Allen Bradley smáspóluefni
MCS MINIATURE CONTACTORS
SELECTION GUIDE
THE MINIATURE MODULAR CONTROL SYSTEM
SMALL IN DIMENSIONS - BIG IN PERFORMANCE
DOL-Starter
Overload Protection
Short Circuit Protection
DOL-Starter
Overload Protection
PROTECTION FOR
AC AND DC MOTORS
• The Bulletin 193-K thermal
overload relay is designed to
work with Bulletin 100-K mini
contactors.
• Sensitivity under phase
loss conditions through
differential mechanism.
• Temperature compensated for
precise motor protection from
-20°C to + 60°C.
SHORT CIRCUIT PROTECTION
RELIABILITY
• The Bulletin 140-M motor protection
circuit breaker is the ideal device for
economic and compact starter solutions
providing short circuit and motor
overload protection.
• The excellent breaking capacity provides
effective, fast shut-off in case of
short-circuits, limiting equipment damage.
Reversing Starter
For Reversing Motors
Overload Protection
Short Circuit Protection
REVERSING AND
STAR-DELTA STARTERS
• Sensitivity under phase loss conditions
through differential mechanism.
• With the Bulletin 100-K mini
contactor and the Bulletin 140-M
circuit breaker, it’s easier than ever
to assemble reversing and
star-delta starters.
• Temperature compensated for precise
motor protection from -20°C to + 60°C.
• Connection kit for easy and timesaving wiring.
• Only one DIN Rail required for the
complete starter.
THE NEW MINIATURE CONTACTOR FROM ROCKWELL AUTOMATION:
• Switching and protection of
DOL or reversing motors up to
5.5 kW at 400V and 690V.
• Switching of illumination or
heating loads up to 20 A.
• Reliability for switching of
signals down to 15V/2 mA.
ON-MACHINE CONTROLS
2
INDUSTRIAL PRODUCTION
COST- AND SPACE-SAVING MOTOR CONTROL HAS A NEW NAME
Reversing power
wiring kit
RATED 690V
104-K AC/DC
Miniature reversing
contactor up to
5.5 kW
ROHS COMPLIANT
CONFORMING TO US, CANADIAN,
AND IEC STANDARDS
SAME DIMENSIONS FOR AC AND DC
Mechanical interlock
for AC/DC contactors
Plug-in surge
suppressor modules
2-pole/4-pole
Auxiliary
contact block
Feeder terminal for
compact bus bars
Three-phase compact bus
bars for feeding up to four
contactors.
Additional contactors can be
added by interconnecting
the bus bars.
STATE-OF-THE-ART CONTROL FOR YOUR APPLICATIONS
LAUNDRY EQUIPMENT
LIGHTNING AND HVAC
PUMPS AND IRRIGATION
3
9 mm
36 mm
TIME-SAVING
FEATURES
PLUGGABLE SURGE
SUPPRESSOR MODULES
COMPACT AUXILIARY
CONTACT BLOCKS
• Suppressor modules are simply
plugged on the front of the
contactors, next to the auxiliary
contact blocks.
• The front pluggable auxiliary contact
blocks are 36 mm wide, leaving space
for a 9 mm wide surge suppressor
module next to it.
• No wiring required: fast and
easy installation.
• Large variety of contact configurations.
MIRROR AND MECHANICALLY LINKED DESIGN
1
3
5
23
21
31
A1
Adder
Deck
Main
Unit
Off
A2
2
4
22
6
a
2a ≥ 0.5 mm
HIGH FLEXIBILITY CONFIGURATION
FOR REVERSING CONTACTORS
• The front pluggable mechanical interlock
for AC and DC contactors allows top
mounting of auxiliary contact blocks and
surge suppressor modules.
• High flexibility for easy tailoring to
application needs.
• All front-mounted modules
are pluggable.
• Sturdy, molded, reversing wiring kits make
the assembly fast and easy.
4
24
32
a
2a ≥ 0.5 mm
ALL-AROUND SAFETY
• 100-K: Mechanically linked performance between main contacts and
internal auxiliary contacts. This feature provides status feedback in the
event of a contact weld.
• 100-K/100-KF: Mirror contact between main and auxiliary contacts as
per IEC 60947-4-1 prevent any status condition if a N.O. power pole
welds.
CHOICE OF
MODULAR STARTERS
• Compact Two-Component Starters using
Bulletin 140-M motor circuit protector
and Bulletin 100-K mini contactors.
• Three-Component Starters with fuse
holders, Bulletin 100-K mini contactors,
and Bulletin 193-K bimetal overload
relays.
• Three-component starters using Bulletin
140M motor circuit protector, Bulletin
100-K mini-contactor and Bulletin
193-K overload relay.
PARALLEL 3-PHASE FEEDING
OF CONTACTORS
• Versions for feeding three or four
contactors; extension is possible.
30 V
125 %
6 mm
SAFETY MARGIN
FOR OVER VOLTAGE
IEC/EN 60947:
MCS MINI
24 V
100 %
85 % - 110 %
71 % - 125 %
VOLTAGE
26,4 V
110 %
20,4 V
85 %
SAFETY MARGIN
FOR UNDER VOLTAGE
71 %
CONTACT RELIABILITY
• Bifurcated, AgNi (silver/nickel)-plated
contacts for high contact reliability for
15V/2 mA electronic signals.
• H-shaped self cleaning auxiliary
contacts provide a 4-way current path
enabling contact reliability
for low energy switching.
17 V
HIGH PERFORMANCE
AC AND DC COILS
• Wide-range DC coils can provide
reliability in case of over- and undervoltage, a common issue with batteryfed control power supply systems.
• The low coil consumption allows the
contactors to be directly controlled
via a PLC.
OPERATOR SAFETY
• 6 mm distance from housing surface
to live parts enables compliance with
dielectric voltage test requirements per
IEC 60947-1 edition 4.
• Increased operator protection against
contact with contactor terminals.
• Optional, integral factory-installed surge
suppressor modules for AC and DC for
limiting coil switching transients.
5
Bulletin 100-K, 700-K, 193-K, 140M, 140F
IEC Miniature Contactors
Selection Overview
IEC Miniature Contactors
• Bulletin 100/104-K Miniature Contactors
Page 8
IEC Miniature Control Relays
• Bulletin 700-K Miniature Control Relays
Page 12
IEC Miniature Thermal Overload Relays
• Bulletin 193-K Miniature Thermal Overload Relays
Page 15
IEC Circuit Breakers
• Bulletin 140M Circuit Breakers
Page 16
• Bulletin 140M Fuse Holders
Page 17
IEC Miniature Starter Selection
• Selection
Rockwell Automation
Page 21
Visit our website: www.ab.com/catalogs
7
Bulletin 100/104-K
IEC Miniature Contactors
Overview/Product Selection
Table of Contents
Bulletin 100-K / 104-K IEC Contactors
Compact size
Product Selection .... this page
Same dimensions for AC and DC
Accessories................ 10
Full-voltage non-reversing and reversing contactors
Specifications............ 22
5, 9, and 12 A Contactors rated at 690V
Approximate
IP2X Finger Protection
Dimensions................. 31
Optional integrated surge suppressor
Compatible with Bulletin 193-K bimetallic overload relay
Standards Compliance
Mirror contacts per IEC 60947-4-1 and mechanically linked contacts IEC/EN 60947-1,-4-1,-5-1,-5-4
per IEC 60947-5-1 on main unit
UL 508
CSA 22.2. No. 14
NF F 62-000
Approvals
CE marked
cULus listed (File No. E41850,
Guide No. NLDX and NLDX7)
Allen-Bradley Bulletin 100-K miniature contactors are designed for commercial and light industrial applications where panel space is at a
premium. These miniature devices, while 45 mm wide, are shallower and have less panel depth requirements than standard IEC
contactors.
The miniature contactors have been designed with flexibility in mind. They are available with AC or DC operating coils, several contact
ratings, and optional 2- or 4-pole adder decks in a variety of auxiliary contact configurations.
Your order must include: cat. no. (with coil voltage code) of the mini contactor specified and, if required, cat. no. of any accessories
Miniature Contactors
Non-Reversing Mini-Contactors — 3 N.O. Power Poles with Auxiliary Contact
Rated
Operational
Current Ie [A]
Ratings for switching AC motors - AC-2, AC-3, AC-4
3Ø kW (50 Hz)
Hp (60 Hz)
40 °C
AC-1
20
20
20
1Ø
230V
1.5
3
3
400/415V
2.2
4
5.5
500V
2.2
4
5.5
Auxiliary Contacts
690V
2.2
4
5.5
115V
1/2
1/2
3/4
3Ø
230V
1
1-1/2
2
200V
1-1/2
2
3
230V
1-1/2
2
3
460V
3
5
7-1/2
575V
3
5
7-1/2
N.O.
N.C.
Pkg.
Qty.1
Cat. No.
1
0
1
100-K05⊗10
0
1
1
100-K05⊗01
1
0
1
100-K09⊗10
0
1
1
100-K09⊗01
1
0
1
100-K12⊗10
0
1
1
100-K12⊗01
1 May be ordered in package quantities of 20. Add letter M to the end of the cat. no. Example: 100-K09ZJ10M.
⊗ The Cat. No. as listed is incomplete. Select a Coil Voltage Code from the table on page 9 to complete the Cat. No.
⊗10 becomes Cat. No. 100-K05ZJ10.
Example: 24V DC: Cat. No. 100-K05⊗
8
Visit our website: www.ab.com/catalogs
Rockwell Automation
Bulletin 100/104-K
IEC Miniature Contactors
Product Selection
Non-Reversing Mini-Contactors — 4 Power Poles
Rated
Operational
Current Ie [A]
3Ø kW (50 Hz)
Hp (60 Hz)
40 °C
AC-1
20
Contact Configuration,
Main Pole
Ratings for switching AC motors - AC-2, AC-3
1Ø
230V
400/415V
1.5
20
2.2
3
20
500V
2.2
4
3
690V
2.2
4
5.5
115V
1/2
4
5.5
3Ø
230V
1/2
5.5
200V
1
1-1/2
1-1/2
3/4
230V
1-1/2
2
2
2
3
460V
575V
3
3
5
3
5
7-1/2
7-1/2
N.O.
N.C.
Pkg.
Qty.1
Cat. No.
4
0
1
100-K05⊗400
3
1
1
100-K05⊗300
2
2
1
100-K05⊗200
4
0
1
100-K09⊗400
3
1
1
100-K09⊗300
2
2
1
100-K09⊗200
4
0
1
100-K12⊗400
3
1
1
100-K12⊗300
2
2
1
100-K12⊗200
1 May be ordered in package quantities of 20. Add letter M to the end of the cat. no. Example: 100-K09ZJ400M.
⊗ The Cat. No. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the Cat. No.
⊗400 becomes Cat. No. 100-K05ZJ400.
Example: 24V DC: Cat. No. 100-K05⊗
Reversing Mini-Contactors — 3 N.O. Power Poles with Auxiliary Contact
Rated
Operational
Current Ie [A]
Auxiliary Contacts
per Contactor1
Ratings for switching AC motors - AC-2, AC-3, AC-4
3Ø kW (50 Hz)
Hp (60 Hz)
40 °C
1Ø
3Ø
AC-1
230V
400/415V
500V
690V
115V
230V
200V
230V
460V
575V
N.O.
N.C.
Cat. No.
20
1.5
2.2
2.2
2.2
—
—
1-1/2
1-1/2
3
3
0
1
104-K05⊗02
20
3
4
4
4
—
—
2
2
5
5
0
1
104-K09⊗02
20
3
5.5
5.5
5.5
—
—
3
3
7-1/2
7-1/2
0
1
104-K12⊗02
1 Used for electrical interlocking
⊗ The Cat. No. as listed is incomplete. Select a standard Coil Voltage Code from the table below to complete the Cat. No.
⊗02 becomes Cat. No. 104-K05KF02.
Example: 230V, 50/60 Hz: Cat. No. 104-K05⊗
Bulletin 104-K reversing contactors are factory assembled and include contactors, mechanical interlock (Cat. No. 100-KMCH) and wiring kit (Cat. No. 100KPR) for power and control circuit (electrical interlock).
⊗ Coil Voltage Code
The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60 Hz:
Cat. No. 100-K09⊗10 becomes Cat. No.100-K09D10.
AC Voltages [V]
24
110
120
230
240
400
480
50 Hz
—
D
—
—
—
—
—
—
60 Hz
—
—
D
—
—
—
B
VC
50/60 Hz
KJ
—
—
KF
KA
KN
—
—
DC Voltages [V]
12
24
110
125
220
250
Standard
ZQ
ZJ
ZD
ZS
ZA
ZT
with Integrated Diode
—
DJ
—
—
—
—
600
For other voltages, see table on page 31
Rockwell Automation
Visit our website: www.ab.com/catalogs
9
Bulletin 100-K, 700-K, 193-K, 140M, 140F
IEC Miniature Contactors
Accessories
Auxiliary Contact Blocks
Connection
Diagrams
Description
Pkg.
Qty. 1
Cat. No.
2
100K05…K12⊗10
1
100-KFC02
1
1
100K05…K12⊗10
1
100-KFC11
2
0
100K05…K12⊗10
1
100-KFC20
0
4
100K05…K12⊗10
1
100-KFC04
1
3
100K05…K12⊗10
1
100-KFC13
3
1
100K05…K12⊗10
1
100-KFC31
2
2
100K05…K12⊗10
1
100-KFC22
4
0
100K05…K12⊗10
1
100-KFC40
0
2
100/104-K,
700-K
1
100-KFA02E
1
1
100/104-K,
700-K
1
100-KFA11E
2
0
100/104-K,
700-K
1
100-KFA20E
0
4
100/104-K,
700-K
1
100-KFA04E
1
3
100/104-K,
700-K
1
100-KFA13E
2
2
100/104-K,
700-K
1
100-KFA22Z
3
1
100/104-K,
700-K
1
100-KFA31Z
4
0
100/104-K,
700-K
1
100-KFA40E
Pkg.
Qty.
Cat. No.
1
100-KMCH
N.C.
For Use With
0
N.O.
21 31
22 32
23 31
24 32
23 33
24 34
21 31 41 51
22 32 42 52
23 31 41 51
24 32 42 52
23 43 53 31
24 44 54 32
23 53 31 41
Front-mounted auxiliary contacts
Auxiliary Contact Blocks
2- and 4-pole versions
Choice of contact configurations
Snap on, no tools required
Electronic-compatible bifurcated contacts for signals down
to 15V/2 mA
Mirror Contact performance per IEC 60947-4-1
24 54 32 42
23 33 43 53
24 34 44 54
51 61
52 62
53 61
54 62
53 63
54 64
51 61 71 81
52 62 72 82
53 61 71 81
54 62 72 82
53 83 61 71
54 84 62 72
53 73 83 61
54 74 84 62
53 63 73 83
54 64 74 84
Control Modules
Connection
Diagrams
Description
Mechanical Interlock
For interlocking of two adjacent contactors
No added width to contactor assembly
Front mount Plug-In type
Optional auxiliary contact blocks and suppressor modules mount
onto the interlock
For Use With
100-K, 700-K
(AC & DC
Control)
11
100-KFSC50
11
100-KFSC280
380…480V AC
11
100-KFSC480
12…55V AC,
12…77V DC
11
100-KFSV55
11
100-KFSV136
11
100-KFSV277
11
100-KFSD250
24…48V AC
R-C Suppressor
Surge Suppressor
Plug-in Type
Limits surge voltage on coil MOV Suppressor
drop-off
Diode
Suppressor
110…280V AC
56…136V AC,
78…180V DC
100/104-K,
700-K
100/104-K,
700-K
137…277V AC,
181…250V DC
12…250V DC
100/104-K,
700-K
1 May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFSC50M.
10
Visit our website: www.ab.com/catalogs
Rockwell Automation
Bulletin 100-K, 700-K, 193-K, 140M, 140F
IEC Miniature Contactors
Accessories
Connecting Components
Description
For Use With
Pkg.
Qty.
Cat. No.
ECO Connecting Module
For DOL and reversing starters
Provides electrical and mechanical link
Connects:
140M-C circuit breakers with 100-K
contactors
140M-C to 100-K
11
140M-C-PEK12
Power Wiring Kit
For Reversing and Star/Delta
combinations. Star-point bridge not
included.
100-K
1
100-KPR
Supply of compact bus bars
100-K
1
100-KWT
For 100-K, 5…12 A contactors
45 mm spacing (3 connections)
100-K
1
100-KW453
For 100-K, 5…12 A contactors
45 mm spacing (4 connections)
100-K
1
100-KW454
Pkg.
Qty.
Cat. No.
Feeder Terminal for Compact Bus
Bars
Three-Phase Compact Bus Bars
1 May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 140M-C-PEK12M.
Combinations possible. Example: For 6 contactor connections use one cat. no. 100-KW453 and one cat. no. 100-KW454.
Timers
Connection
Diagrams
Description
For Use With
~
On-Delay,
0.1…3 s
S1
O/I
100-KT3S
1
Solid-State Timing Element
110…250V AC or DC
100/104-K, 700-K
10
2
On-Delay,
1…30 s
100-KT30S
K1
N
Star-Delta Timer
After the set time
has elapsed, the 110…120V 50/60
Hz
K3 contactor (Y) is
de-energized and
then after a time
220…250V 50/60
of 90 ± 30 ms the
Hz
K2 Contactor
(Delta) is
48V AC 50/60 Hz
energized.
35 mm DIN Rail Mounting Adapter
For easy mounting of timer modules on standard DIN Rail
100-KTSDA1
100/104-K, 700-K
10
100-KTSDA2
100-KTSDA3
10
100-KTM
Pkg.
Qty.
Cat. No.
Label Sheet
10 sheets with 105 self-adhesive paper labels each, 6 x 17 mm
10
100-FMS
Snap-In Hinged Marker Card
5
1492-MH6X12
100-KT
Marking Systems
Description
Rockwell Automation
Visit our website: www.ab.com/catalogs
11
Bulletin 700-K
IEC Miniature Control Relays
Overview/Product Selection
Bulletin 700-K Miniature Control Relays
Table of Contents
IEC compact industrial relay
IP2X Finger Protection
Bifurcated contacts for low-level signals
Optional integrated coil protection diode
Product Selection .... this page
Accessories................ 13
Specifications............ 27
Approximate
Dimensions ................ 31
Standards Compliance
IEC/EN 60947-1,-5-1,-5-4
UL 508
CSA 22.2. No. 14
NF F 62-000
Approvals
CE marked
cULus listed (File No. E33916,
Guide No. NKCR and NKCR7)
4-Pole AC or DC Coil Voltage
AC-12
AC-15 (B600)
Ie [A]
40 °C
Contacts
Ie [A]
60 °C
24/48V
120V
240V
400V
500V
600V
690V
Connection
Diagrams
N.O.
N.C.
Pkg.
Qty. 1
Cat. No.
4
0
1
700-K40E-⊗
3
1
1
700-K31Z-⊗
2
2
1
700-K22Z-⊗
1
700-KL22Z-⊗
A1 13 23 33 43
A2 14 24 34 44
A1 13 33 43 21
10
6
3
3
2
1.2
1
0.6
0.6
A2 14 34 44 22
A1 13 43 21 31
A2 14 44 22 32
A1 13 47 21 35
1+1L 1+1L
A2 14 48 22 36
1 May be ordered in package quantities of 20. Add letter M to the end of the cat. no. Example: 700-K40E-ZJM.
1L = Late break N.C./early make N.O.
⊗ The Cat. No. as listed is incomplete. Select a Coil Voltage Code from the table below to complete the Cat. No.
⊗ becomes Cat. No. 700-K40E-ZJ.
Example: 24V DC: Cat. No. 700-K40E-⊗
⊗ Coil Voltage Code
The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60 Hz:
Cat. No. 700-K40E⊗ becomes Cat. No. 700-K40E-D.
AC Voltages [V]
24
110
120
230
240
400
480
50 Hz
—
D
—
—
—
—
—
—
60 Hz
—
—
D
—
—
—
B
VC
50/60 Hz
KJ
—
—
KF
KA
KN
—
—
DC Voltages [V]
12
24
110
125
220
250
Standard
ZQ
ZJ
ZD
ZS
ZA
ZT
with Integrated Diode
—
DJ
—
—
—
—
600
For other voltages, see table on page 31
12
Visit our website: www.ab.com/catalogs
Rockwell Automation
Bulletin 700-K
IEC Miniature Control Relays
Accessories
Auxiliary Contact Blocks
Connection
Diagrams
Pkg.
Qty. 1
Cat. No.
100/104-K,
700-K
1
100-KFA02E
1
100/104-K,
700-K
1
100-KFA11E
2
0
100/104-K,
700-K
1
100-KFA20E
0
4
100/104-K,
700-K
1
100-KFA04E
1
3
100/104-K,
700-K
1
100-KFA13E
2
2
100/104-K,
700-K
1
100-KFA22Z
3
1
100/104-K,
700-K
1
100-KFA31Z
4
0
100/104-K,
700-K
1
100-KFA40E
Pkg.
Qty.
Cat. No.
100-K, 700-K
(AC & DC
Control)
1
100-KMCH
11
100-KFSC50
100/104-K,
700-K
11
100-KFSC280
380…480V AC
11
100-KFSC480
12…55V AC,
12…77V DC
11
100-KFSV55
11
100-KFSV136
11
100-KFSV277
11
100-KFSD250
Description
N.O.
N.C.
For Use With
0
2
1
51 61
52 62
53 61
54 62
53 63
54 64
Front-mounted auxiliary contacts
Auxiliary Contact Blocks
2- and 4-pole versions
Choice of contact configurations
Snap on, no tools required
Electronic-compatible bifurcated contacts for signals
down to 15V/2 mA
51 61 71 81
52 62 72 82
53 61 71 81
54 62 72 82
53 83 61 71
54 84 62 72
53 73 83 61
54 74 84 62
53 63 73 83
54 64 74 84
1 May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFA02EM.
Control Modules
Connection
Diagrams
Description
Mechanical Interlock
For interlocking of two adjacent contactors
No added width to contactor assembly
Front mount Plug-In type
Optional auxiliary contact blocks and suppressor modules mount
onto the interlock
For Use With
24…48V AC
R-C Suppressor
Surge Suppressor
Plug-in Type
Limits surge voltage on coil MOV Suppressor
drop-off
Diode Suppressor
110…280V AC
56…136V AC,
78…180V DC
100/104-K,
700-K
137…277V AC,
181…250V DC
12…250V DC
100/104-K,
700-K
1 May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFSC50M.
Rockwell Automation
Visit our website: www.ab.com/catalogs
13
Bulletin 700-K
IEC Miniature Control Relays
Accessories
Timers
Connection
Diagrams
Description
Pkg.
Qty.
For Use With
Cat. No.
~
On-Delay,
0.1…3 s
S1
O/I
100-KT3S
1
Solid-State Timing Element
110…250V AC or DC
100/104-K, 700-K
10
2
On-Delay,
1…30 s
100-KT30S
K1
N
35 mm DIN Rail Mounting Adapter
For easy mounting of timer modules on standard DIN Rail
10
100-KTM
Pkg.
Qty.
Cat. No.
Label Sheet
10 sheets with 105 self-adhesive paper labels each, 6 x 17 mm
10
100-FMS
Snap-In Hinged Marker Card
5
1492-MH6X12
100-KT
Marking Systems
Description
14
Visit our website: www.ab.com/catalogs
Rockwell Automation
Bulletin 193-K
IEC Miniature Thermal Overload Relays
Overview/Product Selection
Bulletin 193-K — Miniature Bimetallic Overload Relays
Table of Contents
Standard motor protection for AC and DC motors
Overload protection Trip Class 10A
Auxiliary switch (1 N.O. and 1 N.C.)
Phase loss sensitivity
Manual/Auto reset button
Test release
Stop button
Trip indicator
Product Selection .... this page
Accessories................ this page
Specifications............ 29
Approximate
Dimensions ................ 31
Conformity to Standards
IEC/EN 60947-1,-4-1,-5-1
UL 508
CSA 22.2. No. 14
Bulletin 193-K bimetallic overload relays are designed for use with
Bulletin 100-K contactors and Bulletin 104-K Reversing
Contactors. These class 10A ambient temperature-compensated
thermal overload relays include a differential mechanism for
sensitivity to phase-loss conditions.
Approvals
CE marked
cULus listed (File No. E33916,
Guide No. NKCR)
Miniature Bimetallic Overload Relays
Max. Current Rating Backup gG Fuse [A]
IEC Coordination Type
Mounts to Contactor
100-K05…100-K12
100-K09…100-K12
100-K12
Setting Range [A] 1
0.10…0.16
Type 1
35
Type 2
—
Cat. No.
193-KA16
0.16…0.25
35
—
193-KA25
0.25…0.40
35
2
193-KA40
0.35…0.50
35
2
193-KA50
0.45…0.63
35
2
193-KA63
0.55…0.80
35
4
193-KA80
0.75…1.0
35
4
193-KB10
0.9…1.3
35
6
193-KB13
1.1…1.6
35
6
193-KB16
1.4…2.0
35
10
193-KB20
1.8…2.5
35
20
193-KB25
2.3…3.2
35
20
193-KB32
2.9…4.0
35
20
193-KB40
3.5…4.8
35
20
193-KB48
4.5…6.3
35
20
193-KB63
5.5…7.5
35
20
193-KB75
7.2…10.0
35
20
193-KC10
9.0…12.5
35
20
193-KC12
1 To select the setting range for use in Y-Δ Starters, multiply the rated operating current of the motor by a factor of 0.58.
For motors with Service Factor of 1.15 or greater, use motor nameplate full load current. For motors with service factor of 1.0, use 90% of the motor
nameplate full load current.
Rockwell Automation
Visit our website: www.ab.com/catalogs
15
Bulletin 140M
IEC Circuit Breakers
Overview/Product Selection
Bulletin 140M Motor Protection Circuit Breakers
Table of Contents
Current Range 0.1…25 A
UL Listed for motor loads
− Short-circuit protection
− Overload protection
Visible trip indication
− Additional short-circuit trip identification
High current limiting
High switching capacity
Product Selection.... this page
Accessories ............... 18
Conformity to Standards
IEC/EN 60947-1,-2,-4-1,-5-1
UL 508
CSA 22.2. No. 14
NF F 62-000
Approvals
Bulletin 140M Motor Protection Circuit Breakers provide shortcircuit and overload protection for individual motor loads. Fieldinstalled accessories make installation and wiring easy.
CE marked
cULus listed (File No.
E54612, Guide No. NLRV and
NLRV7)
Product Selection — Motor Protection Circuit Breakers
Short-circuit protection — standard magnetic trip (fixed at 13 x Ie)
Motor overload protection — Trip Class 10
Ultimate
Motor
Interrupting
Rated
Current
Magnetic
Current [kA]
Operational Adjustment
Trip
(Icu)
Current (Ie)
Range
Current
[A]
[A]
400V 480V
[A]
3-phase Hp Ratings [Hp]1
Max. kW, 3-Phase
230V
400/415V
500V
690V
200V
230V
460V
575V
Cat. No.
C-Frame
0.16 A
0.10…0.16
2.1
100
65
—
0.02
—
—
—
—
—
—
140M-C2E-A16
0.25 A
0.16…0.25
3.3
100
65
—
0.06
—
—
—
—
—
—
140M-C2E-A25
0.40 A
0.25…0.40
5.2
100
65
—
0.09
—
—
—
—
—
—
140M-C2E-A40
0.63 A
0.40…0.63
8.2
100
65
0.18
0.25
—
—
—
—
140M-C2E-A63
1.0 A
0.63…1.0
13
100
65
—
—
—
0.5
140M-C2E-B10
1.6 A
1.0…1.6
21
100
65
—
—
0.5...0.75
0.75
140M-C2E-B16
2.5 A
1.6…2.5
33
100
65
0.37
0.75
1.1
1.8
0.5
0.5
0.75...1
1...1.5
140M-C2E-B25
4.0 A
2.5…4.0
52
100
65
0.55...0.75
1.1...1.5
1.5...2.2
2.2...3.0
0.75
0.75
1.5...2
2...3
140M-C2E-B40
6.3 A
4.0…6.3
82
100
65
1.1...1.5
2.2
2.5...3.0
4.0
1
1...1.5
3
5
140M-C2E-B63
10 A
6.3…10
130
100
65
2.2
3.0...4.0
4.0...6.3
5.5...7.5
1.5...2
2...3
5
7.5
140M-C2E-C10
16 A
10…16
208
50
30
3.0...4.0
5.5...7.5
7.5...10
11...13
3
—
7.5...10
10
140M-C2E-C16
20 A
14.5…20
260
15
30
4.0...5.5
7.5...10
11
15...17
5
5
—
15
140M-C2E-C20
25 A
18…25
325
15
25
—
11
15
18.5...22
—
7.5
15
20
140M-C2E-C25
0.06...0.09 0.12...0.18
0.12
0.25
0.25...0.37 0.37...0.55
0.18...0.25 0.37...0.55 0.55...0.75 0.75...1.1
1 Horsepower/kW ratings shown in the table above are for reference. The final selection of the MPCB depends on the actual motor full load current and
service factor.
16
Visit our website: www.ab.com/catalogs
Rockwell Automation
Bulletin 140M, 140F
IEC Circuit Breakers
Accessories
Motor Circuit Protectors
Short-circuit protection — standard magnetic trip (fixed at 13 x Ie)
No motor overload protection, only magnetic trip
For Trip Class 10 motor applications
Separate overload relay required for motor protection
Rated
Magnetic
Operational
Trip
Current [A] Current
(Ie)
[A]
Ultimate
Interrupting
Current [kA], (Icm)
400V
480V
3-phase Hp Ratings [Hp]1
3-phase kW Ratings
230V
400/415V
500V
690V
200V
230V
460V
575V
Cat. No.
C-Frame
0.16 A
2.1
100
65
—
0.02
—
—
—
—
—
—
140M-C2N-A16
0.25 A
3.3
100
65
—
0.06
—
—
—
—
—
—
140M-C2N-A25
0.40 A
5.2
100
65
—
0.09
—
—
—
—
—
—
140M-C2N-A40
0.63 A
8.2
100
65
0.06...0.09
0.12...0.18
0.18
0.25
—
—
—
—
140M-C2N-A63
1.0 A
13
100
65
0.12
0.25
0.25...0.37
0.37...0.55
—
—
—
0.5
140M-C2N-B10
1.6 A
21
100
65
0.18...0.25
0.37...0.55
0.55...0.75
0.75...1.1
—
—
0.5...0.7
5
0.75
140M-C2N-B16
2.5 A
33
100
65
0.37
0.75
1.1
1.8
0.5
0.5
0.75-1
1...1.5
140M-C2N-B25
D-Frame
2.5 A
33
100
65
0.37
0.75
1.1
1.8
0.5
0.5
0.75...1
1...1.5
140M-D8N-B25
4.0 A
52
100
65
0.55...0.75
1.1...1.5
1.5...2.2
2.2...3.0
0.75
0.75
1.5...2
2...3
140M-D8N-B40
6.3 A
82
100
65
1.1...1.5
2.2
2.5...3.0
4.0
1
1...1.5
3
5
140M-D8N-B63
10 A
130
100
65
2.2
3.0...4.0
4.0...6.3
5.5...7.5
1.5...2
2...3
5
7.5
140M-D8N-C10
16 A
208
100
65
3.0...4.0
5.5...7.5
7.5...10
11...13
3
—
7.5...10
10
140M-D8N-C16
25 A
325
50
65
—
11
15
18.5...22
5
5...7.5
15
15...20
140M-D8N-C25
1 Horsepower/kW ratings shown in the table above are for reference. The final selection of the manual starter depends on the actual motor full load
current and service factor.
For Heavy Duty (exceeding Trip Class 10) starting applications, please consult your local sales office.
Bulletin 140F Fuse Holders
Available for UL Class CC or midget fuses and IEC 10 x 38 mm fuses, with or
without blown fuse indication
Lockable in the open position
Compatible with Bulletin 140M wiring and accessories
Compact busbar and connectors to Bulletin 100-C and 100-K contactors
1 N.O./ 1N.C. auxiliary contact, early break N.C.
Provides capability for dropping out contactor before breaking current on fuse
Late make N.O. contact provides positive indication that power circuit is open
Separate overload relay required for motor protection
Approvals
Description
Fuse Holder, CC - 30 A
IEC
CE Mark
UL
CSA
Cat. No.
Yes
Yes
Yes
Yes
140F-D3C-C30
140F-D3C-C30L
Fuse Holder with Blown Fuse Indication, CC - 30 A
Yes
Yes
Yes
Yes
Fuse Holder, Midget - 30 A
Yes
Yes
Yes
Yes
140F-D3M-C30
Fuse Holder with Blown Fuse Indication, Midget - 30 A
Yes
Yes
Yes
Yes
140F-D3M-C30L
Fuse Holder, gG - 32 A
Yes
Yes
No
No
140F-D3F-C30
Fuse Holder with Blown Fuse Indication, gG - 32 A
Yes
Yes
No
No
140F-D3F-C30L
Auxiliary Contact for Fuse Holder (1 N.O. Late Make + 1 N.C. Early Break)
Yes
Yes
Yes
Yes
140F-C-AFA11
Rockwell Automation
Visit our website: www.ab.com/catalogs
17
Bulletin 140M
IEC Circuit Breakers
Accessories
Accessories
Description
Operator Position 1
OFF
ON
Tripped
Term.
No.
Front-Mounted
Auxiliary Contact
1-pole or 2-pole
No additional space
required
- Only (1) per MPCB
Right Side-Mounted
Auxiliary Contact
2-pole
Adds 9 mm to the
width of the device
- (2) per MPCB
Description
O
X
O
13-14
X
O
X
11-12
N.C. Aux
O
X
O
13-14
N.O. Aux
Connection Diagram
N.O. Aux
X
O
X
21-22
N.C. Aux
O
X
O
13-14
N.O. Aux
O
X
O
23-24
N.O. Aux
X
O
X
11-12
N.C. Aux
X
O
X
21-22
N.C. Aux
O
X
O
33-34
N.O. Aux
O
X
O
43-44
N.O. Aux
X
O
X
31-32
N.C. Aux
13
21
14
22
For Use
With
Cat. No.
140M-C,
D, F
140M-C-AFA10
140M-C,
D, F
140M-C-AFA01
140M-C,
D, F
140M-C-AFA11
140M-C,
D, F
140M-C-AFA20
140M-C,
D, F
140M-C-AFA02
140M-C,
D, F
140M-C-ASA20
140M-C,
D, F
140M-C-ASA02
140M-C,
D, F
140M-C-ASA11
31 41
32
X
O
X
41-42
N.C. Aux
O
X
O
33-34
N.O. Aux
X
O
X
41-42
42
N.C. Aux
1 X = Contact Closed; O = Contact Open
18
Visit our website: www.ab.com/catalogs
Rockwell Automation
Bulletin 140M
IEC Circuit Breakers
Accessories
Accessories
Description
Operator Position 1
OFF
O
Front-Mounted Trip
Contact
2-pole
Indicates tripping of
device
No additional space
required
X
Tripped
O
Term.
No.
Description
13-14
N.O. Aux
O
O
X
27-28
N.O. Trip
(Short-Circuit
& Overload)
X
O
X
11-12
N.C. Aux
27-28
N.O. Trip
(Short-Circuit
& Overload)
57-58
N.O. Trip
(Short-Circuit
& Overload)
Connection Diagram
For Use
With
Cat. No.
140M-C,
D, F
140M-C-AFAR10A10
140M-C,
D, F
140M-C-AFAR10A01
11 27
O
O
O
Right-Side Mounted
Trip Contact
2-pole
Indicates tripping of
Motor Protection
Circuit Breaker
Adds 9 mm to the
width of the circuit
breaker
- Only (1) per MPCB
- A Right-Side
mounted Auxiliary
Contact may be
tandem mounted on
top of this Trip
Contact
ON
O
O
O
O
O
X
X
X
X
67-68
N.O. Trip
57-58
N.O. Trip
(Short-Circuit
& Overload)
X
X
O
65-66
N.C. Trip
X
X
O
55-56
N.C. Trip
(Short-Circuit
& Overload)
O
O
X
67-68
N.O. Trip
X
X
O
55-56
N.C. Trip
(Short-Circuit
& Overload)
X
X
O
65-66
N.C. Trip
O
O
X
77-78
N.O. Trip
(Short-Circuit)
65-66
N.C. Trip
(Short-Circuit)
X
X
O
12
28
57 67
I>>
58
140M-C,
140M-C-ASAR10M10
D, F
68
57 65
I>>
140M-C,
140M-C-ASAR10M01
D, F
58 66
140M-C,
140M-C-ASAR01M10
D, F
140M-C,
140M-C-ASAR01M01
D, F
140M-C,
D, F
140M-C-ASAM11
1 X = Contact Closed; O = Contact Open
Rockwell Automation
Visit our website: www.ab.com/catalogs
19
Bulletin 140M
IEC Circuit Breakers
Accessories
Description
For Use With
Cat. No.
140M-C to 100-K
140M-C-PEK12
Spacing Adapter
Required for Self-Protected combination motor controller (Type E) applications
of 140M-C, -D, and -F MPCBs
140M-C, -D
140M-C-TE1
Compact Busbar Feeder Block
Supply of compact busbars
Increases terminal capacity
140M-C, -D
140M-C-WBE
Compact Busbar Feeder Terminal
For supply of commoning links
Top feed — overlaps commoning link
Meets UL Type E spacing requirements
140M-C, -D
140M-C-WTE
ECO Connecting Module
For DOL and reversing starters
Provides electrical and mechanical link
Three-Phase Compact Busbar for 25 A Motor Protection
Circuit Breakers — 63 A Max. Continuous Current
45 mm spacing
For use with front-mounted auxiliary contact
Three-Phase Compact Busbar for 25 A Motor Protection
Circuit Breakers — 63 A Max. Continuous Current
54 mm spacing
For use with side-mounted auxiliary contact
Three-Phase Compact Busbar for 25 A Motor Protection
Circuit Breakers — 63 A Max. Continuous Current
63 mm spacing
For use with side-mounted undervoltage trip and shunt trip
Jumper for 140M-D to 140M-C
Accommodates difference in depth from
140M-D to 140M-C
54 mm spacing
Can be used with all other commoning links
140M-C-W452
2 connections
3 connections
4 connections
140M-C, -D
140M-C-W453
140M-C-W454
5 connections
140M-C-W455
2 connections
140M-C-W542
3 connections
4 connections
140M-C, -D
140M-C-W543
140M-C-W544
5 connections
140M-C-W545
2 connections
140M-C-W632
3 connections
4 connections
140M-C, -D
5 connections
2 connections
140M-C-W633
140M-C-W634
140M-C-W635
140M-D to 140M-C
140M-C-WD542
For complete list of available 140M accessories, please consult the Allen-Bradlay Industrial Controls main catalog.
20
Visit our website: www.ab.com/catalogs
Rockwell Automation
Bulletin 100-K/140M
IEC Miniature Starter Selection
Overview/Product Selection
Table of Contents
Modular Eco Starter Component Selection
Power Range 0.1...12 A
Modular Eco Starter using Bulletin 140M Motor Protection Circuit
Breaker and Bulletin 100-K Mini Contactors
Mounting Options:
Snap Fixing on (1) 35 mm DIN Rail
Product Selection .... this page
+
+
Use the chart to select components based on motor application data.
Mini Starters
DOL- and Reversing-Starters 1
Type 1 Coordination
Max. Hp (60 Hz)
Motor
Current
Adjustment
Range
[A]
200V
230V
460V
Max. kW (50 Hz)
575V
230V
400V
Contactor
500V
Eco Starter
Module
Circuit Breaker
690V
C-Frame and 100-K Mini Contactors
0.1…0.16
⎯
⎯
⎯
⎯
⎯
0.02
⎯
⎯
100-K05⊗.. 140M-C-PEK12 140M-C2E-A16
0.16…0.25
⎯
⎯
⎯
⎯
0.02
0.06
0.06
⎯
100-K05⊗.. 140M-C-PEK12 140M-C2E-A25
0.25…0.4
⎯
⎯
⎯
⎯
0.06
0.09
0.12
⎯
100-K05⊗.. 140M-C-PEK12 140M-C2E-A40
0.4…0.63
⎯
⎯
⎯
⎯
0.09
0.18
0.18
⎯
100-K05⊗.. 140M-C-PEK12 140M-C2E-A63
0.63…1.0
⎯
⎯
⎯
1/2
0.12
0.25
0.37
0.25
100-K05⊗.. 140M-C-PEK12 140M-C2E-B10
1.0…1.6
⎯
⎯
0.5…0.75
3/4
0.25
0.55
0.75
0.37…0.55 100-K05⊗.. 140M-C-PEK12 140M-C2E-B16
1.6…2.5
1/2
1/2
0.75…1
1…1.5
0.55
0.75
1.1
0.75…1.1
100-K05⊗.. 140M-C-PEK12 140M-C2E-B25
2.5…4.0
3/4
3/4
1.5…2
2…3
0.75
1.5
1.8
1.8
100-K05⊗.. 140M-C-PEK12 140M-C2E-B40
4.0…6.3
1
1…1.5
3
5
1.5
2.2
2.2
4
100-K09⊗.. 140M-C-PEK12 140M-C2E-B63
6.3…10
1.6…2
2
5
7.5
2.2
4
4
⎯
100-K12⊗.. 140M-C-PEK12 140M-C2E-C10
10…16
3
⎯
7 1/2
⎯
4
5.5
⎯
—
100-K12⊗.. 140M-C-PEK12 140M-C2E-C16
1 Reversing Starters using 2 contactors 100-K..⊗01 and power wiring kit 100-KPR and if needed mechanical interlock 100-KMCH in addition.
Horsepower and Kilowatt ratings shown in the table are for reference. Final selection of the starter depends upon the actual motor full-load current and
service factor.
⊗ Coil Voltage Code
The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: 120V, 60 Hz:
Cat. No. 100-K09⊗10 becomes Cat. No.100-K09D10.
AC Voltages [V]
24
110
120
230
240
400
480
50 Hz
—
D
—
—
—
—
—
—
60 Hz
—
—
D
—
—
—
B
VC
50/60 Hz
KJ
—
—
KF
KA
KN
—
—
DC Voltages [V]
12
24
110
125
220
250
Standard
ZQ
ZJ
ZD
ZS
ZA
ZT
with Integrated Diode
—
DJ
—
—
—
—
600
For other voltages, see table on page 31
Rockwell Automation
Visit our website: www.ab.com/catalogs
21
Bulletin 100-K
IEC Miniature Contactors
Specifications
IEC Specifications
100/104-K
05
09
100/104-K
12
AC-1 Active Power Load (50 Hz);
Ambient temperature 40°C
Ie
05
≤ 230V
[A]
11.3
20
20
≤ 240V
[A]
11.3
20
20
8
8
400V
[A]
8.5
15.5
15.5
8.3
8.3
415V
[A]
8.5
15.5
15.5
14
14
500V
[A]
6.8
12.4
12.4
14
14
14
690V
[A]
4.9
8.9
8.9
[kW]
17
17
17
230V
[kW]
3
5.5
5.5
[kW]
24
24
24
240V
[kW]
3
5.5
5.5
400V
[kW]
4
7.5
7.5
[A]
230V
[kW]
8
240V
[kW]
8.3
400V
[kW]
14
415V
[kW]
500V
690V
20
20
≤ 690V
[A]
16
16
16
415V
[kW]
4
7.5
7.5
230V
[kW]
6.4
6.4
6.4
500V
[kW]
4
7.5
7.5
240V
[kW]
6.7
6.7
6.7
690V
[kW]
4
7.5
7.5
400V
[kW]
11
11
11
Load Carrying Capacity per UL/CSA
415V
[kW]
12
12
12
General Purpose Current (enclosed)
500V
[kW]
14
14
14
[A]
12
15
18
690V
[kW]
19
19
19
13.8
Switching of 3-phase Motors; (50 Hz)
Ambient temperature 60°C, AC-2, AC-3, AC-4
Rated power (enclosed)
1-phase (100-K)
230V
[A]
6.3
11.3
11.3
240V
[A]
6.3
11.3
11.3
400V
[A]
4.9
8.5
11.5
415V
[A]
4.9
8.5
11.5
500V
[A]
3.9
6.8
9.2
690V
[A]
2.8
4.9
6.7
230V
[kW]
1.5
3
3
240V
[kW]
1.5
3
3
400V
[kW]
2.2
4
5.5
415V
[kW]
2.2
4
5.5
500V
[kW]
2.2
4
5.5
690V
[kW]
2.2
4
5.5
3-phase
22
230V
[A]
2.3
3.9
3.9
240V
[A]
2.3
3.9
3.9
400V
[A]
2
3.6
3.6
415V
[A]
2
3.6
3.6
500V
[A]
1.9
3.2
3.2
690V
[A]
—
—
—
230V
[kW]
0.37
0.75
0.75
240V
[kW]
0.37
0.75
0.75
400V
[kW]
0.75
1.5
1.5
415V
[kW]
0.75
1.5
1.5
500V
[kW]
0.75
1.5
1.5
690V
[kW]
—
—
—
250
250
250
Ops/h
115V
[A]
9.8
9.8
230V
[A]
8
10
12
115V
[Hp]
0.5
0.5
0.75
230V
[Hp]
200V
[A]
230V
[A]
460V
[A]
575V
[A]
200V
1
1.5
2
6.9
7.8
11
6
6.8
9.6
4.8
7.6
11
3.9
6.1
9
[Hp]
1.5
2
3
230V
[Hp]
1.5
2
3
460V
[Hp]
3
5
7.5
575V
[Hp]
3
5
7.5
200V
[Hp]
2.5
3.3
5
230V
[Hp]
2.5
3.3
5
460V
[Hp]
5
8.5
12
575V
[Hp]
5
8.5
12
Wye-Delta (60 Hz)
AC-4 at approximately 200,000 operations
Max. switching
frequency
12
20
≤ 690V
Ambient temperature 60°C
Ie
09
Star-Delta Starting (50 Hz)
Visit our website: www.ab.com/catalogs
Rockwell Automation
Bulletin 100-K
IEC Miniature Contactors
Specifications
Specifications
IEC Specifications
100/104-K
05
09
100/104-K
12
05
09
12
Switching of Power Transformers, AC-6a (50 Hz)
Switching of DC Loads
Inrush Current
Non-inductive/slightly inductive loads or resistance furnaces DC-1 at 60 °C
=n
Rated transformer current
n = 30
24V
[A]
6
9
9
≤ 230V
[A]
2.9
5.4
5.4
1 pole (100-K)
48/60V
[A]
4/1
6/1.5
6/1.5
≤ 240V
[A]
2.9
5.4
5.4
110V
[A]
0.6
1
1
≤ 400V/415V
[A]
2.4
4.1
5.4
220V
[A]
0.2
0.3
0.3
≤ 500V
[A]
1.8
3.2
3.2
440V
[A]
0.08
0.1
0.1
≤ 690V
[A]
—
—
—
24V
[A]
6
9
9
230V [kVA]
1.2
2
2
48/60V
[A]
6
8
8
240V [kVA]
1.2
2
2
110V
[A]
4
6
6
400V [kVA]
1.7
2.8
3.4
220V
[A]
0.8
1.2
1.2
415V [kVA]
1.7
2.8
3.4
440V
[A]
0.2
0.3
0.3
500V [kVA]
1.7
2.8
3.4
24V
[A]
6
9
9
690V [kVA]
2
4
5
48/60V
[A]
6
9
9
9
2 poles in series
3 poles in series
n = 20
≤ 690V
[A]
—
—
—
110V
[A]
6
9
n = 15
≤ 690V
[A]
—
—
—
220V
[A]
3
4
4
440V
[A]
0.4
0.6
0.6
Switching of Lamps
Gas discharge lamps AC5a 220…240V AC (40 °C)
open
[A]
18
18
18
closed
[A]
14.5
14.5
14.5
Shunt-wound Motors
Starting, reverse current braking, reversing, stepping DC-3, 60 °C
3 poles in series
Individually compensated:
Max. capacitance at expected
Short-circuit current of
Filament AC-5b
10 kA
[μF]
750
750
750
20 kA
[μF]
400
400
400
50 kA
[μF]
—
—
—
230/240V
[A]
5
9
9
Switching of Low Inductive Loads in Home Appliances and Similar
Applications per IEC 61095 (50 Hz)
AC-7a
230V
[A]
20
20
20
400V
[A]
20
20
20
230V
400V
[A]
[A]
6
6
11
3 poles in series
11
11
11
Switching of hermetically encapsulated cooling compressor motors
with manual reset of the overload release
AC-8a
400V
[A]
11
18
18
500V
[A]
10
15
15
[A]
5
9
9
[A]
4
6
6
110V
[A]
2
3
3
220V
[A]
0.8
1.2
1.2
440V
[A]
0.15
0.2
0.2
Series-wound Motors
Starting, reverse current braking, reversing, stepping DC-5, 60 °C
Switching of Motor Load for Home Appliances (50 Hz)
AC-7b
24V
48/60V
24V
[A]
5
9
9
48/60V
[A]
2
3
3
110V
[A]
0.6
1
1
220V
[A]
0.1
0.1
0.1
440V
[A]
—
—
—
[A]
60
96
96
[mΩ]
2.2
2.2
2.2
0.3
0.9
0.9
Short Time Withstand ICW, 60 °C
10 s
Resistance and Power Dissipation
Main current circuit resistance, 1
pole
Power dissipation, 3 main poles
Ie AC-3/400V
Total power dissipation
At Ie AC-3/400V
AC control,
warm
[W]
2.1
2.7
2.7
DC control,
warm
[W]
2.9
3.5
3.5
Lifespan
Mechanical
[Mio. op.]
15
15
15
Electrical AC-3 (400 V)
[Mio. op.]
0.7
0.7
0.7
Reversing combination
mechanical, electrical
[Mio. op.]
0.7
0.7
0.7
0.16
(0.35)
0.16
(0.35)
0.16
(0.35)
Weight
AC
DC
Rockwell Automation
Visit our website: www.ab.com/catalogs
DOL
kg (lbs.)
Reversing
kg (lbs.)
—
—
—
DOL
kg (lbs.)
0.2
(0.44)
0.2
(0.44)
0.2
(0.44)
Reversing
kg (lbs.)
—
—
—
23
Bulletin 100-K
IEC Miniature Contactors
Specifications
Cross Sections, Srew Type Terminals
Coil Data
100/104-K
Conductor Cross Sections
- Main Contacts and Auxiliary Contacts
05
09
100/104-K
12
1
Terminal type
Fine stranded
with ferrule
(1) Conductor
(2) Conductors
[mm2]
[mm2]
Solid or coarse
stranded
(1) Conductor
(2) Conductors
1…4
[mm2]
[mm2] 0.75…2.5 + 1…4
Recommended torque
Cross section per UL/CSA
Recommended torque
1 Pozidriv No. 2 / Blade No. 3 screw
Use same cross sections
[Nm]
[AWG]
[lb-in]
0.75…2.5
0.75…2.5
1.2
18…12 10.6
05
09
12
Operating Limits
AC control
pick-up
50 Hz, 60 Hz, 50/60
dropout
Hz
[x Us]
0.85…1.1
[x Us]
0.2…0.75
pick-up
[x Us]
0.8…1.1
9, 12, 24, 110V DC: 0.7…1.25
dropout
[x Us]
0.1…0.75
[VA/W]
35/32
DC control
Coil Consumption
AC control
pick-up
50 Hz, 60 Hz, 50/60
hold-in
Hz
[VA/W]
5/1.8
pick-up
[W]
cold 3.0, warm 2.6
hold-in
[W]
cold 3.0, warm 2.6
closing
delay
[ms]
15…40
opening
delay
[ms]
15…33
opening
delay
[ms]
15…28
closing
delay
[ms]
18…40
opening
delay
[ms]
6…12
With integrated
diode
opening
delay
[ms]
8…12
With external diode
opening
delay
[ms]
35…50
[ms]
>50
DC control
Operating Times
AC
With RC module
DC
Minimal change over-time for
reversing
Short Circuit Coordination
100/104-K
05
09
12
Short Circuit Coordination (Max. Fuse or Circuit Breaker Rating)
Per IEC 60947-4-1 (contactor and fuses only)
DIN Fuses - gG
24
50 kA Available Fault Current
Type "1" (690V)
[A]
35
35
35
Type "2" (690V)
[A]
16
20
20
Visit our website: www.ab.com/catalogs
Rockwell Automation
Bulletin 100-K
IEC Miniature Contactors
Specifications
Auxiliary Contacts and Auxiliary Contact Blocks
General Data
Auxiliary contacts
Internal (100-K) Blocks (100-KF)
Rated Isolation Voltage Ui
Switching of AC Loads
AC-12 Ith
at 40°C
[A]
10
10
IEC
[V]
690
at 60°C
[A]
6
6
UL, CSA
[V]
600
[kV]
6
[V]
230, 240, 400, 415, 500, 690
24V
[A]
6
3
Rated Impulse Voltage
Withstand Uimp
120V
[A]
6
3
Rated Operating Voltage Ue
240V
[A]
3
2
AC
400V
[A]
1.8
1.2
DC
480V
[A]
1.5
1
500V
[A]
1.4
1
600V
[A]
1.2
0.6
690V
[A]
1
0.6
AC-15 at rated voltage of
Switching of DC Loads
DC-12 L/R< 1 ms resistive loads at
24V DC
[A]
6
—
50/60 Hz
[V]
24, 48, 110, 220, 440
Class F according to IEC 60085,
Class 105 insulation system
according to UL 508
Insulation Class of the Coil
Rated coil frequency
AC 50/60 Hz, DC
Ambient Temperature
Storage
[°C]
Operation at rated voltage
[°C]
-55…+80
-25…+60
15% current reduction against 60°C
values
48V DC
[A]
4
—
at 70°C
110V DC
[A]
0.6
—
Climatic Withstand
125V DC
[A]
0.6
—
220V DC
[A]
0.2
—
Max. Altitude of Installation
Site
250V DC
[A]
0.2
—
Protection Class
400V DC
[A]
0.08
—
Single contactor cover
—
440V DC
[A]
0.08
—
Contactor with frame terminal
block
—
24V DC
[A]
4
—
Resistance to Shock
DC-14 L/R< 15 ms inductive loads
with economy resistor in series at
Auxiliary contact
IEC 68-2/EN 60068
[m]
2000 NN
IP2X
IP2X
IEC 68-2/EN 60068
48V DC
[A]
2.5
—
Resistance to Vibration
IEC 68-2/EN 60068
110V DC
[A]
0.4
—
100-K (on main unit)
125V DC
[A]
0.4
—
Mechanically Linked Contacts
IEC 60947-5-1, Annex L
220V DC
[A]
0.12
—
250V DC
[A]
0.12
—
400V DC
[A]
0.05
—
Standards
IEC/EN 60947-1, -4-1, -5-1, -5-4,
UL 508, CSA 22.2. No. 14
440V DC
[A]
0.05
—
Approvals
CE, cULus
24V DC
[A]
2.8
2.3
48V DC
[A]
1.2
1
110V DC
[A]
0.55
0.55
125V DC
[A]
0.55
0.55
220V DC
[A]
0.27
0.27
250V DC
[A]
0.27
0.27
400V DC
[A]
0.15
0.15
440V DC
[A]
0.15
0.15
600V DC
[A]
0.1
0.1
Mirror Contacts
IEC 60947-4 Annex F
100-K and 100-KF
DC-13 switching electromagnets at
Fuse gG
Short-circuit protection with no Welding of contacts per IEC 60947-5-1
[A]
10
10
[A]
10
10
Protective Separation per IEC 609471, Annex N
—
—
Min. switching capacity 15V IEC
[mA]
60947-5-4
—
2
Load Carrying Capacity per UL/CSA
Rated voltage
AC
[V]
max. 600
max. 600
40 °C
[A]
10
10
Switching
capacity
AC
[A]
A 600
B 600
Rated voltage
DC
[V]
max. 600
max. 600
Switching
capacity
DC
[A]
Q 600
Q 600
Continuous
rating
Rockwell Automation
Visit our website: www.ab.com/catalogs
25
Bulletin 100/104-K
IEC Miniature Contactors
Specifications
Life-Load Curves
Electrical life; Ue = 400…460V AC
AC-3
Switching of squirrel-cage motors while starting
AC-1
Non- or slightly inductive loads, resistance furnaces
Contact Life (millions of operations)
10
1
100-K12
100-K09
0.1
100-K05
0.01
1
10
100
Rated current Ie AC-3 [A]
(Dashed curves - - - - AC-1 only, open)
Electrical life; Ue = 400…460V AC
AC-4
Stepping of squirrel-cage motors
10
100-K09; 100-K12
Contact Life (millions of operations)
100-K05
1
0.1
0.01
0.1
1
10
Rated current Ie AC-4 [A]
26
Visit our website: www.ab.com/catalogs
Rockwell Automation
Bulletin 700-K
IEC Miniature Control Relays
Specifications
IEC Specifications
700-K
AC-12 Rated Thermal Current
Ambient temperature 40°C
700-K
Continuous Current
(General Purpose)
24…240V
[A]
10
230…500V
[A]
10
DC-13/Q600
230…690V
[A]
10
1 pole
Ith
Ambient temperature 60°C
300V AC
[A]
5
600V AC
[A]
10
2.3
24V
[A]
48V
[A]
1
24…240V
[A]
6
110V
[A]
0.55
230…500V
[A]
6
125V
[A]
0.55
230…690V
[A]
6
220V
[A]
0.27
250V
[A]
0.27
400V
[A]
0.15
440V
[A]
0.15
600V
[A]
0.1
Ith
AC-15/B600
Switching of Solenoids and contactors
24V
[A]
3
48V
[A]
3
120V
[A]
3
230V
[A]
2
240V
[A]
2
400V
[A]
1.2
480V
[A]
1
500V
[A]
1
600V
[A]
0.6
690V
[A]
0.6
Short-circuit Protection
"gG" Fuse acc. to IEC 60947-5-1, no welding of contacts
Fuse gG
[A]
10
Min. Switching Capacity 15V
For bifurcated contacts (control relays and auxiliary contact blocks)
[mA]
2
[mΩ]
6.5
[W]
2.6
AC control,
warm
[W]
4.4
DC control,
warm
[W]
5.2
Resistance and Power Dissipation
Main current circuit
resistance, 1 pole
Power dissipation Ith, 4 poles
Total power dissipation
Ith
Lifespan
Mechanical
[Mio. op.]
15
Electrical AC-15 (240V / 2 A)
[Mio. op.]
0.7
Weight
AC control
kg (lbs.)
0.16 (0.35)
DC control
kg (lbs.)
0.2 (0.44)
Load Carrying Capacity per UL/CSA
Rated voltage
AC
[V]
max. 600
40 °C
[A]
10
Switching
capacity
AC
[A]
B 600
Rated voltage
DC
[V]
max. 600
Switching
capacity
DC
[A]
Q 600
Continuous
rating
Rockwell Automation
Visit our website: www.ab.com/catalogs
27
Bulletin 700-K
IEC Miniature Control Relays
Specifications
Cross Sections, Srew Type Terminals
Coil Data
Conductor Cross Sections
- Main Contacts and Auxiliary Contacts
700-K
700-K
Operating Limits
1
AC control
50 Hz, 60 Hz, 50/60 Hz
Terminal type
Fine stranded
with ferrule
(1) Conductor
(2) Conductors
[mm2]
[mm2]
Solid or coarse
stranded
(1) Conductor
(2) Conductors
1…4
[mm2]
[mm2] 0.75…2.5 + 1…4
Recommended torque
Cross section per UL/CSA
Recommended torque
[Nm]
0.75…2.5
0.75…2.5
DC control
AC control
50 Hz, 60 Hz, 50/60 Hz
18…12 [lb-in]
10.6
[x Us]
0.85…1.1
dropout
[x Us]
0.2…0.75
pick-up
[x Us]
0.8…1.1
9, 12, 24, 110V DC:
0.7…1.25
dropout
[x Us]
0.1…0.75
pick-up
[VA/W]
35/32
hold-in
[VA/W]
pick-up
[W]
cold 3.0, warm 2.6
hold-in
[W]
cold 3.0, warm 2.6
closing delay
[ms]
15…40
opening delay
[ms]
15…33
opening delay
[ms]
15…28
closing delay
[ms]
18…40
6…12
Coil Consumption
1.2
[AWG]
pick-up
DC control
5/1.8
Operating Times
1 Pozidriv No. 2 / Blade No. 3 screw
Use same cross sections
AC
With RC module
DC
opening delay
[ms]
With integrated diode
opening delay
[ms]
8…12
With external diode
opening delay
[ms]
35…50
General Data
700-K
Rated Isolation Voltage Ui
IEC
[V]
690
UL, CSA
[V]
600
1 minute acc. to IEC 60947-5-1
[V]
—
[kV]
6
[V]
24, 48, 120, 230, 400, 500, 600, 690
[V]
24, 48, 110, 220, 440
Rated Impulse Voltage Withstand Uimp
Rated Operating Voltage Ue
AC
50/60 Hz
DC
Rated Coil Frequency
AC 50/60 Hz, DC
Ambient Temperature
Storage
[°C]
Operation at rated voltage
[°C]
at 70°C
Protection Class
Auxiliary contact
-25…+60
15% current reduction against 60°C values
Climatic Withstand
Max. Altitude of Installation Site
-55…+80
—
[m]
2000 NN
IP2X
—
Standards
IEC/EN 60947-1, -5-1, -5-4,
UL 508, CSA 22.2. No. 14
Approvals
CE, cULus
28
Visit our website: www.ab.com/catalogs
Rockwell Automation
Bulletin 193-K
IEC Miniature Thermal Overload Relays
Specifications
Specifications
Main Circuits
Environmental Ratings
193-K
Rated Isolation Voltage Ui
690V
Rated Impulse Strength Uimp
6 kV
Rated Operating Voltage Ue
IEC/UL
Humidity
Terminal screws
Solid or coarse
stranded
Recommended torque
Pozidriv screwdriver
Slotted screwdriver
M3.5
[mm2]
2 x (1.5…4)
[mm2]
[AWG]
2 x (1.5…4)
2 x (16…10)
[Nm]
[lb-in]
1.2
10.6
Size
[mm]
Storage
Operating
-55…+80 °C (-67…+176 °F)
-20…+60 °C (-4…+140 °F)
Operating
Damp Heat
5…95 % Non-condensing
per IEC 68-2-3 and IEC 68-2-30
690V AC / 600V AC
Wiring cross section
Terminal type
Fine stranded with
ferrule
193-K
Ambient
Temperature
2
1x6
Vibration (per IEC 68-2-6)
3G
Shock (per IEC 68-2-27)
30G
Max. Altitude
2000 m
Pollution Environment
Pollution Degree 3
Degree of Protection
IP2X
Protection
Ambient Compensated, Time Delay,
Phase Loss Sensitive
Type of Relay
Nature of Relay
Bimetallic Overload Relay
Trip Rating
120 % FLA
Trip Class
IEC: 10A, UL 10
Reset Mode
Power dissipation
Control Circuits
Automatic or Manual
up to 0.4 A
7W
0.5…12.5 A
6W
General Data
193-K
193-K
Rated Isolation Voltage Ui
690V AC
Rated Impulse Strength Uimp
4 kV AC
IEC/EN 60947-1, -4-1, -5-1,
UL 508, CSA 22.2. No. 14
Rated Operating Voltage Ue
IEC/UL
Rating Designation
Rated Operating Current Ie
690V AC / 600V AC
A600 / Q300
N.O./N.C.
24V
[A]
4
240V
[A]
2
400V
[A]
1.6
690V
[A]
0.15
24V
[A]
2
110V
[A]
0.4
220V
[A]
0.25
440V
[A]
0.08
Thermal Current Ithe
[A]
5
Short-circuit withstand, fuse gG
[A]
AC-15
DC-13
Contact Reliability
Standards
Certifications
Approximate Weights (unpackaged)
CE, cULus
0.115 kg (0.25 lb)
6
15V, 2 mA
Wiring cross section
Terminal type
Terminal screw
M 3.5
Fine stranded with
ferrule
[mm2]
2 x (1…4)
Solid or coarse
stranded
[mm2]
[AWG]
2 x (1…4)
2 x (18…12)
[Nm]
[lb-in]
1.2
10.6
Recommended torque
Pozidriv screwdriver
Size
2
Slotted screwdriver
[mm]
1x6
Rockwell Automation
Visit our website: www.ab.com/catalogs
29
Bulletin 193-K
IEC Miniature Thermal Overload Relays
Specifications
Thermal Overload Relays
Circuit Diagrams
Trip Characteristics
These trip characteristics refer to IEC 60947 and are average values from cold start at an ambient temperature of 20 °C. Trip time is
pictured as a function of operating current. With the device at normal operating temperature, the trip time decreases to approximately
25% of the shown value.
Minutes
Trip Class 10A
Seconds
3-phase
2-phase
FLA Multiple
30
Visit our website: www.ab.com/catalogs
Rockwell Automation
Bulletin 100/104-K
IEC Miniature Contactors
Specifications/Approximate Dimensions
⊗ Coil Voltage Codes
DC Coil Voltages
AC Coil Voltages
[V]
50 Hz
60 Hz
50/60 Hz
[V]
12
—
—
KQ
9
ZR
24
—
—
KJ (WJ)1
12
ZQ
ZJ (DJ)
DC
32
—
—
VU
24
36
—
—
KV
30
ZC
42
—
—
KW
36
ZW
48
—
—
KY
48
ZY
60
—
—
KR
60
ZZ
70
—
—
VG
72
ZG
110
D (WD)1
—
—
80
ZE
120
—
D (WD)1
—
110
ZD
127
—
—
VS
120
ZU
135
—
—
VE
125
ZS
200
KG
—
—
220
ZA
200-220
—
—
KG
240
ZL
230
—
—
KF (WF)1
250
ZT
240
—
—
KA
250
—
—
VT
380-400
N
—
—
400
—
—
KN
415
—
—
KU
440
B
—
—
480
—
B
—
500
M
—
—
525
VC
—
—
575
—
M
—
600
—
VC
—
(DJ): with integrated Diode
Voltage codes in bold are prefered products. For availabilty of
other voltage codes, please consult your local Allen-Bradley
distributor or representative.
1 (Wx): with built-in Varistor
Bulletin 100-K, 700-K, 193-K Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
78.7 (3-7/64)
44.9 (1-25/32)
49 (1-15/16)
35 (1-25/64)
4 (5/32)
Mounting Position
35.2 (1-25/64)
Without accessories
2 5°
54 (2-1/8)
56 (2-13/64)
108.2 (4-1/4)
49.2 (1-15/16)
50 (1-31/32)
25 °
12 (15/32)*
360°
1 Minimum distance to grounded parts or walls
36.9 (1-29/64)
Rockwell Automation
63.5 (2-1/2)
Visit our website: www.ab.com/catalogs
31
General Terms and Conditions of Sale
TERMS AND CONDITIONS
«General Terms and Conditions of Sale» can be found in publication «6500(EN) - January 2004».
This publication is available as a PDF file (Adobe Acrobat) at
http://www.rockwellautomation.com/termsofsale
32
Visit our website: www.ab.com/catalogs
Rockwell Automation
Notes
Rockwell Automation
Visit our website: www.ab.com/catalogs
33
Notes
34
Visit our website: www.ab.com/catalogs
Rockwell Automation
Publication MCS-SG001A-EN-P – April 2007
©2006 Rockwell Automation, Inc. All Rights Reserved. Printed in Switzerland.