Specification Sheet F32T8 Instant Start Parallel Lamp Operation Project: Catalog#:

Specification Sheet F32T8 Instant Start Parallel Lamp Operation Project: Catalog#:
EPH4/32IS/MV/SC/HE
Specification Sheet
Electronic Fluorescent Ballast
7/21/2014
Project:
4 Lamp
High Ballast Factor High Efficiency
Multi-volt
High Efficiency
Catalog#:
Approved by:
F32T8 Instant Start Parallel Lamp Operation
Lamp Type
No. Of
Lamps
Lamp
Watts
Line
Voltage
Ballast
Factor
Input
Watts
Input
Current
(amps)
Power
Factor
THD
Ballast
Efficacy
Factor
4
4
3
3
4
4
3
3
4
4
3
3
4
4
3
3
4
4
3
3
4
4
3
3
3
3
4
4
3
3
4
4
3
3
4
4
3
3
32
32
32
32
30
30
30
30
28
28
28
28
25
25
25
25
25
25
25
25
17
17
17
17
40
40
32
32
32
32
31
31
31
31
28
28
28
28
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
120
277
1.16
1.16
1.24
1.24
1.16
1.16
1.24
1.24
1.16
1.16
1.24
1.24
1.16
1.16
1.24
1.24
1.17
1.17
1.26
1.26
1.18
1.18
1.27
1.27
1.25
1.25
1.16
1.16
1.24
1.24
1.16
1.16
1.24
1.24
1.16
1.16
1.24
1.24
145
144
120
120
120
120
105
101
116
115
95
98
108
109
92
93
109
109
89
87
75
79
62
66
143
139
145
144
120
120
137
134
113
109
124
128
103
104
1.24
0.53
1.01
0.44
1.01
0.44
0.88
0.37
0.98
0.42
0.80
0.36
0.91
0.40
0.77
0.34
0.92
0.40
0.75
0.32
0.63
0.29
0.52
0.24
1.22
0.51
1.24
0.53
1.01
0.44
1.15
0.49
0.95
0.40
1.05
0.47
0.87
0.38
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.97
0.98
0.97
0.98
0.95
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
<10%
0.80
0.81
1.03
1.03
0.97
0.97
1.18
1.23
1.00
1.01
1.31
1.27
1.07
1.06
1.35
1.33
1.07
1.07
1.42
1.45
1.57
1.49
2.05
1.92
0.87
0.90
0.80
0.81
1.03
1.03
0.85
0.87
1.10
1.14
0.94
0.91
1.20
1.19
F32T8*
F32T8/ES/30
F32T8/ES/28
F32T8/ES/25
F25T8
F17T8
F40T8
FB32T8
FB31T8
FB28T8
* Primary Lamp Design
Ballast Specifications
• Ballast shall have a five-year warranty
• Ballast shall be UL & cUL
• Ballast shall be sound rated Class A
• Ballast shall be Class P Type 1 Outdoor
• Ballast shall have a Lamp Current Crest Factor of <1.7
• Ballast shall withstand line transients as specified in ANSI C62.41-2002 & C82.11-2002
• Ballast shall comply with the limits of FCC Part 18 Class A
• Ballast shall have a lamp operating frequency greater than 40kHz
• Ballast shall have a 0oF/18oC minimum lamp starting temperature for primary lamp
• Ballast shall be Instant Start
• Ballast shall be Parallel Lamp Operation
• Ballast shall have minimum Power Factor of 98% for primary Lamp operation
• Ballast shall operate within +/- 10% of the ballast specified line voltage at 60 Hz
• Ballast shall have a maximum case hot spot temperature of 167oF/75oC
Wiring Diagram
BLACK
WHITE
YELLOW
YELLOW
BALLAST
Dimensions
BLUE
BLUE
RED
RED
LAMP
LAMP
L: 9.5”
W: 1.7”
H: 1.2”
M: 8.9”
LAMP
LAMP
For 3-lamp operation cap one blue lead. Insulate to 600 volts
Side Ballast View
Bottom Ballast View
H
W
• Specifications are subject to change without notice.
Howard Lighting Products | 580 Eastview Drive | Laurel, MS 39443
(toll free) 800.956.3456 | (direct) 601.422.0033 | (fax) 601.422.1652
www.HowardLightingProducts.com
0.31
M
L
W
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement