Lochinvar Copper-Fin II 402-2072, CHN0402, CHN0502, CHN0652, CHN0752, CHN0992, CHN1262, CHN1442, CHN1802, CHN2072 gas boiler Submittal Sheet

Lochinvar Copper-Fin II 402-2072, CHN0402, CHN0502, CHN0652, CHN0752, CHN0992, CHN1262, CHN1442, CHN1802, CHN2072 gas boiler Submittal Sheet

Below you will find brief information for gas boiler Copper-Fin II CHN0402, gas boiler Copper-Fin II CHN0502, gas boiler Copper-Fin II CHN0652, gas boiler Copper-Fin II CHN0752, gas boiler Copper-Fin II CHN0992, gas boiler Copper-Fin II CHN1262, gas boiler Copper-Fin II CHN1442, gas boiler Copper-Fin II CHN1802, gas boiler Copper-Fin II CHN2072. This gas boiler series operates with up to 85% thermal efficiency and its SMART SYSTEMâ„¢ operating control is equipped with a cascade sequencer for up to 8 boilers and front-end capability with Crest or Knight boilers.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Lochinvar Copper-Fin II CHN0402, CHN0502, CHN0652, CHN0752, CHN0992, CHN1262, CHN1442, CHN1802, CHN2072 Submittal Sheet | Manualzz
COPPER-FIN II®
BOILER
Submittal Sheet
CHE-Sub-10b
COPPER-FIN II® GAS BOILER (MODELS 402-2072)
JOB NAME ______________________________________________________________________
LOCATION ______________________________________________________________________
ENGINEER_______________________________________________________________________
MECH. CONTRACTOR ___________________________________________________________
MODEL NO. _____________________________________________________________________
TYPE GAS ______________________________________________________________________
Btu/hr INPUT___________________________Btu/hr OUTPUT___________________________
NOTES
Standard Features
> 85% Thermal Efficiency (AHRI Certified)
> Proportional Firing up to 4:1 Turndown
> Hot Surface Ignition
> Low NOx Operation
> Sealed Combustion
> Low Gas Pressure Operation
> Vertical & Horizontal Venting
> Category I Venting
> Double Wall “B” Vent Material
> Category IV Venting
> AL29-4C Stainless Steel Vent Material
> ASME Copper Finned Tube Heat Exchanger
> ASME Certified, “H” Stamped
> Gasketless design
> 160 psi working pressure
> On/Off Switch
> Combustible Floor Rated (CH 0992 - 2072)
> Adjustable High Limit w/ Manual Reset
> Flow Switch
> Low Air Pressure Switch
> Inlet & Outlet Temperature Sensors
> Easy Access Terminal Strips
> Downstream Test Cocks
> 50 psi ASME Relief Valve
> Temperature & Pressure Gauge
> 1 Year Warranty on Parts (See Warranty for Details)
> 10 Year Limited Warranty (See Warranty for Details)
Optional Equipment
> Alarm
> High & Low Gas Pressure Switches w/ Manual Reset
> Cupro-Nickel Heat Exchanger
> Low Water Cut Off, Probe Type w/ Manual Reset & Test
> Modbus Communications
> BMS Gateway - BACnet or LonWorks
> Combustible Floor Kit (CH 0402-0752)
> Stack Frame
> Low Temperature Protection Valve
> 30 psi ASME Relief Valve
> 75 psi ASME Relief Valve
> 100 psi ASME Relief Valve
> 125 psi ASME Relief Valve
> 150 psi ASME Relief Valve
Smart System™ Features
>SMART SYSTEM™ Operating Control
> 2 Line/16 Character LCD Display
> Built in Cascading Sequencer for up to 8 boilers
> Front End Loading Capability with Crest or Knight Boilers
> Building Management System Integration
with 0-10 VDC Input
> Outdoor Reset Control with Outdoor Air Sensor
> Password Security
> Domestic Hot Water Prioritization
> Low Water Flow Control & Indication
> Inlet & Outlet Temperature Readout
> Freeze Protection
> Service Reminder
> Time Clock
> 0-10 VDC Rate Output
> Condensing Protection
> 0-10 VDC System Pump Speed Input
> Data Logging
> Hours Running, Space Heating
> Hours Running, Domestic Hot Water
> Ignition Attempts
> Last 10 Lockouts
> Programmable System Efficiency Optimizers
> Night Setback
> Anti-Cycling
> Outdoor Air Reset Curve
> Boost Temperature & Time
Firing Codes
> M7 Firing Code - California Code
> M9 Firing Code - Hot Surface Ignition
with Electronic Supervision
> M13 Firing Code - CSD1 / Factory Mutual / GE Gap
Certifications
ANSI Z21.13/CSA 4.9 certified
South Coast Air Quality Management District
Texas Commission on Environmental Quality
> Three Pump Control
> System Pump
> Boiler Pump
> Domestic Hot Water Pump
> High Voltage Terminal Strip
> 120 VAC / 60 Hertz / 1 Phase Power Supply
> Pump Contacts with Pump Relay
> Low Voltage Terminal Strip
> 24 VAC Auxiliary Device Relay Output - Louvers
> Auxiliary Proving Switch Contacts - Louvers
> 3-way Valve Contacts for Low Temperature Protection
> Alarm on Any Failure Contacts
> 0-10 VDC System Pump Speed Contacts
> Runtime Contacts
> DHW Thermostat Contacts
> DHW Tank Sensor Contacts
> Unit Enable/Disable Contacts
> System Sensor Contacts - Supply and Return
> Outdoor Air Sensor Contacts
> Contacts for Air Louvers
> Contacts on Any Failure
> Cascade Contacts
> 0-10 VDC BMS External Control Contact
> 0-10 VDC Rate Contacts
Copper-Fin II® Gas Boiler Dimensions & Specifications
E
F
GAS CONNECTION
0992-2072
GAS CONNECTION
0402-0752
A
G
INLET AIR
FILTER
G
D
OUTLET
INLET
H
C
B
Copper-Fin II Heating Boiler
Dimensions & Spec­i­fi­ca­tions
Net AHRI
Model
Input
Thermal
Output
Rating
Vent
Air
Gas
Shipping
Number MBH Efficiency MBH MBH
A
B
C
D
E
F
G
H
Size Inlet
Conn Weight
CHN0402
399
85%
339
295
31-1/2” 37-3/4” 22-1/4”
12-1/2”
7” 7” 29” 6-1/2”
6” 6” 1-1/4”
378
CHN0502
500
85%
425
370
31-1/2” 45-1/2” 22-1/4”
12-1/2”
7” 7” 29” 6-1/2”
6” 6” 1-1/4”
414
CHN0652
650
85%
553
481
31-1/2” 56-3/4” 22-1/4”
12-1/2”
8-1/2”
8-1/4” 29” 6-1/2”
8” 8” 1-1/4”
500
CHN0752
750
85%
638
555
31-1/2” 64” 22-1/4”
12-1/2”
8-1/2”
8-1/4” 29” 6-1/2”
8” 8” 1-1/4”
543
CHN0992
990
85%
842
732
36” 48-1/4” 33-1/2”
15-3/4”
8-1/2”
8-1/2” 33-3/4”
8-3/4”
10” 10” 2” 773
CHN1262 1,260
85%
1,071
931
36” 58-1/2” 33-1/2”
15-3/4”
10-1/2”
9-1/2” 33-3/4”
8-3/4”
12” 12” 2” 863
CHN1442 1,440
85%
1,224 1,064
36” 68-3/4” 33-1/2”
15-3/4”
10-1/2”
10-1/2” 33-3/4”
8-3/4”
12” 12” 2” 965
CHN1802 1,800
85%
1,530 1,330
36” 82-1/4” 33-1/2”
15-3/4”
11” 11” 33-3/4”
8-3/4”
14” 12” 2” 1,100
CHN2072 2,070
85%
1,760 1,530
36” 92-1/2” 33-1/2”
15-3/4”
11” 11” 33-3/4”
8-3/4”
14” 12” 2” 1,219
Notes: Change ‘N’ to ‘L’ for LP gas models. No deration on LP models
Water connections for models CH 0402-0752 are 2” NPT on 6-1/2” centers.
Header increases “B” dimension 3-1/2” for models CH 0402-0752 and 6 -1/4” for models CH 0992-2072 Water connections for models CH 0992-2072 are 2-1/2” NPT on 11-1/4” centers.
Performance data is based on manufacturer test results.
Venting Options
Aire-LockTM Direct Vent Sealed
Combustion
DirectAire® Vertical
DirectAire® Vertical w/ Sidewall Inlet
Outdoor Installation
Power DirectAire® Horizontal
Powered Side Wall
Sidewall
Lochinvar, LLC
300 Maddox Simpson Parkway
Lebanon, Tennessee 37090
P: 615.889.8900 / F: 615.547.1000
6/15—Printed in U.S.A.

advertisement

Key Features

  • 85% Thermal Efficiency
  • Proportional Firing up to 4:1 Turndown
  • SMART SYSTEMâ„¢ Operating Control
  • ASME Copper Finned Tube Heat Exchanger
  • Vertical & Horizontal Venting
  • Sealed Combustion
  • Low NOx Operation
  • Category I & IV Venting
  • Combustible Floor Rated

Frequently Answers and Questions

What is the thermal efficiency of the Copper-Fin II gas boiler?
The Copper-Fin II gas boiler has an 85% thermal efficiency rating.
What is the turndown ratio of the Copper-Fin II gas boiler?
The Copper-Fin II gas boiler has a proportional firing turndown ratio of up to 4:1.
What type of venting options does the Copper-Fin II gas boiler offer?
The Copper-Fin II gas boiler offers vertical and horizontal venting options, including Category I and IV venting.
What type of combustion system does the Copper-Fin II gas boiler have?
The Copper-Fin II gas boiler uses a sealed combustion system.
What are the NOx emission levels of the Copper-Fin II gas boiler?
The Copper-Fin II gas boiler is designed for low NOx operation.