- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Uninterruptible power supplies (UPSs)
- User manual
Liebert NXL 250-400 kVA, 60Hz, 3-Phase, Single Module and Multi-Module Units, Installation Manual (R09/15) (SL
Add to my manuals60 Pages
advertisement
Liebert
®
NXL
™
UPS
Installation Manual – 250-400kVA, 60Hz, Three-Phase, Single-Module and Multi-Module Units
C
ONTACTING
E
MERSON
N
ETWORK
P
OWER® FOR
S
UPPORT
To contact Emerson Network Power Liebert
®
Services for information or repair service in the United
States, call 1-800-LIEBERT (1-800-543-2378). Liebert Services offers a complete range of start-up services, repair services, preventive maintenance plans and service contracts.
For repair or maintenance service outside the 48 contiguous United States, contact Liebert Services, if available in your area. For areas not covered by Emerson Network Power Liebert Services, the authorized distributor is responsible for providing qualified, factory-authorized service.
For LGS to assist you promptly, please have the following information available:
Part numbers: _________________________________________________________________
Serial numbers:________________________________________________________________
Rating: _______________________________________________________________________
Date purchased: _______________________________________________________________
Date installed:_________________________________________________________________
Location: ______________________________________________________________________
Input voltage/frequency:________________________________________________________
Output voltage/frequency: ______________________________________________________
Battery reserve time:___________________________________________________________
Product Warranty Registration
To register for warranty protection, visit the Service and Support section of our Web site at:
www.liebert.com
Click on Product Registration and fill out the form.
TABLE OF CONTENTS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
. . . . . . . . . . . . . . . . . . .3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
i
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A50
FIGURES
Figure 2 Cabinet arrangement—Liebert NXL 400kVA, 575-600V multi-module and battery cabinets . . . 7
ii
TABLES
Parallel from UPS module Inter-Module Communication Board to other Inter-Module
Wire size, length for digital LBS connection of UPS Inter-Module Communication
iii
iv
Important Safety Instructions
I
MPORTANT
S
AFETY
I
NSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation of your
Liebert NXL UPS.Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the UPS. Retain this manual for use by installing
personnel.
!
WARNING
Risk of electrical shock. Can cause personal injury or death.
This UPS has several circuits that are energized with high DC as well as AC voltages. Check for voltage with both AC and DC voltmeters before working within the UPS. Check for voltage with both AC and DC voltmeters before making contact.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should be involved in installing the UPS or preparing the UPS for installation. When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires.
Extreme caution is required when performing installation and maintenance.
Special safety precautions are required for procedures involving handling, installation and maintenance of the UPS system. Observe all safety precautions in this manual before handling or installing the UPS system. Observe all precautions in the Operation and
Maintenance Manual, SL-25425, before as well as during performance of all maintenance procedures. Observe all DC safety precautions before working on or near the DC system.
!
!
WARNING
Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or death.
Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel. The UPS module weight ranges from 3965 to 6380 lb. (1768 to 2894kg).
Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times.
Slots at the base of the modules cabinets are intended for forklift use. Base slots will support the unit only if the forks are completely beneath the unit.
Read all of the following instructions before attempting to move, lift, remove packaging from or preparing unit for installation.
WARNING
Risk of electrical shock and fire. Can cause equipment damage, personal injury or death.
Under typical operation and with all UPS doors closed, only normal safety precautions are necessary. The area around the UPS system should be kept free of puddles of water, excess moisture and debris.
Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high potential electric charges may exist at the capacitor banks and at the DC connections.
All wiring must be installed by a properly trained and qualified electrician. All power and control wiring must comply with all applicable national, state and local codes.
One person should never work alone, even if all power is disconnected from the equipment. A second person should be standing by to assist and to summon help in case of an accident.
1 Liebert
®
NXL
™
Important Safety Instructions
NOTE
Materials sold hereunder cannot be used in the patient vicinity (e.g., use where UL, cUL or
IEC 60601-1 is required). Medical applications such as invasive procedures and electrical life support equipment are subject to additional terms and conditions.
NOTICE
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communication. Operation of this unit in a residential area may cause harmful interference that the user must correct at his own expense.
Liebert
®
NXL
™
2
Single-Module and Multi-Module Mechanical Installation
1.0
S
INGLE
-M
ODULE AND
M
ULTI
-M
ODULE
M
ECHANICAL
I
NSTALLATION
1.1
Introduction
This following section describes the requirements that must be taken into account when planning the positioning and cabling of the Liebert NXL uninterruptible power supply and related equipment.
This chapter is a guide to general procedures and practices that should be observed by the installing personnel. The particular conditions of each site will determine the applicability of such procedures.
!
WARNING
Risk of electrical shock. Can cause injury or death.
Special care must be taken when working with the batteries associated with this equipment.
When connected together, the battery terminal voltage will exceed 400VDC and is potentially lethal.
NOTICE
All equipment not referred to in this manual is shipped with details of its own mechanical and electrical installation.
NOTICE
Three-phase input supply required.
The standard Liebert NXL UPS is suitable for connection to three-phase, four-wire (+ Earth)
TN-C, TN-S, IT-G, IT-IG or, three-phase, three-wire plus ground, IT-UG.
If using with IT Power system, a 4-pole disconnect device must be included as part of building installation.
NOTICE
Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.
1.2
Preliminary Checks
Before installing the UPS, please carry out the following preliminary checks:
• Visually examine the UPS equipment for transit damage, both internally and externally. Report any damage to the shipper immediately.
• Verify that the correct equipment is being installed. The equipment supplied has an identification tag on the back of the main door reporting: the type, size and main calibration parameters of the
UPS.
• Verify that the UPS room satisfies the environmental conditions stipulated in the equipment specification, paying particular attention to the ambient temperature and air exchange system.
3 Liebert
®
NXL
™
Single-Module and Multi-Module Mechanical Installation
1.3
Environmental Considerations
1.3.1 UPS Room
The UPS module is intended for indoor installation and should be located in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified
operating range (see Environmental Parameters in Table 10).
The Liebert NXL UPS is cooled with the aid of internal fans. To permit air to enter and exit and prevent overheating or malfunctioning, do not cover the ventilation openings.
NOTE
To ensure proper airflow, the unit must be installed only on a solid surface made of a noncombustible material, such as concrete.
The Liebert NXL UPS is equipped with air filters located behind the front doors. A schedule for inspection of the air filters is required. The period between inspections will depend upon environmental conditions.
When bottom entry is used, the conduit plate must be installed.
NOTE
The UPS is suitable for mounting on concrete or other non-combustible surface only.
1.3.2 Storage
Should the equipment not be installed immediately, it must be stored in a room for protection against
excessive humidity and or heat sources (see Environmental Parameters in Table 10).
1.4
Positioning
The cabinet is structurally designed to handle lifting from the base.
Access to the power terminals, auxiliary terminals blocks and power switches is from the front.
The door can be opened to give access to the power connections bars, auxiliary terminal blocks and power isolators. Front door can be opened at 180° for more flexibility in installations.
NOTE
The UPS must be placed a solid surface. There must be no openings in the surface except those required for conduit landing areas. All provided kick plates must be installed.
1.4.1 Moving the Cabinets
The route to be travelled between the point of arrival and the unit’s position must be planned to make sure that all passages are wide enough for the unit and that floors are capable of supporting its weight (for instance, check that doorways, lifts, ramps, etc. are adequate and that there are no impassable corners or changes in the level of corridors).
Ensure that the UPS weight is within the designated surface weight loading (kg/cm
2
) of any handling
equipment. For weight details, see Table 10.
The UPS can be handled with a forklift or similar equipment. Ensure any lifting equipment used in moving the UPS cabinet has sufficient lifting capacity. When moving the unit by forklift, care must be taken to protect the panels. Do not exceed a 15-degree tilt with the forklift. Bottom structure will support the unit only if the forks are completely beneath the unit.
Handling with straps is not authorized.
Liebert
®
NXL
™
4
Single-Module and Multi-Module Mechanical Installation
!
WARNING
Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or death.
Because the weight distribution in the cabinet is uneven, use extreme care while handling and transporting. Take extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel.
The UPS module weight ranges from 3965 to 6380 lb. (1768 to 2894kg).
Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from vertical at all times.
1.4.2 Clearances
The Liebert NXL has no ventilation grilles at either side or at the rear of the UPS. Clearance around the front of the equipment should be sufficient to enable free passage of personnel with the doors fully opened. It is important to leave a distance of 24" (610mm) between the top of the UPS and any overhead obstacles to permit adequate circulation of air coming out of the unit.
1.4.3 Raised Floor Installations
If the equipment is to be located on a raised floor it should be mounted on a pedestal suitably designed to accept the equipment point loading. Refer to the base view to design this pedestal. The top of pedestal must be solid.
NOTE
The UPS must be placed on a solid surface. There must be no openings in the surface except those required for conduit landing areas. All provided kick plates must be installed.
1.4.4 Kick Plate Installation
Kick plates must be installed. If the unit is to be installed in a position that does not permit access to the rear kick plates, then kick plates must be installed before the unit is placed in its final position.
1.4.5 Special Considerations for 1+N Parallel Systems
Consider the grounding configuration of your system before finalizing module placement See 2.5 -
Configuring Neutral and Ground Connections.
Emerson Network Power recommends matching the impedance in the bypass path of paralleled systems as closely as possible.
The impedance mismatch can be minimized by controlling the wiring length of each unit. The design and the layout of the UPS system and associated panels and cabling should be examined closely to ensure that cable lengths and impedances are closely matched. The Liebert 1+N UPS module is supplied with a sharing reactor to minimize the impact of cable impedance mismatch.
The cabling impedance must be carefully controlled to ensure good bypass current sharing.
For Liebert NXL Systems, the cabling impedances must be within 10% from maximum to minimum.
If the cabling impedances need to be greater than 10%, contact your Emerson representative to calculate whether the system will result in an overload condition when operating on bypass.
When bringing the 1+N system online for the first time or after removing one unit, Emerson recommends checking the bypass current mismatch. To check the bypass current mismatch:
1. Place a load on the bypass of each UPS module.
2. View the output current of each unit.
The accuracy of the currents displayed on the UPS module is sufficient for this check. If the mismatch is greater than 10%, the bypass impedances must be balanced or the load must be limited to less than the maximum rating.
5 Liebert
®
NXL
™
Single-Module and Multi-Module Mechanical Installation
1.5
System Composition
A UPS system can comprise a number of equipment cabinets, depending on the individual system design requirements, e.g. UPS cabinet, battery cabinet, maintenance bypass cabinet. In general, all the cabinets used in a particular installation are of the same height. Refer to the drawings provided in
4.0 - Installation Drawings for the positioning of the cabinets as shown in Figures 1 and 2.
1.6
Cable Entry
Cables can enter the UPS cabinet from bottom or top into the Input/Output (I/O) section of the unit,
see the figures in 4.0 - Installation Drawings.
Figure 1 Cabinet arrangement—Liebert NXL single-module, battery cabinets, maintenance bypass cabinet
Applicable to:
250 - 400 kVA 480V, 250 - 300 kVA
575/600V except without
Maintenance Bypass Cabinet
Liebert
NXL
UPS
The side panels and hangers must be removed before the cabinets can be bolted together.
Liebert
NXL
UPS
Maintenance
Bypass
Cabinet
Note: If a maintenance bypass cabinet is used, it must be installed on the right side of the Liebert NXL UPS
Additional
Battery
Cabinet(s)
Battery
Cabinet
Liebert
NXL
UPS
Maintenance
Bypass
Cabinet
Additional
Battery
Cabinet(s)
Battery
Cabinet
Liebert
NXL
UPS
Liebert
NXL
UPS
Battery
Cabinet
Additional
Battery
Cabinet(s)
Liebert
®
NXL
™
6
Single-Module and Multi-Module Mechanical Installation
Figure 2 Cabinet arrangement—Liebert NXL 400kVA, 575-600V multi-module and battery cabinets
The side panels and hangers must be removed before the cabinets can be bolted together.
DC I/O
Section
Liebert
NXL
UPS
I/O
Bypass
Section
Battery
Cabinet
Battery
Cabinet
Liebert
NXL
UPS
7 Liebert
®
NXL
™
UPS Electrical Installation
2.0
UPS E
LECTRICAL
I
NSTALLATION
This chapter provides guidelines for qualified installers who must have knowledge of local wiring practices pertaining to the equipment to be installed.
!
WARNING
Risk of electrical shock. Can cause injury or death.
The UPS contains high DC as well as AC voltages. Check for voltage with both AC and DC voltmeters before working within the UPS.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves, shoes and glasses should be involved in installing the UPS or preparing the UPS for installation.
2.1
External Protective Devices
For safety, it is necessary to install circuit breakers in the input AC supply and external battery system. Given that every installation has its own characteristics, this section provides guidelines for qualified installation personnel with knowledge of operating practices, regulatory standards and the equipment to be installed.
External overcurrent protection must be provided. See Table 10 - Liebert NXL UPS specifications
for overload capacity.
Dual Input
When wiring the UPS with a separate rectifier and bypass input, each input must be protected
separately. Size the breakers according to the input currents shown in Table 10.
Liebert
®
NXL
™
8
UPS Electrical Installation
2.2
Power Cables
The UPS requires both power and control cabling. All control cables, whether shielded or not, should be run separate from the power cables in metal conduits or metal ducts which are electrically bonded to the metalwork of the cabinets to which they are connected
The cable design must comply with the voltages and currents in Table 10, follow local wiring
practices and take into consideration the environmental conditions (temperature and physical support media), room temperature and conditions of installation of the cable and system’s overload
capacity (see 5.0 - Specifications).
For cable entry terminal, refer to Figures 26 28 and 29.
!
WARNING
Risk of electrical shock. Can cause injury or death.
Before cabling the UPS, ensure that you are aware of the location and operation of the external isolators that connect the UPS input/bypass supply to the power distribution panel.
Check that these supplies are electrically isolated, and post any necessary warning signs to prevent their inadvertent operation.
NOTICE
For dual input operation ensure that any busbars between the bypass and the rectifier input are removed.
When sizing battery cables, a maximum volt drop of 2VDC is permissible at the current ratings given
The following are guidelines only and superseded by local regulations and codes of practice where applicable:
• Take special care when determining the size of the neutral cable (grounded conductor), because current circulating on the neutral cable may be greater than nominal current in the case of non-
linear loads. Refer to the values in Table 10.
• The grounding conductor should be sized according to the fault rating, cable lengths, type of protection, etc. The grounding cable connecting the UPS to the main ground system must follow the most direct route possible.
• Consideration should be given to the use of paralleled smaller cables for heavy currents, as this can ease installation considerably.
• AC and DC cables must be run in conduits according to local codes, national codes and standard best practices. This will prevent creation of excess EMI fields.
2.2.1 Sizing the Input Breaker Feeding a Liebert NXL UPS
The rectifier nominal input current value (Table 11) is based on providing enough power to operate
the inverter at full rated load when the input voltage is nominal. The published rectifier maximum input current value is based on the maximum input current limit setting of 125%.
The recommended input breaker ampacity is based on the NEC calculation for a branch circuit with the current limit set at the maximum value. The calculation for an 80% rated breaker is 125% of the nominal current (continuous) plus 100% of the difference between the nominal and the maximum currents (non-continuous). The calculation for a 100% rated breaker is 100% of the nominal current
(continuous) plus 100% of the difference between the nominal and maximum currents
(noncontinuous).
The rectifier input current limit can be adjusted from 25% to 125% of the nominal value. This setting is accessible only to a factory-trained service engineer. The effect of changing this setting is similar to that of changing the setting of the trip unit on a solid-state circuit breaker. With a lower current limit setting, the calculation for the branch circuit will result in a lower value.
The input current limit should not be set less than 105% of the current needed to support the inverter at full load for normal operation. This results in sufficient power to recharge the battery in a reasonable time and to operate over the published input voltage range.
9 Liebert
®
NXL
™
UPS Electrical Installation
2.2.2 Power Cable Connection Procedure
The rectifier input, bypass, output and battery power cables (all require lug type terminations) are
connected to busbars situated in the I/O section as shown in Figures 26 through 31.
Equipment Ground
The equipment ground busbar is located in the I/O section as shown in Figures 26 through 31. The
grounding conductor must be connected to the ground busbar and bonded to each cabinet in the system.
All cabinets and cabling should be grounded in accordance with local regulations.
!
NOTE
Proper grounding reduces problems in systems caused by electromagnetic interference.
WARNING
Failure to follow adequate grounding procedures can result in electric shock hazard to personnel, or the risk of fire, should a ground fault occur.
All operations described in this section must be performed by properly trained and qualified electricians or technical personnel. If any difficulties are encountered, contact Emerson ®
Network Power Liebert Services. See the back page of this manual for contact information.
The grounding and neutral bonding arrangement must be in accordance with local and national codes of practice.
Once the equipment has been positioned and secured, connect the power cables as described below
(refer to the appropriate cable connection drawing in 4.0 - Installation Drawings):
1. Verify that the UPS equipment is isolated from its external power source and all the UPS power isolators are open. Check that these supplies are electrically isolated and post any necessary warning signs to prevent their inadvertent operation.
2. Open exterior and interior panels on the front of the I/O.
3. Connect the ground and any necessary main bonding jumper to the equipment ground busbar located in the I/O section.
4. Make power connections and tighten the connections to the proper torque according to one of the two procedures below, depending on the type of installation:
Ensure correct phase rotation.
• Top Cable Entry (see Figures 19, 20, 25, 28, 29 and 30)
• Bottom Cable Entry (see Figures 19, 20, 25, 28, 29 and 31)
Top Cable Entry
When making the power connections for top cable entry, the recommended order of pulling and installing cables is to start from the top connections to the bottom connections. The cables
must be routed around the fault braces (see Detail in Figure 30). This is to prevent the cables
from contacting other busbars. The recommended conduit layout is shown in Figure 26.
Bottom Cable Entry
When making the power connections for bottom cable entry, the recommended order of pulling and installing cables is to start from the bottom connections to the top connections. The cables
must be routed around the fault braces (see Detail in Figure 31). This is to prevent the cables
from contacting other busbars. The recommended conduit layout is shown in Figure 26.
!
NOTE
For a single input configuration, linking busbars must be installed between the bypass and the rectifier input.
WARNING
Risk of electrical shock. Can cause injury or death.
If the load equipment will not be ready to accept power on the arrival of the commissioning engineer, ensure that the system output cables are safely isolated at their termination.
Liebert
®
NXL
™
10
UPS Electrical Installation
!
WARNING
Risk of electrical shock. Can cause injury or death.
When connecting the cables between the battery extremities to the circuit breaker always connect the circuit breaker end of the cable first.
5. For control connection details, see 2.3 - Control Cable and Communication.
NOTE
If fault bracing brackets were removed during installation, they MUST be replaced.
6. Close and secure the interior and exterior doors.
Figure 3 Cabinet grounding plates
Note location of larger cutouts.
Orient ground plate as shown.
A
Mounting
Hardware
(Supplied)
Detail A
Grounding plates are installed at each shipping split.
Figure 4 Kick plate and filter locations, typical
KICKPLATE
G
KICKPLATE
D
FRONT
REAR
KICKPLATE
KICKPLATE
E
F
DETAIL D
INSTALL M6X25 BOLT,
LCKW AND WSHR
(4) PLACES, FRONT SIDE
DETAIL E
INSTALL M6X25 BOLT,
LCKW AND WSHR
(2) PLACES, EACH SIDE
DETAIL G
INSTALL M6X60 BOLT,
LCKW AND WSHR
(2) PLACES, FRONT SIDE
INSTALL M6X25 BOLT,
LCKW AND WSHR
(4) PLACES, REAR SIDE
NOTE
Kick plates must be installed. If the unit is to be installed in a position that does not permit access to rear kick plates, then kick plates must be installed before the unit is placed in its final position.
11 Liebert
®
NXL
™
UPS Electrical Installation
2.3
Control Cable and Communication
Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery system (external battery circuit breaker), communicate with a personal computer or provide alarm signaling to external devices, or for Remote Emergency Power Off (REPO). The External Interface
Board, arranged for this purpose, is next to the option box in the Rectifier section (refer to 4.0 -
Installation Drawings). The contacts are rated for 250VAC @ 2A.
Figure 5 External Interface Board connections layout
MAINT BYP
ENABLE
TB0821
ACT FILT
CNTL
TB035
P66C P99C
EXTERNA L
CAN
TB0823
EPO
STATUS
LBS VO LTAGE
BATT MTR
OP
TB1156
TB0826
P0808
OPT
PS
TB0829 TB1154B
EXTERNA L
CAN
INT BATT
CAN
TB1154A
EXT BATT
CAN
TB0825
REPO
J4
J5
TB0824
REPO
FORM C
P0831
AUX SPARE
TEMP
P0832
P0801
BATT GND
FLT
TB0815
MOB
TB0811
MIB
TB0810
RIB
TB0830
ACT FILT
STATUS
TB0816
ON GEN
TB0813
MBB
TB0812
BIB
TB0820
KEY
STATUS
TB0819
BYP CNTL
TB0817
RECT
CNTL
TB0818
INV
CNTRLN
Liebert
®
NXL
™
12
UPS Electrical Installation
2.3.1 Dry Contacts
NOTE
If connection to more than one module is required, use a separate contact for each module.
Table 1
Item
Remote EPO
Input Form C
UPS input dry contacts
Terminal
Block
On Generator
Input Form C
TB0824
TB0816
1
2
3
Pin
1
2
3
Connects to
(Description of External Item)
REPO Switch, normally open contact
REPO Switch, common contact
REPO Switch, normally closed contact, set jumper
J5: 1-2 to enable, 2-3 to disable
On Generator switch, closed = On Generator
On Generator switch, common
On Generator switch, closed = Not On Generator
Wire Size/
Max Length
14AWG/
500ft.
(150m).
Table 2
Item
CAN Bus and
24V Power
Supply
UPS control with battery cabinet or module battery disconnect
Terminal
Block
TB1154A
Pin
1
2
3
4
Connects to
(Description of External Item)
Battery Interface Board TB1154-1
Battery Interface Board TB1154-2
Battery Interface Board TB1154-3
Battery Interface Board TB1154-4
Wire Size/
Max Length
18 AWG
1000ft.
(300m).
Table 3 UPS control contacts with global maintenance bypass
Item
Terminal
Block Pin
Connects to
(Description of External Item)
Wire Size/
Max Length
Maintenance
Isolation Breaker
(MIB) Form C
1
Maintenance Bypass
Breaker (MBB) Form C
1
TB0811
TB0813
1 CB aux. contact, closed = CB is closed
2 CB aux. contact, common
3 CB aux. contact, closed = CB is open
1 CB aux. contact, closed = CB is closed
2 CB aux. contact, common
3 CB aux. contact, closed = CB is open
14AWG/500ft.
(150m)
14AWG/500ft.
(150m)
Maintenance Bypass
Enable Form C
1
TB0821
1
2
Maintenance Bypass Cabinet, closed = load not on inverter
Maintenance Bypass Cabinet, common
14AWG/500ft.
(150m)
3
Maintenance Bypass Cabinet, closed = load on inverter
1 REPO Switch, normally open contact
Remote EPO Input
Key Status Input
1
TB0825
TB0820
2 REPO Switch, common contact
1 Key status switch, closed = key removed
2 Key status switch, common
3 Key status switch, closed = key inserted
14AWG/500ft.
(150m)
14AWG/500ft.
(150m)
Module Output Breaker
(MOB) Form C
2
TB0815
1 CB aux. contact, closed = CB is closed
2 CB aux. contact, common
14AWG/500ft.
(150m)
3 CB aux. contact, closed = CB is open
1. For 1+N systems with a maintenance Bypass, these Aux contacts must be run to each module from an isolated source.
2. For 1+N systems, these breaker Aux contact go to the UPS that it is associated with.
3. Key Status Input can be either Form-C, N.O. or N.C. contact.
13 Liebert
®
NXL
™
UPS Electrical Installation
Table 4
Item
UPS control contacts to remote status panel
Terminal
Block Pin
Connects to
(Description of External Item)
Wire Size/
Max Length
CAN Bus and 24V
Power Supply
TB0829
1 Remote Status Panel TB-2
2 Remote Status Panel TB-1
3 Remote Status Panel TB-3
4 Remote Status Panel TB-4
2.3.2 Multi-Module Communication
18 AWG/1000ft.
(300m)
Paralleling cables that connect the module to the system are connected to terminals P3101 and P3103
on the Inter-Module Communication (IMC) board (refer to 4.0 - Installation Drawings).
Table 5 Parallel from UPS module Inter-Module Communication Board to other Inter-Module
Communication Board in system
Terminal Designation
From To Signal Name
Wire Size/
Max Length
Primary Connections
P3101-1 P3101-1 Share CAN +24V
P3101-2
P3101-3
P3101-2
P3101-3
Share CAN common
System CAN +24V
P3101-4
P3101-5
P3101-6
P3101-7
P3101-4
P3101-5
P3101-6
P3101-7
System CAN common
SER synch CAN+24V
SER synch CAN common
Ground - Drain Wire
P3101-14
P3101-8
P3101-9
P3101-10
P3101-14 Ground
P3101-8 PWM synch CAN +24V
P3101-9 PWM synch CAN common
P3101-10 MMS synch CAN +24V
P3101-11 P3101-11 MMS synch CAN common
Redundant Connections
P3103-1
P3103-2
P3103-1
P3103-2
Redundant share CAN +24V
Redundant share CAN common
1000ft.
(300m)
P3103-3
P3103-4
P3103-5
P3103-6
P3103-7
P3103-14
P3103-8
P3103-9
P3103-3
P3103-4
P3103-5
P3103-6
P3103-7
P3103-14
P3103-8
P3103-9
Redundant system CAN +24V
Redundant system CAN common
Redundant SER synch CAN +24V
Redundant SER synch CAN common
Ground - Drain Wire
Ground
Redundant PWM synch CAN +24V
Redundant PWM synch CAN common
1000ft.
(300m)
P3103-10 P3103-10 Redundant MMS synch CAN +24V
P3103-11 P3103-11 Redundant MMS synch CAN common
1. Belden 810x or Belden 89901 cables are the only approved cables.
2. Belden 89901 cable can be used for underground installations.
3. If using multiple parallel cables for each run, all cables must be run in the same conduit.
4. Each cable group should be run in a separate grounded conduit to ensure redundancy.
5. The maximum lengths must include all the parallel cables from the first module to the last module. The primary and redundant cable lengths can be counted separately.
6. The ground pins on the Inter-Module Communication Board (Pins 7 and 14) are connected together on the board. If using cable with only one (1) drain wire, then connect the ground (drain wire) to Pin 7.
7. Care must be taken to prevent the drain wire from touching any other component in the module.
8. Attach control wires to the side of the control door where the Inter-Module Board (IMC) is attached. Do not run wires across the IMC board.
Liebert
®
NXL
™
14
Figure 6 Inter-Module Communication Board wiring diagram—Multi-modules
UPS Electrical Installation
IMC
02-806730-xx
P3103
P3101
UPS 1
IMC
02-806730-xx
P3103
P3101
UPS 2
IMC
02-806730-xx
P3103
P3101
UPS 3
2.4
Digital LBS
The Load Bus Sync interface enables independent UPS units to remain in sync when operating on battery or when supplied by unsynchronized input sources.
Digital LBS cables that connect the module to the system are connected to terminals P3108 and
P3109 on the Inter-Module Communication (IMC) board. See Figure 7
.
Table 6 Wire size, length for digital LBS connection of UPS Inter-Module Communication
Boards
Terminal Designation
From To Signal Name
Wire Size/
Max Length
Digital LBS from UPS inter-module communication board to other UPS inter-module communication board
P3108-1
P3108-2
P3108-1
P3108-2
LBS Synch CANH
LBS Synch CANL
3000ft
(900m)
P3108-3 P3108-3 Ground - Drain Wire
Redundant Digital LBS from UPS Inter-Module Communication Board to Other UPS
Inter-Module Communication Board
P3109-1
P3109-2
P3109-1
P3109-2
Redundant LBS Synch CANH
Redundant LBS Synch CANL
3000ft
(900m)
P3109-3 P3109-3 Ground - Drain Wire
1. Belden 810x or Belden 89901 cables are the only approved cables.
2. Each cable group should be run in a separate grounded conduit to ensure redundancy.
3. The maximum lengths must include all the LBS cables from the first module to the last module.
4. The primary and redundant cable lengths can be counted separately.
5. Belden 89901 cable can be used for underground installations.
6. Attach the control wire to the side of the control door where the Inter-Module Board (IMC) is attached.
Do not run wires across the IMC board.
Figure 7 Inter-Module Communication Board wiring diagram—Digital LBS
IMC
02-806730-xx
P3108
P3109
UPS 1
IMC
02-806730-xx
P3108
P3109
UPS 2
IMC
02-806730-xx
P3108
P3109
UPS 3
15 Liebert
®
NXL
™
UPS Electrical Installation
2.5
Configuring Neutral and Ground Connections
Improper grounding is the largest single cause of UPS installation and startup problems. Grounding techniques vary significantly from site to site, depending on several factors.
Proper grounding should be based on NEC Section 250, but safe and proper equipment operation requires further enhancements. The following pages detail recommendations for grounding various system configurations to ensure optimal UPS system performance.
!
CAUTION
The UPS ground lug must be solidly connected to the service entrance ground by an appropriately sized wire conductor per NEC Article 250. Each conduit or raceway containing phase conductors must also contain a ground wire, both for UPS input and output, which are solidly connected to the ground terminal at each termination point. Conduit-based grounding systems tend to degrade over time. Therefore, using conduit as a grounding conductor for UPS applications may degrade UPS performance and cause improper UPS operation.
2.5.1 Four-Wire Input connections
The UPS module main input and bypass input are connected to a grounded service. In this configuration, the UPS module is not considered a separately derived source. The UPS module output neutral is solidly connected to the building service neutral, which is bonded to the grounding conductor at the service entrance equipment.
Advantages of this configuration include:
• A measure of common-mode noise attenuation, since the isolation (common-mode rejection) occurs as close to the load as practical (i.e., at the PDU).
• The UPS module can be located remotely from the PDU without compromising common-mode noise performance.
• By using UPS modules with 480VAC input and output and creating 208VAC at the PDU, smaller and less costly power feeders can be used and less voltage drop (as a percent of nominal) occurs.
2.5.2 Three-Wire Input Connections
This configuration must NOT be used when single-phase loads are directly connected to the UPS.
The UPS output transformer is considered a separately derived source. The UPS module neutral is bonded to the UPS ground, which is connected to a local grounding electrode in accordance with
NEC 250-26. Please note that this configuration represents a price/performance trade-off. Whenever the UPS module transfers to or from bypass, two AC sources (input and bypass) are briefly connected together and circulating current must flow. In this configuration, the current flows through the ground path, possibly tripping ground fault interrupters (GFIs) and distorting the bypass waveform reference. Proper adjustment of ground fault interrupters is necessary to avoid unwanted tripping.
The time delay should be set to at least 0.2 seconds to prevent tripping when the UPS performs a transfer or retransfer operation.
NOTICE
Risk of improperly set ground fault interrupters. Can cause equipment damage.
Failure to set the ground fault interrupters properly could cause loss of power to the critical load.
2.5.3 Preferred Grounding Configuration, Battery Systems
Open-rack battery systems, depending on local code requirements and customer preference, are normally:
• Floating (ungrounded)
OR
• Center-tapped and floating
Battery cabinet systems must be connected as floating (ungrounded) systems.
Liebert
®
NXL
™
16
UPS Electrical Installation
Center-tapped or grounded battery systems are not possible with battery cabinet systems.
Whether the battery system is open-rack or cabinet, the metal rack parts or cabinet must be grounded to the UPS module ground bus.
2.5.4 Multi-Module Systems
For both N+1 and 1+N systems, the neutrals of all UPS modules in the system must be connected together inside the switchgear or parallel cabinet. The neutral conductors must be rated for 20% of phase conductor current minimum. Site and load conditions will determine if larger neutrals are required.
For Multi-Module systems using a 3-wire bypass, the Neutral-Ground bond must be made at the common neutral connection point in the switchgear or parallel cabinet.
2.5.5 High Resistance Ground Systems
The Liebert NXL is compatible with High Resistance Ground Systems. See your local Emerson representative for details.
2.6
Grounding Diagrams, Single- and Multi-Module Systems
Figure 8 Grounding diagram, three-wire single-module system
UPS
Source
BPSS
N
G
N
G
Figure 9 Grounding diagram, four-wire single-module system
Source
UPS
BPSS
N
G
N
G
17 Liebert
®
NXL
™
Figure 10 Grounding diagram, three-wire multi-module system
UPS #1
Source
N
G
N
G
UPS #2
N
G
UPS #3
Grounding for 1+N systems is wired exactly the same.
N
G
UPS Electrical Installation
Switchgear
N
G
Liebert
®
NXL
™
18
Figure 11 Grounding diagram, four-wire multi-module system
UPS #1
BPSS
Source
N
G
UPS #2
BPSS
N
G
N
G
UPS #3
BPSS
N
G
UPS Electrical Installation
Switchgear
N
G
19 Liebert
®
NXL
™
Optional Equipment
3.0
O
PTIONAL
E
QUIPMENT
3.1
Single-Module System Options
3.1.1 Matching Maintenance Bypass Cabinet
A matching Liebert NXL Maintenance Bypass cabinet is available. See Maintenance Bypass Cabinet
Installation Manual (SL-24532) for more details.
3.1.2 Battery Temperature Sensor
The optional external battery temperature sensor kit, supplied separately from the battery circuit breaker, contains one probe and one temperature transport board.
3.1.3 Load Bus Synch
An optional Load Bus Synch (LBS) system can be used to synchronize two Liebert NXL UPSs or an
Liebert NXL UPS to a Liebert Series 610 UPS.
3.1.4 Remote Alarm Panel
The remote alarm panel has LED alarm lights. An audible alarm sounds upon any alarm condition.
The surface- or flush-mounted NEMA 1 enclosed panel indicates: Load on UPS, Load on Bypass,
Battery Discharging, Low Battery Warning, Overload Warning, Ambient Overtemp Warning, UPS
Alarm Condition and New Alarm Condition (for a second UPS alarm condition).
3.2
Communication and Monitoring
• Liebert IntelliSlot
™
Unity Card
• Alber Battery Monitoring System
• Programmable Relay Board
• Input Contact Isolator Board
3.2.1 Alber Monitoring System
The matching Liebert NXL Battery Cabinet allows installing an optional Alber Battery monitoring system in the cabinet. The Alber Battery Monitoring by Liebert continuously checks all critical battery parameters, such as cell voltage, overall string voltage, current and temperature. Automatic periodic tests of internal resistance of each battery will verify the battery’s operating integrity.
Additional capabilities include automatic internal DC resistance tests and trend analysis providing the ability to analyze performance and aid in troubleshooting.
Liebert
®
NXL
™
20
Optional Equipment
3.2.2 Programmable Relay Board
The Programmable Relay Board (PRB) provides a means to trigger an external device when an event occurs in the Liebert NXL. Each PRB has eight channels. Each channel has Form-C dry contacts rated at 1A @ 30VDC or 125VAC @ 0.45A.
Any alarm/event can be programmed to any channel or channels. Up to four (4) events can be programmed to a relay. If multiple events are grouped to one relay, group the events logically to simplify troubleshooting when an event is triggered. The same alarm/event can be programmed to more than one channel. Up to two Programmable Relay Boards can be installed in the Liebert NXL for a total of 16 channels. Programming is performed through the HMI touchscreen display.
NOTE
Up to two (2) PRB’s can be installed in the Liebert NXL.
Figure 12 Control wiring, Programmable Relay Board
1 2 3 4 5 6 7 8 9 10 11 12 1314 1516
J71
1 2 3 4 5 6 7 8 9 10 11 121314 15 16
J72
1 2 3 1 2 3 4 5 6 7 8 9 10 111213141516
J74
J73
1. Customer control wiring connection points are terminals 1 through 15. (Pin 16 not used on J71, J72, and
J73.)
2. Programmable Relay Board option includes eight signal channels with two Form-C dry contacts per
3. All control wiring (by others) must be run separate from power wiring. Control wiring runs should not be combined in the same conduit.
4. Contact ratings: 1A @ 30VDC or 125VAC @ 0.45A
5. Maximum cable length 500 ft. (152m) with #16AWG and flexible stranded cable.
6. All wiring must be in accordance with national and local electrical codes.
Table 7 Programmable Relay Board pinout
Terminal
Block Channel Pin No.
Common
CH1
A
B
1-3
4-6
J71 A 7-9
CH2
B
A
10-12
13-15
CH3
B
A
1-3
4-6
J72
CH4
B
A
7-9
10-12
TB3
CH5
CH6
CH7
B
A
B
A
B
A
13-15
1-3
4-6
7-9
10-12
13-15
J74
CH8
B 1-3
Note: Pin 16 not used on J71, J72, and J73.
10
13
1
4
7
10
13
1
4
7
10
13
1
1
4
7
Normally
Closed
5
8
11
14
8
11
14
2
2
11
14
2
5
2
5
8
Normally
Open
6
9
12
15
9
12
15
3
3
12
15
3
6
3
6
9
21 Liebert
®
NXL
™
Optional Equipment
Configuring the Programmable Relay Board Settings
1. Press Internal Option Settings from the Config menu.
2. Press which Programmable Relay Board will be configured. The Programmable Relay Board dialog box is displayed.
3. Press the Relay channel
4. Press up to four (4) events. Selected events will show up under Relay 1 Assignment.
NOTE
To deselect an event, click on the event.
5. Repeat Steps 3 and 4 for each relay.
6. Press SAVE to keep the settings.
Figure 13 Programmable relay board dialog box
• Assignment—0 to 4 event (default: 0)
• Delay, sec—0 to 99.9 (default: 0)
3.2.3 Input Contact Isolator Board
The Input Contact Isolator Board (ICI) provides a Liebert NXL module interface for up to eight external user alarm or message inputs to be routed through the NXL’s alarm network. The eight contacts are normally open dry contacts. When a contact closes, an event is triggered.
NOTE
Up to two (2) ICI’s can be installed in a Liebert NXL.
The Input Contact Isolator options are configured through the Input Contact Isolator dialog box, which is accessed from the Internal Option Settings under the Config dialog box on the HMI touchscreen display. The Input Contact Isolator dialog box contains eight choices to match the eight channel input board. You can label each button to identify the event associated with the contact.
When the dialog box is accessed, each button flashes to display the Input Contact Isolator number and the user entered label. This label also appears in the Display Panel when an event related to an
Input Isolator Connector is triggered.
Liebert
®
NXL
™
22
Optional Equipment
The Input Contact Isolator dialog box allows you to:
• Label the input contact assignments for your setup.
• Set the delay for an external event triggering an alarm.
• Review the isolator contact assignments, once the labels are entered.
The delay allows setting the number of seconds that a condition must exist before it will trigger an alarm. To configure the Input Contact Isolator relays:
1. Press Internal Option Settings from the Config menu.
2. Press which Input Contact Isolator is to be configured. The Input Contact Isolator dialog box is displayed.
Figure 14 Input contact isolator dialog box
• Assignment—Custom, Pre-assigned (default: “Input Contact” XY)
• Delay, sec—0 to 99.9 (default: 0)
• Message—Custom: 0-19 characters
3. To assign labels for each channel:
a. Press Pre-assigned for default labels on Channels 1-6 (See Table 8)
b. For Custom labels
1. Press Custom to unique labels.
2. Click on Input Contact XX button. A keyboard is displayed to allow naming alarms.
3. Enter the name of the alarm set for that input. For example, a fan problem could be indicated by naming the button FAN.
4. Press OK on the keyboard to keep your label.
4. Press DELAY.
a. A keypad is displayed prompting you for a delay time, in seconds, for a condition to exist before the alarm is triggered.
b. Enter the delay value. The range for the values are from 0 (zero) to 99.9 seconds.
c. Press OK on the keypad to keep your setting. The value you entered is displayed in the field adjacent to the corresponding input contact.
5. Repeat Steps 3 and 4 for each input contact.
23 Liebert
®
NXL
™
Optional Equipment
6. Press SAVE after you have configured all input contacts.
Be sure to press Save even if you have accessed this dialog only to change a setting.
7. This information is not saved if control power is removed.
Table 8 Input Contact Isolator Board pre-assigned values
Channel
Number
6
7
4
5
8
1
2
3
ICI #1
Pre-Assigned Label
ICI #2
Pre-Assigned Label
Reduced Rect ILimit
Reduced Batt ILimit
Stop Battery Charge
Stop Battery Charge
Stop Battery Charge
Stop Battery Charge
Inhibit Rect Restrt
Inhibit Byp Restrt
Inhibit Inv Restrt Stop Battery Charge
Input Trap Filter Disconnect Inhibit IP Standby
Suspend ECO Mode
Stop Battery Charge
Stop Battery Charge
Figure 15 Optional Input Contact Isolator Board
No Customer Connection
Table 9
1 2 3 4 5 6 7 8 9 10 11 1213 14 1516
J51
1. Customer control wiring connection points are terminals 1 through 16 (see
2. Customer provided normally open dry contacts for user alarm messages.
3. All control wiring (by others) must be run separate from power wiring.
Control wiring runs should not be combined in the same conduit.
4. Signal voltage: 100mA @ 12VDC.
5. Maximum cable length 500 ft. (152m) with #16AWG and flexible stranded cable.
6. All wiring must be in accordance with national and local electrical codes.
Input Contact Isolator Board control wiring connections
Input Contact
1
2
3
4
5
6
7
8
Pin No.
13
14
15
16
9
10
11
12
7
8
5
6
3
4
1
2
Liebert
®
NXL
™
24
Installation Drawings
4.0
I
NSTALLATION
D
RAWINGS
Figure 16 Outline drawing, 250kVA, 480V Liebert NXL
57.5"
(1460mm)
64.2"
(1630mm)
TOP VIEW
(Doors Open)
71.8" (1824mm)
Cable Entry
Conduit Plte
See Detail A
2.2 (57mm)
Outside
Panel
15"
(380mm)
.9" (23mm)
Outside
Panel
33.5" (850mm)
21.4"
(544mm)
Power Cable
Conduit Plate
76.8"
6.9" (175mm)
CONDUIT
DETAIL A
Control Cable
Conduit Plate
12.1"
(307mm)
(1950mm)
FRONT
RIGHT SIDE
11.4"
(290mm)
1.7" (43mm)
Outside Frame
2.5" (64mm)
To Outside
FRONT
Control Cable
Conduit Plate
Cable Entry
Conduit Plate
See Detail B
10.4"
(264mm)
Power Cable
Conduit Plate
BOTTOM
Notes
1. All dimensions are in inches (mm).
7.3"
(185mm)
11.9"
(302mm)
2. 24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical while handling.
4. Top and bottom cable entry available through removable conduit plates.
Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate conduits.
7. All wiring is to be in accordance with national and local electrical codes
8. Width dimension is with side panels. Subtract 1.4" (35mm) for dimensions
with both side panels removed.
9. Depth dimension includes the front door and rear panel.
10. Refer to technical information drawing for 250kVA/225kW UPS.
CONDUIT
DETAIL B
U40-2C-1001
Rev. 6
7.1" (180mm)
.2"
(5mm)
21.9
(556mm)
2.6 (66mm)
Outside Frame
25 Liebert
®
NXL
™
Figure 17 Outline drawing, 250kVA, 575/600V; and 300kVA, 480/575/600V Liebert NXL
Installation Drawings
63.8"
(1620mm)
TOP VIEW
(Doors Open)
78.5" (1994mm)
Cable Entry
Conduit Plate
See Detail A
33.5"
(850mm)
2.2" (57mm)
Outside Panel 15"
(380mm)
.9" (23mm)
Outside
Panel
21.4"
(544mm)
Power Cable
Conduit Plate
6.9" (175mm)
76.8"
(1950mm)
Control Cable
Conduit Plate
CONDUIT
DETAIL A
12.1
(307mm)
FRONT
FRONT
RIGHT SIDE
11.4"
(290mm)
Control Cable
Conduit Plate
Cable Entry
Conduit Plate
See Detail B
10.4"
(264mm)
Power Cable
Conduit Plate
BOTTOM VIEW
7.3"
(185mm)
Notes:
1. All dimensions are in inches (mm).
2.24" minimum clearance above unit required for air exhaust.
3. Keep cabinet within 15 degrees of vertical while handling.
4. Top and bottom cable entry available through removable
conduit plates. Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate conduits.
7. All wiring is to be in accordance with national and local electrical codes.
8. Width dimension is with side panels. Subtract 1.4" (35mm) for
dimensions with both side panels removed.
9. Depth dimension includes the front door and rear panel.
10. Refer to technical information drawing for 250kVA 575V or 600V UPS.
11.9"
(302mm)
CONDUIT
DETAIL B
U40-2C-1006
Rev. 2
1.7" (43mm)
Outside Frame
2.5" (64mm) to Outside
7.1" (180mm)
.2"
(5mm)
21.9"
(556mm)
2.6" (66mm)
Outside Frame
Liebert
®
NXL
™
26
Figure 18 Outline drawing, 400kVA, 480V Liebert NXL
2.2" (57mm)
Outside of Panel
69.5"
(1766mm)
Top View (Doors Open)
78.5"
(1994mm)
Installation Drawings
15.0"
(380mm)
.9" (23mm)
Outside Panel
Cable Entry
Conduit Plate
See Detail A
27.3"
(693mm)
Power Cable
Conduit Plate
39.4"
(1000mm)
6.9"
(175mm)
Control Cable
Conduit Plate
CONDUIT
DETAIL A
12.1"
(307mm)
76.8"
(1950mm)
11.4"
(290mm)
1.7" (43mm)
Outside Frame
2.5" (64mm)
To Outside
FRONT VIEW
FRONT
RIGHT SIDE VIEW
Control Cable
Conduit Plate
7.1" (180mm)
.2"
(5mm)
Cable Entry
Conduit Plate
See Detail B
Power Cable
Conduit Plate
11.1"
(281mm)
27.8"
(706mm)
7.3"
(185mm)
11.9"
(302mm)
Note:
BOTTOM VIEW
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit required for air exhaust and 36" (914)
front access required for service.
3. Keep cabinet within 15 degrees of vertical while handling.
4. Top and bottom cable entry available through removable access plates.
Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
CONDUIT
DETAIL B
2.6" (66mm)
Outside Frame
6. Control wiring and power wiring must be run in separate conduits.
7. All wiring is to be in accordance with national and local electrical codes.
8. Width dimension includes side panels. Subtract 1.4" (35mm) when removing both side panels.
9. Depth dimension includes the front door and rear panel.
10. See technical information drawing for shipping weights.
U40-4C-1001
Rev. 5
27 Liebert
®
NXL
™
Figure 19 Outline drawing, 400kVA, 575V/600V Liebert NXL
Installation Drawings
Cable Entry
Conduit Plate
Actual Usable Area
10.2" x 34.2"
(260mm x 870mm)
75.3"
(1912mm)
TOP VIEW
76.8"
(1950mm)
UPS Cabinet
61.8" (1570mm)
98.4" (2500mm)
FRONT VIEW
I/O Bypass Cabinet
36.6" (930mm)
FRONT
39.4"
(1000mm)
RIGHT SIDE VIEW
2.9"
(74mm)
Cable Entry
Conduit Plate
See Detail A
To Outside
Outside
Frame
FRONT
Cable Entry
Conduit Plate
BOTTOM VIEW
NOTE:
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit required
for air exhaust, and 36" (914) front access required for service.
Actual Usable Area
12.8" x 34.2"
(325mm x 870mm)
3. Keep cabinet within 15 degrees of vertical while handling.
4. Top and bottom cable entry available through removable
access plates. Remove punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate conduits.
7. All wiring is to be in accordance with national and local electrical codes
8. Width dimension includes one side panel. Subtract 0.7" (17mm)
when removing the side panel.
9. Depth dimension includes the front door and rear panel.
10. See technical information drawing for shipping weights.
Detail A
I/O Bypass Cabinet
Bottom
Cable Entry
U40-4C-1006
Rev. 2
3.1"
(80mm)
Liebert
®
NXL
™
28
Figure 20 Outline drawing, 400kVA, 575V/600V Liebert NXL with DC I/O cabinet
Installation Drawings
Cable Entry
Conduit Plate
Actual Usable Area
10.2" x 34.2"
(260mm x 870mm)
(Service)
Access Plate
12" x 12.3"
(305mm x 312mm)
19.2"
(488mm)
Cable Entry
Conduit Plate
Actual Usable
Area
12.1"
(307mm)
TOP VIEW
75.3"
(1912mm)
76.8"
(1950mm)
DC I/O Cab.
Outside
Frame
3.1"
(80mm)
UPS Cabinet
77.9" (1978mm)
114.5" (2908mm)
FRONT VIEW
FRONT
To Outside
2.5"
(64mm)
I/O Bypass Cabinet
2.9"
(74mm)
36.6" (930mm)
To Outside
Outside
Frame
FRONT
Cable Entry
Conduit Plate
Actual Usable Area
9.2" x 34.2"
(233mm x 870mm)
Cable Entry
Conduit Plates
See Detail A
DETAIL A
DC I/O Cabinet
Bottom Cable Entry
Cable Entry
Conduit Plate
Actual Usable Area
12.8" x 34.2"
(325mm x 870mm)
FRONT
DETAIL B
I/O Bypass Cabinet
Bottom Cable Entry
39.4"
(1000mm)
RIGHT SIDE VIEW
3.1"
(80mm)
Note:
1. All dimensions are in inches (mm].
2. 24" (610) minimum clearance above unit
required for air exhaust and 36" (914)
front access required for service.
3. Keep cabinet within 15 degrees of vertical
while handling.
4. Top and bottom cable entry available
through removable access plates. Remove,
punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for
forklift handling.
6. Control wiring and power wiring must be
run in separate conduits.
7. All wiring is to be in accordance with national
and local electrical codes.
8. Width dimension includes side panels.
Subtract 1.4" (35mm) when removing both
side panels.
9. Depth dimension includes the front door
and rear panel.
10. See technical information drawing
for shipping weights.
Cable Entry
Conduit Plate
See Detail B
U40-4C-1008
Rev. 2
BOTTOM VIEW
29 Liebert
®
NXL
™
Figure 21 Main components, 250kVA, 480V Liebert NXL
HMI Screen
HMI Keylock or
EMO Button
(Optional)
Liebert
IntelliSlot
Housings
Installation Drawings
Module Output
Circuit Breaker (CB2)
Back Feed
Breaker (BFB)
External
Interface
Board (EIB)
Main Input
Circuit Breaker (CB1)
Option Box
(6 Slots Available)
Input/Output
Cabinet
Liebert
®
NXL
™
Doors and Inner Skins Removed
30
U40-2C-1000
Rev. 4
Figure 22 Main components, 250kVA, 575/600V, and 300kVA, 480/575/600V Liebert NXL
HMI Screen
HMI Keylock or
EMO Button
(Optional)
Liebert
IntelliSlot
Housings
Installation Drawings
Module Output
Circuit Breaker (CB2)
Back Feed
Breaker (BFB)
External
Interface
Board (EIB)
Main Input
Circuit Breaker (CB1)
Option Box
(6 Slots Available)
Input/Output
Cabinet
Doors and Inner Skins Removed
31
U40-3C-1000
Rev. 5
Liebert
®
NXL
™
Installation Drawings
Figure 23 Main components, 400kVA, 480V Liebert NXL
HMI Screen
HMI Keylock or
EMO Button
(Optional)
Liebert
IntelliSlot
Housings
External
Interface
Board (EIB)
Module Output
Circuit Breaker (CB2)
Back Feed
Breaker (BFB)
Main Input
Circuit Breaker (CB1)
Option Box
(6 Slots Available)
Input/Output
Cabinet
Liebert
®
NXL
™
Doors and Inner Skins Removed
32
U40-4C-1000
Rev. 3
Figure 24 Main components, 400kVA, 575V/600V Liebert NXL
HMI Screen
External
Interface
Board
(EIB)
Main Input
Circuit
Breaker
(CB1)
Installation Drawings
Backfeed
Breaker
(BFB)
Module Output
Circuit Breaker
(CB2)
DC Negative
Busbar
DOORS REMOVED
DC Positive Busbar
DOORS AND INNER SKINS REMOVED
Liebert
IntelliSlot
Housings
Bypass Input
& Neutral
Busbars
Output
& Neutral
Busbars
Rectifier
Input
Busbars
Ground
Busbar
U40-4C-1005
Rev. 0
33 Liebert
®
NXL
™
Installation Drawings
Figure 25 Main components, 400kVA, 575V/600V Liebert NXL with DC I/O cabinet
HMI Screen
External
Interface
Board (EIB)
Backfeed
Breaker (BFB)
Main Input
Circuit
Breaker
(CB1)
Module Output
Circuit Breaker
(CB2)
DC Positive
Busbar
DC Negative
Busbar
Ground
Busbar
DOORS REMOVED
DOORS AND INNER SKINS REMOVED
Liebert
IntelliSlot
Housings
Bypass Input &
Neutral Busbars
Output &
Neutral Busbars
Rectifier
Input
Busbars
Ground
Busbar
U40-4C-1007
Rev. 0
Liebert
®
NXL
™
34
Figure 26 Input/output conduit detail drawing, 250-300kVA, all voltages, Liebert NXL
DC
3" Conduit, 2 Places
Input
3.5" Conduit, 2 Places
Output
3.5" Conduit, 2 Places
Output
3.5" Conduit, 2 Places
Input
3.5" Conduit, 2 Places
DC
3" Conduit, 2 Places
Installation Drawings
Low Voltage
1.5" Conduit
FRONT
TOP VIEW
Low Voltage
1" Conduit, 14 Places
FRONT
Low Voltage
1.5" Conduit
BOTTOM VIEW
Extended position
76.8" (1950mm)
See Detail D
For DC Busbars
DC Positive
DC Negative
See Note 6
Ground Bus
(Top Entry)
See Detail D
For Input Busbars
UPS Input
Bypass
Neutral
B
59.4" (1509mm)
56.4" (1432mm)
52.9" (1343mm)
49.4" (1255mm)
46.4" (1178mm)
43.4" (1102mm)
Output
D
Inner Panel
Removed
For Clarity
31.4" (797mm)
28.4" (721mm)
25.4" (645mm)
21.9" (556mm)
A
Ground Bus
(Bottom Entry)
Output
Neutral
C
FRONT RIGHT SIDE VIEW
.0"
(0mm)
Ø .56"
(14mm)
Typical
1.75
(44mm)
Typical
.87"
(22mm)
.87"
(22mm)
.98"
(25mm)
1.10"
(28mm)
1.75
(44mm)
Typical
(Bottom
Entry)
1.75
(44mm)
Typical
(Top
Entry)
DETAIL A
Notes:
1. All dimensions are in inches (mm).
DETAIL B
Ø .56"
(14mm) Typical
2. 24" (610) minimum clearance above unit required for air exhaust,
and 36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical while handling.
4. Top and bottom cable entry available through removable
access plates. Remove punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. These brackets can be removed during installation but must be
replaced after installation.
7. Control wiring and power wiring must be run in separate conduits.
8. All wiring is to be in accordance with national and local electrical
codes.
1.75
(44mm)
Typical
Ø .56"
(14mm)
Typical
1.75
(44mm)
Typical
(Bottom
Entry)
.88" x .56" Slot
(22mm x 14mm)
6 Places
Each Bar
1.75
(44mm)
Typical
DETAIL C
DETAIL D
1.75
(44mm)
Typical
Ø .56"
(14mm) Typical
Rev. 3
(Top Entry)
U40-3E-1400
35 Liebert
®
NXL
™
Installation Drawings
Figure 27 Input/output terminal detail, 400kVA, 480V Liebert NXL
DC
(2) 3" Conduit
Bypass
(2) 3.5" Conduit
Input
(2) 3" Conduit
Output
(2) 3.5" Conduit
Output
(2) 3.5" Conduit
Input
(2) 3" Conduit
Bypass
(2) 3.5" Conduit
DC
(2) 3" Conduit
Ø.56
(14)Typ.
1.75 (44)
Typ.
.87
(22)
.87 (22)
.98 (25)
1.1
(28)
Low Voltage
1.5" Conduit
DETAIL A
1.75 (44)
Typ. (Bottom (Entry)
TOP VIEW
Low Voltage
(14) 1" Conduit
BOTTOM VIEW
Low Voltage
(14) 1" Conduit
1.75 (44)
Typ.(Top
(Entry)
76.8
(1950)
Bypass
Neutral
DC Positive
Dc Negative
See Note 6
A
Ground Bus
Location
(Top Entry)
Bypass Input
Rectifier Input
Output
Inner Panel
Removed
For Clarity
D
B
C
59.4 (1509)
56.4 (1432)
1.75 (44)
52.9 (1343)
Typ.
49.4 (1255)
46.4(1178)
43.4 (1102 )
40.4 (1026)
37.4(950)
34.4 (874)
.56
(14)Typ.
31.4(797)
28.4 (721)
25.4 (645)
DETAIL B
Ø .56
(14)Typ.
1.75 (44)
Typ.
DETAIL C
21.9 (556)
1.75 (44)
Typ.
(Bottom
(Entry)
1.75 (44)
Typ. (Top
(Entry)
Ground Bus
(Bottom Entry)
Output
Neutral
0
.88 x .56 Slot
6 Places
DETAIL D
Each Bar
Ø .56
(14)Typ.
FRONT
NOTES
1. All dimensions are in inches (mm).
RIGHT SIDE VIEW
2. 24" minimum clearance above unit required
for air exhaust.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through
removable access plates. Remove, punch to
suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. These brackets can be removed during installation but
must be replaced after installation.
7. Control wiring and power wiring must be run in separate conduits.
8. Unless otherwise noted, use copper or aluminum conductors
suitable for at least 75°C.
9. All wiring is to be in accordance with national and local
electrical codes.
Liebert
®
NXL
™
36
Figure 28 Input/output terminal detail, 400kVA, 575V/600V Liebert NXL
Installation Drawings
BOTTOM
Cable Entry
Conduit Plate
12.8" x 33.9"
(325mm x 861mm)
FRONT
TOP
Cable Entry
Conduit Plate
12.6" x 37"
(320mm x 940mm)
Bypass Input and Neutral
See Detail A
3.1" (80mm)
Typ.
Between
Busbars
51.4"
(1305mm)
Output and Neutral
See Detail B
DETAIL A
Ø .512"
(13mm) Typ.
Ground
See Detail D
Detail A & B:
Suitable for two-hole lugs
(3 each) at 1.75" spacing between hole centers and
1.75" max. tongue width.
32.9"
(835mm)
15.6"
(396mm)
15.2"
(385mm)
RIGHT SIDE VIEW
3.1"
(80mm)
Typ. Between
Busbars
Rectifier Input
See Detail C
FRONT
Ø .512"
(13mm) Typ.
DETAIL B
Notes:
1. All dimensions are in inches (mm).
2. 24" minimum clearance above unit is required.
3. Keep cabinet within 15 degrees of vertical.
1.75" (44mm)
Rev. 0
Ø.563" (014mm) Typ.
U40-4E-1408
1.75" (44mm)
4. Top and bottom cable entry available through removable
access plates. Remove and punch to suit conduit size
2.56"
0.87" (22mm)
(65mm) Typ
and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. These brackets can be removed during installation but must
be replaced after installation.
7. Control wiring and power wiring must be run in separate conduits
8. All wiring is to be in accordance with national and local electrical codes.
DETAIL C
Ø .512"
(13mm) Typ.
1.1" (28mm)
0.99" (25mm)
DETAIL D
37 Liebert
®
NXL
™
Installation Drawings
Figure 29 Input/output terminal detail, 400kVA, 575V/600V Liebert NXL with DC I/O cabinet
FRONT
Ø.563" (014mm) Typ.
1.75"
(44mm)
Cable Entry
Conduit Plate
9.2" x 17.1"
(233 x 435mm)
2 Places
Cable Entry
Conduit Plate
20.6" x 15"
(524 x 381mm)
2" (51mm) Typ.
DETAIL A
DC POSITIVE
Ø.563" (014mm) Typ.
1.75"
(44mm)
BOTTOM
FRONT
TOP
2" (51mm) Typ.
DETAIL B
DC NEGATIVE
Ø.563" (014mm) Typ.
1.75"
(44mm)
DC Positive
See Detail A
47.1"
(1197mm)
35.3"
(897mm)
24.5"
(622mm)
LEFT SIDE VIEW
DC Negative
See Detail B
Ground
See Detail C
FRONT
1.75" (44mm)
DETAIL C
GROUND
NOTES
1. All dimensions are in inches (mm).
2 .24" minimum clearance above unit is required.
3 . Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through
removable access plates. Remove and punch
to suit conduit size and replace.
5. Unit bottom is structurally adequate for
forklift handling.
6. These brackets can be removed during installation
but must be replaced after installation.
7. Control wiring and power wiring must be run
in separate conduits
8. All wiring is to be in accordance with national
and local electrical codes.
U40-4E-1407
Rev. 0
Liebert
®
NXL
™
38
Figure 30 Top cable entry routing and installation order
FOR UNIT RATINGS
250kVA- 480/575/600V
300kVA- 480/575/600V
400kVA- 480V
Fault Brace
Bypass Input
Fault Brace
Rectifier Input
Fault Brace
Output
DC (Positive)
DC (Negative)
Ground
(Top Entry)
Bypass
Neutral
Bypass
Input
Fault Brace
Bypass Input
Fault Brace
Rectifier Input
Rectifier
Input
OUTPUT
Fault Brace
Output
Ground
(Bottom Entry)
Output
Neutral
FRONT VIEW
SIDE VIEW
Installation Drawings
Output Conduit
Input Conduit
Bypass Conduit
DC Conduit
DC (Positive)
DC (Negative)
Bypass Neutral
Bypass Input
(Phase C)
Rectifier Input
(Phase C)
Output (Phase C)
Output Neutral
39
Recommended cable installation order :
1. DC Power
2. Bypass Neutral
3. Bypass Input Power
(Phases A-B-C)
4. Rectifier Input Power
(Phases A-B-C)
5. Output Power
(Phases A-B-C)
6. Output Neutral
7. Ground
The cables must be routed around the fault braces to prevent the cables from coming in contact with other busbars.
Liebert
®
NXL
™
Installation Drawings
Figure 31 Bottom cable entry routing and installation order
FOR UNIT RATINGS
250kVA- 480/575/600V
300kVA- 480/575/600V
400kVA- 480V
Fault Brace
Bypass Input
Fault Brace
Rectifier Input
Fault Brace
Output
DC (Positive)
DC (Negative)
Ground (Top Entry)
Bypass Neutral
Fault Brace
Bypass Input
Bypass Input
Fault Brace
Rectifier Input
Rectifier
Input
Fault Brace
Output
Output
Ground (Bottom Entry)
Output Neutral
FRONT VIEW
DC (Positive)
DC (Negative)
Bypass Neutral
Bypass Input
(Phase C)
Rectifier
Input
(Phase C)
Output
(Phase C)
Output
Neutral
Input Conduit
Bypass Conduit
Output
Conduit
DC Conduit
SIDE VIEW
Recommended cable installation order :
1.) Output Neutral
2.) Output Power
(Phases A-B-C)
3.) Rectifier Input Power
(Phases A-B-C)
4.) Bypass Input Power
(Phases A-B-C)
5.) Bypass Neutral
6.) DC Power
7.) Ground
The cables must be routed around the fault braces to prevent the cables from coming in contact with other busbars.
Liebert
®
NXL
™
40
Installation Drawings
Figure 32 Single-input busbar arrangement—250-400kVA units
12 x4
13 x4
11
13 x4
14 x8
15 x4
3 Places
Isometric View
250, 300 and 400kVA Units
Not all parts shown for clarity
Figure 33 Low-voltage cable entry—250-400kVA units
REMOVE PLATES
FLIP PLATES
INSTALL
Low-voltage cables can be install through the top of each unit. The entry conduit landing plate is shipped inverted.
To install, remove conduit plate, flip and reinstall. Removal of side plate is for access to pull wires.
41 Liebert
®
NXL
™
Specifications
5.0
S
PECIFICATIONS
Table 10 Liebert NXL UPS specifications
250kVA
480V
250kVA
575/600V
300kVA
480V
300kVA
575/600V
400kVA
480V
400kVA
575/600V
Input Parameters
Input Voltage to Rectifier, VAC
Input Voltage to Bypass, VAC
Input Voltage Range, VAC
480/575/600V 3-phase, 3-wire
480/575/600V 3-phase, 3-wire
+10% to -15
-15% to -20% *
-20% to -30% **
<-30% ***
60 Input Frequency, Hz
Permissible Input Frequency Range,
Hz
Reflected Input THDi at Nominal
Voltage at Full Load, %
Power Walk-In, sec
Bypass Neutral Current
Battery & DC Parameters
Battery Type
Nominal Battery Bus, VDC
Battery Float Voltage, VDC
Minimum End of Discharge Voltage,
VDC
55 to 65
<10% with 6-pulse & Passive Filter
1 to 30 (selectable) in 1 sec. Increment
1.7 times full-phase current
VRLA (Valve Regulated Lead Acid) or (FLA) Flooded Lead Acid
480V
540V
384V (for VRLA / Flooded Lead Acid)
DC Ripple Voltage in Float & Const
V Ch. Mode, %
Temperature Compensated Battery
Charging
Output Parameters
Inverter Type
Output Power, kW
<1 (RMS value) < 3,4% V pp
Standard (with temperature probe)
Output Voltage, VAC
Output Voltage Regulation, %
Output Voltage Regulation (100%
Unbalanced Load)
Output Frequency, Hz
Output Frequency Regulation, %
Output THDv Linear Load at
Nominal Voltage, %
225
IGBT-based Sine-Sine PWM Controlled
270
480V 3-ph, 4-w
< 1% (3-phase RMS average)
< 2% (3-phase RMS average)
60
± 0.1
<2%
Output THDv at Nominal Voltage
Including a 100kVA Non Linear Load per EN 62040-3, %
Capacity to Handle High Crest
Factor Load
Capacity to handle Step Load, %
2.5% (max)
3:1
Transient Recovery (linear loads), %
Unbalance Loads Current Capacity
0-100 or 100-0
Within 5% peak-to-peak in one line cycle.
100% of nominal phase current
* The UPS will operate at full load, but the battery charge will either be reduced or off (depending on input current).
** The UPS will operate at full load, but UPS may source share with the batteries (depending on input current).
*** UPS will be in Battery mode
360
400kVA
575/600V with DC
I/O
Cabinet
Liebert
®
NXL
™
42
Specifications
Table 10 Liebert NXL UPS specifications (continued)
250kVA
480V
250kVA
575/600V
300kVA
480V
300kVA
575/600V
400kVA
480V
400kVA
575/600V
Capacity to Handle Leading PF Load
0.9 lag to Nom at 0.95 Lead at 0,9 Lead
Voltage Displacement, ° el
Overload Conditions, % FL
Subject to Max. kW rating
Subject to Max. kW rating
Subject to 12.5% kW derate or same Rating and 50°F (10°C) Temp. Derate
120° ±1° el (with 100% unbalanced load)
105% for 85 minutes
110% for 60 minutes
125% for 10 minutes
150% for 1 minute
Physical Parameters and Standards, in (mm)
71.8
(1823)
33.5
(850)
Height
SMS
Weight, Unpacked, lb. (kg) approximate
1+N
Weight, Unpacked, lb. (kg) approximate
Max heat Dissipation, Full Load,
BTU/hr (kW)
Cooling Air CFM
Color
Front Door Opening (for serviceability)
3965
(1798)
4040
(1833)
<54,000
(15.8)
5440
(2468)
78.5 (1993)
4840
(2195)
5515
(2502)
<54,000
(15.8)
4915
(2229)
<62,000
(18.2)
5894
39.4 (1000)
76.8 (1950)
5440
(2468)
5515
(2502)
<64,500
(18.9)
Black (ZP-7021)
More than 180°
6280
(2849)
6380
(2894)
<74,500
(21.8)
98.4
(2500)
7945
(3604)
8045
(3649)
<86,300
(25.3)
7092
Degree of Protection for UPS
Enclosure
Minimum Clearance, Top, in (mm)
Minimum Clearance, Back, in (mm)
Minimum Clearance, Sides, in (mm)
Location of Cable Entrance
Standards and Conformities
IP 20 (with and without front door open)
24 (610)
0
0
Top or Bottom
UL 1778, 4th Ed; CSA 22.2 107.3; FCC Part 15, Class A
FCC, Class A—Standard; IEC62040-2, Level 4, Criteria A
EN61000-4-3, Level 3, Criteria A;
EN61000-4-6, Level 4, Criteria A; EN61000-2-2, Criteria A
EN61000-4-4, Level 4, Criteria A
ANSI C62.41, Category A3 &B3; IBC 2012/CBC 2010
ISTA Procedure 1H; WEEE
Environmental Parameters
Storage Temperature Range, °F
(°C)
-13 to 158 (-25 to 70)
Operating Temperature Range, °F
(°C)
Acoustical Noise, dBA
32 to 104 (0 to 40) (UPS)
Relative Humidity
68
95% or less
Non-Condensing (Operating and Non-Operating)
Maximum Altitude Above MSL, ft (m)
4920 (1500) (as per IEC 62040/3) - 1% Max kW derate / 328 rise between 4921-9842
(100m rise between 1500-3000m)
1. Width dimensions are with side panels attached. Subtract 1.4" (35mm) for dimensions without side panels.
2. Depth dimensions include the front door and rear panel.
400kVA
575/600V with DC
I/O
Cabinet
114.5
(2908)
8275
(3754)
8375
(3799)
<86,300
(25.3)
43 Liebert
®
NXL
™
Specifications
Table 11 Current ratings—rectifier input
UPS Rating kVA kW
Voltage,
VAC
Nominal
Current
Maximum
Current
300
300
400
400
400
250
250
250
300
270
270
360
360
360
225
225
225
270
575
600
480
575
600
480
575
600
480
308
295
497
419
401
312
260
250
371
386
368
621
524
502
389
326
312
464
Table 12 Current ratings—bypass input
UPS Rating kVA kW
300
300
400
400
400
250
250
250
300
225
225
225
270
270
270
360
360
360
Voltage,
VAC
480
575
600
480
575
600
480
575
600
Nominal
Current
301
251
241
361
301
289
481
402
385
Table 13 Current ratings—output
UPS Rating Voltage, kVA kW VAC
250 225
250 225
250 225
300 270
300 270
300 270
400 360
400 360
400 360
480
575
600
480
575
600
480
575
600
Nominal
Current
301
289
481
402
385
301
251
241
361
Notes on Tables
1. Nominal input current (considered continuous) is based on full-rated output load. Maximum current includes nominal input current and maximum battery recharge current (considered noncontinuous).
Continuous and noncontinuous current are defined in NEC 100.
2. Maximum input current is controlled by the current limit setting, which is adjustable. Values shown are for a maximum setting of 125%. The standard factory setting is 125%. If a smaller input feed breaker is used, the input current limit must be adjusted accordingly.
3. For units with an input transformer, the Rectifier Input Feed Breaker must be set to handle the Liebert NXL transformer inrush of up to eight times the nominal current.
4. For breaker coordination while the module is overloaded, see the current-
versus-time values on the overload curves, Figures 34 and 35.
5. The battery current is at an EOD voltage of 1.61 volts/cell.
Table 14 Current ratings—battery
UPS Rating kVA kW
250
300
400
400
225
270
360
360
AC Input/Output
Voltage, VAC
480, 575 and 600
480, 575 and 600
480
600
Maximum Battery
Current at EOD
615
730
980
990
Liebert
®
NXL
™
44
Specifications
Table 15 Recommended conduit and cable sizes
UPS Rating kVA
250
250
250
300
300
300
400
270
270
270
360
kW
225
225
225
400 360
400 360
Bypass Input
Voltage
(VAC)
480
575
600
480
575
600
480
575
600
(# of conduits); size of conduits; # -size of phase cables per conduit; size of cable for ground per conduit
Copper Conductors
(2) 2C 3-250kcmil, #3AWG
(2) 1.5C 3-#4/0AWG, #3AWG
(2) 1.5C 3-#4/0AWG, #3AWG
(2) 2C 3-350kcmil, #2AWG
(2) 2C 3-250kcmil, #3AWG
(2) 1.5C 3-#4/0AWG, #3AWG
(2) 2.5C, 3-500kcmil, #1/0AWG
(2) 2.5C 3-350kcmil, #2AWG
(2) 2.5C 3-350kcmil, #2AWG
Aluminum Conductors
(2) 2C 3-350kcmil, #1AWG
(2) 1.5C 3-250kcmil, #1AWG
(2) 1.5C 3-250kcmil, #1AWG
(2) 2.5C 3-500kcmil, #1/0AWG
(2) 2.0C 3-350kcmil, #1AWG
(2) 2.0C 3-300kcmil, #1AWG
(2) 2.5C 3-750kcmil, #3/0AWG
(2) 2.5C 3-500kcmil, #1/0AWG
(2) 2.5C 3-500kcmil, #1/0AWG
UPS Rating kVA
250
250
250
300
300
300
400
400
400
Output kW
225
225
225
270
270
270
360
360
360
Voltage
(VAC)
480
575
600
480
575
600
480
575
600
(# of conduits); size of conduits; # -size of phase cables per conduit;
#-size of neutral cables per conduit; size of cable for ground per conduit
Aluminum Conductors Copper Conductors
(2) 2.5C 3-250kcmil, 2-#4/0AWG, #3AWG
(2) 2C 3-#4/0AWG, 2-#2/0AWG, #4AWG
(2) 2C 3-#4/0AWG, 2-#2/0AWG, #4AWG
(2) 2.5C 3-350kcmil, 2-#4/0AWG, #3AWG
(2) 2.5C 3-250kcmil, 2-#4/0AWG, #3AWG
(2) 2C 3-#4/0AWG, 2-#4/0AWG, #4AWG
(3) 3.5C, 3-600kcmil, 2-500kcmil, #1/0AWG
(2) 2.5C 3-#4/0AWG, 2-#4/0AWG, #2AWG
(2) 2.5C 3-#4/0AWG, 2-#4/0AWG, #2AWG
(2) 2.5C 3-350kcmil, 2-#250kcmil, #1AWG
(2) 2.0C 3-250kcmil, 2-#4/0AWG, #2AWG
(2) 2.0C 3-250kcmil, 2-#4/0AWG, #2AWG
(2) 2.5C 3-500kcmil, 2-300kcmil, #1AWG
(2) 2.5C 3-350kcmil, 2-250kcmil, #1AWG
(2) 2.5C 3-300kcmil, 2-250kcmil, #2AWG
(2) 3.5C 3-750kcmil, 2-500kcmil, #1/0AWG
(2) 3C 3-300kcmil, 2-300kcmil, #1/0AWG
(2) 3C 3-300kcmil, 2-300kcmil, #1/0AWG
UPS Rating kVA
250
250
250
300
300
300
400
kW
225
225
225
270
270
270
360
400 360
400
Battery
360
Voltage
(VAC)
480
575
600
480
575
600
480
575
600
(# of conduits); size of conduits; # -size of phase cables per conduit;
#-size of neutral cables per conduit; size of cable for ground per conduit
Aluminum Conductors Copper Conductors
(2) 2.5C 2-250kcmil, 2-#4/0AWG, #3AWG
(2) 2C 3-#4/0AWG, 2-#2/0AWG, #4AWG
(2) 2C 3-#4/0AWG, 2-#2/0AWG, #4AWG
(2) 2.5C 3-350kcmil, 2-#4/0AWG, #3AWG
(2) 2.5C 3-250kcmil, 2-#4/0AWG, #3AWG
(2) 2C 3-#4/0AWG, 2-#4/0AWG, #4AWG
(3) 3.5C, 3-600kcmil, 2-500kcmil, #1/0AWG
(2) 2.5C 3-#4/0AWG, 2-#4/0AWG, #2AWG
(2) 2.5C 3-#4/0AWG, 2-#4/0AWG, #2AWG
(2) 2.5C 3-350kcmil, 2-#250kcmil, #1AWG
(2) 2.0C 3-250kcmil, 2-#4/0AWG, #2AWG
(2) 2.0C 3-250kcmil, 2-#4/0AWG, #2AWG
(2) 2.5C 3-500kcmil, 2-300kcmil, #1AWG
(2) 2.5C 3-350kcmil, 2-250kcmil, #1AWG
(2) 2.5C 3-300kcmil, 2-250kcmil, #2AWG
(2) 3.5C 3-750kcmil, 2-500kcmil, #1/0AWG
(2) 3C 3-300kcmil, 2-300kcmil, #1/0AWG
(2) 3C 3-300kcmil, 2-300kcmil, #1/0AWG
(# of conduits); size of conduits; # -size of phase cables per conduit; size of cable for ground per conduit
UPS Rating kVA
250
300
400
kW
225
270
360
Copper Conductors
(2) 2C 2-600kcmil, #1/0AWG
(2) 2.5C 2-750kcmil, #1/0AWG
(3) 2C, 2-500kcmil, #2/0AWG
Aluminum Conductors
(2) 2.5C 2-750kcmil, #3/0AWG
(3) 2.0C 2-500kcmil, #3/0AWG
(3) 2.0C 2-600kcmil, #4/0AWG
45 Liebert
®
NXL
™
Specifications
Table 15 Recommended conduit and cable sizes
Bonding
UPS Rating Main Bonding Jumper/Grounding Electrode Conductor kVA kW Copper Conductors Aluminum Conductors
250
300
225
270
(1) #1/0AWG/ (1) #1/0AWG
(1) #2/0AWG/ (1) #2/0AWG
(1) #1/0AWG/ (1) #1/0AWG
(1) #2/0AWG/ (1) #2/0AWG
400 360 (1) #2/0AWG/ (1) #2/0AWG (1) #2/0AWG/ (1) #2/0AWG
1. Recommended cable sizes are 167°F (75°C) (THW) wire at 86°F (30°C) ambient. Unless otherwise noted, use copper or aluminum conductors suitable for at least 75°C.
2. For continuous operations not at 86°F (30°C), recommend that the site planner choose the appropriate cable type based on the particular installation requirements.
3. Conduit size is based on FMC type conduit with two neutral conductors rated at 200% of phase.
Liebert
®
NXL
™
46
Figure 34 Inverter overload data
Specifications
47
Time, seconds
Continuous
Liebert
®
NXL
™
Figure 35 Bypass overload data
Specifications
Liebert
®
NXL
™
48
Time, Seconds
Continuous
Specifications
Table 16 Recommended lug sizes
Cable Size
T&B Copper
One Hole
T&B Copper
Two Hole
#8AWG
#6AWG
#4AWG
#2-3AWG
#1AWG
#1/0AWG
#2/0AWG
#3/0AWG
#4/0AWG
250kcmil
300kcmil
350kcmil
400kcmil
500kcmil
600kcmil
750kcmil
54930BE
54905BE
54906BE
54942BE
54947BE
54950BE
54951BE
54965BE
54970BE
54913BE
54914BE
54915BE
54916BE
54918BE
54920BE
54922BE
54850BE
256-30695-868
256-30695-733
54811BE
54857BE
256-30695-593
54862BE
54864BE
54866BE
54868BE
54870BE
54872BE
54874BE
54876BE
54878BE
54880BE
T&B Aluminum
One Hole
60104-TB
60109-TB
60114-TB
60120
60126
60132
60138
60144
60150
60156
60162
60165
60168
60171
60176
60178
T&B Aluminum
Two Hole
60244
60250
60256
60262
60267
60269
60273
60275
60277
—
—
—
—
—
—
60238
Table 17 Recommended torque values
Grade 5 Steel – Unified Thread System Torque Units - lbf.*in.
Size
1/4
5/16
3/8
7/16
1/2
Fastener
Finish =>
9/16
14
20
13
20
12
18
Threads/
Inch, T pi
20
28
18
24
16
24
Plain Steel
No Washer/
Flat Washer
Lock
Washer
593
662
904
1,020
1,305
1,456
101
116
209
231
370
420
—
—
934
1,050
—
—
—
—
224
246
392
442
Class 8.8 Steel – Metric Thread System Torque Units - N*m
Zinc Plating
No Washer/
Flat Washer
534
596
814
918
1,175
1,310
91
104
188
208
333
378
Lock
—
—
203
223
355
400
—
—
844
948
—
—
M5
M6
M8
Fastener
Finish =>
Washer Size
M10
M12
M14
Thread
Pitch T
0.8
0.5
1
0.75
1.25
1
1.5
1.25
1.75
1.25
2
1.5
p
Plain Steel
No Washer/
Flat Washer
6.1
6.9
10
11
25
27
50
53
87
95
139
151
Lock
Washer
—
—
—
—
—
—
64
67
128
136
—
—
Zinc Plating
No Washer/
Flat Washer
5.5
6.2
9
10
23
24
45
47
78
86
125
136
Lock
Washer
59
61
119
127
—
—
—
—
—
—
—
—
49 Liebert
®
NXL
™
A
PPENDIX
A - C
ABINET
I
NTERCONNECTION
Figure 36 Cabinet interconnection cabling
Specifications
Liebert
®
NXL
™
50
Figure 37 Cabinet interconnection cabling (continued)
Specifications
Load V/I Board
51 Liebert
®
NXL
™
Specifications
Table 18 Cabinet interconnection cabling
Cable Part # Cabinet Start
These Cables Already Connected to UPS
606986G1 I/O Bypass - IntelliSlot
606980G3 I/O Bypass - BPSS Board
606985G1 I/O Bypass - BPSS Board
607080G1 I/O Bypass - BPSS Board
These Cables Already Connected to I/O Bypass
I/O Bypass - BFB
607011G1
I/O Bypass - BFB
I/O Bypass - CT7
607024G1
607045G1
I/O Bypass - CT8
I/O Bypass - CT9
I/O Bypass - Fan13
I/O Bypass - Fan14
Source: 608841P1, Rev. 0
Connector
Label
PIN1, PIN2
P0500
P0501
P44
Cabinet Finish
UPS - EIB Board
UPS - UPSC Board
UPS - UPSC Board
UPS - Power Supply
BYP_PS_B
BYP_PS_C
X1, X2
UPS - F42
UPS - F43
UPS - Load V/I Board
X1, X2
X1, X2
UPS - Load V/I Board
UPS - Load V/I Board
CONNECTOR1 UPS - Fan Interface Board
CONNECTOR2 UPS - Fan Interface Board
Connector
Label
IntelliSlot
P0500
P0501
P44
F42-1
F43-1
P0713
P0714
P0715
P1005
P1006
Liebert
®
NXL
™
52
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2013 Liebert Corporation
All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks or registered trademarks of their respective owners.
SL-25420_REV15_09-15
Emerson Network Power
Division: Liebert
Web: www.emerson.com
Technical Support / Service
Web Site
www.liebert.com
Monitoring
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
www.EmersonNetworkPower.com
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 16 Equipment Ground
- 17 Figure 3 Cabinet grounding plates
- 17 Figure 4 Kick plate and filter locations, typical
- 19 Table 1 UPS input dry contacts
- 19 Table 2 UPS control with battery cabinet or module battery disconnect
- 19 Table 3 UPS control contacts with global maintenance bypass
- 20 Table 4 UPS control contacts to remote status panel
- 20 Table 5 Parallel from UPS module Inter-Module Communication Board to other Inter-Module Communication Board in system
- 21 Figure 6 Inter-Module Communication Board wiring diagram—Multi-modules
- 27 Figure 12 Control wiring, Programmable Relay Board
- 27 Table 7 Programmable Relay Board pinout
- 28 Configuring the Programmable Relay Board Settings
- 28 Figure 13 Programmable relay board dialog box
- 29 Figure 14 Input contact isolator dialog box
- 30 Table 8 Input Contact Isolator Board pre-assigned values
- 30 Figure 15 Optional Input Contact Isolator Board
- 30 Table 9 Input Contact Isolator Board control wiring connections