KSBS ANALOG SUBTRACTOR INSTALLATION BEFORE USE ....


Add to my manuals
3 Pages

advertisement

KSBS ANALOG SUBTRACTOR INSTALLATION BEFORE USE .... | Manualzz

KSBS

INSTRUCTION MANUAL

ANALOG SUBTRACTOR

BEFORE USE ....

Thank you for choosing M-System. Before use, check the package you received as below.

If you have any problems or questions with the product, please contact M-System's Sales Office or representatives.

■ PACKAGE INCLUDES:

Signal conditioner (body + base socket) ................. (1)

Input resistors ......................................................... (2)

The resistors are provided only with current input type.

■ MODEL NO.

Check that model No. described on specification label is exactly what you ordered.

■ INSTRUCTION MANUAL

This manual describes necessary points of caution when you use this product, installation, connection and basic maintenance procedures.

MODEL

KSBS

INSTALLATION

Detach the yellow clamps located at the top and bottom of the unit for separating the body from the base socket.

■ DIN RAIL MOUNTING

Set the base socket so that its

DIN rail adaptor is at the bottom. Position the upper hook at the rear side of base socket on the DIN rail and push in the lower. When removing the socket, push down the DIN rail adaptor utilizing a screwdriver (–) and pull.

Clamp

(top & bottom)

DIN Rail

35mm wide

Spring Loaded

DIN Rail Adaptor

■ WALL MOUNTING

Refer to the drawings in the following page.

Shape and size of the base socket are slightly different with various socket types.

COMPONENT IDENTIFICATION

Base Socket Body

Specification

Label

Input Resistor

Zero Adj.

Span Adj.

K -UNIT

P. 1 / 3 EM-3639

KSBS

TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the connection diagram label on top of the unit.

When input resistors are provided with the module, attach them together with input wiring to the input screw terminals.

■ DIMENSIONS

CLAMP

(top & bottom)

7.8 (.31)

DIN RAIL

35mm wide

6 5 4 3

50 (1.97)

■ CONNECTION DIAGRAM

INPUT 1

INPUT 2

+

R

*

3

4

+

R

*

5

6

1 +

2 –

7 U(+)

8 V(–)

OUTPUT

POWER

* Input shunt resistor attached for current input.

103 (4.06)

123 (4.84)

2–4.5 (.18) dia.

MTG HOLE

15 (.59) deep

8–M3.5

SCREW

7 8 1 2

40 (1.57)

50 (1.97) [3.3 (.13)]

•When mounting, no extra space is needed between units.

■ TERMINAL ASSIGNMENTS

INPUT RESISTOR

(model: REM)

6 5 4 3

7 8 1 2

Input shunt resistor attached for current input.

P. 2 / 3 EM-3639

CHECKING

1) Terminal wiring: Check that all cables are correctly connected according to the connection diagram.

2) Power input voltage: Check voltage across the terminal 7

– 8 with a multimeter.

3) Input: Check that the input signal is within 0 – 100% of the full-scale.

4) Output: Check that the load resistance meets the described specifications.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered specifications, therefore you usually do not need any calibration.

For matching the signal to a receiving instrument or in case of regular calibration, adjust the output as explained in the following.

■ HOW TO CALIBRATE THE DC OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient accuracy level. Turn the power supply on and warm up for more than 10 minutes.

1) ZERO: Apply the input signals which should lead the calculated result as 0%, and adjust output to 0%.

2) SPAM: Apply the input signals which should lead the calculated result as 100%, and adjust output to 100%.

3) Check ZERO adjustment again.

4) When ZERO value is changed, repeat the above procedure

1) – 3).

EQUATION

Output = K

1

×

Input 1 – K

2

×

Input 2

(K

1

×

Input 1 > K

2

×

Input 2)

K

1

, K

2

: 0.10 – 2.00 (parameters)

Output, Input 1

×

K

1

, Input 2

×

K

2

: 0 – 100%

K

1

, K

2

are ex-factory specified.

KSBS

POINTS OF CAUTION

■ GENERAL

• Before you remove the unit from its base socket or mount it, turn off the power supply and input signal for safety.

■ ENVIRONMENT

• When heavy dust or metal particles are present in the air, install the unit inside proper housing and ventilate it.

• Do not install the unit where it is subjected to continuous vibration. Do not apply physical impact to the unit.

• Environmental temperature must be within -5 to +60

°

C (23 to 140

°

F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation.

■ WIRING

• Do not install cables (power supply, input and output) close to noise sources (relay drive cable, high frequency line, etc.).

• Do not bind these cables together with those in which noises are present. Do not install them in the same duct.

■ AND ....

• The unit is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.

MAINTENANCE

Regular calibration procedure is explained below:

■ CALIBRATION

Warm up the unit for at least 10 minutes. Apply the input signals which should lead the calculated results as 0%, 25%,

50%, 75% and 100%. Check that the output signal for the respective input signal remains within accuracy described in the data sheet.

When the output is out of tolerance, recalibrate the unit according to the "ADJUSTMENT PROCEDURE" explained earlier.

M-SYSTEM WARRANTY

M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies, under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.

THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED

WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR

SPECIAL DAMAGES OF ANY KIND WHATSOEVER.

M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]

P. 3 / 3 EM-3639

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement