- Home
- Domestic appliances
- Climate control
- Split-system air conditioners
- Trane
- 4TTR4036L
- User manual
- 24 Pages
Trane 4TTR4036L Installer's Manual
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
18-AC89D1-1
Installer’s Guide
Condensing Units
4TTB3018–060
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.
Note: The manufacturer recommends installing only approved matched indoor and outdoor systems. All of the manufacture’s split systems are A.H.R.I. rated only with TXV/EEV indoor systems. Some of the benefits of installing approved matched indoor and outdoor split systems are maximum efficiency, optimum performance and the best overall system reliability.
Table of Contents
Section 1. Safety ..................................................................................... 2
Section 2. Unit Location Considerations.............................................. 3
Section 3. Unit Preparation .................................................................... 5
Section 4. Setting the Unit ..................................................................... 5
Section 5. Refrigerant Line Considerations ......................................... 6
Section 6. Refrigerant Line Routing ..................................................... 7
Section 7. Refrigerant Line Brazing ...................................................... 8
Section 8. Refrigerant Line Leak Check ............................................. 10
Section 9. Evacuation ........................................................................... 11
Section 10. Service Valves ................................................................... 11
Section 11. Electrical - Low Voltage .................................................... 13
Section 12. Electrical - High Voltage ................................................... 16
Section 13. Start Up .............................................................................. 17
Section 14. System Charge Adjustment ............................................. 18
Section 15. Checkout Procedures and Troubleshooting ................... 22
Section 1. Safety
▲
WARNING
This information is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may result in personal injury and/or property damage. The manufacture or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use.
▲
WARNING
These units use R-410A refrigerant which operates at 50 to 70% higher pressures than R-22. Use only
R-410A approved service equipment. Refrigerant cylinders are painted a “Rose” color to indicate the type of refrigerant and may contain a “dip” tube to allow for charging of liquid refrigerant into the system. All R-410A systems use a POE oil that readily absorbs moisture from the atmosphere. To limit this
“hygroscopic” action, the system should remain sealed whenever possible. If a system has been open to the atmosphere for more than 4 hours, the compressor oil must be replaced. Never break a vacuum with air and always change the driers when opening the system for component replacement. For specific handling concerns with R-410A and POE oil reference Retrofit
Bulletins SS-APG006-EN and APP-APG011-EN or
APP-APG012-EN.
▲
WARNING
UNIT CONTAINS R-410A REFRIGERANT!
R-410A operating pressures exceed the limit of R-22.
Proper service equipment is required. Failure to use proper service tools may result in equipment damage or personal injury.
SERVICE
USE ONLY R-410A REFRIGERANT AND AP-
PROVED POE COMPRESSOR OIL.
▲
WARNING
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counterclockwise until the valve stem just touches the rolled edge. No torque is required. Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and /or property damage.
▲
WARNING
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and troubleshooting of this product, it may be necessary to work with live electrical components. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
▲
CAUTION
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
▲
CAUTION
Scroll compressor dome temperatures may be hot. Do not touch the top of compressor; it may cause minor to severe burning.
2 18-AC89D1-1
Section 2. Unit Location Considerations
2.1 Unit Dimensions and Weight
Table 2.1
Unit Dimensions and Weight
Models
4TTB3018E
4TTB3024E
4TTB3030D
4TTB3036D
4TTB3042D
4TTB3048D
4TTB3060D
H x D x W (in)
29 x 30 x 33
29 x 30 x 33
29 x 30 x 33
33 x 30 x 33
29 x 34 x 37
29 x 34 x 37
37 x 34 x 37
* Weight values are estimated.
Weight* (lb)
153
156
173
190
196
203
226
When mounting the outdoor unit on a roof, be sure the roof will support the unit’s weight.
Properly selected isolation is recommended to alleviate sound or vibration transmission to the building structure.
2.2 Refrigerant Piping Limits
1. The maximum length of refrigerant lines from outdoor to indoor unit should NOT exceed sixty (60) feet.
2. The maximum vertical change should not exceed sixty (60) feet.
3. Service valve connection diameters are shown in Table 5.1.
Note: For line lengths greater than sixty (60) feet, Refer to Refrigerant Piping Application
Guide, SS-APG006-EN or Refrigerant Piping
Software Program, 32-3312-03 (or latest revision).
Standard
Line Set
60’ Max
Line Length
60’
Max
Vertical
Change
60’
Max
Vertical
Change
D
W
H
18-AC89D1-1 3
2.3 Suggested Locations for Best Reliability
Ensure the top discharge area is unrestricted for at least five (5) feet above the unit.
Three (3) feet clearance must be provided in front of the control box (access panels) and any other side requiring service.
Do not locate close to bedrooms as operational sounds may be objectionable.
Avoid Install
Near Bedrooms
Min. 12” to
Shrubbery
Min 5’ Unrestricted
Min 3’
Unrestricted
Access Panel
Position the outdoor unit a minimum of 12” from any wall or surrounding shrubbery to ensure adequate airflow.
Outdoor unit location must be far enough away from any structure to prevent excess roof runoff water from pouring directly on the unit.
Min. 12” to
Shrubbery
Min. 12” to Wall
2.4 Coastal Considerations
If installed within one mile of salt water, including seacoasts and inland waterways, models without factory supplied Seacoast Salt Shields require the addition of BAYSEAC001 (Seacoast Kit) at installation time.
4 18-AC89D1-1
Section 3. Unit Preparation
3.1 Prepare The Unit For Installation
STEP 1 - Check for damage and report promptly to the carrier any damage found to the unit.
STEP 2 - To remove the unit from the pallet, remove tabs by cutting with a sharp tool.
Section 4. Setting the Unit
4.1 Pad Installation
When installing the unit on a support pad, such as a concrete slab, consider the following:
• The pad should be at least 1” larger than the unit on all sides.
• The pad must be separate from any structure.
• The pad must be level.
• The pad should be high enough above grade to allow for drainage.
• The pad location must comply with National,
State, and Local codes.
18-AC89D1-1 5
Section 5. Refrigerant Line Considerations
5.1 Refrigerant Line and Service Valve Connection Sizes
Table 5.1
Model
4TTB3018E
4TTB3024E
4TTB3030D
4TTB3036D
4TTB3042D
4TTB3048D
4TTB3060D
Line Sizes
Vapor
Line
Liquid
Line
5/8
5/8
3/4
3/4
3/8
3/8
3/8
3/8
3/4
7/8
7/8
3/8
3/8
3/8
Service Valve Connection Sizes
Vapor Line
Connection
Liquid Line
Connection
5/8
5/8
3/4
3/4
3/8
3/8
3/8
3/8
3/4
7/8
7/8
3/8
3/8
3/8
5.2 Factory Charge
Trane outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit, fifteen (15) feet of tested connecting line, and the smallest indoor evaporative coil match.
If connecting line length exceeds fifteen (15) feet and/or a larger indoor evaporative coil is installed, then final refrigerant charge adjustment is necessary.
5.3 Required Refrigerant Line Length
Determine required line length and lift. You will need this later in STEP 2 of Section 14.
Total Line Length = __________ Ft.
Total Vertical Change (lift) = __________ Ft.
5.4 Refrigerant Line Insulation
Important: The Vapor Line must always be insulated. DO NOT allow the Liquid Line and
Vapor Line to come in direct (metal to metal) contact.
Line Length
Liquid Line
Vapor Line
Insulation
6 18-AC89D1-1
5.5 Reuse Existing Refrigerant Lines
▲
CAUTION
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
For retrofit applications, where the existing indoor evaporator coil and/or refrigerant lines will be used, the following precautions should be taken:
• Ensure that the indoor evaporator coil and refrigerant lines are the correct size.
• Ensure that the refrigerant lines are free of leaks, acid, and oil.
Important: For more information see publication number SS-APG006-EN.
Section 6. Refrigerant Line Routing
6.1 Precautions
Important: Take precautions to prevent noise within the building structure due to vibration transmission from the refrigerant lines.
Comply with National, State, and Local Codes when isolating line sets from joists, rafters, walls, or other structural elements.
For Example:
• When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type hangers.
• Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
• Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
• Isolate the lines from all ductwork.
• Minimize the number of 90º turns.
8 Feet Maximum
Joist/Rafter
Isolator
18-AC89D1-1
Side View
8 Feet Maximum
Secure Vapor line from joists using isolators every 8 ft. Secure
Liquid Line directly to Vapor line using tape, wire, or other appropriate method every 8 ft.
Isolation From Joist/Rafter
Line Set
7
8 Feet Maximum
Wall
Isolator
Line Set
Side View
8 Feet Maximum
Secure Vapor Line using isolators every 8 ft. Secure Liquid Line directly to Vapor Line using tape, wire, or other appropriate method every 8 ft.
Isolation In Wall Spaces
Wall
Sealant
Insulation
Vapor Line
Isolation Through Wall
Section 7. Refrigerant Line Brazing
7.1 Braze The Refrigerant Lines
STEP 1 - Remove caps or plugs. Use a deburing tool to debur the pipe ends. Clean both internal and external surfaces of the tubing using an emery cloth.
Ductwork
Isolator
DO NOT hang line sets from ductwork
Line Set
8 18-AC89D1-1
STEP 2 - Remove the pressure tap cap and valve cores from both service valves.
STEP 3 - Purge the refrigerant lines and indoor coil with dry nitrogen.
STEP 4 - Wrap a wet rag around the valve body to avoid heat damage and continue the dry nitrogen purge.
Braze the refrigerant lines to the service valves.
Continue the dry nitrogen purge. Do not remove the wet rag until all brazing is completed.
Important: Remove the wet rag before stopping the dry nitrogen purge.
NOTE: Precautions should be taken to avoid heat damage to basepan during brazing. It is recommended to keep the flame directly off of the basepane.
18-AC89D1-1 9
STEP 5 - Replace the pressure tap valve cores after the service valves have cooled.
Section 8. Refrigerant Line Leak Check
8.1 Check For Leaks
STEP 1 - Pressurize the refrigerant lines and evaporator coil to 150 PSIG using dry nitrogen.
150 PSIG
STEP 2 - Check for leaks by using a soapy solution or bubbles at each brazed location.
Remove nitrogren pressure and repair any leaks before continuing.
10 18-AC89D1-1
Section 9. Evacuation
9.1 Evacuate the Refrigerant Lines and Indoor Coil
Important: Do not open the service valves until the refrigerant lines and indoor coil leak check and evacuation are complete.
STEP 1 - Evacuate until the micron gauge reads no higher than 350 microns, then close off the valve to the vacuum pump.
STEP 2 - Observe the micron gauge. Evacuation is complete if the micron gauge does not rise above 500 microns in one (1) minute.
Once evacuation is complete blank off the vacuum pump and micron gauge, and close the valves on the manifold gauge set.
0350
Microns
ON OFF
1 MIN.
Section 10. Service Valves
10.1 Open the Gas Service Valve
Important: Leak check and evacuation must be completed before opening the service valves.
NOTE: Do not vent refrigerant gases into the atmosphere
STEP 1 - Remove valve stem cap.
STEP 2 - Using an adjustable wrench, turn valve stem 1/4 turn counterclockwise to the fully open position.
STEP 3 - Replace the valve stem cap to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
CAP
1/4 TURN ONLY
COUNTERCLOCKWISE
FOR FULL OPEN
POSITION
VALVE STEM
UNIT SIDE
OF VALVE
PRESSURE TAP PORT
GAS LINE CONNECTION
18-AC89D1-1 11
10.1 Open the Liquid Service Valve
▲
WARNING
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counterclockwise until the valve stem just touches the rolled edge. No torque is required.
Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and /or property damage.
Important: Leak check and evacuation must be completed before opening the service valves.
STEP 1 - Remove service valve cap.
STEP 2 - Fully insert 3/16” hex wrench into the stem and back out counterclockwise until valve stem just touches the rolled edge (approximately five (5) turns.)
STEP 3 - Replace the valve cap to prevent leaks.
Tighten finger tight plus an additional 1/6 turn.
Cap
Unit Side of Service
Valve
3/16” Hex Wrench
Rolled Edge to
Captivate Stem
Hex Headed
Valve System
Service Port
Section 11. Electrical - Low Voltage
11.1 Low Voltage Maximum Wire Length
Table 11.1 defines the maximum total length of low voltage wiring from the outdoor unit, to the indoor unit, and to the thermostat.
WIRE SIZE
18 AWG
16 AWG
14 AWG
Table 11.1
24 VOLTS
MAX. WIRE LENGTH
150 Ft.
225 Ft.
300 Ft.
12 18-AC89D1-1
11.2 Low Voltage Hook-up Diagrams
Air Handler
Hook-up Diagram
Air Conditioner
Neatly bundle all low voltage wires as shown.
Comfort Control
R
Y1
G
W1
W2
B
Red
Yellow
Green
White
Black
Blue
Air Handler
R
Y
LO
Y
BK
G
W1
W2
W3
B
Yellow
Blue
Yellow
Blue
Notes:
1. If electric heat does not have 3rd contactor (CH), connect a jumper wire from W3 to W2. If electric heat does not have 2nd contactor (BH), connect a jumper wire from W2 to
W1.
2. Ylo and BK may not be present on unit.
Variable Speed Furnace
Hook-up Diagram
Air Conditioner
Neatly bundle all low voltage wires as shown.
Comfort Control
R
Y1
G
W1
W2
B
Red
Yellow
Green
White
Black
Blue
Variable Speed
Furnace
R
BK
Y
Y
G
LO
W1
W2
B
O
Yellow
Blue
Yellow
Blue
18-AC89D1-1
Notes:
1. If single stage heating thermostat is used, jumper
W1-W2 on furnace terminal strip.
13
Communicating Indoor Unit with 24 V Control Hook-up
Diagram
Air Conditioner
Neatly bundle all low voltage wires as shown.
Comfort Control
R
Y1
G
W1
W2
B
Red
Yellow
Green
White
Black
Blue
Comm. Variable Speed
Furnace or Air Handler
R
BK
D
Y1
Y2
G
W1
W2
W3
B
O
Yellow
Blue
Yellow
Blue
Notes:
1. See User Interface setup menu for 24 VAC control mode and cooling CFM options.
2. W3 terminal may not be present on unit.
3. If single stage heating thermostat is used, jumper
W1-W2 on furnace terminal strip.
Communicating Indoor Unit in Comm. Mode
Hook-up Diagram
Air Conditioner
Neatly bundle all low voltage wires as shown.
Communicating
Comfort Control
(*CONT900)
D
R
B
Brown
Red
Blue
Comm. Variable Speed
Furnace or Air Handler
D
R
BK
Y1
Y2
G
W1
W2
W3
B
O
Yellow
Blue
Yellow
Blue
Notes:
1. See User Interface setup menu for cooling
CFM options.
2. W3 terminal may not be present on unit.
14 18-AC89D1-1
*AM7 Air Handler
Hook-up Diagram
Air Conditioner
Neatly bundle all low voltage wires as shown.
Comfort Control
W
G
Y1
O
R
B
Y2
Field wiring
White
Green
Yellow
Red
Blue
Air Handler
W3
W2
W1
G
YI (In)
O
R
B
YO
(Out)
Y2
DH/BK
B - Blue
Y1 - Yellow
Blue
Yellow
Must configure to
“ON” for AC Units.
Must configure to “OFF” for single-stage compressors.
1
R1
U1
R4
Control Board on
HP
1
1
}
Capacity (Tons)
AC (System)
2 (Stages)
2 (Compressor)
S1
R NET 1
R NET 2
CFM/Ton
}
Cool Off Delay
}
INDOOR
on
R13
R14
D9
Torque
C10
R22
S2
+12V
CFM
*AM4 and GAM5 Air Handler
Hook-up Diagram
Comfort Control
White
Green
Yellow
Orange
Red
Blue
W
G
Y
O
R
B
White
Green
Yellow
Red
Blue
Field wiring
18-AC89D1-1
Air Handler
W3
W2
W1
G
YI (In)
O **
R **
B
YO (Out)
B - Blue
Y - Yellow
Air Conditioner
Neatly bundle all low voltage wires as shown.
Blue Yellow
1. * For multiple stages of electric heat, jumper W1,
W2, and W3 together if comfort control has only one stage of heat.
2. ** R to O jumper must be in place as shown for cooling only, non-heat pump systems for proper operation.
3. Yi and Yo connections must be made as shown for freeze protection and internally mounted condensate overflow circuits to work properly.
4. Internally mounted condensate switch is optional and must be ordered separately.
5. If 3rd party condensate overflow switches are installed, they should be wired in series between
YO and Y to the outdoor unit.
15
Section 12. Electrical - High Voltage
12.1 High Voltage Power Supply
▲
WARNING
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and troubleshooting of this product, it may be necessary to work with live electrical components.
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
The high voltage power supply must agree with the equipment nameplate.
Power wiring must comply with national, state, and local codes.
Follow instructions on unit wiring diagram located on the inside of the control box cover and in the
Service Facts document included with the unit.
12.2 High Voltage Disconnect Switch
Install a separate disconnect switch at the outdoor unit.
For high voltage connections, flexible electrical conduit is recommended whenever vibration transmission may create a noise problem within the structure.
12.3 High Voltage Ground
Ground the outdoor unit per national, state, and local code requirements.
16 18-AC89D1-1
Section 13. Start Up
13.1 System Start Up
STEP 1 - Ensure Sections 7 through 12 have been completed.
STEP 2 - Set System Thermostat to OFF.
STEP 3 - Turn on disconnect(s) to apply power to the indoor and outdoor units.
STEP 4 - Wait one (1) hour before starting the unit if compressor crankcase heater accessory is used and the Outdoor Ambient is below
70ºF.
STEP 5 - Set system thermostat to ON.
DONE
OFF
CANCEL
ON
OFF
60 MIN.
DONE
ON
CANCEL
18-AC89D1-1 17
Section 14. System Charge Adjustment
14.1 Temperature Measurements
STEP 1 - Check the outdoor temperatures.
Subcooling (in cooling mode) is the only recommended method of charging above 55º F ambient outdoor temperature.
For best results the indoor temperature should be kept between 70º F to 80º F.
Note: It is important to return in the spring or summer to accurately charge the system in the cooling mode when outdoor ambient temperature is above 55º F.
14.2 Subcooling Charging in Cooling (Above 55º F Outdoor Temp.)
STEP 1 - Use the refrigerant line total length and lift measurements from Section 5.3.
Total Line Length = __________ Ft.
Vertical Change (Lift) = __________ Ft.
LIFT
120º F
55º F
Outdoor Temp
80º F
70º F
Indoor Temp
18 18-AC89D1-1
STEP 2 - Determine the final subcooling value using total Line Length and Lift measured in STEP 1 and the charts below.
1.5 Ton Subcooling Charging Table
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
60
50
40
30
25
20
15
10
0 10 20 25
Add 2º
Add 1º
Use Design Subcool Value (8º)
30 40
TOTAL REFRIGERANT LINE LENGTH (FEET)
60
Add 5º
Add 4º
Add 3º
Add 2º
80
2 and 3 Ton Subcooling Charging Table
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
60
50
40
30
25
20
15
10
0 10 20 25
Add 1º
Add 3º
Add 2º
Use Design Subcool Value (10º)
30 40
TOTAL REFRIGERANT LINE LENGTH (FEET)
60 80
2.5 Ton Subcooling Charging Table
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
60
50
40
30
25
20
15
10
0 10 20 25
Use Design Subcool Value (10º)
30 40
TOTAL REFRIGERANT LINE LENGTH (FEET)
60
Add 3º
Add 2º
Add 1º
80
3.5 Ton Subcooling Charging Table
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
60
50
40
30
25
20
15
10
0 10 20 25 30 40
Add 3º
Add 1º
Add 2º
Use Design Subcool Value (10º)
TOTAL REFRIGERANT LINE LENGTH (FEET)
60
Add 4º
Add 3º
Add 2º
Add 1º
80
4 Ton Subcooling Charging Table
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
60
50
40
30
25
20
15
10
0 10 20 25
Add 1º
Use Design Subcool Value (10º)
30
Add 3º
40
TOTAL REFRIGERANT LINE LENGTH (FEET)
Add 6º
Add 5º
Add 4º
Add 2º
60
Add 7º
Add 6º
Add 5º
Add 3º
80
5 Ton Subcooling Charging Table
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
60
50
40
30
25
20
15
10
0 10 20
Use Design Subcool Value (10º)
25 30
Add 2º
Add 1º
40
TOTAL REFRIGERANT LINE LENGTH (FEET)
Add 5º
Add 4º
Add 3º
Add 2º
Add 1º
60
Add 6º
Add 5º
Add 4º
Add 3º
Add 2º
Add 1º
80
Design Subcooling Value = __________º F
(from nameplate or Service Facts)
Subcooling Correction = __________º F
Final Subcooling Value = __________º F
STEP 3 - Stabilize the system by operating for a minimum of 20 minutes.
At startup, or whenever charge is removed or added, the system must be operated for a minimum of 20 minutes to stabilize before accurate measurements can be made.
18-AC89D1-1
20 MIN.
19
STEP 4 - Measure the liquid line temperature and pressure at the outdoor unit’s service valve.
Measured Liquid Line Temp = __________ º F
Liquid Gage Pressure = __________ PSI
Final Subcooling Value = __________ º F
107 °F
STEP 5 - Use the final subcooling value, refrigerant temperature and pressure from STEP 4, to determine the proper liquid gage pressure using
Table 14.2.
Example: Assume a 12º F Final Subcooling value and liquid temp of 90º F.
1. Locate 12º F Final Subcooling in Table 14.2.
2. Locate the Liquid Temperarature (90º F) in the left column.
3. The Liquid Gage Pressure should be approximately 327 PSI. (This is the shown as the intersection of the Final Subcooling column and the Liquid Temperature row.
90
95
100
105
110
115
120
125
75
80
85
55
60
65
70
Table 14.2
(
°
R-410A REFRIGERANT CHARGING CHART
LIQUID
TEMP
F)
FINAL SUBCOOLING (
°
F)
8 9 10 11 12 13 14
LIQUID GAGE PRESSURE (PSI)
179 182 185 188 191 195 198
195 198 201 204 208 211 215
211 215 218 222 225 229 232
229 232 236 240 243 247 251
247 251 255 259 263 267 271
267 271 275 279 283 287 291
287 291 296 300 304 309 313
309 313 318 322 327 331 336
331 336 341 346 351 355 360
355 360 365 370 376 381 386
381 386 391 396 402 407 413
407 413 418 424 429 435 441
435 441 446 452 458 464 470
464 470 476 482 488 495 501
495 501 507 514 520 527 533
From Dwg. D154557P01 Rev. 3
20 18-AC89D1-1
STEP 6 - Adjust refrigerant level to attain proper gage pressure.
Add refrigerant if the Liquid Gage Pressure is lower than the chart value.
1. Connect gages to refrigerant bottle and unit as illustrated.
2. Purge all hoses.
3. Open bottle.
4. Stop adding refrigerant when liquid line temperature and Liquid Gage
Pressure matches the charging chart
Final Subcooling value.
Recover refrigerant if the Liquid Gage Pressure is higher than the chart value.
STEP 7 - Stabilize the system.
1. Wait 20 minutes for the system condition to stabilize between adjustments.
Note: When the Liquid Line Temperature and
Gage Pressure approximately match the chart, the system is properly charged.
2. Remove gages.
3. Replace service port caps to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
STEP 8 - Verify typical performance.
Refer to System Pressure Tables in the Service
Facts to verify typical performance.
18-AC89D1-1
20 MIN.
(Example only - see Service Facts)
OD **
Coil ****
85
80
75
70
65
60
115
110
105
100
95
901
18
A018
24
B025
Outdoor Size & Coil
30 36
42 3
B031 B036 C043
Liquid Pressure (PSIG)
490 495 495
455
435
405
380
355
330
310
285
270
250
230
460
440
410
380
355
335
310
290
270
250
230
465
435
405
380
355 4
330
305
290
255
245
230
48
C049
495
460
435
405
380
350
330
305
285
265
245
230
60
D064
505
475
450
420
390
365
340
320
295
280
255
235
OD **
Coil ****
Outdoor Temp.
(Degree F)
Indoor Wet Bulb
(Degree F)
110
100
90 1
80
70
60
71
67 2
63
59
71
67
63
59
71
67
63
59
71
67
63
59
71
67
63
59
71
67
63
59
18
A018
24
B025
Outdoor Size & Coil
30
B031
36
B036
42 3
C043
48
C049
60
D064
Suction Pressure (PSIG)
144
135
127
119
141
132
124
116
152
143
135
126
147
139
130
122
138
129
121
113
134
126
118
110
145
136
127
119
141
133
125
117
153
144
135
127
148
140
131
123
138
130
122
114
135
127
119
110
144
135 4
126
117
141
132
123
115
152
142
133
124
147
138
129
121
138
129
121
112
135
126
118
110
145
136
128
120
142
129
125
117
153
145
136
128
149
140
131
123
138
130
122
114
135
127
119
112
142
132
124
116
138
129
121
113
150
141
132
124
146
136
128
119
135
126
118
110
132
123
115
107
21
STEP 9 - Record System Information for reference.
Record system pressures and temperatures after charging is complete.
Outdoor model number = _________________
Measured Outdoor Ambient = __________ º F
Measured Indoor Ambient = __________ º F
Measured Liquid Line Temp = __________ º F
Measured Suction Line Temp = __________ º F
Liquid Gage Pressure = __________ PSI
Suction Gage Pressure = __________ PSI
Section 15. Checkout Procedures and Troubleshooting
15.1 Operational And Checkout Procedures
Final phases of this installation are the unit Operational and Checkout Procedures. To obtain proper performance, all units must be operated and charge adjustments made.
Important: Perform a final unit inspection to be sure that factory tubing has not shifted during shipment. Adjust tubing if necessary so tubes do not rub against each other when the unit runs. Also be sure that wiring connections are tight and properly secured.
CHECKOUT PROCEDURE
After installation has been completed, it is recommended that the entire system be checked against the following list:
1. Leak check refrigerant lines. ........................................ [ ]
2. Properly insulate suction lines and fittings. ................... [ ]
3. Properly secure and isolate all refrigerant lines. ........... [ ]
4. Seal passages through masonry.
If mortar is used, prevent mortar from coming into direct contact with copper tubing. .......................... [ ]
5. Verify that all electrical connections are tight. ............... [ ]
6. Observe outdoor fan during on cycle for clearance and smooth operation. .................................................. [ ]
7. Be sure that indoor coil drain line drains freely. Pour water into drain pan. ............................................................... [ ]
8. Be sure that supply registers and return grilles are open and unobstructed. ......................................................... [ ]
9. Be sure that a return air filter is installed. ..................... [ ]
10. Be sure that the correct airflow setting is used.
(Indoor blower motor) ................................................... [ ]
11. Operate complete system in each mode to ensure safe operation. .................................................. [ ]
22 18-AC89D1-1
15.2 Troubleshooting
SYSTEM FAULTS
W
HA
T T
O
CH
EC
K M
PO
W
HIG
H V
OD
E
ER
S
OLT
AG
CO
UP
PLY
E W
MP
RE
CO
IRIN
G
SS
OR
RU
N C
IO
L
APA
CIT
OR
STA
RT
C
APA
STA
RT
CIT
OR
NTA
CT
OR
R
EL
C
LO
W
CO
NT
VO
LTA
RO
AY
ON
TAC
TS
GE
W
IRIN
L T
RA
NS
FO
G
TH
ER
RM
ER
CO
NTA
MO
LO
STA
T
W
CT
OR
C
VO
LTA
ST
UC
K C
OM
OIL
GE
FU
SE
INE
FF
PR
ES
ICIE
SO
RE
F. U
R
NT
C
ND
OM
P.
ER
CH
RE
F. O
AR
GE
VE
RC
EX
CE
SS
IVE
E
NO
HA
RG
E
VA
P. L
NC
ON
OA
D
DE
NS
RE
S.
O.D
. A
O.D
IR
RE
TX
V/E
AB
LE
S
. A
IRF
CIR
LO
W
CU
LAT
EV
S
TU
CK
IO
N
SU
RE
S.
RE
F. C
O
PE
N
PE
RH
EAT
I.D
. A
IR.
IRF
LO
W
RE
ST
RIC
TIO
SO
V C
SO
V L
NS
CH
OIL
D
EA
KIN
G
*
EC
K V
EF
EC
ALV
DE
FR
OS
TIV
E
E L
EA
DE
FR
OS
T R
EL
KIN
G
T C
ON
AY
D
EF.
TR
OL
D
EF.
REFRIGERANT CIRCUIT
Head Pressure Too High
Head Pressure Too Low
Suction Pressure Too High
Suction Pressure Too Low
Liquid Refrig. Floodback (TXV/EEV)
Liquid Refrig. Floodback
(Cap. Tube)
I.D. Coil Frosting
Compressor Runs
Inadequate or No Cooling/Htg
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
S
S
S
S
S
S
P
P
P
P
P
ELECTRICAL
Compressor & O.D. Fan
Won’t Start
Compressor Will Not Start
But O.D. Fan Runs
O.D. Fan Won’t Start
Compressor Hums But Won’t Start
Compressor Cycles on IOL
I.D. Blower Won’t Start
C
H
C
H
C
H
C
H
C
H
C
H
P
P
P
P
P
P
P
P
P
P
P
P
P
P
S
S
S
S
P
P
P
P
P
P
P
P
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
P
P
P
P
S
S
S
S
P
P
P
P
S
S
P
P
P
P
P
P
S
S
DEFROST
Unit Won’t Initiate Defrost
Defrost Terminates on Time
Unit Icing Up
C
H
C
H
C
H
P
P
C - Cooling H - Heating P - Primary Causes S - Secondary Causes
P
P
P
P
P
P
P
P
P
P
P
P
P
P
S
S
S
S
S
S
S
P
S
S
S
S
S
S
S
*
- 3 Phase Only
S
S
S
S
S
S
S
P
P
S
S
S
S
S
S
S
S
S
S
S
S
S
S
P
P
P
P
P
P
S
S
S
S
S
S
S
S
S
P
P
S
S
S
S
S
S
S
S
S
S
P
P
P
P
P
S
S
P
P
P P
P
P
18-AC89D1-1 23
The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
Representative-only illustrations included in this document.
24
© 2011 Trane U.S.,Inc. 07/11
18-AC89D1-1
advertisement
Related manuals
advertisement
Table of contents
- 2 Section 1. Safety
- 3 Section 2. Unit Location Considerations
- 5 Section 3. Unit Preparation
- 5 Section 4. Setting the Unit
- 6 Section 5. Refrigerant Line Considerations
- 7 Section 6. Refrigerant Line Routing
- 8 Section 7. Refrigerant Line Brazing
- 10 Section 8. Refrigerant Line Leak Check
- 11 Section 9. Evacuation
- 11 Section 10. Service Valves
- 13 Section 11. Electrical - Low Voltage
- 16 Section 12. Electrical - High Voltage
- 17 Section 13. Start Up
- 18 Section 14. System Charge Adjustment
- 22 Section 15. Checkout Procedures and Troubleshooting