Below you will find brief information for Emergency Shower SAFE-T-ZONE SE-623, Eye/Face Wash SE-400. This unit includes a floor mounted emergency deluge shower and aerated eye/face wash combination unit. The shower is supplied with a 1” NPTF stay-open full flow ball valve, activated by triangular pull handle. The eye/face wash is supplied with 1/2” NPTF stay-open full flow ball valve, activated by push handle. The unit should be connected to an uninterrupted source of potable water, with a minimum flowing pressure of 20 PSI and a maximum static pressure of 125 PSI. This unit meets existing ANSI Z358.1 Standards and OSHA Rules.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Emergency Shower SAFE-T-ZONE SE-623 Installation Manual | Manualzz

SPEAKMAN COMPANY

SE-623 Installation, Maintenance & Operation Instructions

SAFE-T-ZONE

® EMERGENCY SHOWER AND EYE/FACE WASH

DESCRIPTION

Floor mounted emergency deluge shower and aerated eye/face wash combination unit. Shower is supplied with a 1” NPTF stay-open full flow ball valve, activated by triangular pull handle. Eye/face wash is supplied with 1/2” NPTF stay-open full flow ball valve, activated by push handle.

SPECIFICATIONS

SHOWER HEAD: 8” Dia. Stainless Steel.

FLOW CONTROL: Internal 20 gpm Regulator.

VALVE: 1” NPT Female Stainless Steel. Full Flow Stay-Open Ball Valve.

ACTIVATOR: Stainless Steel Tube.

STANCHION: 1-1/2” Stainless Steel, 18 Gauge Tubing.

INLET & WASTE: 1-1/4” NPT Male.

FLOOR FLANGE: Stainless Steel With (4) 7/16” Dia. Mounting Holes On 4” Centers.

FINISH: Stainless Steel.

EYE/FACE WASH: SE-400 (Reference additional SE-400 I.M.O. sheet)

SHIPPING WEIGHT: 37 lb.

EMERGENCY SIGN: 12” x 7-7/8” Plastic Wall Sign.

OPTIONS

◊ AL1

(Air Horn Alarm)

◊ AL2

(Electrical Alarm)

◊ XPR

(Extended Pull Rod)

◊ HS

(Hand-held Spray)

◊ AL3

(Electrical Alarm)

◊ PC

(Polished Chrome Shower Head)

◊ AL2-C1D2

◊ AL3-C1D2

(Electrical Alarm / Haz. Area)

◊ BH

(Brass Shower Head)

(Electrical Alarm / Haz. Area)

◊ SPV

(Anti-Scald Protection Valve)

◊ FPV

(Anti-Freeze Protection Valve)

◊ VPL

(Vapor Proof Light)

◊ FLW

(Flow Switch)

◊ HFO

(Hand and Foot Operation)

◊ SGN6

(Combination Floor Sign)

INSTALLATION

When assembling use wrench to tighten connection joints. Be sure and use pipe sealant on all threaded connections. Review drawing (as shown on other side) to assure proper location of inlets, outlets, and accessories.

The best method to assembling this unit is as follows: (1) Mount the bottom stanchion section to the floor using suitable anchors. Then assemble the middle section and then the top section, making sure rubber sealing gasket is seated correctly. (Use pipe sealant on all joints). (2) Rest the eye/face wash bowl on the rubber washer and drain spud, making sure to get the bowl as level as possible. (3) Once bowl is positioned correctly on spud, apply plumbers putty to drain strainer and tighten with hex tool (supplied). (3) Take 1/2” stainless steel flexible hose and connect it to the 1/2” NPTM supply outlet located on stanchion and the 1/2” in-line strainer on eye/face wash. (4)

Assemble pull rod and shower head. (5) Once unit is completely assembled, connect potable water supply to 1-1/4” top inlet, and 1-1/4” waste to bottom outlet. Failure to use potable water can result in emergency units producing impure or contaminated water causing possible further injury. The drain tailpiece or waste should be connected to an adequate drain in compliance with local plumbing codes.

OPERATION

The to discharge water until the valve is manually closed. This is done by pushing up the pull handle to the off position. manually pulled back up to the off position.

TESTING PROGRAM

The American National Standards Institute (ANSI) states that all safety emergency equipment shall be activated

on a weekly basis to flush the line and verify proper operation. Speakman Company furnishes a testing record tag

(91-0635) with each unit. On this tag the date of inspection and the inspector’s initials should be noted.

MAINTENANCE

The valve and the eye/face wash are the only portion of the unit that may require maintenance. Should you need parts to repair this unit, please reference the parts listing below for correct part numbers.

Reference additional technical sheets (supplied) for information on the SE-400 eye/face wash, SE-911-SS valve, and SE-880 shower head. Before any maintenance is done be sure to shut the water

supply off.

WARNING: Use only genuine Speakman parts when repairing

or replacing components. To order parts call 1-800-537-2107.

SE-623 REPLACEMENT/REPAIR PARTS

ITEM PART/GROUP # DESCRIPTION

1

2

SE-911-SS

SE-880

1” Ball Valve with Pull Rod

8” Stainless Steel Shower head

3

4

5

G47-0043

SE-400

63-0027

G74-0032-SS

S/S Flexible Hose

6

FLOW DATA

SHOWER:

FLOW PRESSURE PSI (BAR)

FLOW RATE GPM (LPM)

30 (2.07)

20 (75)

60 (4.14)

25 (94)

EYE/FACE WASH:

FLOW PRESSURE PSI (BAR)

FLOW RATE GPM (LPM)

30 (2.07)

9.55 (36.6)

NOTE: This unit should be connected to an uninterrupted source of potable water, with a minimum flowing pressure of 20 PSI and a maximum static pressure of 125 PSI.

Note: All units meet existing

ANSI Z358.1 Standards and

OSHA Rules. Product improvements may cause specification and dimensional changes without notice.

2/06

92-1492 Rev-8

advertisement

Key Features

  • Floor mounted
  • Deluge shower
  • Aerated eye/face wash
  • Stay-open full flow ball valve
  • Triangular pull handle
  • Push handle
  • ANSI Z358.1 Standards
  • OSHA Rules

Frequently Answers and Questions

How do I activate the shower?
Pull the triangle pull handle. The shower will continue to discharge water until the valve is manually closed by pushing up the pull handle to the off position.
How do I activate the eye/face wash?
Push the push handle back 90°. The unit will operate until the push handle is manually pulled back up to the off position.
What is the recommended testing program?
Activate the unit weekly to flush the line and verify proper operation. Use the provided testing record tag (91-0635) to note the date of inspection and the inspector's initials.
What kind of water should I use?
Use potable water only. Failure to use potable water can result in emergency units producing impure or contaminated water causing possible further injury.
Where should I connect the drain tailpiece?
Connect the drain tailpiece or waste to an adequate drain in compliance with local plumbing codes.