ADAPTSd

ADAPTSd
ADAPT Sphere
TM
Active communicative, supply air diffuser for the WISE system
ADAPT Sphere
Quick facts
►►Supply air diffuser with an active damper
►►Pressure-dependent and cleanable
►►Integrated sensor module
►►Simple wiring, Plug & Play
►►Communication via Modbus RTU
►►Supplied complete with connection box, CONNECT
Adapt
►►Complemented with the WISE templates,
containing detailed descriptions for planning
►► Allows for control of:
– Heat alternatively, cooling valve
(max. 3 actuators per master)
– Slaves (supply or extract air, 3 pcs)
– Lighting (via relay)
Quick Selection
AIR FLOW – SOUND LEVEL – COOLING EFFECT
max q (l/s)
Size
min q*)
(l/s)
50 Pa / 30 dB(A)
50 Pa / 35 dB(A)
max p**)
(W)
160
0/5
50
85
480
200
0/10
65
100
625
*)
The first value indicates closed damper, the second value
indicates lowest adjustable air flow.
**)
Max. cooling effect is calculated at ∆t=8K and for an air
flow at 50 Pa and 30 dB(A).
1
WISE
Technical Description
Design
ADAPT is a series of flow-controlled supply air diffusers for
the Swegon WISE system:
• The air diffuser controls the airflow with an active slot
behind the frontplate.
• An ADAPT diffuser is always supplied with a
commissioning box.
• Inside the air diffuser, is a controller providing all the
required set points and control functions as well as a
multi-functional sensor module, see figure 1.
Functions in the Master diffuser
• Cools/heats and ventilates with air.
• Two stage cooling with water in the second stage, cannot
be combined with heating.
• Controls airflow with regard to temperature and presence.
• Ventilation boost after longer periods of unoccupancy.
• Provision for wiring to a CO2 controller.
• Provision for manually setting set points.
• Has provision for connection to a main control system
(Modbus).
• Emergency functions for closing / opening of the damper.
• Control of the heating in sequence unless 2-stage
cooling has been selected.
• Indication via LED. Indicates current operating mode and
warns of malfunctions in the diffuser.
• Comfort control indicated by the LED if the room temperature or CO2 value deviates too much from the set point,
not activated by default.
Planning – WISE Templates
See separate documentation, ”WISE Project manual”,
available for download from www.swegon.se.
In addition, Swegon sales personnel can supply WISE
templates containing descriptions with detailed information
regarding functionality, flowcharts, wiring diagrams and
demarcation list for various constructions.
1
2
Sensor module
A sensor module is integrated in all ADAPT supply air
diffusers, containing the following functions:
• A temperature sensor controls the airflow to maintain
required temperature in the room.
• A presence detector makes it possible to save additional
energy by lowering the airflow when there are no occupants in the room.
• The presence signal from the air diffuser can be fetched
for controlling the lighting, for instance, and in this way
save more energy.
3
Figure 1. The sensor module of ADAPT Sphere
with connection for TUNE Adapt.
1. Temperature detector
2. In-operation indicator, green, red and orange LED.
3. Presence detector
Connectivity
In each delivery of a master diffuser, a CONNECT Adapt connection box is included:
• The connection box replaces the coupling box which otherwise is mounted on a wall/ceiling for wiring a 24 V supply
voltage to the air diffuser and Modbus networks.
• Both air diffuser and connection box are equipped with
RJ45 quick-fit connectors for quick and fault-free wiring.
• The device has provision for connection to a main control
system (BMS/SCADA) via ModBus.
• Accessory cable, LINK Modbus (RJ12) can be connected
between air diffuser and connection box. The air diffuser
will then be ready for the main control system.
• From the connection box, control functions for heating in
sequence, CO2 sensor and set point adjuster, can also be
connected.
2
Swegon reserves the right to alter specifications.
Figure 2. Connection box, CONNECT Adapt.
20151013
www.swegon.com
WISE
Installation
A detailed installation instruction is enclosed with each
delivery and can also be downloaded from www.swegon.
1.If the air diffuser backing box is fitted to an ADAPTER
diffuser mounting plate, it should be fitted first. Place
the air diffuser backing box with the diffuser mounting
plate in the supporting framework of the suspended
ceiling before you install the commissioning box.
2.The commissioning box can be suspended from a ceiling
and connected to duct system. Use hanger system A or B.
3.Press the ADAPT Sphere air diffuser into the outlet of
the commissioning box. Make sure that the orientation
of the sensor module aligns with the extension of the
room. Then fixate and secure the diffuser with screws
or pop rivets. Readjust the hanger rods of the commissioning box if necessary, so that the air diffuser is firmly
positioned against the false ceiling.
• The commissioning box is made of galvanized sheet
steel with internal insulation.
Maintenance
• The ADAPT air terminals can be cleaned on the outside, if necessary, using lukewarm water with dishwashing detergent added.
• The duct system is accessible without need for tools.
(See the separate installation instruction)
Declaration
Declaration of Construction Materials is available for download from www.swegon.com.
Electrical data
ADAPT is supplied with power via the connection box.
For more information about various wiring and room solutions, see the Technical Section.
24 V AC ±10 %
Max. power consumption
3 VA
Cable rating
0,6 A
Ambient temperature
A
0 °C - +50 °C
Forms of delivery
B
• Some of the ADAPT-products are available from stock
with standard settings.
• At delivery, a master air diffuser contains a complete air
diffuser with commissioning box, connection box CONNECT Adapt and 5 metre long RJ45 cable LINK Adapt.
• Delivery of a slave air diffuser contains a complete air diffuser with commissioning box and 5 metre long RJ45
Standard settings
Temperatures (°C)
Figure 3. ADAPT Sphere, installation.
Commissioning
• Normally, the ADAPT air terminals are preset from the
factory based on design values.
• The TUNE Adapt hand-held terminal is used for manually checking the current air flow through the air diffuser, and for changing set points, if required.
• For more information, see the installation - Commissioning - Maintenance instruction as well as the TUNE
Adapt user manual.
Materials and finish
22
±1K
Absence
22
+3 / -2 K
Night-time cooling
18
Morning heat
25
Airflows (l/s)
Absence
Min.
airflow
Max.
airflow
The smallest size
0/5
10
60
The largest size
0/10
15
90
Air quality (ppm)
Min.
Max.
800
1000
CO2
Presence
Switch on delay
Switch out delay
• ADAPT air terminals are made of galvanized sheet steel,
with parts made of plastic, rubber and also contain
electronic components.
• The ADAPT air terminals are powder coated in Swegon’s white interior standard colour RAL 9003/NCS S
0500-N, both on the inside and on the outside.
• The sensor module and connection box are made of
ABS plastic.
Swegon reserves the right to alter specifications.
Presence
0 sec.
20 min.
Communication Modbus RTU by RS-485
Modbus ID
Speed
1
38,400 bps
Bit length
8 bits
Stop bits
1 bit
Parity
20151013
None
www.swegon.com
3
ADAPT Sphere
Supply voltage
WISE
Sizing
• The specified sound levels dB(A) are applicable to
rooms with an equivalent sound absorption area of
10 m2 (4 dB room attenuation).
• The throw L0.2 is measured under isothermal discharge
conditions.
• Recommended max. permitted temperature below
room temperature is 12 K.
• All technical data applies to 360° distribution pattern.
• For calculating the air stream propagation, air velocities
in the occupancy zone, or sound levels in rooms with
other dimensions, we refer to our ProAir Web calculation
program. ProAir Web is available at www.swegon.com.
Engineering graphs
Air flow – Pressure drop – Sound level – Throw
• The diagrams should not be used for commissioning.
• The dB(C) value is normally 6-9 dB higher than the
dB(A) value.
• The throw can be read at the design max. air flow and
pressure drop.
• The slot opening of the diffuser is shown at 0, 1, 3, 6
and 15 mm.
• Sizing example – size 160:
– Given airflow 10-50 l/s at Pt 50 Pa.
– Max. sound level 30 dB(A)
– Max. throw at line 06 = 3.8 meters.
Sound data
63
125
250
500
1000 2000 4000
160
1
0
-2
1
0
-6
-16
-20
200
-1
3
0
2
-1
-7
-17
-22
Tol. ±
2
2
2
2
2
2
2
2
06
40 dB(A)
300
8000
03
15
Mid-frequency (Octave band) Hz
Size
pt Pa
0
500
400
01
ADAPT Sphere 160
Sound power level, Lw (dB)
Table, Kok
35
200
30
100
25
20
50
40
30
20
Sound attenuation DL
Table DL
10
5
Mid-frequency (Octave band) Hz
Size
63
125 250
500
1000 2000 4000
160
16
12
14
19
21
17
200
18
11
13
20
19
Tol. ±
2
2
2
2
2
3
4
5
10
20
8000
15
20
18
06
17
20
18
03
2
2
2
30
0,4 0,5
20
40
50
1
30
40
50
100
2
100
200
3
4
5
40
50
300
400 500
10
200 l/s 300
m3/h
20
30
l0,2 m
06
01
pt Pa
0
500
400
03
ADAPT Sphere 200
15
300
200
40 dB(A)
35
100
30
25
50
40
20
30
20
10
5
3
4
5
10
20
30
40
20
50
30
100
200
100
300
200 l/s 300
400 500
m3/h
10
20
15
06
03
0,3
4
Swegon reserves the right to alter specifications.
0,4 0,5
20151013
1
2
3
4
5
www.swegon.com
l0,2 m
WISE
Dimensions and weights
Size
Ordering key
Dimensions (mm)
Product
ØA
B
C
ØD
Ød
E
160
380
404
288
159
200
295
200
456
504
332
199
250
345
Dimensions (mm)
F
G
H
I
ØJ
K
Weight
(kg)
200
195
375
45
280
100
6,3
200
240 230
ØJ = Hole cutting size
CL = Center line
465
45
350
115
9,0
Size
160
Circular active air diffuser for ceiling
ADAPT S
d
-bbb
-c
Version:
Connection dimensions:
M: Master
S: Slave
N.B.! Specify absence, min./max. airflows in your specification!
Standard range: Size: 160, 200
Accessories
ADAPTER
H
DETECT Quality Temperature and CO2sensor with set point
selector knob
CL
B
Ø
CL D
G
F E
C
I
Ød
ØA
Figure 4. ADAPT Sphere, dimension figure.
Swegon reserves the right to alter specifications.
TUNE Adapt
Hand-held terminal for reading/changing
settings
TUNE Temp
Temperature adjuster
LINK Modbus
RJ12-cable for connecting up Modbus RTU
LINK Adapt
RJ45 cable for connecting up in other lengths
SPLIT Link
Split connector
FIX Link
For securing cords to ducts, etc.
POWER Adapt
Transformer
ACTUATOR
Valve actuator, on/off
VALVE
Radiator valve
ADAPT Relay
Relay for light or heat control
ADAPT TR
Semi-conductor relay for lighting or heat
control
CABLE Ext
Extension cable between box and air diffuser
LINK Wa
Network cable for Modbus, complies with the
EIA-485 standard
Each accessory is described in more detail in a separate
product sheet available at www.swegon.se.
20151013
www.swegon.com
5
ADAPT Sphere
K
Kassettplåt för 600x600 undertak
Was this manual useful for you? yes no
Thank you for your participation!