H932

H932
Engineering Specifications
Hawkeye Model H932 0-5 VDC Analog Current Sensor with Command
Relay
1. The current sensor shall be self powered
2. The current sensor shall be a split-core type with self-gripping iris that
adheres to electrical conductors…no drill mounting required
3. The current sensor shall have an integral start/stop command relay
4. The 24 VAC/DC relay output rating shall be 3A inductive, 5A resistive @ 30
VDC, 240 VAC
5. The current sensor shall have three switch selectable pre-calibrated ranges of
30, 60, and 120A with a full scale output of 5 VDC
6. The current sensor shall be accurate to +/- 2.0% of the range over a
temperature range of -15ο to 60ο C
7. The current sensor shall be isolated to 600 VAC RMS
8. The current sensor shall have a removable mounting bracket for installation
flexibility
9. The current sensor output shall be 0-5 VDC
10. The current sensor hole size shall be (LxW)…1.1”X 0.9”
11. The current sensor dimensions shall be (LxWxH)…2.9”X2.58”X1.04”
12. The current analog current sensor shall be Hawkeye model 932
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement