Airedale ZCV, ZCF Ceiling Unit Ventilator Installation and Service Manual
Below you will find brief information for Ceiling Unit Ventilator ZCV, Ceiling Unit Ventilator ZCF. This manual provides instructions for the installation and servicing of the Airedale Varsity Ceiling Unit Ventilator models ZCV and ZCF. The manual covers topics such as installation clearance, piping installation, electrical wiring, start-up procedures, maintenance, and troubleshooting.
Advertisement
Advertisement
AIR14-501.1
5H103597A2
January, 2014
INSTALLATION AND SERVICE MANUAL
Varsity
TM
Ceiling Unit Ventilator
Models ZCV and ZCF
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death, and could cause exposure to substances which have been determined by various state agencies to cause cancer, birth defects or other reproductive harm.
Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
IMPORTANT
1. The use of this manual is specifically intended for a qualified installation and service agency.
A qualified installation and service agency must perform all installation and service of these appliances.
2. ZCV and ZCF units with DX evaporator coils contain the refrigerant R-410A. Review the
R-410A Material Safety Data Sheet (MSDS) for hazards and first aid measures.
3. Refrigerant charging should only be carried out by an EPA-certified air conditioning contractor.
WARNING
This unit contains R-410A high pressure refrigerant.
Hazards exist that could result in personal injury or death. Installation, maintenance, and service must only be performed by an HVAC technician qualified in R-410A refrigerant and using proper tools and equipment. Due to much higher pressure of R-410A refrigerant, DO NOT USE service equipment or tools designed for refrigerants other than R410A.
Inspection On Arrival
1. Inspect unit upon arrival. In case of damage, report it immediately to transportation company and your local factory sales representative.
2. Check rating plate on unit to verify that power supply meets available electric power at the point of installation.
3. Inspect unit received for conformance with description of product ordered (including specifications where applicable).
THIS MANUAL IS THE PROPERTY OF THE OWNER.
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
2
SPECIAL PRECAUTIONS
SPECIAL PRECAUTIONS
THE INSTALLATION AND MAINTENANCE INSTRUCTIONS
IN THIS MANUAL MUST BE FOLLOWED TO PROVIDE
SAFE, EFFICIENT, AND TROUBLE-FREE OPERATION. IN
ADDITION, PARTICULAR CARE MUST BE EXERCISED
REGARDING THE SPECIAL PRECAUTIONS LISTED BELOW.
FAILURE TO PROPERLY ADDRESS THESE CRITICAL
AREAS COULD RESULT IN PROPERTY DAMAGE OR LOSS,
PERSONAL INJURY, OR DEATH. THESE INSTRUCTIONS
ARE SUBJECT TO ANY MORE RESTRICTIVE LOCAL OR
NATIONAL CODES.
HAZARD INTENSITY LEVELS
1. DANGER: Indicates an imminently hazardous situation which, if not avoided, WILL result in death or serious injury.
2. WARNING: Indicates a potentially hazardous situation which, if not avoided, COULD result in death or serious injury.
3. CAUTION: Indicates a potentially hazardous situation which, if not avoided, MAY result in minor or moderate injury.
4. IMPORTANT: Indicates a situation which, if not avoided, MAY result in a potential safety concern.
DANGER
Appliances must not be installed where they may be exposed to potentially explosive or flammable atmosphere.
WARNING
1. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
2. All appliances must be wired strictly in accordance with the wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.
3. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.
4. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% greater than rated voltage.
5. When servicing or repairing this equipment, use only factory-approved service replacement parts. Refer to the rating plate on the appliance for complete appliance model number, serial number, and company address.
Any substitution of parts or controls not approved by the factory will be at the owner’s risk.
CAUTION
1. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% less than the rated voltage.
2. Units not approved for use in potable water systems.
3. Hot water supplied to the hot water heating option must not exceed 200°F temperature or 125 PSIG pressure.
4. Do not operate the units within steam pressure greater than 10 PSIG. Steam pressure must be 10 PSIG or lower to avoid excessive discharge air temperatures that could cause burns or personal injury.
5. Do not overcharge the refrigeration system. This can lead to elevated compressor discharge pressure and possibly flooding the compressor with liquid.
6. Do not attempt to reuse any mechanical or electrical component which has been wet. Such component must be replaced.
IMPORTANT
1. Start-up and adjustment procedures should be performed by a qualified service agency.
2. No water-flow can cause a freeze condition resulting in damage to the coil.
3. Never leave the unit filled with water in a building without heat unless antifreeze has been added.
4. All refrigeration checks must be made by a qualified
R-410A refrigeration technician.
5. Do not release refrigerant to the atmosphere. When adding or removing refrigerant, all national, state/ province, and local laws must be followed.
6. To check most of the Possible Remedies in the troubleshooting guide listed in Tables 15.1 & 16.1, refer to the applicable sections of the manual.
Table of Contents
Inspection on Arrival . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Special Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Hazard Intensity Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
SI (Metric) Conversion Factors. . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Unit Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Drainage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Piping Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Piping Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Terminal Strip Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Start-Up Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Pre-Start Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Unit Start-Up Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Typical Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . 7-8
Start-Up Sheet - Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-10
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Component Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-16
Replacement Parts / Model Nomenclature. . . . . . . . . . . . . . . . . . .17
Serial Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
AIR14.501.1
UNIT LOCATION
Table 3.1 - SI (Metric) Conversion Factors
To Convert Multiply By To Obtain
"W.C.
psig
0.24
6.893 kPa kPa
°F (°F-32) x 0.555 °C
inches
feet
CFM
25.4
0.305 meters
0.028 m mm
3
/min
UNIT LOCATION
To Convert Multiply By To Obtain
CFH
Btu/ft
3
pound
Btu/hr 0.000293 kW/hr
gallons
psig
1.699 m
0.453
3.785
27.7
3
/min
0.0374 mJ/m kg liters
"W.C.
3
DANGER
Appliances must not be installed where they may be exposed to potentially explosive or flammable atmosphere.
Handling
Each unit will be shipped to the site secured to a wood skid using metal brackets. Whenever possible, all lifting and handling of the unit should be done with the packing and skid in position.
Due to the length of the unit, 72" forklift tines are recommended to avoid damaging the unit.
Remove the metal brackets prior to lifting the unit off of the skid.
When slinging or using a forklift to lift the unit, the support points should be sufficiently apart to give stability when lifting. Unless otherwise noted the lifting points should be equidistant from the centerline. Extreme care should be taken not to drop the unit
Considerable damage can occur to the unit during positioning, in particular, to the paneling and exterior paint. Use an adequate number of personnel and the correct tools when moving the unit.
A lifting device such as a forklift is needed to install this product.
A special key is provided with the unit for use with the tamperproof cabinet locks on the top and front panels. The use of torque screwdrivers on panel, cover or component mounting screws is not recommended. Hand-start all screws. If electric drills are used – set at the lowest possible torque.
8. For units with outside air, inspect the wall sleeve and louver installation for gaps that would allow leakage of outdoor air into the space. All joints and abutments should be sealed with waterproof sealant.
Drainage
Units with cooling coils have a condensate drain pan connection and 3/4" ID condensate line. The condensate drain pan connection is field changeable and can be mounted on either the left or right side of the unit. To change the connection location, remove the condensate line from the elbow. Remove the elbow from the drain pan and remove the plug from the opposite side of the drain pan. Re-install the elbow and the plug on the opposite sides of the drain pan. Re-connect the condensate line.
The condensate line must be connected to the main drain system in accordance with any local codes and general good piping practice. For units equipped with an optional condensate pump, the maximum lift is 15 feet.
Electrical
Electrical wiring should be done in accordance with all applicable national and local codes. It is the responsibility of the electrical contractor to adhere to such codes. The warranty will be voided if wiring is not in accordance with the specifications of the unit. Use copper conductors only.
All power supply wiring must be capable of carrying the maximum current load under no fault conditions at the stipulated voltages. Care should be taken to avoid significant voltage drops.
A knockout with strain relief is provided on the electrical box for power wiring. Each unit is supplied with terminal strip for power connection.
Preparation
1. Select the unit location. Check that ceiling is capable of supporting the weight of the unit.
2. Check to make sure that the units will have adequate installation clearance around them.
3. The cabinet must be suspended using the four mounting holes located on the top of the unit from ceiling joists or other suitable supports. Do not suspend the unit at any other locations. The unit is to be installed level front to back and side to side.
4. Before installation, ensure that the correct electrical power supplies are available for the unit.
5. Each unit requires an independently fused and isolated power supply.
6. If the installation has multiple units, check that unit model and tagging corresponds with the installation plans.
Please contact your Airedale representative immediately if discrepancies are noted.
7. Note that units with cooling coils will have a condensate connection and suitable provisions should be made for draining. If multiple units tee into a common drain manifold, it must be sized to ensure free draining with all the units in operation.
AIR14.501.1
INSTALLATION
The instructions detailed below are for the Installation of a
“standard” unit. Accommodations and adjustments will be required for the usage of additional unit options/accessories.
Should assistance be required for the installation of these additional items, consult Modine at the phone number listed on the back cover of this manual.
1. Remove both end panels to allow for access to the mounting holes. If installation does not allow for access through the end of the unit, remove bottom panels prior to placing unit on lifting device.
2. Place protective material on the supports of the lifting device to prevent scratching or denting of the unit. Place unit on the lifting device supporting the unit across its entire length.
3. Raise the unit to the mounting position. Use field supplied rods and fasteners with 1-1/2" diameter washers to suspend the unit at the mounting holes located at the top of the unit
(see Figure 4.1). The unit must be suspended at each of the
(4) 1 inch mounting holes. Do not suspend from any other locations.
4. Install unit level and plumb to prevent excessive vibration and premature failure. To ensure proper drainage unit must be level. Do not mount unit on a slope. Tighten all fasteners.
5. Make the condensate drain connection to the unit.
3
4
START-UP PROCEDURE
Figure 4.1 - Mounting Hole Locations
PIPING ACCESS
PANELS
01.00
MOUNTING HOLES
(TYPICAL 4)
REMOVE END PANELS
FOR ACCESS TO
MOUNTING HOLES
A
17.13
7.55
Table 4.1 - Mounting Hole Location Dimension A
Model Size
750
1000
1250
1500
Dimension A (inches)
48.25
60.25
72.25
84.25
6.88
Piping Installation - Chilled/Hot Water Coils
CAUTION
1. Units not approved for use in potable water systems.
2. Hot water supplied to the hot water heating option must not exceed 200°F temperature or 125 PSIG pressure.
3. Do not attempt to reuse any mechanical or electrical component which has been wet. Such component must be replaced.
1. Chilled water and hot water coils are supplied, from the factory, with unions. Field installed piping can be mounted to the supplied unions with 3/4" female sweat connections.
Factory assembled piping packages are supplied with matching unions on the coil and the piping assembly.
2. Install shut-off valves in lines to and from each coil to allow maintenance or replacement of unit without shutting down and draining entire system (see Figures 4.2 and 4.3).
3. Include a circuit setter in the return line for water flow regulation.
4. A drain valve (hose bib) should also be provided for each coil to allow removal of water from the coil if located in an area subject to freezing.
5. It is advisable to use a pipe line strainer before each coil.
6. Provide adequate pipe hangers, supports, or anchors to secure the piping system independently of the coil.
Figure 4.2 - Typical 2-Way Piping Installation
Piping Installation – Direct Expansion (DX) Coils
CAUTION
1. ZCV and ZCF units with DX evaporator coils contain the refrigerant R-410A. Review the R-410A Material Safety
Data Sheet (MSDS) for hazards and first aid measures.
2. Refrigerant charging should only be carried out by an
EPA-certified air conditioning contractor.
Note: R-410A refrigerant is the only approved refrigerant for this system.
The unit should be piped up in accordance with good refrigeration and/or plumbing practices.
The outdoor condensing unit must be connected to the indoor unit coil using field supplied refrigerant grade (ACR) copper tubing that is internally clean and dry. Units should be installed only with the tubing sizes for the approved system combination as specified in Table 12.1.
Condensing unit is typically factory charged for a 15-foot lineset.
For additional lineset lengths please refer to manufacturer’s charging chart.
See the installation and maintenance manual provided with the condensing unit for installation, evacuation and system charge information.
Figure 4.3 - Typical 3-Way Piping Installation
AIR14.501.1
INSTALLATION
Piping Installation - Steam Coils
CAUTION
Do not operate the units within steam pressure greater than
10 psig. Steam pressure must be 10 psig or lower to avoid excessive discharge air temperatures that could cause burns or personal injury.
1. Steam coils are supplied from the factory with 1" NPT connections
2. A steam trap should be provided with a trap of sufficient size and capacity to pass a minimum of two times the normal condensate released by the unit at the minimum differential pressure in the system.
Piping Insulation
Chilled water and condensate pipes should be insulated right up to the coil to prevent condensation which can damage objects located below the piping. Chilled water valves must also be insulated to prevent sweating. Hot water pipes should be insulated to reduce heat loss and to prevent overheating of the end compartment.
Wiring
WARNING
1. Disconnect power supply before making wiring connections to prevent electrical shock and equipment damage.
2. All appliances must be wired strictly in accordance with the wiring diagram furnished with the appliance. Any wiring different from the wiring diagram could result in a hazard to persons and property.
3. Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rating of at least 105°C.
4. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% greater than rated voltage.
Installation of wiring must conform with local building codes, or in the absence of local codes, with the National Electric
Code ANSI/NFPA 70 - Latest Edition. Unit must be electrically grounded in conformance to this code. In Canada, wiring must comply with CSA C22.1, Part 1, Electrical Code.
Electric wiring must be sized to carry the full load amp draw of the motor, starter and any controls that are used with the unit.
See Table 12.2 for Electrical Data.
Any damage to or failure of units caused by incorrect wiring of the units is not covered by warranty.
Once the piping installation is complete, the electrical supply can be connected to the terminal strip in the electrical box.
When installing any wiring into the control box, extra cable must be left outside the panel to allow the panel to open fully. Failure to follow these instructions may cause damage to the wiring and/or the unit.
Terminal Strip Connections
The terminal strip connections are designed to clamp down on the wires. To properly connect the wires to the terminal strip:
1. Push a small flat-head screwdriver into the square hole on the terminal. Press firmly until the screwdriver hits the back stop and opens the terminal (see Figure 5.1).
2. Remove approximately 3/8" of insulation from the end of the wire and push the stripped wire into the oval hole in the terminal.
3. Remove the screwdriver. Pull on the wire to make sure that it is securely clamped in the terminal.
4. Make sure that the terminal clamp is in contact with bare wire
(insulation removed).
Figure 5.1 - Terminal Strip
CAUTION
1. Ensure that the supply voltage to the appliance, as indicated on the serial plate, is not 5% less than the rated voltage.
2. Do not attempt to reuse any mechanical or electrical component which has been wet. Such component must be replaced.
AIR14.501.1
5
6
START-UP PROCEDURE
START-UP PROCEDURE
IMPORTANT
1. Start-up and adjustment procedures should be performed by a qualified service agency.
2. No water-flow can cause a freeze condition resulting in damage to the coil.
3. Never leave the unit filled with water in a building without heat unless antifreeze has been added.
See start-up sheet examples - Figures 9.1 and 10.1.
Pre-Start Checks
1. Check that the supply voltage matches the unit supply voltage listed on the Unit Serial Plate. Verify that all wiring is secure and properly protected. Trace circuits to insure that the unit has been wired according to the wiring diagram.
2. Check that the unit has no visible damage and that all the components are secure.
3. Check that all field electrical and mechanical work has been performed according to all applicable Federal, State, and
Local codes.
4. Check the supply voltage to the unit is within +/- 5% of the voltage on the unit serial plate.
5. Check that the system has been correctly flushed.
6. Check for any water leaks.
7. The unit and interconnecting piping have been evacuated correctly and the condensing unit service valves are open
(DX Cooling units only).
8. Check that the plug is installed for the condensate connection that is not being used.
10. Check that the motor is secure and the shaft and blower set screws are tight. Rotate the blower shaft by hand.
11. Check that the filters have been properly installed.
Unit Start-Up Procedure
Note: For models with DX Cooling, see the installation and maintenance manual provided with the condensing unit for startup information.
1. (DX Cooling models only) Ensure that the condensing unit start-up procedure has been carried out, as detailed in the condensing unit installation and maintenance manual.
2. (DX Cooling models only) The compressor should be isolated by removing the connection at the Y1 terminal on the indoor unit. Main power can now be applied to the indoor and outdoor units. A system electrical check can now be carried out.
3. Switch the 3-speed switch to position 1, 2 or 3.
4. Switch the disconnect switch to the “ON” position.
5. Confirm that the blower motor is rotating in the correct direction and blowing air out of the supply air grill.
6. (Units with Chilled Water, Hot Water and Steam coils only)
Ensure all valves are open to the unit.
7. (Units with Chilled Water and Hot Water only) Check water flow rates and pressure drops and compare to design.
8. Check that the dampers are not obstructed and move through their full range of motion.
9. During the unit operation, measure and record all the information that is required to complete the Start-Up Sheets that are supplied with the unit. Copy the information onto the
Start-Up Sheets (Figures 9.1 and 10.1) in this manual for your records.
10. (DX Cooling models only) Shut unit down and disconnect the main power. The compressor signal Y1 (disconnected from the indoor unit in step 2) can now be re-connected and main power applied to the system.
Note: (DX Cooling models only) The 24V power for the indoor unit control circuit is supplied from a unit factory-installed transformer. When the indoor and outdoor units are supplied from separate main supplies, care must be taken to ensure that the outdoor unit is isolated whenever the indoor unit power is removed. Failure to do so may result in freeze ups and other damage to the unit.
AIR14.501.1
START-UP PROCEDURE
Typical Sequence of Operation
Supply Fan
The supply fan shall run at all times when unit is in occupied mode. When in unoccupied mode, the supply fan shall run only on a call for heating or cooling. The supply fan speed can be adjusted using the standard equipped manual 3-speed switch.
If equipped with Modine Control System, the supply fan is programmed to run for 2 minutes (adjustable) after the heating or cooling cycle ends.
Hot Water or Steam with Valve Control
Units with a hot water or steam coil and non-Carel controls desiring valve control shall use a spring-return, normally open modulating valve operated by a proportional signal (2-10VDC) or a tri-state (24VAC) signal. Units with Carel controls desiring valve control shall use a modulating control valve with a proportional signal. When the room temperature is below the heating setpoint, the valve shall open proportionally according to the adjustable proportional band. The adjustable proportional band on the Carel controller is set to a default 1˚F (example: valve is 50% open when room temperature is 0.5˚F from setpoint). If for any reason the supply air temperature drops below 55˚F (adjustable), the valve shall modulate open to maintain 55˚F.
Freeze Stat (Optional)
On units equipped, an adjustable auto-resetting freeze stat is factory set to trip at 35˚F. If the coil temperature reaches the limit and the freeze stat trips, it shall automatically reset when the coil temperature rises 5˚F above the setpoint. The freeze stat shall be wired so that upon tripping, power is removed from the supply fan, the outside air damper closes, and either the
HW valve opens (model digit 3=V) or the face & bypass damper goes to full bypass (model digit 3=F).
Outside Air and Return Air Dampers (Optional)
The outside air and return air dampers control the mixture of return air and outside air drawn through the unit. Both dampers are linked together and are controlled by an actuator requiring a
2-6VDC proportional signal. At 2V, the dampers are positioned for full return air and no outside air. At 6V, the dampers are positioned for full outside air and no return air. The outside air damper shall open to a minimum position to provide ventilation requirements when the room is occupied. When in heating mode, if the space temperature is more than 4˚F from the heating setpoint, the outside air damper shall fully close. The outside air damper shall also be fully closed during unoccupied mode. If the unit is equipped with a CO
2
sensor, the outside air damper shall modulate open proportionally to compensate for the CO
2
levels in the room.
The dampers can act as economizers for free-cooling. If cooling is required and the outside air temperature is below the economizer outside air lockout temperature (60˚F recommended) and above 35˚F (adjustable), the outside air damper shall modulate open. On units with a Carel controller, the outside air damper shall fully open when the room temperature is above the setpoint by more than 1˚F (adjustable).
Within 1˚F, the proportional band adjusts the outside air damper.
When the unit is in free-cooling, water valves shall be fully closed, and if equipped, the face & bypass damper should move to full bypass position. The outside air lockout temperature on
Carel units is factory set to 60˚F and is adjustable.
Chilled Water with Valve Control
Units with a chilled water coil and non-Carel controls desiring valve control shall use a non-spring return modulating valve operated by either a proportional (2-10VDC) or a tri-state
(24VAC) signal. Units with a chilled water coil and Carel controls desiring valve control shall use a modulating valve requiring a tri-state signal. When the room temperature is above the cooling setpoint, the valve shall open proportionally according to the adjustable proportional band. The adjustable proportional band on the Carel controller is set to a default 1˚F (example: valve is
50% open when room temperature is 0.5˚F from setpoint). The
Carel controller will not allow the chilled water valve to open when the outside air temperature is below 55˚F.
Direct Expansion (DX) Cooling Control
When the room temperature is above the cooling setpoint, the compressor will be energized. The compressor will de-energize when the room temperature falls below the cooling setpoint.
If the factory installed low limit stat detects indoor evaporator coil temperatures below its set point, the compressor will be disabled.
Chilled Water with Face & Bypass Control
Units equipped with a chilled water coil and face & bypass control shall modulate the face & bypass damper via a spring return actuator, controlled by a proportional signal (2-5.5V).
The face & bypass damper regulates the amount of return air and outside air passing through the chilled water coil. On a call for cooling, the damper shall open to the face of the coil proportionally based on how many degrees the room temperature is from the setpoint. The adjustable proportional band on the Carel controller is set to a default 1˚F (example: damper is 50% open when room temperature is 0.5˚F from setpoint). When the damper is in full bypass position (2V), all return and outside air bypasses the chilled water coil. When the damper is in full face position (5.5V), all return and outside air passes through the chilled water coil.
Hot Water with Face & Bypass Control
Units equipped with a hot water or steam coil and face & bypass control shall modulate the face & bypass damper via a spring return actuator, controlled by a proportional signal (2-5.5V).
The face & bypass damper regulates the amount of return air and outside air passing through the heating coil. On a call for heating, the damper shall open proportionally based on how many degrees the room temperature is from the setpoint. The adjustable proportional band on the Carel controller is set to a default 1˚F (example: damper is 50% open when room temperature is 0.5˚F from setpoint). When the damper is in full bypass position (2V), all return and outside air bypasses the heating coil. When the damper is in full face position (5.5V), all return and outside air passes through the heating coil. If for any reason the supply air temperature drops below 55˚F
(adjustable), the heating valve shall open (if equipped) and the face and bypass damper shall modulate to maintain 55˚F.
Units desiring valve control to provide heating and cooling on a single water coil (2-pipe system) and not using Carel controls shall use a spring-return, normally open modulating valve operated by a proportional signal (2-10VDC) or a tristate (24VAC) signal. Units with Carel controls shall use a modulating control valve with a proportional signal. On a call for heating or cooling (depending on the season), the valve
AIR14.501.1
7
SEqUENCE OF OPERATION
shall open proportionally based on how many degrees the room temperature is from the setpoint. The adjustable proportional band on the Carel controller is set to a default 1˚F (example: valve is 50% open when room temperature is 0.5˚F from setpoint). If for any reason the supply air temperature drops below 55˚F (adjustable), the water valve shall modulate open to maintain 55˚F. On 2-pipe units not having Carel controls or not connected to a network, an optional aquastat is recommended to prevent inadvertent changeover of heating/cooling modes.
Condensate Pan Float Switch (Optional)
On units equipped with a condensate pan float switch, the normally closed switch shall be wired such that the chilled water valve closes or the outdoor condensing unit is disabled
(DX Cooling Models Only) upon tripping. On Carel units, the switch shall be wired normally closed into a digital input of the controller. If the unit is also equipped with a condensate pump, both the condensate pump limit switch and condensate pan float switch shall be wired in series.
Hot Water and Chilled Water (2-Pipe) with
Face & Bypass Control
Units desiring face and bypass control to provide heating and cooling on a single water coil (2-pipe system) shall modulate the face & bypass damper via a spring return actuator, controlled by a proportional signal (2-5.5V). The face & bypass damper regulates the amount of return air and outside air passing through the water coil. On a call for heating or cooling (depending on the season), the damper shall open proportionally based on how many degrees the room temperature is from the setpoint. The adjustable proportional band on the Carel controller is set to a default 1˚F (example: damper is 50% open when room temperature is 0.5˚F from setpoint). When the damper is in full bypass position (2V), all return and outside air bypasses the water coil. When the damper is in full face position (5.5V), all return and outside air passes through the water coil. If for any reason the supply air temperature drops below 55˚F (adjustable), the water valve shall open (if equipped) and the face and bypass damper shall modulate to maintain 55˚F.
CO
2
Sensor (Optional)
An optional CO
2
sensor with a range of 0-2000 ppm producing an output signal of 4-20mA is available to modulate the outside air damper. If equipped, the outside air damper shall modulate open proportionally to compensate for the CO room. On Carel units, if the CO
2
2
levels in the
(adjustable), the damper shall remain at its normal minimum position. If the CO
2
level increases above 800 ppm, the damper begins to open according to the proportional band.
The proportional band is set to a default of 200 ppm and is adjustable. Using the default, once the CO
2
level reaches 1000 ppm, the damper shall be at its maximum ventilation position.
Fire Detector (Optional)
Units equipped with an optional fire detector shall shut down power to the supply fan and close all dampers upon the detection of a fire.
2-Position Control Valves
Optional spring-return, 2-position control valves can be used to control the end of cycle flow on both chilled and hot water coils.
On a chilled water coil, a normally closed valve is used. On a hot water coil or 2-pipe changeover system, a normally open valve is used.
The 2-position valve used on a chilled water coil shall open on a call for cooling when the outside air temperature is greater than
55˚F (adjustable). When the outside air temperature is less than
55˚F, the valve should remain closed and free cooling shall be utilized. The 2-position chilled water valve shall be closed when the 2-position hot water valve is open (when equipped). The valve is controlled by a 24VAC digital output.
The 2-position valve used on a hot water coil shall open on a call for heating. The valve shall always open when the outside air temperature drops below 40˚F. This is to prevent the coil from freezing or nuisance tripping of the freeze stat. The
2-position hot water valve shall be closed when the 2-position chilled water valve is open (if equipped). The valve is controlled by a 24VAC digital output.
The 2-position valve used on a 2-pipe changeover system shall operate like the 2-position chilled water valve in cooling mode, and like the 2-position hot water valve in heating mode.
Smoke Detector (Optional)
Units equipped with an optional smoke detector shall shut down power to the supply fan and close all dampers upon the detection of smoke. The LED on the smoke detector will stay on solid. Cycle the power Off and then On to reset.
Condensate Pump (Optional)
On units equipped with a condensate pump, the pump shall begin to run once the condensate reaches a set level. The pump comes with an internal safety switch that can be wired either normally open or normally closed. The safety switch shall be wired such that the chilled water valve closes when it trips.
On Carel units, the switch shall be wired normally closed into a digital input of the controller. If the unit is also equipped with a condensate pan float switch, both switches shall be wired in
8
series.
AIR14.501.1
START-UP SHEET - EXAMPLE
Figure 9.1 - Start-Up Sheet - EXAMPLE Page 1
AIR14.501.1
9
START-UP SHEET - EXAMPLE
Figure 10.1 - Start-Up Sheet - EXAMPLE Page 2
10
AIR14.501.1
DIMENSIONS
Figure 11.1 - Unit Dimensions
AIR14.501.1
Table 11.1 - Unit Dimensions
Model Size
750
1000
1250
1500
Dimensions (inches)
W1 W2
62
74
86
98
36
48
60
72
11
TECHNICAL DATA
Table 12.1 - Technical Data
ZCF & ZCV
SUPPLY FAN
Fan Quantity
Fan Diameter
Fan Width
Standard Motor Size (Qty 1)
Standard Motor Type
Airflow (High/Medium/Low)
Max External Static Pressure
COIL WATER VOLUME
1 Row
2 Row
3 Row
4 Row
CONNECTIONS
Water Coils
Evaporator Coil
Steam Coil
Condensate Line
UNIT WEIGHT (approximate)
Shipping Weight
Operating Weight
FILTER
Quantity
Dimensions
Table 12.2 - Electrical Data
Motor Size
½ Hp EC Motor
½ Hp EC Motor with
Condensate Pump
FLA
7.7
9.2
115V
MCA
9.6
11.1
Units
hp cfm in.Wg
gal gal gal gal
Inches
Inches
Inches
Inches lbs.
lbs.
in.
MOP
15
15
FLA
5
5.6
208V
MCA
6.3
6.9
MOP
10
10
750
2
8.06
7.15
1/2
750/650/550
0.25
0.32
0.51
0.72
0.92
375
320
1
10 X 36
1000 1250
Direct Drive Centrifugal
3 4
8.06
7.15
8.06
7.15
1/2 1/2
ECM - Electronically Commutated Motor
1000/850/750
0.25
1250/1100/1000
0.25
1500
4
8.06
7.15
1/2
1500/1250/1000
0.25
0.38
0.63
0.91
1.17
0.44
0.76
1.1
1.42
Unions with 3/4" female solder joint
3/4" OD Suction, 1/2" OD Liquid
1" NPT
3/4” ID condensate line
0.5
0.88
1.28
1.66
420
365
470
410
1" Woven Fiberglass, 70-75% Arrestance
2 2
10 X 24 10 X 30
520
450
2
10 X 36
FLA
4.3
4.8
230V
MCA
5.4
5.9
MOP
8
10
FLA
4.1
4.6
277V
MCA
5.1
5.6
MOP
6
6
12
AIR14.501.1
COMPONENT LAYOUT
Figure 13.1 - Exploded View
END
PANELS
BASE ASSEMBLY
DAMPER ASSEMBLY
CONTROL PANEL
FILTER
COIL ASSEMBLY
BLOWER
ASSEMBLY
BOTTOM
PANELS
DISCHARGE AIR PANEL
ASSEMBLY
AIR14.501.1
13
MAINTENANCE
MAINTENANCE
WARNING
When servicing or repairing this equipment, use only factoryapproved service replacement parts. A complete replacement parts list may be obtained by contacting Modine Manufacturing
Company. Refer to the rating plate on the appliance for complete appliance model number, serial number, and company address. Any substitution of parts or controls not approved by the factory will be at the owner’s risk.
CAUTION
Do not attempt to reuse any mechanical or electrical component which has been wet. Such component must be replaced.
IMPORTANT
To check most of the possible remedies in the troubleshooting guide listed in Tables 15.1 & 16.1, refer to the applicable sections of the manual.
The routine care and maintenance of this unit will increase longevity, provide for the proper operational performance, and reduce the probability of failure.
Once the unit is operational, it will be necessary to perform certain routine maintenance/service checks. Following is a
Maintenance Schedule with the recommended checks. If your unit is equipped with special features, there may be additional checks that are required. Consult Modine for assistance.
The use of torque screwdrivers on panel, cover or component mounting screws is not recommended. Hand-start all screws.
If electric drills are used – set at the lowest possible torque.
Figure 14.1 - Filter Location
Access
Access to the unit is gained by opening the bottom access panels.
Maintenance Schedule
Every ONE (1) MONTHS
With the Disconnect in the “OFF” position: check the filter(s) and replace if necessary. Remove the filter support bracket and slide the filter(s) out of the track. Replace with new filter(s) and reinstall the filter support bracket (see Figure 14.1). Never run the unit without filters.
Every SIX (6) MONTHS
(Before the heating and cooling season)
1. Check for correct fan operation, no excessive noise or vibrations.
With the Disconnect Switch in the “OFF” position:
2. Inspect all electrical circuits including optional components and sensors for loose connections and signs of overheating, arcing, chafing or other physical damage. The electrical control section should also be wiped clean of all dirt that may affect the unit operation.
3. Check the filter(s) and replace if necessary. Remove the filter support bracket and slide the filter(s) out of the track. Replace with new filter(s) and reinstall the filter support bracket (see
Figure 14.1). Never run the unit without filters.
4. Check the control wiring and sensors. Check the operation and sequencing of controls and ensure that all relevant set points are recorded.
5. Check all warning labels to ensure they can be read and that they have not been removed.
6. Inspect condensate hose for any possible clogs.
7. Check for general obstructions to inlet and discharge openings.
8. Oil the fan motor by adding 3 drops of SAE 20 weight nondetergent oil to the two oil holes on the fan motor.
9. Fill the fan shaft bearing cup with oil. The fan shaft bearing is located in the housing at the opposite end of the fan shaft from the motor (see Figure 14.2). Additional bearing cup in middle of unit on 1250 and 1500 CFM units accessible through front panel.
Figure 14.2 - End Shaft Bearing Cup Location
14
FILTER
FILTER SUPPORT
BRACKET
FAN SHAFT
BEARING
FILTER/DAMPER
ACCESS PANEL
AIR14.501.1
TROUBLESHOOTING
Table 15.1 - Troubleshooting - General
Trouble
A. Unit Not Operating -
Power On
B. Unit Operating -
No Mechanical
Heating / Cooling
C. No Indoor Fan
D. Hot Water / Chilled
Water Valve Not
Operational (Option)
E. DX Split Units Only:
Low Suction Pressure
(LP Switch Tripped)
Possible Cause Possible Remedy
1. Unit mounted disconnect in the “OFF” position. 1. Turn the disconnect switch to the “ON” position.
2. Unit mounted 3-speed selector switch in the
“0” position.
2. Turn the 3-speed selector switch to the “1, 2, or 3” position.
3. Unit switched OFF in the microprocessor.
4. Delay on start set incorrectly.
5. Unit not in occupied mode.
3. Consult microprocessor documentation.
4. Consult microprocessor documentation.
5. Consult microprocessor documentation, and consult microprocessor occupied setpoints.
6. Fire/smoke alarm tripped.
7. Tripped circuit breakers.
8. Loose mains or control wiring.
9. Occupancy sensor malfunction.
6. De-energize and re-energize unit.
7. Reset the tripped circuit breaker(s).
8. With power OFF from distribution panel inspect the field wiring connections in the electrical panel.
9. Inspect connections beginning with sensor input from the microprocessor.
10. Manually reset at stat.
10. Hot water freeze protection (optional) stat tripped.
1. Heating/cooling not required.
2. No output from microprocessor.
3. DX Split Units Only: HP/LP pressure safety switch(es) tripped (open).
4. DX Split Units Only: Internal overload switch on compressor tripped (open).
5. Loose control wiring connections.
6. Tripped circuit breakers.
7. Low temperature unit lockout.
8. DX Split Units Only: Compressor faulty.
1. Verify applicable set point with return air temperature.
2. Consult microprocessor documentation.
3. Inspect high and low system pressures and wiring.
Check for dirty filters in Heat Pump mode.
4. Wait for compressor motor windings to cool down
(This switch is automatic reset).
5. Inspect connections beginning with compressor output from the microprocessor.
6. Reset the tripped circuit breaker(s).
7. Consult microprocessor setpoints.
8. Replace compressor.
9. Condensate pan/pump float switch tripped.
1. Motor tripped on internal overload.
2. Fan not required
3. No power to the fan.
4. Current sensor fault.
1. Heating not required.
2. Loose wiring connections.
3. Faulty heating actuator.
4. Isolation valves are open.
5. Check for DC control signal.
1. Low refrigeration charge.
2. Clogged filter(s).
3. Clogged liquid line filter drier.
4. Improper expansion valve setting or valve malfunctioning.
5. Low/restricted supply airflow.
9. Check condensate pan/pump and piping for blockage.
1. Let motor cool down and reset - possible bad motor or blocked filter.
2. Consult microprocessor documentation, or set thermostat to “ON”. Check if unit is in unoccupied and standby mode.
3. Check to make sure plugs are locked in place and all pins are secure. Check for 24V control signal.
4. Make sure sensor is functioning correctly.
1. Consult microprocessor documentation.
2. Inspect connections beginning with valve output from the microprocessor. Check to ensure 24V supply power is present at actuator.
3. Replace actuator if faulty.
4. Check for additional external isolation valves.
5. Check for 2-10vDC signal from microprocessor.
1. Measure unit operating pressures. Add charge and check for leaks.
2. Replace filter(s) as necessary.
3. Replace drier with a direct replacement. Follow proper procedure.
4. Check operation and superheat settings.
5. Check diffusers, filters and supply motor to ensure appropriate airflow.
AIR14.501.1
15
TROUBLESHOOTING
Table 16.1 - Troubleshooting - General
Trouble
F. DX Split Units Only:
Low Discharge
Pressure
G. DX Split Units Only:
High Suction Pressure
H. DX Split Units Only:
High Discharge
Pressure
I. Condensate Leaking
J. Microprocessor Not
Working - Faulty
Operation
Possible Cause
1. Low refrigeration charge.
2. Faulty compressor.
3. Faulty reversing valve.
4. Outdoor air sensor out of calibration.
Possible Remedy
1. Measure unit operating pressures. Add charge and check for leaks.
2. Replace compressor.
3. Evacuate system and replace reversing valve.
4. Check outdoor air sensor for accuracy.
1. Excessive load.
1. Check occupancy of space.
2. Expansion valve malfunctioning (overfeeding). 2. Check remote bulb is secure and vapor sealed, and regulate superheat.
3. Faulty compressor.
1. Loose sensor wire connectors.
2. Strategy file corrupted.
3. Replace compressor.
1. Improper installation of wall sleeve and louver. 1. Ensure splitter plate is in contact with the back of the louver blade and the unit to ensure no re-circulation of exhaust air takes place.
2. Dirty condenser coils.
3. System overcharged.
2. Clean condenser coil.
3. Remove excess refrigerant.
4. Noncondensables in system.
5. Condenser fan speed is too slow (cooling mode).
1. Condensate drain not piped up.
2. Condensate pan/line plugged.
3. Condensate pump (optional) faulty.
4. Evacuate refrigerant circuit and recharge.
5. Not applicable, refer to manufacturer's Technical Manual.
1. Pipe condensate drain.
2. Clean drain pan and piping.
3. Check operation of condensate pump. Replace pump if necessary.
1. Inspect sensor connections at the microprocessor.
2. Consult microprocessor documentation.
3. Loose control wiring.
3. Check 24V power supply wiring.
16
AIR14.501.1
REPLACEMENT PARTS
REPLACEMENT PARTS
For ease of identification when ordering replacement parts or contacting the factory about your unit, please quote the unit type and unit serial number. This information can be found on the serial plate attached to your unit (see Figure 18.1).
When a component part fails, a replacement part should be obtained through our Parts Department. If the part is considered to be under warranty, the following details are required to process this requirement:
Figure 17.1 - Model Nomenclature
1. Full description of part required, including Unit’s part number, if known.
2. The original equipment serial number.
3. An appropriate purchase order number.
To order replacement parts contact technicalservice@
na.modine.com or call 1-800-828-4328.
AIR14.501.1
17
SERIAL PLATE
Figure 18.1 - Serial Plate EXAMPLE
18
AIR14.501.1
THIS PAGE LEFT BLANk INTENTIONALLY
AIR14.501.1
19
COMMERCIAL WARRANTY
Seller warrants its products to be free from defects in material and workmanship, EXCLUSIVE, HOWEVER, of failures attributable to the use furnished by Seller, or any charges for any such labor or materials, whether such labor, materials or charges thereon are due to replacement of parts,
Seller in any way so as, in the judgment of Seller, to affect its stability, nor which has been subjected to misuse, negligence, or operating conditions in
WARRANTIES, EITHER EXPRESS OR IMPLIED, WHETHER ARISING
FROM LAW, COURSE OF DEALING, USAGE OF TRADE, OR OTHERWISE,
BEYOND THE PRODUCT DESCRIPTION CONFIRMED BY BUYER AND
SELLER AS OF THE DATE OF FINAL AGREEMENT.
units, or if the product in the judgment of SELLER has been installed in a corrosive atmosphere, or subjected to corrosive fluids or gases, been subjected contrary to SELLER’S printed instructions, or if the serial number has been altered, defaced or removed.
ANY OTHER CONSEQUENTIAL OR INCIDENTAL DAMAGES OF ANY KIND
RESULTING FROM THE ORDER OR USE OF ITS PRODUCT, WHETHER
BUYER’S REMEDY FOR BREACH OF WARRANTY, EXCLUSIVE OF ALL
OTHER REMEDIES PROVIDED BY LAW, IS LIMITED TO REPAIR OR
WITH TRANSPORTATION CHARGES PREPAID AND WHICH THE
EXAMINATION OF SELLER SHALL DISCLOSE TO HAVE BEEN DEFECTIVE;
BUYER’S REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE
LIMITED TO ONE YEAR FROM DATE OF SHIPMENT FROM SELLER. FOR
REMEDY FOR BREACH, AS LIMITED HEREIN, SHALL BE LIMITED TO
TEN YEARS FROM DATE OF SHIPMENT FROM SELLER.
transferred or assigned. No provision is made in these warranties for any labor allowance or field labor participation. Seller will not honor any expenses incurred in its behalf with regard to repairs to any of Seller’s products. No credit shall be issued for any defective part returned without proper written
OPTIONAL SUPPLEMENTAL WARRANTY
Provided a supplemental warranty has been purchased, Seller extends the warranty herein for an additional four (4) years on certain compressors.
Provided a supplemental warranty has been purchased, Seller extends the warranty herein for an additional four (4) years or nine (9) years on certain heat exchangers.
EXCLUSION OF CONSUMABLES & CONDITIONS BEYOND SELLER’S
CONTROL gas, belts, filters, fuses and other items consumed or worn out by normal wear and tear or conditions beyond Seller’s control, including (without limitation as to generality) polluted or contaminated or foreign matter contained in the air or water utilized for heat exchanger (condenser) cooling or if the failure of the part
Component
Applicable Models
“APPLICABLE WARRANTY PERIOD”
Heat Exchangers
Gas-Fired Units except PSH/BSH
TEN YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
TEN YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN TEN YEARS
FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN ONE
HUNDRED TWENTY-SIX MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER
OCCURS FIRST
Heat Exchangers
Low Intensity Infrared Units
Compressors
Condensing Units for Cassettes
Burners
Low Intensity Infrared Units
Other
Components excluding Heat Exchangers,
Coils, Condensers, Burners, Sheet Metal
FIVE YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
FIVE YEARS FROM DATE OF RESALE BY BUYER OR ANY OTHER USER, WITHIN FIVE YEARS
FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN SIXTY-SIX
MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
TWO YEARS FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
TWO YEARS FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN
THIRTY MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
Heat Exchangers/Coils
Indoor and Outdoor Duct Furnaces and
System Units, PSH/BSH, Steam/Hot Water Units,
Oil-Fired Units, Electric Units, Cassettes,
Vertical Unit Ventilators, Geothermal Units
Compressors
Vertical Unit Ventilators, Geothermal Units
Burners
High Intensity Infrared Units
Sheet Metal Parts
All Products
ONE YEAR FROM DATE OF FIRST BENEFICIAL USE BY BUYER OR ANY OTHER USER, WITHIN
ONE YEAR FROM DATE OF RESALE BY BUYER IN ANY UNCHANGED CONDITION, OR WITHIN
EIGHTEEN MONTHS FROM DATE OF SHIPMENT FROM SELLER, WHICHEVER OCCURS FIRST
As Modine Manufacturing Company has a continuous product improvement program, it reserves the right to change design and specifications without notice.
© Modine Manufacturing Company 2014
Commercial Products Group
Modine Manufacturing Company
1500 DeKoven Avenue
Racine, WI 53403
Phone: 1.866.823.1631 (toll free) www.modinehvac.com/schoolsystems

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- Ceiling Mount
- Direct Expansion (DX) or water coils
- 3-speed fan control
- Optional condensate pump
- Optional outside air and return air dampers
- Optional fire and smoke detectors
- Optional CO2 sensor
- Optional freeze stat
- Built-in filter
- Multiple model sizes