- Industrial & lab equipment
- Personal safety & protection
- Fire protection
- Fire Control Instruments
- RZA-10 L
- User manual
- 28 Pages
Fire Control Instruments RZA-10 L, LS2 remote fire annunciator User manual
Below you will find brief information for remote fire annunciator RZA-10, remote fire annunciator RZA-10L, remote fire annunciator RZA-10LS2. The RZA-10 Series Annunciators are compact, attractive LED-type fire annunciators designed for use with the FC-10C Fire Alarm Control Communicator. The RZA-10L and RZA-10LS2 are models which do not have function switches or a key-switch. The RZA-10LS2 provides zone 9 and 10 alarm LEDs that are yellow for supervisory functions. The RZA-10 Series Annunciators are capable of displaying independent zone fire alarm, process monitor alarm, trouble and supervisory status. They also provide system status LEDs to display Power, Alarm, Trouble, Supervisory and Signals Silenced conditions. The RZA-10 model is also capable of performing system acknowledge, silence, drill and reset remotely.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
Fire Control Instruments, Inc.
301 2nd Avenue
Waltham, MA 02451-1133, USA
Phone (781) 487-0088
FAX: (781) 370-4132
The RZA-10 Series
Remote Fire Annunciators
for use with the
FC-10C
Fire Alarm Control/Communicator
Document # 51063
9/15/98 Revision:
P/N 51063:A ECN 98-422
A
2
Document 51063 Rev A 9/15/98 P/N 51063:A
Contents
Section One: RZA-10 Series Annunciators ...................................... 4
Features ................................................................................................. 4
Figure 1-1: Component Summary ......................................................... 5
Figure 1-2: Wiring to Terminals ............................................................. 6
SW1 DIP Switch Settings ...................................................................... 7
Figure 1-3: SW1 DIP Switch Settings Example .................................... 7
Figure 1-4: SW2 DIP Switch Settings Example .................................... 8
Table 1-1: RZA-10 Series Annunciator Addressing .............................. 9
Figure 1-5: Typical Configuration .......................................................... 9
LED Indicators and Piezo Sounder ..................................................... 10
Switch Functions for RZA-10 Only ...................................................... 11
Section Two: RZA-10 Series Annunciators Mounting ................... 13
Figure 2-1: RZA-10 Series Hardware ................................................. 13
Figure 2-2: RZA-10 Series Backboxes ................................................ 13
Figure 2-3: RZA-10 Series Semi-flush Mounting ................................ 14
Figure 2-4: RZA-10 Series Surface Mounting ..................................... 15
Section Three: RZA-10 Series Electrical Connections ................. 16
Figure 3-1: Power Connection ............................................................. 16
Figure 3-2: LED-10IM Installation ....................................................... 17
Figure 3-3: EIA-485 Connection ......................................................... 18
Figure 3-4: Wiring FACP to RZA-10 Series ........................................ 19
Section Four: EIA-485 Shield Terminations ................................... 20
When the EIA-485 Shield is not in Conduit ........................................ 20
When the EIA-485 Shield is in Full Conduit ....................................... 21
Spare Slide-In Labels for RZA-10 Series Annunciators ............... 23
Document 51063 Rev A 9/15/98 P/N 51063:A
3
Section One: RZA-10 Series Annunciators
RZA-10
RZA-10L and RZA-10LS2
The RZA-10 Series Annunciators consist of the RZA-10, RZA-10L and RZA-10LS2.
They are compact, attractive LED-type fire annunciators designed for use with the
FC-10C Fire Alarm Control Communicator. The RZA-10L and RZA-10LS2 are models which do not have function switches or a key-switch. The RZA-10LS2 provides zone 9 and 10 alarm LEDs that are yellow for supervisory functions.
The RZA-10 Series Annunciators are capable of displaying independent zone fire alarm, process monitor alarm, trouble and supervisory status. They also provide system status LEDs to display Power, Alarm, Trouble, Supervisory and Signals Silenced conditions. The RZA-10 model is also capable of performing system acknowledge, silence, drill and reset remotely.
Communication between the control panel and the RZA-10 Series Annunciators is accomplished over a two-wire serial interface employing the EIA-485 communication standard. Up to 32 RZA-10 Series Annunciators may be connected to the two-wire EIA-
485 circuit. The annunciators may be powered from the host FACP or remote, UL listed, filtered, regulated power supplies.
Features - all models
• Zone Alarm and Trouble LEDs.
• System Status LEDs for Power (green), Alarm (red), Trouble (yellow), Supervisory
(yellow) and Signals Silenced (yellow).
• Local piezo sounder with alarm and trouble resound.
• Distinctly different flash rates for LEDs and piezo sounder distinguish system status:
üfire alarm = 1 second on and 1 second off
üprocess monitor alarm = 1/4 second on and 1/4 second off
üsupervisory alarm = 1/2 second on and 1/2 second off
• EIA-485 connects to control panel terminal port (requires LED-10IM module).
• Plug-in terminal blocks for ease of installation and service.
• DIP switch controls transmit/receive mode.
• Up to 32 RZA-10 Series Annunciators per FC-10C.
• Mounting options:
üSurface mount in three gang electrical box P/N: SBB-3
üSemi-flush mount in three-gang electrical box P/N: 10103 (2 3/16" min. depth)
üCan be located up to 6,000 feet (1,800 m) from the panel using 18 AWG wire
• Slide-in labels for custom labeling.
• Simple programming at FC-10C panel enables communications to RZA-10 Series annunciators.
4
Document 51063 Rev A 9/15/98 P/N 51063:A
RZA-10 only:
• Function switches for:
üAcknowledge üSignal Silence üDrill üSystem Reset
• Enable/Disable key-switch for function switches.
• DIP switches control local functions such as piezo enable/disable, function switches and key-switch enable/disable.
Key-switch Enable/Disable for RZA-10 Only
(not used on the RZA-10L or RZA-10LS2)
Receive-Transmit/Receive only not used
RZA-10 Series Address
Top view
Note: TB1 & TB2 are located on backside of PCB
Piezo Enable/Disable
ROM
Membrane Connectors
Membrane switch connectors
Piezo Sounder
The RZA-10 Series sounder, if enabled, will be activated when any new alarm or trouble is received from the panel. It is silenced by pressing an ACKNOWLEDGE or
SILENCE switch. Piezo must not be disabled without approval of LAHJ (Local Authority Having Jurisdiction).
Figure 1-1: Component Summary
Document 51063 Rev A 9/15/98 P/N 51063:A
5
Side view
(rotated 180 o from above
[Top] view)
Earth Ground Option
-24 VDC OUT
-24 VDC IN
+24 VDC OUT
+24 VDC IN
No connection
+EIA-485
-EIA-485
Shield
No connection
Note: These connections must be power-limited and the +24 volt nominal power (18 VDC to 26 VDC) must be filtered.
Current Consumption @ 24 VDC nominal (filtered)
Normal/Standby (no activity): 23 mA
Trouble Condition: 31 mA
Alarm: 28 mA (1 zone in alarm)
40 mA (all 10 zones in alarm)
AC Fail: 24 mA
Figure 1-2: Wiring to Terminals
6
Document 51063 Rev A 9/15/98 P/N 51063:A
SW1 DIP Switch Settings
The OPEN position on SW1 is the OFF state. Refer to Figure 1-3 for an explanation of
DIP switch positions. SW1 switch settings are as follows:
1 through 6 - RZA-10 Series annunciator address switches.
The first six switches are used to set the address of the annunciator. The OFF
(OPEN) up position equals a binary 1 and the ON down position equals a binary 0. Refer to Table 1-1 for information on setting these switches for specific addresses. Each RZA-10 Series annunciator connected to the EIA-
485 communication bus must have a unique address.
7 - Not used
8 - ON = Receive/Transmit, OFF (OPEN) = Receive Only
Switch 8 set to ON position enables Receive/Transmit mode for the RZA-10
Series annunciator. This allows the annunciator to receive and display system status information and to transmit supervision status. It also allows the RZA-10 model to transmit system control data such as Acknowledge/Step, Reset,
Signal Silence and Drill. Switch 8 set to the OFF position enables Receive
Only mode which allows the annunciator to receive and display system status information but prevents supervision status from being transmitted back to the
FACP. It also prevents function switch operation on the RZA-10 model. To ensure annunciator supervision for all RZA-10 Series annunciators and function switch capability for the RZA-10 model, each annunciator connected to the EIA-485 communication bus must have a unique address and should be set to enable Receive/Transmit Mode.
DOWN POSITION = ON
UP (OPEN) POSITION = OFF
NOTE - SW1 DIP switch settings as illustrated in Figure 1-3 are as follows:
1) DIP switches 1 - 6: Address 08 (see Table 1-1).
2) DIP switch 7: Not used.
3) DIP switch 8: ON = Receive/Transmit
Figure 1-3: SW1 DIP Switch Settings Example
Document 51063 Rev A 9/15/98 P/N 51063:A
7
SW2 DIP Switch Settings
SW2 switch settings are as follows:
1 - RZA-10 Only (not used on RZA-10L and RZA-10LS2)
ON = Key-switch Enable, OFF = Key-switch Disable.
Switch 1 set to the ON position enables the key-switch operation. The keyswitch may now be used to enable RZA-10 model membrane (control) switches, allowing remote switch functions, or lockout the switches, preventing remote switch functions. Switch 1 set to the OFF position disables the key-switch operation. Refer to Operation Section for key-switch function description.
2 - ON = Piezo sounder enabled, OFF = Piezo sounder disabled.
CAUTION: Piezo sounder must not be disabled without prior approval of the
Local Authority Having Jurisdiction.
UP POSITION = OFF
DOWN POSITION = ON
Figure 1-4: SW2 DIP Switch Settings Example
RZA-10 Series Addressing
SW1 DIP switches 1 through 6 are used for addressing the RZA-10 Series annunciators. Each device connected to the EIA-485 communication bus must have a unique address. This allows specific data to be transmitted between the FACP and that device and for individual supervision of each annunciator by the FACP. Switch settings and the corresponding addresses are shown in Table 1-1. (Address '00' is invalid).
Note: 1 = Switch in the UP (OPEN) position.
0 = Switch in the DOWN position.
Example: ADDRESS SWITCH SETTINGS
1 2 3 4 5 6
08 0 0 1 0 0 0
Addressing Switches
8
Document 51063 Rev A 9/15/98 P/N 51063:A
INVALID
01
02
03
04
05
06
07
08
09
14
15
16
10
11
12
13
ADDRESS
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
0
0
SWITCH SETTINGS
0
0
0
0
1
1
0
0
0
3
0
1
1
0
1
1
1
1
1
1
1
1
0
0
0
0
0
4
0
1
1
0
1
1
0
0
0
0
0
0
0
0
0
0
0
2
0
0
0
1
0
0
0
0
1
1
0
0
0
0
0
1
1
5
0
1
1
0
0
0
1
1
0
1
0
1
0
1
1
0
1
6
0
0
1
0
0
1
0
1
ADDRESS
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
0
1
21
22
23
24
25
26
17
18
19
20
27
28
29
30
31
32
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
0
SWITCH SETTINGS
0
1
0
0
1
1
0
0
0
3
0
1
1
1
1
1
0
1
0
1
1
0
0
0
0
1
4
0
1
1
0
1
1
0
1
0
0
1
0
1
1
1
0
5
0
0
1
1
0
1
0
Table 1-1: RZA-10 Series Annunciator Addressing
Typical Configuration
The RZA-10 Series annunciators indicate the status of the FC-10C, display zone status and require no programming. In addition, the RZA-10 model offers multiple annunciator locations with the capability of remote Acknowledge, Signal Silence, Drill and Reset functions.
1
0
1
0
1
0
0
1
0
6
1
1
0
1
0
1
0
NOTES:
1) EIA-485: Maximum of 6,000 feet (1,800 m) total cable length from FACP to RZA-10 Series annunciators. Circuit is power-limited.
2) Up to 32 RZA-10 Series annunciators may be used on the EIA-485 circuit. The FC-10C can power a maximum of seven annunciators. If additional annunciators are connected, a UL listed power supply may be used to supply additional power, the power supply must be regulated, power-limited and UL listed for Fire Protective Signaling Systems. (Power supplies used for this purpose must have their negative terminals commoned together).
3) Between each annunciator are four wires: A twisted-shielded pair for data communications and a pair for 24 VDC power.
4) A mix of RZA-10 Series annunciators can be connected to the same EIA-485 circuit.
Figure 1-5: Typical Configuration
Document 51063 Rev A 9/15/98 P/N 51063:A
9
LED Indicators and Piezo Sounder
The RZA-10 Series annunciators provide LEDs which indicate the system and zone status of its associated FC-10C fire alarm control/communicator.
AC
Power
This is a green LED which illuminates if AC power is applied to the host FACP. The green LED will turn off if AC power to the host FACP is lost.
Alarm
This is a red LED that flashes (1 second on, 1 second off) when one or more fire alarms occur. The piezo sounder turns on steady for alarm. The LED illuminates steadily and the piezo silences when an
Acknowledge or Silence switch is pressed. The
Alarm LED turns off when the Reset switch is pressed after the alarm condition has been cleared.
Trouble
This is a yellow LED that flashes (1 second on, 1 second off) when one or more trouble conditions occur. The piezo sounder pulses (1 second on, 1 second off). The LED turns on steady and the piezo silences when an Acknowledge or Silence switch is pressed. The LED turns off when all trouble conditions are cleared. This LED will also illuminate if the microprocessor watchdog circuit within the annunciator is activated.
Supervisory
This is a yellow LED that flashes (½ second on, ½ second off) when one or more supervisory conditions occur, such as a sprinkler valve tamper condition.
The piezo sounder pulses (½ second on, ½ second off). The LED illuminates steadily and the piezo silences when an Acknowledge or
Silence switch is pressed. The Supervisory LED turns off when a Reset switch is pressed after clearing the supervisory condition.
RZA-10 and RZA-10L Only
Zone Alarm - Zones 1 through 10
This is a red LED that flashes when a fire alarm, supervisory alarm or process monitoring alarm occurs on the corresponding zone. The LED flashes at a 1 second on/1 second off rate for a fire alarm condition, a ½ second on/½ second off rate for a supervisory alarm and a ¼ second on/¼ second off rate for a process monitoring alarm. The piezo sounder will pulse at a rate corresponding to the flashing LED. The LED illuminates steadily and the piezo silences when an Acknowledge or Silence switch is pressed. The LED turns off when the fire alarm, process monitoring alarm or supervisory alarm is cleared on the corresponding zone and the Reset switch is pressed.
10
Note: Be certain to use customized slide-in label to identify the zone function, since the red LED will flash for a variety of conditions as programmed in the FACP. Refer to the FC-10C Manual P/N 51057 for details.
Document 51063 Rev A 9/15/98 P/N 51063:A
RZA-10LS2 Only
Zone Alarm - Zones 1 through 8
The red LED for Zones 1 through 8 on the
RZA-10LS2 operate the same as on the
RZA-10 and RZA-10L. Refer to the previous section.
Zone Alarm - Zones 9 and 10
This is a yellow LED on Zones 9 and 10 of the RZA-10LS2 only. These two zones should be used to annunciate supervisory alarms only (primarily designed for
Canadian Supervisory Service). Approval from the Local Authority Having
Jurisdiction is required in order to annunciate fire alarms or process monitor alarms on these zones. The LED flashes at a ½ second on/½ second off rate for a supervisory alarm. The piezo sounder will pulse at a rate corresponding to the flashing LED. The LED illuminates steadily and the piezo silences when an
Acknowledge or Silence switch is pressed. The LED turns off when the supervisory alarm is cleared on the corresponding zone and the Reset switch is pressed.
Zone Trouble - Zones 1 through 10 (All RZA-10 Series)
This is a yellow LED that flashes when a zone trouble condition occurs on the corresponding zone. The LED flashes at a 1 second on/
1 second off rate for a zone trouble condition. The piezo sounder will pulse at a rate corresponding to the flashing LED. The LED illuminates steadily and the piezo silences when the Acknowledge or Silence switch is pressed. The LED turns off when all trouble conditions on the corresponding zone are cleared.
Switch Functions for RZA-10 Model Only
Key-switch
The key-switch is used to enable and disable the operation of the membrane
(control) switches if switch 1 on DIP switch
SW2 has been placed to the ON position.
Key-switch
(shown in Off Position)
To enable the Acknowledge, Silence, Drill and Reset function switches, insert a standard control panel key into the keyswitch located at the top right corner of the
RZA-10. Make certain the key is inserted completely before attempting to turn it.
Turn the key clockwise until it stops. Leave the key inserted while pressing the function switches. When finished with the function switches, turn key-switch counterclockwise to disable function switches.
Note: The key-switch should normally be in the disabled position (fully counterclockwise), with the key removed and access to the key restricted to authorized personnel only. Do not leave the key unattended in the RZA-10.
Document 51063 Rev A 9/15/98 P/N 51063:A
11
12
Acknowledge
When the Acknowledge switch is pressed and released, the RZA-10 sends an Acknowledge command to the control panel. Pressing the Acknowledge switch silences the local piezo sounder, the sounders located in all other system annunciators and the sounder located on the Fire Alarm Control Panel's main circuit board.
It will also change all flashing system LEDs to steady on. Only one press is necessary regardless of the number of new alarms, troubles or supervisory signals.
An acknowledge message is also sent to the printer and the history files in the
FC-10C.
Silence
When the Silence switch is pressed and released, the RZA-10 sends a Signal Silence command to the control panel. The Silence switch performs the same functions as the Acknowledge switch. In addition, if an alarm exists, it turns off all silenceable
NAC outputs only and causes the FACP ALARM SILENCE LED and the RZA-10
SIGNAL SILENCE LED to turn on. It also sends an ALARM SILENCED message to the printer and the history file within the FC-10C. A subsequent new alarm will resound the appropriate Notification Appliance Circuits (NACs) and local sounders.
Drill: Hold 2 Sec.
When the Drill switch is pressed and held for at least two seconds (time required to prevent accidental activations), the RZA-10 will transmit a drill command to the control panel. This command causes the FACP to turn on all main panel NAC outputs. In the event that the system was previously silenced, the drill command will also turn off the ALARM SILENCE LED. (The Silence switch operates on silenceable NAC outputs only).
Reset
When the System Reset switch is pressed and released, the RZA-10 sends a Reset command to the control panel. This will turn off all Notification Appliance Circuits, temporarily turns off resettable power to
4-wire detectors, and sends a "SYSTEM RESET" message to the FACP display, printer and FC-10C history files. It also turns on all system LEDs, piezo sounders and FACP LED display segments as long as the
Reset switch is held (lamp test). Any alarm or trouble that exists after a Reset will resound the system.
Document 51063 Rev A 9/15/98 P/N 51063:A
Section Two: Mounting RZA-10 Series Annunciators
Screw
RZA-10 Series Annunciator Preparation
The RZA-10 Series can be surface mounted in a three-gang electrical box, P/N SBB-3 or semiflush mounted in a three-gang electrical box,
P/N 10103 or equivalent, with a minimum depth of 2 3/16". Select and remove the appropriate knockout(s), pull the necessary wires through the knockouts and mount the three-gang box in or on the wall depending on the type of installation desired. Be certain that power is not applied to the wiring during the installation procedure.
Screw
Note: To ensure static protection, all enclosures, including the RZA-10 Series electrical
box, must be connected to earth ground! Never use the shield of the communications wiring for static protection.
To mount the RZA-10 Series Annunciator in the electrical box, the trim ring must first be removed. The trim ring is held in place by two screws inserted through the top and bottom edge as illustrated above. Removal of the trim ring will expose a metal flange with mounting holes.
RZA-10 Series flange
RZA-10 Series Trim ring
(P/N 23165)
Figure 2-1: RZA-10 Series Hardware
3-Gang Electrical Box P/N: 10103
(semi-flush mount)
3-Gang Electrical Box P/N: SBB-3
(surface mount)
Figure 2-2: RZA-10 Series Backboxes
Document 51063 Rev A 9/15/98 P/N 51063:A
13
Semi-flush Mount Backbox
Remove the plug-in terminal blocks from the RZA-10 Series circuit board. Connect the
EIA-485 and power wiring into the terminal block positions illustrated in Figures 3-1 and
3-3. Plug the terminal blocks back into the TB1 and TB2 connectors on the back of the annunciator circuit board.
Set DIP switches SW1 and SW2 for the desired options (refer to switch settings in
Figures 1-3, 1-4 and Table 1-1).
Mount the RZA-10 Series to the three-gang electrical box using the four mounting holes on the annunciator flange and the four screws provided for this purpose. Replace the trim ring and secure with the two screws which were previously removed. Adjust the plastic trim ring to the surface of the wall before tightening the screws. Do not overtighten.
RZA-10 Series flange
Mounting Holes (4)
Three-gang electrical box (P/N 10103 or equivalent with 2 3/16" minimum depth).
flange
14
EIA-485 and power wiring
RZA-10 Series
Figure 2-3: Semi-flush Mounting
Document 51063 Rev A 9/15/98 P/N 51063:A
Surface Mount Backbox
Remove the plug-in terminal blocks from the RZA-10 Series circuit board. Connect the
EIA-485 and power wiring into the terminal block positions illustrated in Figures 3-1 and
3-3. Plug the terminal blocks back into the TB1 and TB2 connectors on the back of the annunciator circuit board.
Set DIP switches SW1 and SW2 for the desired options (refer to switch settings in
Figures 1-3, 1-4 and Table 1-1).
Mount the RZA-10 Series to a three-gang electrical box using the four mounting holes on the annunciator flange and the four screws provided for this purpose. Replace the trim ring and secure with the two screws which were previously removed. Do not overtighten.
RZA-10 Series flange
Mounting Holes (4)
Three-gang electrical box (P/N SBB-3 or equivalent with 2.75" minimum depth).
flange
EIA-485 and power wiring
RZA-10 Series
Figure 2-4: Surface Mounting
Document 51063 Rev A 9/15/98 P/N 51063:A
15
Section Three: RZA-10 Series Electrical Connections
The RZA-10 Series Annunciators can be powered by the FC-10C power output or from a remote, UL listed, filtered power supply such. The power run to the RZA-10 Series must be power-limited but need not contain a power supervision relay since loss of power is inherently supervised through loss of communication with the annunciator.
Maximum RZA-10 Series current draw from the power supply under alarm condition is
28 mA. Maximum current draw from the control panel's secondary power source
(batteries) under loss of AC power is 24 mA.
RZA-10 Series
Plug-in terminal blocks
Earth Ground Option n/c
+ 24 VDC
From Main Power Supply
- 24 VDC
+ 24 VDC
To next annunciator or ACM-8RF
- 24 VDC
Note: All connections are power-limited and supervised.
Figure 3-1: Power Connection
16
Document 51063 Rev A 9/15/98 P/N 51063:A
LED-10IM
The LED-10IM Interface Module provides an EIA-485 port to support the FCI-RZA-10
Series, and the Fire•Lite AFM Series and LDM Series annunciators as well as the
ACM-8RF Remote Relay Module and is therefore required when connecting these devices to the FC-10C. The FC-10C supervises EIA-485 wiring for open circuits via the
LED-10IM Interface Module. The LED-10IM plugs into connector J6 located in the upper right corner of the FC-10C main circuit board.
Install the two supplied standoffs into the FACP main circuit board. Ensure that the metal standoff is installed in the position indicated in the illustration below. Carefully align the two connectors and press the LED-10IM module securely into place. Make certain the pins are properly aligned to prevent bending or breaking of any pins. It is important that the supplied screw and washer be used to secure the module to the metal standoff. This is necessary in order to help protect against electrical transients.
Note: Refer to the FC-10C Manual Programming Section for information on programming the RZA-10 Series Annunciators into the system.
LED-10IM
Metal
Standoff
FC-10C
Figure 3-2: LED-10IM Installation
Document 51063 Rev A 9/15/98 P/N 51063:A
17
RZA-10 Series
Plug-in terminal blocks
No connection
Shield
+ EIA-485
- EIA-485
TB2
Refer to Note 6
Notes:
1) All connections are power-limited and supervised.
2) A maximum of 32 RZA-10 Series Annunciators may be connected to this circuit.
3) 6,000 feet (1,800 m) maximum distance @ 18 AWG (0.75 mm 2 ) between the panel and annunciators.
4) Use overall foil/braided-shield twisted pair cable suitable for EIA-485 applications (refer to Section
Four for shield termination information).
5) The EIA-485 circuit is rated at 5.5 VDC maximum and 60 mA maximum.
6) The RZA-10 Series Annunciators must have the supplied R120 (120 ohm) resistor installed across the EIA-485 terminals on the last or only device connected to the EIA-485 bus as shown.
The resistor is required for impedance matching.
Figure 3-3: EIA-485 Connection
18
Document 51063 Rev A 9/15/98 P/N 51063:A
24 VDC TB2
Terms 1 (+) and 2 (-)
FC-10C
LED-10IM
RZA-10 Series in grounded box
EIA-485
RZA-10 Series in grounded box
Refer to Note 4
CAUTION! Please be certain to secure the LED-10IM module to the FC-10C and to keep all wiring from mechanically interfering with the LED-10IM.
Note:
1) Twisted, shielded wire is recommended for the EIA-485 communications loop.
2) Four-conductor, overall shielded wire may be used for the four EIA-485 wires and the two power wires. It is, however, strongly recommended that the power and communication wires be separate whenever possible.
3) Refer to Figures 3-1, 3-2 and 3-3 for RZA-10 Series and LED-10IM terminal designations.
4) The RZA-10 Series Annunciators must have the supplied R120 (120 ohm) resistor installed across the EIA-485 terminals on the last or only device connected to the EIA-485 bus as shown.
The resistor is required for impedance matching.
Figure 3-4: Wiring FACP to RZA-10 Series Annunciator
Document 51063 Rev A 9/15/98 P/N 51063:A
19
Section Four: EIA-485 Shield Terminations
The EIA-485 circuit must be wired using a twisted-shielded pair cable having a characteristic impedance of 120 ohms, +/- 20%. Do not run cable adjacent to, or in the same conduit as, 120-volt AC service, noisy electrical circuits that are powering mechanical bells or horns, audio circuits above 25 V
RMS
, motor control circuits, or SCR power circuits
Note: To ensure static (ESD - electrostatic discharge) protection, all enclosures,
including the RZA-10 Series electrical box, must be connected to earth ground! Never use the EIA-485 shield for this purpose. The EIA-485 shield is for radiated noise emission protection (RFI, EMI). Refer to the following figures.
The EIA-485 shield should be terminated as follows:
When the EIA-485 shield is not in conduit: The EIA-485 loop allows the FACP to
communicate with the annunciators. The shield for the EIA-485 loop must be connected to earth ground at the FACP but must be left floating (no connection) at the annunciator if it is the first or only device on the EIA-485 loop. If a second annunciator is connected, the shield leaving the first annunciator must be left floating. The shield entering the second annunciator must be connected to the 3gang box or Earth Ground terminal (TB1-6 & 7) on the second annunciator. If additional annunciators are connected, the shield leaving each enclosure must be left floating and the shield entering each must be connected to the 3-gang box or the Earth Ground Terminal (TB1-6 & 7) on the annunciator.
Connect the drain wire to the outside of the FC-10C cabinet via a
BX-type connector.
Shield Drain Wire
(+) EIA-485
FC-10C
20
Shield
RZA-10
RZA-10
EIA-485 Loop not in conduit
Document 51063 Rev A 9/15/98 P/N 51063:A
(-) EIA-485
FACP
RZA-10
When the EIA-485 shield is in full conduit: The EIA-485 loop allows the FACP to
communicate with the annunciator(s). The shield for the EIA-485 loop must be connected to earth ground at the FACP, but must be left floating (no connection) at the annunciator if it is the first or only device on the EIA-485 loop. If a second annunciator is connected, the shield leaving the first annunciator must be left floating. The shield entering the second annunciator must be connected to the
Earth Ground Terminal (TB1- 6 & 7) on the second annunciator. If additional annunciators are connected, the shield leaving each annunciator must be left floating and the shield entering the following unit must be connected to the Earth
Ground Terminal (TB1 - 6 & 7) on the annunciator.
Caution! Do not allow the floating (no connection) end of the shield to contact the conduit. The floating end should be insulated from earth ground.
RZA-10 Series
Connect the shield drain wire to the Earth
Ground Terminal on the annunciator.
TB2-1 (+) EIA-485
TB2-2 (-) EIA-485
RZA-10 Series Box
Shield Drain Wire
TB1-6 Earth Ground
(IN)
Shield
FC-10C
RZA-10
Series
RZA-10
Series
RZA-10
Series
EIA-485 Loop
in Conduit
Notes:
1) Power-limited 24 VDC regulated power may be run in the same conduit as the EIA-485 wiring.
2) Twisted, shielded wire is recommended for the EIA-485 communications loop.
3) Each RZA-10 Series Annunciator's electrical backbox is connected to earth ground via the conduit.
4) Shield is connected to the FACP cabinet (earth ground) leaving the FACP.
Document 51063 Rev A 9/15/98 P/N 51063:A
21
Notes
22
Document 51063 Rev A 9/15/98 P/N 51063:A
Slide-In Labels for the RZA-10 Series Annunciators
Slide-in labels for Zones 1-10 are included with the RZA-10 Series Annunciators. In the event that these labels are damaged or lost, remove this page from the manual and type the appropriate information on the labels shown below. Type on the lines provided to ensure centering of information in label windows. Carefully cut out the labels and insert them into the two label slots on the top left side of the annunciator face plate.
Label #1 Label #2
Note: To ensure the best fit, cut directly along the dotted line surrounding each label.
Custom User
Label #1
Custom User
Label #2
Custom User
Label #1
Custom User
Label #2
Document 51063 Rev A 9/15/98 P/N 51063:A
23
Notes
24
Document 51063 Rev A 9/15/98 P/N 51063:A
Notes
Document 51063 Rev A 9/15/98 P/N 51063:A
25
Notes
26
Document 51063 Rev A 9/15/98 P/N 51063:A
Document 51063 Rev A 9/15/98 P/N 51063:A
27
28
Document 51063 Rev A 9/15/98 P/N 51063:A
advertisement
Key Features
- Compact, attractive LED-type annunciators
- Display independent zone fire alarm, process monitor alarm, trouble and supervisory status
- System status LEDs
- Local piezo sounder
- EIA-485 communication interface
- Plug-in terminal blocks
- DIP switch controls
- Up to 32 annunciators per FC-10C
- Mounting options: surface, semi-flush
- Slide-in labels
Frequently Answers and Questions
How many RZA-10 series annunciators can be connected to the FC-10C?
What is the maximum distance between the FC-10C and the RZA-10 series annunciators?
What is the maximum current draw from the power supply under alarm condition?
Related manuals
advertisement
Table of contents
- 4 Section One: RZA-10 Series Annunciators
- 4 Features
- 5 Figure 1-1: Component Summary
- 6 Figure 1-2: Wiring to Terminals
- 7 SW1 DIP Switch Settings
- 7 Figure 1-3: SW1 DIP Switch Settings Example
- 8 Figure 1-4: SW2 DIP Switch Settings Example
- 9 Table 1-1: RZA-10 Series Annunciator Addressing
- 9 Figure 1-5: Typical Configuration
- 10 LED Indicators and Piezo Sounder
- 11 Switch Functions for RZA-10 Only
- 13 Section Two: RZA-10 Series Annunciators Mounting
- 13 Figure 2-1: RZA-10 Series Hardware
- 13 Figure 2-2: RZA-10 Series Backboxes
- 14 Figure 2-3: RZA-10 Series Semi-flush Mounting
- 15 Figure 2-4: RZA-10 Series Surface Mounting
- 16 Section Three: RZA-10 Series Electrical Connections
- 16 Figure 3-1: Power Connection
- 17 Figure 3-2: LED-10IM Installation
- 18 Figure 3-3: EIA-485 Connection
- 19 Figure 3-4: Wiring FACP to RZA-10 Series
- 20 Section Four: EIA-485 Shield Terminations
- 20 When the EIA-485 Shield is not in Conduit
- 21 When the EIA-485 Shield is in Full Conduit
- 23 Spare Slide-In Labels for RZA-10 Series Annunciators