS(S) RTZ
RTZRTZRTZ(RTZ)Z
SSS(S) TS
TSTSTS(TS) Y
SSSS RTZRTZ2
SSSS TSTS2
SSS(S) RTS
RTSRTSRTS(RTS) Y
SSS(S) L
SSSS RTSRTS2
SSSS LL2
SSS(S) RL
SSS(S) P
SSS(S) RP
SSS(S) V
SSS(S) RV
SSS(S) X
SS(S) RL
SSS(S) P
SSS(S) RP
SSS(S) V
VVV(V) Z
SSS(S) RV
RVRVRV(RV) Z
SSS(S) X
SSSS RLRL2
SSSS PP2
SSSS RPRP2
SSSS VV2
SSSS RVRV2
SSSS XX2
Format #
B, D
4+2/Expanded
SSSS AZ
SSSS RAZ
SSSS TZZ
SSSSRTZZ
SSSS TSY
SSSS RTSY
SSSS LL2
SSSS RLRL2
SSSS PP2
SSSS RPRP2
SSSS VV2
SSSS RVZ
SSSS XX2
15465 Rev F 5/2/97 P/N 15465:F
21
22
Where:
P2
RP
RP2
V
V2
RV
RV2
X
X2
Y
SSS 0r
SSSS = Subscriber ID
A = Alarm (1st digit)
A2
Z
= Alarm (2nd digit)
= Zone Number
RA
RA2
TZ
TZ2
RTZ
= Alarm Restore (1st digit)
= Alarm Restore (2nd digit)
= Zone Trouble (1st digit)
= Zone Trouble (2nd digit)
= Zone Trouble Restore (1st digit)
RTZ2 = Zone Trouble Restore (2nd digit)
TS
TS2
= System Trouble (1st digit)
= System Trouble (2nd digit)
RTS = System Trouble Restore (1st digit)
RTS2 = System Trouble Restore (2nd digit)
L
L2
RL
RL2
P
= Low Battery (1st digit)
= Low Battery (2nd digit)
= Low Battery Restore (1st digit)
= Low Battery Restore (2nd digit)
= AC Loss (1st digit)
= AC Loss (2nd digit)
= AC Loss Restore (1st digit)
= AC Loss Restore ( 2nd digit)
= Supervisory Condition (1st digit)
= Supervisory Condition (2nd digit)
= Supervisory Condition Restore (1st digit)
= Supervisory Condition Restore (2nd digit)
= Test Report (1st digit)
= Test Report (2nd digit)
= 6 = AC Loss
= 7 = Ground Fault
= 8 = Low Battery
= 9 = No Battery
= A = Telco Primary Line Fault
= B = Telco Secondary Line Fault
= C = Main Bell Fault, Annunciator Fault
= D = Communication Fault to Primary Number
= E = Communication Fault to Secondary Number
= F = System Off Normal Fault/System Fault (Slave Operation,
See Section 6.0)
Note: For Expanded Reporting, the control panel automatically adds the digit corresponding to the zone number, and the second digit corresponding to any system trouble condition. Only the first digit is programmable.
15465 Rev F 5/2/97 P/N 15465:F
Transmittal Priorities
The integral communicator transmits highest priority events first.
Events in terms of priority are listed below in descending order:
1: Alarms (Highest Priority Level)
Pull Stations
Waterflow
Smoke Detector
Other Alarm Types
2: Supervisory Zone
3: Faults
AC Fail
Zonal faults
Earth fault
Low battery/No battery
Telephone line fault
Bell circuit fault
Communication Trouble
Annunciator Trouble
4: Restoral
AC
Zones
Earth
Battery
Telephone Line
Bell
Communication
Annunciator Trouble
5: 24 Hour Test (Lowest Priority)
15465 Rev F 5/2/97 P/N 15465:F
23
24
Red LEDs are provided on the control panel circuit board to identify which telephone line is activated. Also a green LED (labeled "Kissoff") will turn on whenever the control panel has successfully transmitted reports to the Central Station. The "Kissoff" LED may turn on several times during communications.
The chart below shows UL listed receivers compatible with the MS-5012:
Table 2.4-2: Compatible UL Listed Receivers
Format #
(Addresses 16 & 42)
0
Not Used
1
Not Used
2
3+1/Standard/1800/2300
✔ ✔
(2)
3
3+1/Expanded/1800/2300
✔ ✔
(2)
✔ ✔
(4)
✔
4
5
3+1/Standard/1900/1400
3+1/Expanded/1900/1400
✔ ✔
(2)
✔ ✔
(2)
✔ ✔
✔
(4)
(4)
✔
✔
✔
(4)
✔
✔
(5,6)
✔
6
4+1/Standard/1800/2300
7
4+1/Expanded/1800/2300
✔ ✔
(2)
8
4+1/Standard/1900/1400
✔ ✔
(2)
✔ ✔
(2)
✔
✔
✔
(4)
(4)
(4)
✔
✔
✔
✔
(5)
✔
9
4+1/Expanded/1900/1400
✔ ✔
(2)
✔
(4)
✔
A
4+2/Standard/1800/2300
B
4+2/Expanded/1800/2300
✔ ✔
(2)
C
4+2/Standard/1900/1400
✔ ✔
(2)
✔ ✔
(2)
✔
✔
✔
(4)
(4)
(4)
✔
✔
✔
✔
(5)
✔
D
4+2/Expanded/1900/1400
E
Not Used
✔ ✔
(2)
✔
(4)
✔
F
Not Used
(1) With 685-8 Line Card with Rev 4.4d software.
(2) With 9002 Line Card Rev 9035 software or 9032 Line Card with 9326A
software.
(3) Rev. 4.0 software.
(4) FBI CP220FB Rec-11 Line Card with Rev 2.6 software and a
memory card with Rev 3.8 software.
(5) Model 6500 with Rev 600 software.
(6) Model 6000 with Rev 204 software.
(7) With Rev B control card at rev. 1.4 software and Rev C line card at rev
1.5 software.
(8) Version 1.62 software.
15465 Rev F 5/2/97 P/N 15465:F
3.0 Installation
3.1 Cabinet
Mounting Options
The cabinet may be either semi-flush or surface mounted. The cover is removable during the installation period.
The cabinet mounts using two key slots and two additional 0.250" diameter holes located in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom. Refer to Figure 3.2-1 for cabinet dimensions.
Figure 3.1-1:
The MS-5012
3.2 Input Circuits
The MS-5012 has five zone input circuits. The maximum loop resistance limit for each is 100 ohms. All field wiring of each zone is supervised for opens and ground faults. Both conditions are visually and audibly annunciated as well as communicated to a Central Station.
Zone 1 is a Style B Initiating Device Circuit (IDC) designed to accept any
N.O. contact device on TB2, terminals 1-2. It is power limited to 2.66 mA
(standby) and 4.46 mA in alarm. Factory Default is “Pull Station.” Refer to
Section 4.0: Programming.
Zone 2 is a Style B Initiating Device Circuit designed to accept any N.O.
contact device and conventional 2-wire, 12-volt smoke detectors on TB2, terminals 3-4. It's power limited to 7.17 mA in standby and 24 mA in alarm. For a list of compatible 2-wire detectors refer to Fire-Lite
Compatibility Document. Factory Default is “2-wire Detectors.” Refer to
Section 4.0 Programming.
Zone 3 is a Style D Initiating Device Circuit. It is designed to accept: N.O.
contact devices, 2-wire smoke detectors and Waterflow sensing devices on
TB2, terminals 5-8. It's power limited to 7.17 mA in standby and 24 mA in
Alarm. A maximum of five waterflow devices may be used per NFPA 71.
For a list of compatible 2-wire detectors refer to Fire-Lite Compatibility
Document. Factory Default is "Waterflow." Refer to Section 4.0
Programming.
15465 Rev F 5/2/97 P/N 15465:F
25
Draw wires through the respective knockout locations.
Dimensions:
The door is 14.714" high x 12.714" wide. The backbox is 14.5" high x 12.5" wide x 2.875" deep.
Metal gauge is 18. The metal finish is Fire-Lite standard red. Knock-outs are provided on the top and sides, to provide ease of wire entry.
26
Figure 3.2-1: Cabinet Dimensions & Knockout Locations
15465 Rev F 5/2/97 P/N 15465:F
Note: When zone 3 is programmed to accept 2-wire smoke detectors, it will only function as a NFPA Style-B initiating device circuit. See figure 3.2-1.
Zone four is a Style B circuit designed as a Supervisory zone or may accept any N.O. contact device on TB2, terminals 9-10. As a
Supervisory zone, the circuit may or may not be able to detect a supervisory alarm condition after the occurrence of an open in the loop wiring. It's power limited to 2.66 mA in Standby and 4.46 mA in alarm.
Factory Default is "Supervisory." Refer to Section 4.0 Programming.
Zone five is a Style B Initiating Device Circuit designed as a general purpose "initiating zone." It will accept any N.O. contact device on
TB2, terminals 11-12. It's power limited to 2.66 mA in Standby and
4.46 mA in alarm. Factory Default is "4-wire Smoke Detector." Refer to
Section 4.0 Programming.
Four wire smoke detectors may be connected to any zone. Resettable power is provided via terminals TB2, 13 and 14. See Figure 3.2-1 for proper connection of 4-wire detectors..
It is allowable to mix an assortment of device types on any zone, however it is not recommended. By not mixing device types on any zone, messages sent to the Central Station may be very specific and detailed.
INPUTS
TB2
6 +
7
-
8
-
9
+
10
-
11
+
12
-
13 +
14 -
1
+
2 -
3
+
4
-
5
+
S S
+ +
W
-
W
-
T T
Pull Stations
2-Wire
Smoke
Detectors
Waterflow Devices
Terminal Block 2
Supervisory
Tamper Switches
4-Wire
Smoke
Detectors
UL Listed
Supervision
Relay
P/N A77-716-01
2-Wire
Smoke
Detectors
7
8
5
6
S S
Zone 3 Connection of 2-wire detectors. Style B only.
Figure 3.2-2 : Initiating Device Circuits
15465 Rev F 5/2/97 P/N 15465:F
27
28
For example, default programming provides the following: when Zone
1 activates, it will be reported to the central station as “Manual Pull
Station Alarm." For Zone 4 alarm, the report will be “Supervisory
Alarm." For reporting formats that do not allow for detailed reports, the message will be: “Zone 1 alarm” or “Zone 4 alarm." Refer to Section
2.4 and 4.3.
3.3 Output Circuits
One Style Y Notification Appliance Circuit is provided. This supervised circuit allows for polarized bells, strobes and horns to be powered in an alarm condition. Deliverable power is up to one amp of special purpose power. See Figure 3.3-1. For a list of compatible devices refer to the Fire-Lite Compatibility Document. A minimum
300mA load is required.
Provision is available to interconnect to two independent telephone lines. Telephone line control/command is possible via double line seizure as well as usage of an RJ31X style interconnection. See Figure
3.5-1.
Relay driver outputs are available for: Alarm, Trouble, Supervisory, and Communicator Failure. These outputs can be used to drive UL-864 listed remote relays. See Figure 3.3-1.
TB3
5
6
7
3
4
1
2
+
_
OUTPUTS
+
_
Bell(s)
+ 13.8V
General Alarm
General Trouble
Supervisory
Communication Fail
Terminal Block 3
Note: -Active Low
-40MA Each (Max)
{
Open
Collector
Outputs
Figure 3.3-1 : Output Circuits
15465 Rev F 5/2/97 P/N 15465:F
TB3
5
6
3
4
7
+13.8V
UL Recognized Enclosure
General
Alarm
General
Trouble
Supervisory
Communication
Fail
Relays
Note: Wiring from TB3 to Relays is power-limited but not supervised.
Figure 3.3-2: Driving Relays from Open Collector Outputs
The control panel's open collector outputs on Terminal TB3 can be used to activate UL-864 listed remote relays. Outputs are rated for 40 mA.
The normal condition for each output is as shown below:
TB3-4 Alarm Off (de-energized)
TB3-5 Trouble On (energized)
TB3-6 Supervisory
TB3-7 Communications Failure
Off (de-energized)
Off (de-energized)
Relays must be placed in a UL-864 recognized enclosure. Wiring from the control panel's terminals on TB3 to the relays must be less than 3 feet in length enclosed in conduit. Wiring from the relay outputs must remain in the same room as the location of the enclosure and be enclosed in conduit.
15465 Rev F 5/2/97 P/N 15465:F
29
3.4 UL Power-
limited Wiring
Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25" away from any nonpower-limited circuit wiring.
Furthermore, all power-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the MS-5012 is shown below.
Power-limited Circuits
Power-limited
Circuits
Power-limited
Circuits
AC Power
Figure 3.4-1: Typical Wiring Diagram for UL Power-limited Requirements
30
15465 Rev F 5/2/97 P/N 15465:F
3.5 Digital
Communicator
Two independent telephone lines can be connected to the MS-5012.
Telephone line control/command is made possible via double line seizure as well as usage of an RJ31X style interconnection. Note: It is
critical that the panel's digital communicator be located as the first device on the incoming telephone circuit to properly function.
The control panel's digital communicator is built right into the main board. All that is required to install the system is the connection and wiring of two phone lines as shown below:
(Primary Lines)
Incoming Telco
Phone Lines
Tip
Ring
Green Wire
Red Wire
Ring
To premise phones
Tip
1 2 3 4 5 6 7 8
Tip
Green Wire
Ring
Red Wire
(Secondary Lines)
Incoming Telco
Phone Lines
Ring
To premise phones
Tip
1 2 3 4 5 6 7 8
7 foot
Cable
(MCBL-7)
(not suppliedorder separately)
Figure 3.5-1 : Wiring Jacks
15465 Rev F 5/2/97 P/N 15465:F
31
3.6 Operating
Power
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. Primary power source is 120 VAC, 50/60 HZ, 0.32A. Run a pair of wires from the protected premises main breaker box to the black and white primary leads of the MS-5012 system transformer. As per the National Electric Code, use 14 AWG (1.6 mm O.D.) or heavier gauge wire with 600V insulation wiring. No other equipment may be connected to this circuit. In addition, this circuit must be provided with overcurrent protection and may not contain any power disconnect devices.
Connect the backbox ground stud to a solid earth ground (a metallic cold water pipe may be suitable in some installations). This connection is vital to maintaining the control panel's immunity to unwanted transients generated by lightning and electrostatic discharge.
Secondary Power Source (Batteries)
The battery charger is current limited and capable of recharging sealed lead acid type batteries. The charger shuts off when the system is in alarm.
32
Figure 3.6-1: MS-5012 Power Connections
15465 Rev F 5/2/97 P/N 15465:F
Optional AC Terminal Block
An optional AC terminal block is available for the MS-5012 Control Communicator. The terminal block can only be used on the newer, larger (14.5" x 12.5" x 2.875") backbox. It cannot be installed in the older, smaller (12.0" x 9.0" x 2.75") backbox.
CAUTION! Make certain all power (AC and battery) is removed before any connections are made.
1. Mount the optional AC terminal block to the lower left of the MS-5012 backbox using two supplied screws.
2. Connect AC power wiring to the optional terminal block as shown in Figure 3.6-2.
3. Connect the black and white wires (primary) from the MS-5012 system transformer to the optional terminal block as illustrated below. Make certain the black AC wire (Hot) is connected opposite the black transformer wire and the white AC wire (Neutral) is connected opposite the white transformer wire.
4. Make certain that the yellow wires (secondary) from the MS-5012 system transformer are connected to Terminal Block TB1 located in the lower left corner of the MS-5012 main circuit board.
5. Install a jumper between the terminal block and the backbox ground stud as illustrated below.
This will be used to provide lightning protection to the panel. (Make certain the jumper is connected opposite the green AC ground wire on the terminal block).
6. Install a solid earth ground connection to the backbox ground stud as illustrated below. This will be used to provide lightning protection to the panel.
7. Press the AC terminal cover firmly into place.
8. Reapply AC and battery power to the MS-5012 Control Communicator.
MS-5012 Main Circuit Board
MS-5012 Backbox
Figure 3.6-2: Optional AC Terminal Block Installation
15465 Rev F 5/2/97 P/N 15465:F
33
34
3.7 Optional
Boards
ADM-12 Annunciator Driver Module
The Annunciator Driver Module supports the RZA-5F Remote Annunciator module.
Annunciator wiring is supervised for open conditions by this module. The Annunciator
Driver Module mounts to the main board, occupying one of the two option connectors.
(See Section 1.6)
The RZA-5F Remote Annunciator mounts on a standard single-gang box, and provides LED indication of the following:
Alarm Zone 1 (red)
Alarm Zone 2 (red)
Alarm Zone 3 (red)
Alarm Zone 4 (red)
Alarm Zone 5 (red)
System Trouble (yellow)
The remote annunciator provides individual zone alarm LEDs, a system trouble LED, a piezo sounder and a remote sounder shut off switch.
A Local Trouble Sounder and
Silence Switch are also provided.
All LED wiring is supervised for open conditions. Any open condition will cause the System
Trouble LED to illuminate.
NOTE: The Remote Annunciator requires the use of an ADM-12
Annunciator Driver Module.
15465 Rev F 5/2/97 P/N 15465:F
Remote Annunciator
screw # 6-32 x 1.00" LG
Figure 3.7-1: Installing the Annunciator in a Single Gang Box
+12V
ADM-12
Note: Make wiring connections with system power off. Maximum wire impedance is 100 ohm per wiring connection.
Figure 3.7-2: Wiring the RZA-5F/ADM-12
RZA-5F
15465 Rev F 5/2/97 P/N 15465:F
35
4.0 Programming Instructions
Programming
Mode
Programming of the MS-5012 is possible at any time except when an alarm condition is present in the Normal Mode of operation.
The MS-5012 has been designed for many different types of applications.
After examining your specific application, review the programming options and choose the entries best suited for your system.
The MS-5012 has a built-in programmer. All programming selections are stored in nonvolatile Electrically-Erasable Programmable Read-Only
Memory (EEPROM). This ensures that the control panel will remember all entries made in programming mode even if both AC and battery power are removed.
The user must program the primary and secondary phone numbers, account numbers and 24 hour test report times for each Central Station account and the current time. The control panel comes with factory chosen options/features already programmed. Other options/features may be programmed if desired. If all factory default settings are acceptable, programming is complete.
4.1 Entering
Program Mode
To enter the Program Mode, press the
w key once, (the display will go
blank) you then have ten seconds to start entering the code (
7764) .
☛
7764 spells PROG on a Touch-Tone® phone
If an incorrect key is entered, just reenter the proper 4-digit code before hitting the t
key
7
77
776
7764
Note that as you enter information into the control panel, the digits will scroll across the display from right to left
You are allowed a pause of up to 10 seconds in between each number while entering the code. The control panel will then be in Program Mode and show the display
00 F. You are allowed up to ten minutes of idle
time at this point before starting your programming, otherwise the control panel will go back to Normal Mode. You also have a maximum of 10 minutes between any key stroke.
36
15465 Rev F 5/2/97 P/N 15465:F
When in Programming Mode, the trouble light will be on, the trouble relay driver will be activated, but the communicator will not be activated to report this trouble. Transmissions started before entering
program mode will continue during programming.
4.2 Switch
Functions
The first three locations from the left represent the memory address which can go from 00 up to 243 (Alpha characters are not used). The last location (farthest right) represents the contents of the memory address. The first address displayed is shown below:
00 F address data
The Function of each switch is shown below:
No function in this mode entry
These keys can be used for address entry and/or data
{ u v w
123f q'
- Select operating mode
- Increment memory address
456e r
789d s= a0bc t
- Decrement memory address
- Once = First memory address
Twice = type any address
- Save data, go to next address
4.3 Programming
Programming the Primary phone number. (00-15)
Sixteen addresses are set aside with "F" being the factory default.
(from
00 F to
15 F
).
If your phone # is 484-7161, type
4
, the display will read
00 4
, press t to save and bring you to the next address
01 F
.
Enter the remaining numbers in their respective addresses:
4 8 4 7 1 6 1 F F F F F F F F F
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 .
37
15465 Rev F 5/2/97 P/N 15465:F
38
Valid entries are 0 - F with the numeric digits as dialed numbers and hex digits indicating the following:
A= * on a Touchtone phone keypad
B= # on a Touchtone phone keypad
C= look for secondary dial tone for up to 2 seconds (then, dial anyway)
D= 3-second pause
E= 5-second pause
F= end of phone number
Programming Primary Number Communication Format. (16)
One location is needed to select the Communication Format to the primary phone number. Address 16 is used for this purpose. The default
(factory setting) for this address is A
16 A
, which is 4+2 Standard,
1800 Hz "Carrier", 2300 Hz "ack." You may enter 2 through D in place of the default, then hit
[ENTER/STORE].
Zero through F represents the following:
0: Not Used
1: Not Used
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK --- Table 4.3-1
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK -- Table 4.3-1
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK --- Table 4.3-1
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK--- Table 4.3-1
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK --- Table 4.3-1
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK -- Table 4.3-1
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK --- Table 4.3-1
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK - Table 4.3-1
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK -- Table 4.3-2
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK - Table 4.3-1
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK -- Table 4.3-2
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK - Table 4.3-1
E: Not Used
F: Not Used
Note: Consult your Central Station for proper selection or consult our factory representatives. For any format chosen, the MS-5012 automatically programs all of the event codes. See the following tables.
15465 Rev F 5/2/97 P/N 15465:F
Table 4.3-1:
3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats
If "2, 3, 4, 5, 6, 7, 8, 9, B or D" are entered for address 16, the following data is automatically programmed for the Primary phone number event codes.
Enter '0' for the Setting to disable the report.
105
106
107
108
109
110
111
100
101
102
103
104
95
96
97
98
99
90
91
92
93
94
85
86
87
88
89
80
81
82
83
84
73
74
75
76
77
78
79
Address
68
69
70
71
72
Description
Primary # Zone 1 Alarm Code
Primary # Zone 2 Alarm Code
Primary # Zone 3 Alarm Code
Primary # Zone 4 Alarm Code
Primary # Zone 5 Alarm Code
Primary # AC Fault Code
Primary # Zone 1 Fault Code
Primary # Zone 2 Fault Code
Primary # Zone 3 Fault Code
Primary # Zone 4 Fault Code
Primary # Zone 5 Fault Code
Primary # Earth Ground Code
Primary # Low Battery Code
Primary # No Battery Code
Primary # Telco Prim. Line Fault Code
Primary # Telco Sec. Line Fault Code
Primary # Bell Fault Code
Primary # Comm Trouble Pri. #
Primary # Comm Trouble Sec. #
Primary # Annunciator Fault Code
Primary # System Off Normal Code
Primary # Zone 1 Alarm Restoral Code
Primary # Zone 2 Alarm Restoral Code
Primary # Zone 3 Alarm Restoral Code
Primary # Zone 4 Alarm Restoral Code
Primary # Zone 5 Alarm Restoral Code
Primary # AC Fault Restoral Code
Primary # Zone 1 Fault Restoral Code
Primary # Zone 2 Fault Restoral Code
Primary # Zone 3 Fault Restoral Code
Primary # Zone 4 Fault Restoral Code
Primary # Zone 5 Fault Restoral Code
Primary # Earth Ground Restoral Code
Primary # Low Battery Restoral Code
Primary # No Battery Restoral Code
Primary # Telco Pri. Line Fault Restoral
Primary # Telco Sec. Line Fault Restoral
Primary # Bell Fault Restoral Code
Primary # Comm Trouble Rest. Pri. #
Primary # Comm Trouble Rest. Sec. #
Primary # Annunciator Fault Restoral
Primary # System Return to Normal Code
Primary # 24 Hour Test Code
Primary # System Abnormal Test Report
E
E
E
E
E
E
E
E
E
E
9
F
E
E
E
E
E
E
E
E
E
E
F
F
F
F
E
F
F
F
F
F
F
F
F
F
F
1
8
1
F
F
1
1
Factory
Setting
15465 Rev F 5/2/97 P/N 15465:F
39
40
Table 4.3-2:
4+2 Standard Format
If "A or C" are entered for address 16, the following data is automatically programmed for the Primary phone number event codes.
Enter '00' for the Setting to disable the report.
Address
132-133
134-135
136-137
138-139
140-141
142-143
144-145
146-147
148-149
150-151
152-153
154-155
112-113
114-115
116-117
118-119
120-121
122-123
124-125
126-127
128-129
130-131
92-93
94-95
96-97
98-99
100-101
102-103
104-105
106-107
108-109
110-111
68-69
70-71
72-73
74-75
76-77
78-79
80-81
82-83
84-85
86-87
88-89
90-91
Description Settings
Primary # Zone 1 Alarm Code
Primary # Zone 2 Alarm Code
Primary # Zone 3 Alarm Code
Primary # Zone 4 Alarm Code
Primary # Zone 5 Alarm Code
Primary # AC Fault Code
Primary # Zone 1 Fault Code
Primary # Zone 2 Fault Code
Primary # Zone 3 Fault Code
Primary # Zone 4 Fault Code
Primary # Zone 5 Fault Code
Primary # Earth Ground Code
Primary # Low Battery Code
Primary # No Battery Code
Primary # Telco Pri. Line Fault Code
Primary # Telco Sec. Line Fault Code
Primary # Bell Fault Code
Primary # Comm Trouble Pri. #
Primary # Comm Trouble Sec. #
Primary # Annunciator Fault Code
Primary # System Off Normal Code
Primary # Zone 1 Alarm Restoral Code
Primary # Zone 2 Alarm Restoral Code
Primary # Zone 3 Alarm Restoral Code
Primary # Zone 4 Alarm Restoral Code
Primary # Zone 5 Alarm Restoral Code
Primary # AC Fault Restoral Code
Primary # Zone 1 Fault Restoral Code
Primary # Zone 2 Fault Restoral Code
Primary # Zone 3 Fault Restoral Code
Primary # Zone 4 Fault Restoral Code
Primary # Zone 5 Fault Restoral Code
Primary # Earth Ground Restoral Code
Primary # Low Battery Restoral Code
Primary # No Battery Restoral Code
E 7
E 8
E 9
Primary # Telco Primary Line Fault Restoral E A
Primary # Telco Secondary Line Fault Restoral E B
Primary # Bell Fault Restoral Code
Primary # Comm Trouble Rest. Pri. #
Primary # Comm Trouble Rest. Sec. #
Primary # Annunciator Fault Restoral
Primary # System Return to Normal Code
Primary # 24 Hour Test Code
Primary # System Abnormal Test Report
E C
E D
E E
E C
E F
9 9
9 1
E 1
E 2
E 3
E 4
E 5
E 2
E 3
E 4
E 5
E 6
F D
F E
F C
F F
E 1
F 8
F 9
F A
F B
F C
F 2
F 3
F 4
F 5
F 7
1 1
1 2
1 3
8 4
1 5
F 6
F 1
15465 Rev F 5/2/97 P/N 15465:F
Programming the Primary Number Account Code (17-20) takes up four locations at addresses 17-20. The defaults are all "0"s.
17 0
Valid entries are (0-9 and A-F). The number of digits entered must match the format selection. If programming "2, 3, 4, or 5" into address
16, enter 3 digits. (location 20 is ignored) If programming "6, 7, 8, 9, A,
B, C, or D" into address 16, enter 4 digits.
Programming the Primary Number 24 Hour Test Time (21-24).
Use military time when entering the 24 hour "test" time. The 24 hour test time over phone number 1 to the central station takes up four locations, from addresses 21-24. The default is 00:00 (12:00 midnight).
The limits for each location are as follows: 21: enter 0, 1, 2; 22: enter
0-9; 23 : enter 0-5; 24: enter 0-9. Note: Do not use A-F.
Programming Primary Number 24/12 Hour Test Time (25). The test message sent to the Primary phone number may be sent every 12 or 24 hours. If the message is to be sent every 24 hours, leave the factory default entry of zero. If 12 hour test reports are needed, enter a "1" into this address.
Programming the Secondary Phone Number (26-41) is similar to the primary phone number located in addresses 00 - 15. The defaults are also all "F"s.
4 8 4 7 1 6 1 F F F F F F F F F
26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 .
Programming Secondary Number Communication Format (42) is programmed the same way as the primary number's Comm Format in address 16. Default entry is "A" 4+2 Standard. Choose one entry from the list below:
0: Not Used
1: Not Used
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK --- Table 4.3-3
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK -- Table 4.3-3
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK --- Table 4.3-3
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK--- Table 4.3-3
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK --- Table 4.3-3
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK -- Table 4.3-3
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK --- Table 4.3-3
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK - Table 4.3-3
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK -- Table 4.3-4
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK - Table 4.3-3
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK -- Table 4.3-4
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK - Table 4.3-3
E: Not Used
F: Not Used
15465 Rev F 5/2/97 P/N 15465:F
41
42
Table 4.3-3:
3+1 and 4+1 Standard and Expanded, 4+2 Expanded
If "2, 3, 4, 5, 6, 7, 8, 9, B or D" are entered for address 42, the following is automatically programmed for the Secondary phone number event codes. Enter '0' for the Setting to disable the report.
Factory
Address
191
192
193
194
195
186
187
188
189
190
196
197
198
199
181
182
183
184
185
176
177
178
179
180
171
172
173
174
175
166
167
168
169
170
161
162
163
164
165
156
157
158
159
160
Description
Secondary # Zone 1 Alarm Code
Secondary # Zone 2 Alarm Code
Secondary # Zone 3 Alarm Code
Secondary # Zone 4 Alarm Code
Secondary # Zone 5 Alarm Code
Secondary # AC Fault Code
Secondary # Zone 1 Fault Code
Secondary # Zone 2 Fault Code
Secondary # Zone 3 Fault Code
Secondary # Zone 4 Fault Code
Secondary # Zone 5 Fault Code
Secondary # Earth Ground Code
Secondary # Low Battery Code
Secondary # No Battery Code
Secondary # Telco Pri. Line Fault Code
Secondary # Telco Sec.Line Fault Code
Secondary # Bell Fault Code
Secondary # Comm Trouble Pri. #
Secondary # Comm Trouble Sec. #
Secondary # Annunciator Fault Code
Secondary # System Off Normal Code
Secondary # Zone 1 Alarm Restoral Code
Secondary # Zone 2 Alarm Restoral Code
Secondary # Zone 3 Alarm Restoral Code
Secondary # Zone 4 Alarm Restoral Code
Secondary # Zone 5 Alarm Restoral Code
Secondary # AC Fault Restoral Code
Secondary # Zone 1 Fault Restoral Code
Secondary # Zone 2 Fault Restoral Code
Secondary # Zone 3 Fault Restoral Code
Secondary # Zone 4 Fault Restoral Code
Secondary # Zone 5 Fault Restoral Code
Secondary # Earth Ground Restoral Code
Secondary # Low Battery Restoral Code
Secondary # No Battery Restoral Code
Secondary # Telco Line 1 Fault Restoral
Secondary # Telco Line 2 Fault Restoral
Secondary # Bell Fault Restoral Code
Secondary # Comm Trouble Rest. Pri. #
Secondary # Comm Trouble Rest. Sec. #
Secondary # Annunciator Fault Restoral
Secondary # System Return to Normal Code
Secondary # 24 Hour Test Code
Secondary # System Abnormal Test Report
Setting
E
E
E
E
E
E
E
9
F
E
E
E
E
E
E
E
E
E
E
F
E
E
E
E
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
1
1
1
8
1
15465 Rev F 5/2/97 P/N 15465:F
Table 4.3-4:
4+2 Standard Format
If "A or C" are entered for address 42, the following is automatically programmed for the Secondary phone number event codes. Enter '00' for the Setting to disable the report.
Factory
Address Description
216-217
218-219
220-221
222-223
224-225
226-227
228-229
230-231
232-233
234-235
236-237
238-239
240-241
242-243
196-197
198-199
200-201
202-203
204-205
206-207
208-209
210-211
212-213
214-215
176-177
178-179
180-181
182-183
184-185
186-187
188-189
190-191
192-193
194-195
156-157
158-159
160-161
162-163
164-165
166-167
168-169
170-171
172-173
174-175
Setting
Secondary # Zone 1 Alarm Code
Secondary # Zone 2 Alarm Code
Secondary # Zone 3 Alarm Code
Secondary # Zone 4 Alarm Code
Secondary # Zone 5 Alarm Code
Secondary # AC Fault Code
Secondary # Zone 1 Fault Code
Secondary # Zone 2 Fault Code
Secondary # Zone 3 Fault Code
Secondary # Zone 4 Fault Code
Secondary # Zone 5 Fault Code
Secondary # Earth Ground Code
Secondary # Low Battery Code
Secondary # No Battery Code
Secondary # Telco Prim. Line Fault Code
Secondary # Telco Sec. Line Fault Code
Secondary # Bell Fault Code
Secondary # Comm Trouble Pri. #
Secondary # Comm Trouble Sec. #
Secondary # Annunciator Fault Code
Secondary # System Off Normal Code
Secondary # Zone 1 Alarm Restoral Code
Secondary # Zone 2 Alarm Restoral Code
Secondary # Zone 3 Alarm Restoral Code
Secondary # Zone 4 Alarm Restoral Code
Secondary # Zone 5 Alarm Restoral Code
Secondary # AC Fault Restoral Code
Secondary # Zone 1 Fault Restoral Code
Secondary # Zone 2 Fault Restoral Code
Secondary # Zone 3 Fault Restoral Code
Secondary # Zone 4 Fault Restoral Code
Secondary # Zone 5 Fault Restoral Code
Secondary # Earth Ground Restoral Code
Secondary # Low Battery Restoral Code
Secondary # No Battery Restoral Code
Secondary # Telco Prim.Line Fault Restoral
Secondary # Telco Sec. Line Fault Restoral
Secondary # Bell Fault Restoral Code
Secondary # Comm Trouble Rest. Pri. #
Secondary # Comm Trouble Rest. Sec. #
Secondary # Annunciator Fault Restoral E C
Secondary # System Return to Normal Mode E F
Secondary # 24 Hour Test Code 9 9
Secondary # System Abnormal Test Report 9 1
E 4
E 5
E 7
E 8
E 9
E A
E B
E C
E D
E E
E 5
E 6
E 1
E 2
E 3
F F
E 1
E 2
E 3
E 4
F B
F C
F D
F E
F C
F 5
F 7
F 8
F 9
F A
F 6
F 1
F 2
F 3
F 4
1 1
1 2
1 3
8 4
1 5
15465 Rev F 5/2/97 P/N 15465:F
43
44
Secondary Number Account Code (43-46) is programmed in addresses 43 - 46 in the same manner as the primary phone number
Account Code. Default entries are all "0's."
Secondary Number 24-Hour Test Time (47-50) is programmed in addresses 47-50 in the same manner as the primary number 24-Hour
Test Time. Default is 00:00 (12:00 midnight).
Secondary Number 24/12 Hour Test Time (51) The test message sent to the Secondary phone number may be sent every 12 or 24 hours. If the message is to be sent every 24 hours, leave the factory default entry of zero. If 12 hour test reports are needed, enter a "1" into this address.
Programming Zone 3 Functionality (52)
The following entries may be selected: 0 = non silenceable Waterflow
Zone, 1 = N.O. contact device zone or silenceable Waterflow zone, 2 =
2-Wire detector device zone. If "0" is entered, address 53-54 must be programmed if a delay is needed. Selecting a "1" entry allows any
Normally Open contact device to be connected on this zone. Selecting a
"2" entry allows for 2-wire detectors to be connected on this zone.
(Style B only) Factory setting is "0," non silenceable Waterflow zone.
Programming Waterflow Retard Timer (53-54) This field allows you to select a delay of up to 89 seconds for declaring a "Waterflow Alarm."
Factory default is one second. The default for addresses 53 and 54 are
"00" (no additional delay). Valid keys for 53 are 0-8, and 0-9 for 54.
Program an entry into this address only if selecting a "0" in address 52 above. Be careful to include any built in delays of the waterflow device.
Programming AC Loss Reporting Delay (55) Enter a digit of 1, 2, 3,
4, 5, or 6 corresponding to the number of hours to be delayed in reporting loss of AC power. Factory default is 6-hour delay. 0=6 hours,
1=7 hours, 2=8 hours, 3=9, 4=10, 5=11, and 6=12.
Slave Communicator/Fire Panel Selection (56)
Leaving address 56 at "0" means the MS-5012 is operating as a fire
panel only. Selecting "1" will make it operate as a slave communicator
only. See Section 6, Slave Communicator Configuration. Selecting "2" will make it operate as a Fire panel/communicator.
For Addresses 57 - 67 leave the location programmed at "0" to accept the factory default, or set the location to "1" to change it.
Secondary Phone Number (57) Leaving address 57 at "0" means that reports will be transmitted to the secondary number only if calls to the primary number are unsuccessful. Programming a "1" causes all reports to be transmitted to the secondary number.
15465 Rev F 5/2/97 P/N 15465:F
Alarm Verification on Detector Zones 2 and 3 (58) Factory Default setting for this address is "0" which means no alarm verification.
Entering a "1" enables verification for zone 2 and zone 3. Consult
local Authority Having Jurisdiction (AHJ) prior to altering this address.
Alarm verification works only on zones programmed as 2-wire detector zones. After detecting an alarm, the panel removes power from all zones for 6 seconds, resetting all 2-wire smoke detectors.
Power is reapplied and a 12 second retard period allows detectors to stabilize. During the retard/reset period of 18 seconds, subsequent alarms by the same initiating zone are ignored. An alarm detected on any other 2-wire detector zone during the retard period will cause immediate verified alarms. A subsequent alarm on the initiating zone occurring within the confirmation time will cause a verified alarm.
Note: Mixing devices on zones designated as 2-wire smoke zones is not recommended.
During the alarm verification period, access to other modes of operation is prevented.
Note: Consult local Authority Having Jurisdiction (AHJ) prior to altering addresses 59, 60, 61 and 62.
Silence Inhibit (59) The factory default "0" disables the silence inhibit feature. A "1" selects the following function: Silencing of the
Notification Appliance Circuit and piezo is prohibited for 1 minute.
Auto Silence (60) For address 60, you may leave the default at "0" to allow the Notification Appliance Circuit to remain on until it's reset, or select "1" to automatically silence the Notification Appliance Circuit
after 10 minutes.
Trouble Reminder (61) Factory default "0" disables the trouble reminder feature. Selecting "1" will cause a reminding "beep" every 15 seconds during an alarm (after the silence switch is pressed) and
"beep" every two minutes during a trouble condition. The "beeps" from the on board sounder will occur until the alarm or fault is cleared.
Bell Disable (62) For location 62, choosing default "0" means the
Notification Appliance Circuit is enabled. Setting the address to "1," causes the bell to be disabled during an alarm. Entering a "1" causes the Trouble LED to remain on and bell fault message sent to the
Central Station(s).
15465 Rev F 5/2/97 P/N 15465:F
45
46
Annunciator Present (63) Factory default is "0", no annunciator present. Changing address 63 to a "1" means that an annunciator is in use.
Zone 4 Function Select (64) Zone 4 is factory set at "0" to be a
Supervisory Zone. (Accepts N.O. Supervisory devices) Changing address 64 to "1" allows Zone 4 to accept any N.O. contact device.
Note: When Address 64 is changed to "1", the messages transmitted to the Central Stations must be changed to reflect the new setting. If using 3+1, 4+1 or 4+2 Expanded Formats, Address 71 must be changed to "1" and Address 159 must be changed to "1". If using 4+2
Standard Formats, Address 74 must be changed to "1" and Address 162 must be changed to "1."
Address (65) Not used.
Touchtone/Rotary Select (66) A "0" programmed in this address by the factory triggers Touchtone dialing over both phone lines. Select
"1" for rotary dialing.
Make Break Ratio (67) Use the address only if you have chosen "1" for address 66. The make/break ratio is factory set to "0" which is 67/
33, but may be changed to "1" which is a 62/38 ratio.
Programming Event Codes (68-243)
Tables 4.3-1 to 4.3-4 list messages or "event codes" that are sent to the
Central Station. The selections made for the Primary Number
Communication Format (address 16) and the Secondary Number
Communication Format (address 42) automatically program addresses
68-243 with factory default selections.
Any of the event codes may be changed. Consult your Central Station
prior to altering the event codes. Entering a code of "zero" will cause the communicator to NOT transmit the message. For the 3+1, 4+1 formats or the 4+2 expanded format enter a single zero. For the 4+2 standard format enter two zeros.
Be certain to disable the reports in pairs. The pair should include both the activation of the event and the restoral of the event. For example to disable Zone 1 Fault Code from being transmitted, enter a '0' or '00' for the Fault Code plus a '0' or '00' for the Zone 1 Fault Restoral Code.
The exception to this is for the 24 Hour Test Reports and the
Abnormal Test Reports.
15465 Rev F 5/2/97 P/N 15465:F
End Programming
Exit Programming Mode by pressing w
, followed by the 4-digit code corresponding to an alternate mode of operation, then hit enter/store.
During Program Mode, if no key is pressed within 10 minutes, the panel will revert to normal mode.
Programming the Real-Time Clock
Entering an address greater than 243 will cause a display of the current time. On initial power up, the clock will start running from the factory setting of 00:00 (military time). The far left digit will be flashing, indicating that this will be the first digit to be programmed. Simply enter the correct digits of the current time, followed by enter/store.
15465 Rev F 5/2/97 P/N 15465:F
47
5.0 Servicing
5.1 Walk Test Mode
The MS-5012 provides the capability to perform a one-man walk test of the system without triggering the communicator or the alarm output relay driver. Walk Test allows for testing of the five zones (initiating circuits). The first initiating device activated on a zone will cause the
Notification Appliance (bell) Circuit to turn on for four seconds.
Subsequent device activations on the same zone will cause the NAC to turn on for one second. Any smoke detectors that are activated will be reset. Zonal faults (open circuits) will cause the NAC to remain steadily on. Prior to entering Walk Test Mode, check to be certain that all system faults have been cleared. Note: The trouble relay will be
activated while the control panel is in this mode. Placing the control panel into walk test mode will only be possible if the system has no active alarms.
Pressing the Mode key followed by the 4-digit code
9255
[ENTER/STORE]
will place the control panel into Walk Test Mode.
☛
9255 spells "WALK" on a Touch-Tone® phone.
Once in Walk Test Mode, the MS-5012 will immediately:
✔ Turn on the trouble LED.
✔ Activate/energize the trouble relay driver.
✔ Turn on the Notification Appliance Circuit output for four
seconds for the first alarm event on a zone. Subsequent alarms will sound for one second. Troubles cause the IAC to remain on.
✔ Disable the alarm relay.
✔ Display all alarm, conditions as they occur.
✔ Display ground faults as they occur.
✔ Continue to communicate any events not yet acknowledged at
the Central Station.
During Walk Test Mode, zonal activity is displayed in real time as it occurs. At the end of Walk Testing the system, the display will show the last event that occurred. To view all events stored during Walk
Test, use the up arrow, down arrow and 1st Event keys. The down arrow key moves the Walk Test list to show older - previous events.
The up arrow key moves the Walk Test list to show newer - most recent events. Pressing the 1st Event key at any time will cause the display of the first event stored upon initial entry into Walk Test
Mode. While in Walk Test Mode, the control panel will store up to 128 events in the Walk Test File for later recall and display.
48
15465 Rev F 5/2/97 P/N 15465:F
To return the MS-5012 to normal mode, press the mode key, the numbers
6676 and the
ENTER/STORE
key. Any delay between key entries greater than 10 seconds causes the control panel to remain in Walk Test Mode.
The control panel will automatically revert back to Normal Mode if no system activity has occurred for 60 minutes. This would include pressing any keys or activity on any zone. Exiting Walk Test mode erases the Walk Test file from memory.
5.2 History Mode
All Normal Mode events are stored in a History File list for future recall. Recall is possible via the 4-character display. See the following page for a list and description of each event displayed.
The History File list is a first-in first-out (FIFO). In this manner, only the most recent events may be called up from memory. Old events will be overwritten i.e., “pushed out” of the FIFO.
The number of stored events is 16. The History File is kept in E2 memory. Complete power loss will not erase the list.
Pressing the w
key followed by
4478
[ENTER/STORE] places the control panel into History Mode. This will not occur if there
are any active alarm conditions present. The event displayed, is the most recent event.
☛
4478 spells "HIST" on a Touch-Tone® phone.
Once in History Mode, the control panel will:
✔ Turn on the trouble LED.
✔ Energize/activate the trouble relay driver.
✔ Disable the Notification Appliance Circuit output.
✔ Disable the alarm relay driver.
✔ Display all events as they occurred since the last time the Histo-
ry File list was cleared. The most recent event will be displayed first.
✔ Ignore all other keys other than those mentioned in this section.
✔ Continue to communicate any events not yet acknowledged at
the Central Station.
The down arrow key moves the History File to show older-previous events. The up arrow key moves the History file to show newer-most recent events.
15465 Rev F 5/2/97 P/N 15465:F
49
50
Shown below is the list of messages as they will appear on the display:
DISPLAY EVENT
A 1
Zone 1 Alarm
A 2
Zone 2 Alarm
A 3
Zone 3 Alarm
A 4
Zone 4 Alarm
A 5
Zone 5 Alarm
5uP4
Supervisory Alarm
AC
AC Loss
F 1
Zone 1 Fault
F 2
Zone 2 Fault
F 3
Zone 3 Fault
F 4
Zone 4 Fault
F 5
Zone 5 Fault bELL
Bell Fault (open or short)
F E
Earth Fault
F A
Annunciator Fault no 1
Primary Phone Line Fault no 2
Secondary Phone Line Fault rES
Reset Switch pressed
PH 1
Primary Number Communication Fault
PH 2
Secondary Number Communication Fault no b
No Battery
Lo b
Low Battery
51LE
Silence Switch pressed
To erase the list, press the Silence key twice before exiting the History Mode. A lack of keyboard activity for a period of 10 minutes will cause the control panel to return to normal mode.
15465 Rev F 5/2/97 P/N 15465:F
5.3 Troubleshoot
Mode
In this mode, the voltage of the input zones, AC voltage and battery voltage will be displayed on the 4-character display. The internal voltmeter reads the voltage present at: (1) the zone inputs, (2) the AC power input and (3) the battery terminal leads. A lack of keyboard activity for a period of 20 minutes will cause the control panel to return to normal mode.
To get into the Troubleshoot Mode, press w 8768 and
ENTER/STORE.
☛
8768 spells "TROU" on a Touch-Tone®
phone.
Once in this mode, the MS-5012 will:
✔ Turn on the trouble LED.
✔ Energize/activate the trouble relay driver.
✔ Disable the Notification Appliance Circuit output.
✔ Disable the alarm relay driver.
✔ Continue to communicate any events not yet acknowledged
at the Central Station.
Pressing a
[ENTER/STORE] displays the AC input voltage
.
Pressing b
[ENTER STORE] will display the Battery Voltage. Pressing
1 through
5 followed by
[ENTER/STORE]
displays the zone voltage of the selected zone. The
q r
and s keys do not function in this mode.
Below is listed the “nominal threshold voltages” for each zone:
Zone # Normal w/E.O.L.
Shorted Open CKT.
1
2
3
4
5
5.15V
11.75V
11.75V
5.15V
5.15V
0.15V
8.7V
8.7V
.15V
.15V
12.9V
12.9V
12.9V
12.9V
12.9V
Readings will vary proportionately depending upon system load and AC line voltage. Listed below is the AC line voltage range. The AC ON indicator will turn off when the AC line voltage drops below the Low
Line “threshold,” and the trouble LED will turn on.
Low Line Normal
AC Line Voltage: 102VAC 115VAC
High Line
132VAC
Below is shown the critical battery threshold conditions:
Normal Low Battery
Battery Voltage: 13.7V
10.2V
Note: Make measurements after allowing 48 hours to charge a depleted battery.
If battery does not show normal reading, replace it.
15465 Rev F 5/2/97 P/N 15465:F
51
Pressing
c
[ENTER/STORE]
causes seizure of the Primary line and the red LED signifying Primary line active turns on. After a delay of three seconds, the control panel goes off hook to acquire a dial tone. Connecting a telephone handset across the telephone transformer allows number dialing. See figure 5.3-1. Pressing
c
[ENTER/STORE] a second time hangs up the call. Repeated entries of
c places the phone on and off
hook.
5.4 Lamp Test
To perform a Lamp Test, press Mode then
5267 followed by
[ENTER/STORE]
. This will test all system LEDs except the Primary
Active LED and Secondary Active LED. The LEDs will stay on for five seconds, then the control panel will return to normal mode.
☛
5267 spells "LAMP" on a Touch-Tone® phone.
Figure 5.3-1: Handset Connection
Tip (green)
Ring (red)
Carefully
Connect Here
52
15465 Rev F 5/2/97 P/N 15465:F
Programming Reference Sheet
--- To enter Programming, press Mode: 7 7 6 4, Enter
❑
00
❑
01
❑
02
❑
03
❑
04
❑
05
❑
06
❑
07
❑
08
❑
09
❑
10
❑
11
❑
12
❑
13
❑
14
❑
15
Addresses 00 to 15 store the Primary Phone Number. Enter "F" to represent the end of the number.
❑
16
Primary Comm Format: Enter 0 - F.
❑
17
❑
18
❑
19
❑
20
Primary Account Code: Valid keys are 0-F.
❑
21
❑
22
❑
23
❑
24
Primary 24-Hour Test Time. Enter military time (i.e. 1400 for 2 PM)
❑
25
Primary 24/12 Hour Test Time. Enter "1" for 12 hour; "0" for 24 hour.
❑
26
❑
27
❑
28
❑
29
❑
30
❑
31
❑
32
❑
33
❑
34
❑
35
❑
36
❑
37
❑
38
❑
39
❑
40
❑
41
Addresses 26-41 store the Secondary Phone Number. Enter "F" to represent the end of the number.
❑
42
Secondary Comm Format: Enter 0-F.
❑
43
❑
44
❑
45
❑
46
Secondary Account Code: Valid keys are 0-F.
❑
47
❑
48
❑
49
❑
50
Secondary 24-Hour Test Time. Enter military time (i.e. 1400 for 2 pm)
❑
51
Secondary 24/12 Hour Test Time. Enter "1" for 12 hour; "0" for 24 hour.
❑
52
Zone 3 Function Select (0 = Waterflow, 1 = N.O. contact devices, 2 = 2-Wire detectors)
❑
53
❑
54
Waterflow Reporting Delays. Valid keys for field 53 are 0-8, and 0-9 for field 54.
❑
55
AC Loss. Enter number of hours to delay reporting of AC loss. (0=6 hours, 1=7 hours ...6=12 hours)
❑
56
Slave Comm Selection.
"0" for panel only; set to "1" for slave operation; "2" for fire control/comm operation
❑
57
Secondary Phone Number. Enter "0" for secondary as a backup; "1" to transmit always.
❑
58
Alarm Verify. Enter "0" for no verification; "1" for verification.
❑
59
Silence Inhibit.
Enter "0" to disable silence inhibit; "1" to enable.
❑
60
Auto Silence. Enter "1" to silence notification appliances 10 minutes after activation.
❑
61
Trouble Reminder. Enter "1" to enable reminder beep (alarm-every 15 seconds; trouble-every 2 minutes.)
❑
62
Bell Disable. Enter "1" to disable the panels Notification Appliance Circuit.
❑
63
Annunciator Present. Enter "1" if an annunciator is wired to the system.
❑
64
Zone 4 Function Select.
Enter "0" for supervisory service; "1" for N.O. contact devices.
❑
65
Not used.
❑
66
Touchtone Rotary Select. Enter "0" for touchtone dialing, "1" for rotary.
❑
67
Make Break Ratio. Enter "0" for 67/33 make/break ratio; "1" for 62/138.
15465 Rev F 5/2/97 P/N 15465:F
53
❑
❑
68
81
❑
❑
69
82
❑
❑
70
83
❑
96
❑
71
❑
❑
84
97
Programming Reference Sheet
❑
72
❑
73
❑
74
❑
75
❑
76
❑
77
❑
85
❑
86
❑
87
❑
88
❑
89
❑
90
❑
78
❑
91
❑
❑
79
92
❑
❑
80
93
❑
98
❑
99
❑
100
❑
101
❑
102
❑
103
❑
104
❑
105
❑
106
❑
94
❑
95
❑
107
❑
108
❑
109
❑
110
❑
111
❑
112
❑
113
❑
114
❑
115
❑
116
❑
117
❑
118
❑
119
❑
120
❑
121
❑
122
❑
123
❑
124
❑
125
❑
126
❑
127
❑
128
❑
129
❑
130
❑
131
❑
132
❑
133
❑
134
❑
135
❑
136
❑
137
❑
138
❑
139
❑
140
❑
141
❑
142
❑
143
❑
144
❑
145
❑
146
❑
147
❑
148
❑
149
❑
150
❑
151
❑
152
❑
153
❑
154
❑
155
❑
156
❑
157
❑
158
❑
159
❑
160
❑
161
❑
162
❑
163
❑
164
❑
165
❑
166
❑
167
❑
168
❑
169
❑
170
❑
171
❑
172
❑
173
❑
174
❑
175
❑
176
❑
177
❑
178
❑
179
❑
180
❑
181
❑
182
❑
183
❑
184
❑
185
❑
186
❑
187
❑
188
❑
189
❑
190
❑
191
❑
192
❑
193
❑
194
❑
195
❑
196
❑
197
❑
198
❑
199
❑
200
❑
201
❑
202
❑
203
❑
204
❑
205
❑
206
❑
207
❑
208
❑
209
❑
210
❑
211
❑
212
❑
213
❑
214
❑
215
❑
216
❑
217
❑
218
❑
219
❑
220
❑
221
❑
222
❑
223
❑
224
❑
225
❑
226
❑
227
❑
228
❑
229
❑
230
❑
231
❑
232
❑
233
❑
234
❑
235
❑
236
❑
237
❑
238
❑
239
❑
240
❑
241
❑
242
❑
243
54
15465 Rev F 5/2/97 P/N 15465:F
Programming Reference Sheet
Factory Default Settings
--- To enter Programming, press Mode: 7 7 6 4, Enter.
❑
00
❑
01
❑
02
❑
03
❑
04
❑
05
❑
06
❑
07
❑
08
❑
09
❑
10
❑
11
❑
12
❑
13
❑
14
❑
15
Addresses 00 to 15 store the Primary Phone Number. Enter "F" to represent the end of the number.
❑
16
Primary Comm Format:(4+2 Standard 1800/2300)
❑
17
❑
18
❑
19
❑
20
Primary Account Code.
❑
21
❑
22
❑
23
❑
24
Primary 24-Hour Test Time. 0000=12:00 midnight.
25
Primary 24/12 Hour Test Time. "0" for 24 hour.
❑
26
❑
27
❑
28
❑
29
❑
30
❑
31
❑
32
❑
33
❑
34
❑
35
❑
36
❑
37
❑
38
❑
39
❑
40
❑
41
Addresses 26-41 store the Secondary Phone Number. Enter "F" to represent the end of the number.
❑
42
Secondary Comm Format (4+2 Standard 1800/2300)
❑
43
❑
44
❑
45
❑
46
Secondary Account Code
❑
47
❑
48
❑
49
❑
50
Secondary 24-Hour Test Time
51
Secondary 24/12 Hour Test Time. "0" for 24 hours.
❑
52
Zone 3 Function Select. 0 = Waterflow
❑
53 54
Waterflow Reporting Delays. No delay.
55
AC Loss. 6 hours.
56
Slave Comm Selection.
"0" for panel only operation.
57
Secondary Phone Number. "0" secondary as a backup.
58
Alarm Verify.
"0" no verification.
❑
59
Silence Inhibit.
"0" disable silence inhibit.
60
Auto Silence.
"0" disable auto silence.
61
Trouble Reminder. "0" disable trouble reminder.
62
Bell Disable. "0" Bell enabled.
63
Annunciator Present.
"0" no annunciator.
64
Zone 4 Function Select. "0" supervisory service.
65
Not used.
❑
66
Touchtone Rotary Select. "0" touchtone dialing.
67
Make Break Ratio.
15465 Rev F 5/2/97 P/N 15465:F
55
Programming Reference Sheet
(Factory Default Settings)
❑
68
❑
81
❑
69
❑
82
❑
70
❑
83
❑
71
❑
84
❑
72
❑
85
❑
73
❑
86
❑
74
❑
87
❑
75
❑
88
❑
76
❑
89
❑
77
❑
90
❑
78
❑
91
❑
79
❑
92
❑
80
❑
93
❑
94
❑
95
❑
96
❑
97
❑
98
❑
99
❑
100
❑
101
❑
102
❑
103
❑
104
❑
105
❑
106
❑
107
❑
108
❑
109
❑
110
❑
111
❑
112
❑
113
❑
114
❑
115
❑
116
❑
117
❑
118
❑
119
❑
120
❑
121
❑
122
❑
123
❑
124
❑
125
❑
126
❑
127
❑
128
❑
129
❑
130
❑
131
❑
132
❑
133
❑
134
❑
135
❑
136
❑
137
❑
138
❑
139
❑
140
❑
141
❑
142
❑
143
❑
144
❑
145
❑
146
❑
147
❑
148
❑
149
❑
150
❑
151
❑
152
❑
153
❑
154
❑
155
❑
156
❑
157
❑
158
2
❑
159
❑
160
❑
161
❑
162
❑
163
❑
164
❑
165
❑
166
❑
167
❑
168
❑
169
❑
170
❑
171
❑
172
❑
173
❑
174
❑
175
❑
176
❑
177
❑
178
❑
179
❑
180
❑
181
❑
182
❑
183
❑
184
❑
185
❑
186
❑
187
❑
188
❑
189
❑
190
❑
191
❑
192
❑
193
❑
194
❑
195
❑
196
❑
197
❑
198
❑
199
❑
200
❑
201
❑
202
❑
203
❑
204
❑
205
❑
206
❑
207
❑
208
❑
209
❑
210
❑
211
❑
212
❑
213
❑
214
❑
215
❑
216
❑
217
❑
218
❑
219
❑
220
❑
221
❑
222
❑
223
❑
224
❑
225
❑
226
❑
227
❑
228
❑
229
❑
230
❑
231
❑
232
❑
233
❑
234
❑
235
❑
236
❑
237
❑
238
❑
239
❑
240
❑
241
❑
242
❑
243
56
15465 Rev F 5/2/97 P/N 15465:F
6.0 Slave Communicator Configuration
The MS-5012 may be used as a slave communicator to a host or "Master" fire alarm control panel (FACP). Figure 6.0-1 shows a typical connection.
All wiring between the Master and the MS-5012 is supervised. 2.2K End-
Of-Line resistors should be connected as shown in Figure 6.0-1.
In slave configuration, the five zones become five channels that may be triggered by the relay outputs of any host FACP. Zone 1/Channel 1 is used for general alarm, Zone 2/Channel 2 is used for general trouble and Zone
4/Channel 4 is used for supervisory. Zones/Channels 3 and 5 may be programmed to match the FACP relay function.
The factory settings for Zone 2/Channel 2 activation and restoral are altered as follows: If 2, 3, 4, 5, 6, 7, 8, 9, B or D is entered for address 16 or 42, the report code for Zone 2 Alarm Code (address 69, 157) = F, Zone
2 Restoral Code (address 90, 178) = E. If "A or C" are entered for address
16 or 42, the report code for Zone 2 Alarm Code (addresses 70-71, 158-
159) = FF, Zone 2 restoral code (addresses 112-113, 200-201) = EF.
It is important to note that activation of Zone 2 in Slave Communicator
Configuration will cause the yellow trouble LED to flash and the trouble sounder to pulse, however, the red alarm LED will not activate and the
notification appliances will not sound.
Location 56 must be programmed to a '1' to enable the control panel as a slave communicator. When programming the MS-5012 as a slave communicator (address 56=1), first program the communication formats
(addresses 16 and 42) followed by the slave communicator selection at address 56. This sequence allows the MS-5012 to automatically program the proper report codes. Do not program location 56 first and then alter the format selections at addresses 16 and 42.
If any of the report codes are to be altered from the factory defaults, follow the steps above and exit program mode. Next reenter program mode and alter any event codes.
After programming is complete, the enter/store key or the up, down arrow keys may be used to view programmed entries. However, do not use the enter key to view location 56 since it will reprogram the factory default event codes.
Be certain to connect the MS-5012 primary AC power to the same branch circuit as the host FACP.
57
15465 Rev F 5/2/97 P/N 15465:F
Battery Connection
The MS-5012 contains a battery disconnect relay which has multiple purposes. The primary purpose is to disconnect the battery when the battery voltage is less than 7.0 volts during an AC loss condition. This prevents the MS-5012 from transmitting erroneous data to a Central
Station under unsafe operating power. Also, with AC power applied, the disconnect relay allows for battery voltage measurements in the normal and troubleshoot modes.
Due to the presence of the disconnect relay, it is not possible to initially (out of the box) power up an MS-5012 from the battery. AC power must first be applied for 6 seconds. Once AC power is applied, do not connect a low capacity battery (less than 7.0 volts) to the system.
When replacing a bad battery, turn off AC power before connecting the new battery.
6.0-1: Slave Communicator Connections
Inputs are supervised and power limited
Relays in the Master FACP activate various input circuits on the MS-5012. Messages (event codes) programmed for a particular input circuit (channel) will be transmitted to the central station upon relay activation.
58
15465 Rev F 5/2/97 P/N 15465:F
Appendix A: Power Calculations
Use the Total Standby and Alarm Load Currents calculated in Tables A-1 and A-2 for the following battery calculation.
Standby Load Current
(Amps)
[ ]
X
Required Standby Time in Hours (24 or 60
Hours)
[ ]
= ___________
Alarm Load Current (Amps)
[ ]
X
Required Alarm Time in Hours (i.e. 5 min. =
0.084 hours)
[ ]
= ___________
Add Standby and Alarm Load for Required Ampere Hour Battery
Multiply by the Derating Factor of 1.2
Total Ampere Hours (AH) Required
= ___________
= ___________
= ___________
Select a battery with a greater amp/hour rating.
Notes: * NFPA 72-1993 Central Station, Local and Proprietary Protected Premises systems require 24 hours of standby.
* NFPA 72-1993 Auxiliary and Remote Station systems require 60 hours of standby.
15465 Rev F 5/2/97 P/N 15465:F
59
The MS-5012 provides regulated power for operating the fire alarm control panel, operating external devices, and operating the standby battery. The power for operating external devices is limited. Use Table A-1 (standby or nonalarm) and Table A-2 (alarm) to determine if external loading is within the capabilities of the power supply.
Table A-1: Regulated Load in Standby
@12 VDC
Device Type
Main Circuit Board
ADM-12
RZA-5F
2-wire Detector Heads
4-wire Detector Heads
Power Supervision
Relays
2
Auxiliary Outputs:
TB3-4 Alarm
TB3-5 Trouble
TB3-6 Supervisory
TB3-7 Comm. Fail
Additional Current
Draw from TB-3
(non alarm)
# of Devices
1
(1 max.)
(1 max.)
[ ]
[ ]
[ ]
.
(1 max.)
(1 max.)
(1 max.)
(1 max.)
X
X
X
X
X
X
.
X
X
X
X
Current
(Amps)
0.074
0.012
0.012
[ ]
[ ]
0.025
.
0
0.040
1
0
0
=
=
=
=
.
=
=
=
=
=
=
Total Current
(Amps)
0.074
=
Sum Column for Standby Load
= Amps
Note:
1. Current draw only if End-of-Line relay is installed between TB3-3 and TB3-5. Current shown is maximum
available from TB3 Terminal 5.
2. Use compatible listed power supervision relay only.
3. Refer to Device Compatibility Document for 2-wire smoke detector standby current.
60
15465 Rev F 5/2/97 P/N 15465:F
Table A-2: Regulated Load in Alarm
@12 VDC
Device Type
Main Circuit Board
ADM-12
RZA-5F
4-wire Smoke Detector
Power Supervision
2
Relay
Auxiliary Outputs:
TB3-4 Alarm
TB3-5 Trouble
TB3-6 Supervisory
TB3-7 Comm. Fail
# of Devices
1
(1 max.)
(1 max.)
[ ]
[ ]
.
(1 max.)
(1 max.)
(1 max.)
(1 max.)
X
.
X
X
X
X
X
X
X
X
Notification Appliances [ ] X
0.025
.
0.040
0.040
0
0
_____
Current
(Amps)
0.170
0.032
1
0.030
1
[ ]
=
.
=
=
=
=
=
=
=
=
Total Current
(Amps)
0.170
=
Notification Appliances
Additional Current
Draw from TB-3 (alarm current)
[ ] X _____ =
=
Sum Column for Alarm Load
= Amps
Note:
1. Current shown is with all LEDs illuminated.
2. Use compatible listed power supervision relay only.
15465 Rev F 5/2/97 P/N 15465:F
61
Index
A
ADM-12 Annunciator Driver Module 10, 33, 34
C
Circuits 8, 11
Clock 45
D
Digital Communicator 9, 20, 31
Displays 8, 15, 35
F
Factory Default Settings 54, 55
Features 7
H
History Mode 48
I
Initiating Device Circuits 27
K
Kissoff 24
L
Lamp Test 51
M
Messages 49
Mounting Options 25
O
Optional Boards 10
P
Power Calculations 58
Primary Phone number 36
Programming Mode 35
R
Relays 29
Remote Annunciator 10, 33, 34
S
Secondary Phone Number 40, 43
Slave Communicator Configuration 56
Switches 8, 14, 36
1st Event 15
Enter/Store 15
Mode Switch 15
Silence Switch 15
T
Troubleshoot Mode 50
W
Walk Test Mode 47
Wiring Jacks 31
62
15465 Rev F 5/2/97 P/N 15465:F
15465 Rev F 5/2/97 P/N 15465:F
63
Technical Publishing
Limited Warranty
Fire-Lite ®
warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service.
Products are date stamped at time of manufacture. The sole and exclusive obligation of Fire-Lite
®
is to repair or replace, at its option, free of charge for parts and labor, any part which is defective in materials or workmanship under normal use and service.
For products not under Fire-Lite
®
manufacturing date-stamp control, the warranty is eighteen (18) months from date of original purchase by Fire-Lite
®
's distributor unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply. This warranty is void if the product is altered, repaired or serviced by anyone other than Fire-Lite
®
or its authorized distributors or if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our customer service department. Return product, transportation prepaid, to
Fire-Lite ®
, 12 Clintonville Road, Northford, Connecticut 06472-1653.
This writing constitutes the only warranty made by Fire-Lite
®
with respect to its products. Fire-Lite
®
does not represent that its products will prevent any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that Fire-Lite
®
is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse, abuse, accident or similar incident.
Fire-Lite ®
GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR
OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE
HEREOF. UNDER NO CIRCUMSTANCES SHALL Fire-Lite
®
BE LIABLE FOR ANY
LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR
CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE
Fire-Lite ®
PRODUCTS. FURTHERMORE, Fire-Lite
®
SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF,
OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS
PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by Fire-
Lite ®
. No increase or alteration, written or verbal, of the obligation of this warranty is authorized.
"Fire-Lite" is a registered trademark.
12 Clintonville Road, Northford, CT 06472
Phone: (203) 484-7161
FAX: (203) 484-7118
Document WARFBG-C.PM6 04/02/96

Download
Key features
5 zone fire alarm panel
Digital communicator
Waterflow, smoke, pull station support
Telephone line supervision
Event history storage
Supervisory zone
Programmable zone ID
Annunciator module support
Remote annunciator support
UL listed
Frequently asked questions
The MS-5012 panel has 5 zones.
The MS-5012 panel accepts waterflow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally open contact devices.
The digital communicator transmits system status (alarms, troubles, AC loss, etc.) to a UL recognized Central Station via the public switched telephone network.
Yes, the MS-5012 panel supports the RZA-5F Remote Annunciator module.
Yes, the MS-5012 panel is UL listed.