- No category
advertisement
Rail-DALI User Guide
(Version 5.5)
Rail-DALI is a DMX / DALI interface. It will convert either 256 channels from DMX to DALI or 64 channels & 16 groups from DALI to DMX. Using the unique features of intelligent DALI and RDM it allows system information from the fixtures back to the controller (DMX to DALI only). In DMX to
DALI mode all parameters including start address are set using RDM. This can be done using any of the following products: Jump-Start & Net-Lynx O/P or Ether-Lynx via an Art-Net network. For more information see App Note 36 & 39 at www.ArtisticLicence.com
Key Features include:
Four independent DALI bus circuits
Bi-directional data
Upto 256 channel conversion (DMX to DALI only)
8Hz (min) DALI Refresh rate (64 channel mode)
RDM (Remote Device Management Draft V1.0)
DMX512-A compatible
Microprocessor controlled
Surface mount or DIN rail mounted
User configurable: o DMX to DALI / DALI to DMX Converter o Multiple Configuration Options
Specification:
Input Voltage:
Maximum Power:
Internal Fuse:
Dimensions:
Mounting:
IP:
Listings:
Operation Mode:
Factory Default:
9V - 24V DC
7W
500mA Electronic fuse
W:88 H:90 D:58mm
DIN Rail or surface mount
Indoor use only
CE, FCC
DMX to DALI or DALI to DMX
DMX to DALI mode
Power Supply Options:
(order separately)
PSU-9-1.5-FER
Output: 9V 1.5A
Input: Auto-sensing
Max Rail-DALIs: 1
Listing: CE / FCC / UL / PSE
PSU-24-2-DR
Output:
Input:
24V 2A
Auto-sensing
Max Rail-DALIs: 2
Listing: CE / FCC / UL / PSE
Refresh Rates on DMX to DALI:
Personality Mode
0
1
2
3
4 Channel mode
16 Channel mode
64 Channel mode
256 Channel mode
Worst Case
Refresh Rate
64mS
400mS
1Sec
4 Sec
Copyright © Artistic Licence Engineering Ltd. All rights reserved.
Rail-DALI Wiring Diagram: (DMX to DALI)
Mode: In ‘DMX to DALI mode’ values from a DMX controller will be converted to DALI channels with respect to the assigned personality and start addresses. Each of the four DMX channel blocks are converted to the corresponding DALI channel or group on one of the four output circuits
Input: DMX512-A
Output: 4 x DALI circuit (64 channels per circuit)
DIP Switches: 1, 2, 3 to the ‘OFF’ position
Personality 0: (Dip Sw4 = ON, Dip Sw5 = ON)
4 channel mode – each DALI circuit is broadcast controlled by a single DMX channel
DMX Channel
Start Address
Start Address + 1
Start Address + 2
Start Address + 3
Output
Broadcast on DALI Circuit 1
Broadcast on DALI Circuit 2
Broadcast on DALI Circuit 3
Broadcast on DALI Circuit 4
Personality 1: (Dip Sw4 = ON, Dip Sw5 = OFF)
16 channel mode – each DALI group is controlled by a single DMX channel, broadcast on all circuits
DMX Channel
Start Address
Start Address + 1
…
Start Address + 15
Output (all circuits)
Group 1 Broadcast
Group 2 Broadcast
…
Group 16 Broadcast
Personality 2: (Dip Sw4 = OFF, Dip Sw5 = ON)
64 channel mode – each DALI group is controlled by a single DMX channel, each DALI network is addressed by 16 different channels
DMX Ch DALI Circuit 1 DMX Ch DALI Circuit 2 DMX Ch DALI Circuit 3 DMX Ch DALI Circuit 4
SA + 0
SA + 1
…
SA + 15
Group 1
Group 2
…
Group 16
SA + 16
SA + 17
…
SA + 31
Group 1
Group 2
…
Group 16
SA + 32
SA + 33
…
SA + 47
Group 1
Group 2
…
Group 16
SA + 48
SA + 49
…
SA + 63
Group 1
Group 2
…
Group 16
Personality 3: (Dip Sw4 = OFF, Dip Sw5 = OFF)
256 channel mode – each DALI ballast is a sub device and is addressed by a single DMX channel
DMX Ch
SA + 0
SA + 1
…
SA + 63
DALI Circuit 1
Channel 1
Channel 2
…
Channel 64
DMX Ch
SA + 64
SA + 65
…
SA + 127
DALI Circuit 2 DMX Ch
Channel 1
Channel 2
SA + 128
SA + 129
…
Channel 64
…
SA + 191
DALI Circuit 3 DMX Ch
Channel 1
Channel 2
SA + 192
SA + 193
…
Channel 64
Termination Link: Fit only if unit is last in the DMX line
…
SA + 255
DALI Circuit 4
Channel 1
Channel 2
…
Channel 64
Feedback: Lamp status information from the DALI fixtures are fed back to the DMX controller using RDM
Rail-DALI Wiring Diagram: (DALI to DMX)
Mode: In ‘DALI to DMX mode’ Rail-DALI is used to convert DALI values from a DALI controller into
DMX channels
Input: 1 x DALI
Output: DMX (64 channels, 16 groups)
DIP Switches: 1, 2, 3 to the ‘ON’ position
Conversion: In DALI to DMX mode both channel values and group values are converted into DMX.
The table below illustrates the relationship
Default addressing is set to consecutive channels
DALI Channel DMX Address DALI Group DMX Address
1
2
3
…
…
63
64
1
2
3
…
…
63
64
1
2
3
…
…
15
16
65
66
67
…
…
79
80
Termination Link: Always fit
Feedback: Currently there is no feedback from RDM to DALI. Rail-DALI will respond to ‘Query
Status’ command to show that each DALI channel is being used
The wiring diagrams should only be used as a guide. For further information please look at the official DALI specification on wiring a DALI circuit.
Note: It is recommended that wires from the PSU to the Rail-DALI have a ferrite core, or similar suppression device, fitted. This should be located close to the Rail-DALI.
CE Compliance
Rail-DALI is CE compliant when installed in a shielded and earthed metal case
DIP Switches:
DIP Switch
1
2
3
4 5
On Mode
DALI to DMX
DALI to DMX
DALI to DMX
Personality
ON ON
Off Mode
DMX to DALI
DMX to DALI
DMX to DALI
0: 4 channel mode (DMX to DALI only)
88.00 mm
44.00 mm
ON OFF 1: 16 channel mode (DMX to DALI only)
OFF ON 2: 64 channel mode (DMX to DALI only)
OFF OFF 3: 256 channel mode (DMX to DALI only)
6 Not-Connected
DIN Rail Surface Mounting:
To use the surface mount option push the three bottom tabs out until they click into place. We recommend using an M4 Pan head screw.
22.70 mm
65.30 mm
22.70 mm
The DIN Rail Range:
Rail-Split RDM – A fully bi-directional six channel DMX512 splitter and distribution amplifier
Rail-Pipe – A six channel intelligent power supply / low voltage dimmer
Rail-Switch – Provides six mains voltage relays with DMX512 and RDM Draft V1.0 support
Rail-Demux – Provides 16 DMX512 to analogue outputs and RDM Draft V1.0 support
Rail-Tran – Provides six Darlington transistor outputs, operation to 50V DC at 450mA, product total 750mA
Rail-DALI – A 256 channel bi-directional DMX / DALI interface
Rail-Patch – A DIN Rail mounted patch panel for a 5pin XLR to screw terminal connection
Rail-PSU-D4 – A four circuit DALI Bus PSU
CP12 –
An LED dimmer designed to control high power LED devices
Net-Pipe – A high power Ethernet controlled LED dimmer
Artistic Licence
© Artistic Licence Engineering Ltd. 2004
24 Forward Drive
Christchurch Avenue
Harrow
Middlesex
England
HA3 8NT
Tel: +44 (0)20 88 63 45 15
Fax: +44 (0)20 84 26 05 51
Email: [email protected]
The information contained in this document is subject to change without notice. Artistic Licence Engineering Ltd. makes no warranty of any kind with regard to this material, including, but not limited to, the implied warranties of fitness for a particular purpose.
Artistic Licence Engineering Ltd. shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance or use of this material. All trademarks are acknowledged.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project