MXF SIGNAL TRANSMITTER BEFORE USE .... INSTRUCTION MANUAL

MXF SIGNAL TRANSMITTER BEFORE USE .... INSTRUCTION MANUAL
MXF
INSTRUCTION MANUAL
SIGNAL TRANSMITTER
MODEL
(front configurable function module)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket)....................... (1)
■ MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ CONFORMITY WITH EC DIRECTIVES
• This equipment is suitable for Pollution Degree 2 and Installation Category II. Basic insulation (signal input to
output: 300V) is maintained. Prior to installation, check
that the insulation class of this unit satisfies the system
requirements.
•Altitude up to 2000 meters
•The equipment must be mounted inside a panel.
•Insert a noise filter for the power source connected to the
unit. TDK-Lambda Noise Filter Model MZS-1206-33 or
equivalent is recommended.
•The actual installation environments such as panel configurations, connected devices and connected wires may
affect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
■ POWER INPUT RATING & OPERATIONAL RANGE
•Locate the power input rating marked on the product and
confirm its operational range as indicated below:
Rating 100 – 240V AC: 85 – 264V, 47 – 66 Hz,
approx. 3VA at 100V
approx. 4.5VA at 200V
approx. 5.5VA at 264V
Rating 24V DC: 24V ±10%, approx. 3.5W
Rating 110V DC: 85 – 150V, approx. 3.5W
■ UNPLUGGING THE UNIT
•Before you remove the unit from its base socket or mount
it, turn off the power supply and input signal for safety.
MXF
■ ENVIRONMENT
•Indoor use
•When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ventilation.
•Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
•Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
•Do not install cables (power supply, input and output)
close to noise sources (relay drive cable, high frequency
line, etc.).
•Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
•The unit is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
COMPONENT IDENTIFICATION
Base Socket
Connection Diagram
Specifications
Body
INSTALLATION
Detach the yellow clamps located at the top and bottom of
the unit to separate the body from the base socket.
■ DIN RAIL MOUNTING
Set the base socket so that its
DIN rail adaptor is at the bottom. Position the upper hook
at the rear side of base socket
on the DIN rail and push in
the lower. When removing
the socket, push down the
DIN rail adaptor utilizing a
minus screwdriver and pull.
■ WALL MOUNTING
Refer to “EXTERNAL DIMENSIONS.”
Clamp
(top & bottom)
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
Shape and size of the base socket
are slightly different with various
socket types.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1718 Rev.6
P. 1 / 4
MXF
FRONT VIEW & PROGRAMMING
■ PROGRAMMING PROCEDURE
1) Press ITEM UP or DOWN key until ITEM display indicates “01”.
2) Press DATA UP or DOWN key and choose “2” on DATA display.
1 : Data indication only.
2 : All parameters are modifiable.
3) Press ITEM UP or DOWN key until ITEM display shows the
ITEM No. you need to change.
4) Press DATA UP or DOWN key and choose a DATA No. or value
you need on DATA display.
5) Repeat above 3 and 4. (Entered data is stored 1 sec. after the
operation has been complete.)
6) Press ITEM UP or DOWN key until ITEM display indicates “01”.
7) Press DATA UP or DOWN key and choose “1” on the display.
8) Press ITEM UP or DOWN key until ITEM display indicates “P”.
DATA display shows process input. You can now check data setting by choosing ITEM No.
Note : DO NOT press UP and DOWN keys simultaneously.
DATA
DATA Display
ITEM
Polarity LED
Programming
Error LED
ITEM No. Display
PL1
PL2
ITEM
DATA
PL3
PL4
DATA UP-DOWN Keys
ITEM No. UP-DOWN Keys
ITEM MDF.
DATA
CONTENTS
DEFAULT
CODE
P
N/A
-9999 – 9999 Output display in engineering unit (as set in ITEM 14/15)
-- 01
1, 2, 3
Modification code
1 :Data indication only.
1
2 :All parameters are modifiable.
3 :Only ITEM 24 is modifiable.
02
N/A
0 – 99
Status indication (“0” is normally indicated.)
-- 03
N/A
0, 1, 2
Input range code
0 : S1 (-1 – +1V)
S1 : 0
1 : S2 (-10 – +10V)
S2 : 1
2 : S3 (-30 – +30V)
S3 : 2
04
N/A
0, 1, 2
Output range code
0 : V1 (-1 – +1V)
V1 : 0
1 : V2 (-10 – +10V)
V2 : 1
2 : Z1 (0 – 20mA)
Z1 : 2
05
N/A
-15.0 – 115.0 Input indicated in % (of the range set in ITEM 19/20)
-- 06/L
2
-15.0 – 115.0 Output indicated in % with ITEM 01 DATA 1 (of the range set in ITEM 21/22) --
Loop test output with ITEM 01 DATA 2 (‘L’ is indicated as ITEM No.)
(Use DATA UP/DOWN key to set the output signal.)
07
2
-99.99 – 99.99 Zero adjustment (%) (fine adj. of the value set in ITEM 19)
0.00
08
2
0.000 – 9.999 Gain adjustment (fine adj. of the value set in ITEM 20)
1.000
09
2
0, 1, 2, 3
Function
0 : Proportional F (X) = X
0
1 : Square F (X) = X2
2 : Reciprocal F (X) = 1/100X
3 : Square root F (X) = √X *1
10
2
-99.99 – 99.99 Output bias (%)
0.00
11
2
0.000 – 9.999 Output gain
1.000
12
2
-15.0 – 115.0 Output low limit (%) (ITEM 12 < ITEM 13)
-15.0
13
2
-15.0 – 115.0 Output high limit (%) (ITEM 12 < ITEM 13)
115.0
14
2
-9999 – 9999 Display range scaling 0% *20.0
15
2
-9999 – 9999 Display range scaling 100% *2100.0
16
2
0, 1, 2, 3
Decimal point position 0 : _ _ _ _
1
1 : _ _ _ . _
2 : _ _ . _ _
3 : _ . _ _ _
17
2
0, 1, 2, 3, 4
Moving average (sampling cycle: 10 msec.)
0
0: No 1: 4 samples 2: 8 samples 3: 16 samples 4: 32 samples
18
2
0, 1 – 60
Power-saving mode
0 : Continuous display
10
1 – 60 : Time before display turned off (minutes)
19
2
-1.00 – 1.00
Input code S1
0% input voltage (V) *3-1.00
20
2
-1.00 – 1.00
100% input voltage (V) *31.00
19
2
-10.0 – 10.0
Input code S2
0% input voltage (V) *3-10.0
20
2
-10.0 – 10.0
100% input voltage (V) *310.0
19
2
-30.0 – 30.0
Input code S3
0% input voltage (V) *3-30.0
20
2
-30.0 – 30.0
100% input voltage (V) *330.0
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1718 Rev.6
P. 2 / 4
MXF
ITEM MDF.
CODE
DATA
CONTENTS
DEFAULT
21
2
-1.00 – 1.00
Output code V1
0% output voltage (V) *4-1.00
22
2
-1.00 – 1.00
100% output voltage (V) *41.00
21
2
-10.0 – 10.0
Output code V2
0% output voltage (V) *4-10.0
22
2
-10.0 – 10.0
100% output voltage (V) *410.0
21
2
0.0 – 20.0
Output code Z1
0% output current (mA) *4
4.0
22
2
0.0 – 20.0
100% output current (mA) *4
20.0
23
2
0, 1
Output characteristic 0: Positive
1: Negative (inverted output)
0
24
3
0, 1
Reset all settings *5
0
25
N/A
---
ROM version
--*1 :The calculated result with the input ≤0.001 is rounded to 0.
*2 :Of the range set in ITEM 07/08. ITEM 14 < ITEM 15.
*3 :ITEM 19 < ITEM 20.
*4 :ITEM 21 < ITEM 22.
*5 :Press DATA UP key and choose DATA 1. Double-click DATA DOWN key. The display shows DATA 0 after the initialization is complete.
■ SELECTING INPUT RANGE
[E.G.] -5.0 to 5.0V DC
1) Program Mode
Set ITEM 01 – DATA 2 to turn the unit into Program
Mode.
2) 0% Input Voltage
Choose ITEM 19 – DATA -5.0.
3) 100% Input Voltage
Choose ITEM 20 – DATA 5.0.
4) Monitor Mode
Set ITEM 01 – DATA 1 to turn the unit into Monitor
Mode.
5) PV Indication
Press ITEM UP or DOWN key until ITEM display indicates “P”.
■ RESET ALL SETTINGS
Returning the unit into the factory-default settings.
1) Turn the unit into Reset Mode.
Set ITEM 01 – DATA 3 to turn the unit into Reset
Mode.
2) Call up the Reset menu.
Choose ITEM 24 – DATA 1. (Press DATA UP key.)
3) Resetting Enable
Double-click DATA DOWN key. DATA 0 is displayed after the initialization is complete.
4) Turn the unit into Monitor Mode.
If necessary, go to Moving Average and other adjustments.
Set the unit to Monitor Mode other than for programming.
■ PROGRAMMING ERROR LED, PL2
When the PL2 is turned on, identify the cause of error with
ITEM 02 (Status Indication).
■ SELECTING OUTPUT RANGE
[E.G.] -10.0 to 0.0V DC
1) Turn the unit into Program Mode.
2) 0% Output Voltage
Choose ITEM 21 – DATA -10.0.
3) 100% Output Voltage
Choose ITEM 22 – DATA 0.0.
4) Turn the unit into Monitor Mode.
5) Set to ITEM P.
■ DISPLAY RANGE SCALING
[E.G.] PV display range -10.0 to 10.0 modified to show
-6500 to 350
1) Turn the unit into Program Mode.
2) Decimal Point Position
Choose ITEM 16 – DATA 0.
3) 0% Scaling Value
Choose ITEM 14 – DATA -6500.
(Negative [–] range is identified with the PL1 turned on.)
4) 100% Scaling Value
Choose ITEM 15 – DATA 350.
5) Turn the unit into Monitor Mode.
6) Set to ITEM P.
REF. ERROR
0
Normal
12 Output Hi/Lo limit setting: Low Limit > High Limit
See ITEM 12/13.
14 Display range scaling: 0% Setting > 100% Setting,
or Overrange: See ITEM 14 / 15.
19 Input range setting: 0% Setting > 100% Setting
See ITEM 19 / 20.
21 Output range setting: 0% Setting > 100% Setting
See ITEM 21 / 22.
99 Memory error: Initialize all the settings of the
unit by operating ITEM 24 and program the unit
again.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1718 Rev.6
P. 3 / 4
MXF
TERMINAL CONNECTIONS
CHECKING
Connect the unit as in the diagram below or refer to the connection diagram on top of the unit.
1) Terminal wiring: Check that all cables are correctly connected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
7 – 8 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Output: Check that the load resistance meets the described specifications.
INPUT
+ 3
1 +
– 4
2 –
OUTPUT
7 U(+)
8 V(–)
POWER
MAINTENANCE
Regular calibration procedure is explained below:
■ CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accuracy described in the data sheet. When the output is out of
tolerance, recalibrate the unit as explained earlier (ITEM
07 and 08).
EXTERNAL DIMENSIONS unit: mm (inch)
CLAMP
(top & bottom)
20
(.79)
7.8 (.31)
50 (1.97)
127 (5)
5
4
3
7
8
1
2
2–4.5 (.18) dia.
MTG HOLE
15 (.59) deep
8–M3.5
SCREW
107 (4.21)
6
80 (3.15)
80 (3.15)
35.4 (1.39)
DIN RAIL
35mm wide
[3.3 (.13)]
40 (1.57)
50 (1.97)
• When mounting, no extra space is needed between units.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1718 Rev.6
P. 4 / 4