XR20 Program Manual
XR20 Command Processor Panel
Programming Guide
26 Zone Burglary/Fire/Access Control Panel with Built-in Communicator
Do Not Throw Away!
This programming guide contains information you need to program and
service the XR20 panel and should be kept along with your other DMP
technical documentation.
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
LT-0305 (1/98)
MODEL XR20 PROGRAMMING GUIDE
When using the Series XR20 control for any UL, NFPA, CSFM or other listing
organization's approved methods, refer to this manual and the XR20 Installation Guide
(LT-0229). These documents outline the installation and programming requirements of
all applications for which the XR20 is approved.
Copyright © 1996, 1997, 1998 Digital Monitoring Products, Inc.
Information furnished by DMP is believed to be accurate and reliable.
This information is subject to change without notice.
TABLE OF CONTENTS
Section
Section
REMOTE OPTIONS
INTRODUCTION
Remote Options ....................................................... 4.1
Before You Begin .................................................... 1.1
Remote Key ............................................................. 4.2
Getting Started ........................................................ 1.2
Manufacturer Authorization ..................................... 4.3
Programming Menu ................................................. 1.3
Armed Rings ............................................................ 4.4
Programmer Lockout Codes .................................... 1.4
Disarmed Rings ....................................................... 4.5
Reset Timeout ......................................................... 1.5
Alarm Receiver Authorization .................................. 4.6
Special Keys ............................................................ 1.6
Service Receiver Authorization ............................... 4.7
Entering Alpha Characters ...................................... 1.7
Remote Disarm ........................................................ 4.8
Entering Non-Alpha Characters ............................... 1.8
Keypad Prompts Display Current Programming ...... 1.9
SYSTEM REPORTS
System Reports ....................................................... 5.1
INITIALIZATION
Initialization .............................................................. 2.1
Opening/Closing Reports ........................................ 5.2
Clear All Codes ........................................................ 2.2
Abort Reports .......................................................... 5.3
Clear Schedules ...................................................... 2.3
Zone Restoral Reports ............................................ 5.4
Clear Events ............................................................ 2.4
Bypass Reports ....................................................... 5.5
Clear Zone Programming ........................................ 2.5
Code Change Reports ............................................. 5.6
Clear Programming ................................................. 2.6
Ambush Reports ...................................................... 5.7
COMMUNICATION
Communication ........................................................ 3.1
Communication Type ............................................... 3.2
Account Number ...................................................... 3.3
Transmit Delay ........................................................ 3.4
DTMF ....................................................................... 3.5
Event Manager ........................................................ 3.6
Test Frequency ........................................................ 3.7
Test Time ................................................................. 3.8
Receiver 1 Programming ......................................... 3.9
Alarm Reports ..................................................... 3.10
Supervisory and Trouble Reports........................ 3.11
Opening/Closing and User Reports ..................... 3.12
Test Report .......................................................... 3.13
Backup Reporting ................................................ 3.14
First Telephone Number ...................................... 3.15
Second Telephone Number ................................ 3.16
Receiver 2 Programming ......................................... 3.17
Pager Reporting .................................................. 3.18
Alarm Reports ..................................................... 3.19
Supervisory and Trouble Reports........................ 3.20
Opening/Closing and User Reports ..................... 3.21
Test Report .......................................................... 3.22
Backup Reporting ................................................ 3.23
First Telephone Number ...................................... 3.24
Second Telephone Number ................................ 3.25
Pager Identification Number ................................ 3.26
SYSTEM OPTIONS
System Options ....................................................... 6.1
Area Mode ............................................................... 6.2
Closing Code ........................................................... 6.3
Closing Check ......................................................... 6.4
Entry Delay .............................................................. 6.5
Exit Delay ................................................................ 6.6
Cross Zone Time ..................................................... 6.7
Power Fail Delay ..................................................... 6.8
Reset Swinger Bypass ............................................ 6.9
Telephone Access ................................................... 6.10
OUTPUT OPTIONS
Output Options ........................................................ 7.1
Bell Cutoff Time ....................................................... 7.2
Automatic Bell Test .................................................. 7.3
Bell Action ................................................................ 7.4
Fire Type ................................................................. 7.4A
Burglary Type ..................................................... 7.4B
Supervisory Type ............................................... 7.4C
Panic Type ......................................................... 7.4D
Emergency Type ................................................ 7.4E
Auxiliary 1 Type ................................................. 7.4F
Auxiliary 2 Type ................................................. 7.4G
TABLE OF CONTENTS
Section
STOP
OUTPUT OPTIONS (continued)
Stop ......................................................................... 10.1
Output Action ........................................................... 7.5
Cutoff Outputs ......................................................... 7.5A SET LOCKOUT CODE
Output Cutoff Time .................................................. 7.5B
Set Lockout Code .................................................... 11.1
Communication Failure Output ................................ 7.5C
APPENDIX
Fire Alarm Output .................................................... 7.5D
Status List ................................................................ 12.2
Fire Trouble Output ................................................. 7.5E
False Alarm Reduction Features ............................. 12.3
Ambush Output ........................................................ 7.5F
4-2 Reporting Operation .......................................... 12.4
Entry Output ............................................................ 7.5G
Zone Type Descriptions ........................................... 12.5
Exit Output ............................................................... 7.5H
Manual Telephone Line Seizure .............................. 12.6
Ready Output .......................................................... 7.5I
Default Panel Programming .................................... 12.7
Armed Output .......................................................... 7.5J
4-2 Reporting to Central Station Receivers ............. 12.8
Burglary Output ....................................................... 7.5K
4-2 Communication Reports .................................... 12.9
Ground Start Output ................................................ 7.5L
4-2 Examples ........................................................... 12.11
4-2 Communication Format Configuration ............... 12.12
AREA INFORMATION
Numeric Pager Message Formats ........................... 12.13
Area Information ...................................................... 8.1
FA426 Wireless Operation ...................................... 12.14
Area Number ........................................................... 8.2
FA113 User's Guide ................................................ 12.15
Area Name .............................................................. 8.3
Automatic Arming .................................................... 8.4
Bad Zones ............................................................... 8.5
Automatic Disarming ............................................... 8.6
ZONE INFORMATION
Zone Information ..................................................... 9.1
Zone Number ........................................................... 9.2
Zone Name .............................................................. 9.3
Zone Type ............................................................... 9.4
Zone Type Specifications ........................................ 9.4A
Area Number ........................................................... 9.5
Arming Zone Area Assignment ................................ 9.6
Style ......................................................................... 9.6A
Next Zone ................................................................ 9.7
Alarm Action ............................................................ 9.8
Disarmed Open ....................................................... 9.9
Message To Transmit ........................................ 9.9A
Output Number ................................................... 9.9B
Output Action ..................................................... 9.9C
Swinger Bypass ....................................................... 9.10
Entry Delay .............................................................. 9.11
Cross Zone .............................................................. 9.12
Priority ..................................................................... 9.13
Introduction
1-INTRODUCTION
Introduction
1.1
Before You Begin
About this Manual
This manual provides programming information for the DMP XR20 Command Processor Panel. After this
Introduction, the remaining sections describe the functions of each programming menu item along with
their available options. The XR20 contains all of its programming information in an on board processor
and does not require an external programmer.
Reading the Contents
Before starting to program, we recommend you read through the contents of this manual. The information
contained here allows you to quickly learn the programming options and operational capabilities of the
XR20 panel.
In addition to this manual, you should also read and be familiar with the following XR20 documents:
• XR20 User's Guide (LT-0303)
• XR20 Installation Guide (LT-0229)
• XR20 Product Specification (LT-0301)
Programming Information Sheet
Included with each XR20 panel is the Programming Information Sheet. This sheet lists the various keypad
prompts and available options for programming the panel. Before starting, we recommend you completely
fill out both sides of the sheet with the programming options you intend to enter into the panel.
Having completed programming sheets available while entering data helps to prevent errors and can
shorten the length of time you spend programming. Completed sheets also provide you with an accurate
account of the panel's program you can keep on file for future system service or expansion.
The remainder of this Introduction tells you how to start and end an XR20 programming session.
1.2
Getting Started
The XR20 Command Processor panel must be completely installed before you begin programming. Make
sure the panel is properly grounded and the AC and battery wires are connected to the correct panel
terminals.
Initializing the Panel
When programming an XR20 panel for the first time, or rewriting the entire program of an existing XR20,
use the Initialization function described in section 2. Initializing clears the panel's memory of any old or
incorrect data and sets user number 32 to user code 99.
Program from any Keypad Address
You can program the XR20 panel from any keypad connected to the keypad data bus. See the XR20
Installation Guide (LT-0229) for keypad addressing and installation information.
Accessing the Programmer
To access the programmer function of the XR20:
1. Place a slotted screwdriver across the two J16 reset jumpers for two seconds.
2. Remove the screwdriver.
3. Enter the code 6653 (PROG) into the keypad.
4. Enter your Lockout Code.
5. The keypad displays: PROGRAMMER.
You are now ready to start programming the XR20 panel. Pressing the COMMAND key scrolls you
through the programming menu items listed in section 1.3.
XR20 Programming Guide
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
Page 1
1-INTRODUCTION
1.3
Programming Menu
There are 10 programming menu items to choose from:
Menu Item
Initialization
Communication
Remote Options
System Reports
System Options
Output Options
Area Information
Zone Information
Stop
Set Lockout Code
Section in this manual
2
3
4
5
6
7
8
9
10
11
To select a section for programming, press any one of the top row SELECT keys when the name of that
section is displayed on the keypad. The detailed instructions for each programming step are found in
sections 2 to 11 of this manual.
1.4
Programmer Lockout Codes
Although the XR20 panel allows you to enter the built-in Programmer without a lockout code, we
recommend you install one to restrict programming access to only those persons your company
authorizes. You can do this by using SET LOCKOUT CODE at the end of the programming menu.
Installing a lockout code
1. After entering the Programmer menu, the keypad displays PROGRAMMER. Press the
COMMAND key until SET LOCKOUT CODE is displayed (after STOP).
2. Press any top row SELECT key. At the ENTER CODE: - display, enter a 1 to 5 digit programmer
lockout code. Press COMMAND.
3. The displays shows ENTER AGAIN. Enter the same lockout code again and press COMMAND.
The display shows CODE CHANGED. The new code number must now be entered before the
Programmer menu can be accessed.
The lockout code number should be written down and kept in a secure place with access limited to
authorized persons only.
Lost Lockout Code requires factory reset: If you lose or forget the lockout code, the panel must be
sent back to the factory to be reset. There is no field option for gaining access to the panel without a valid
lockout code.
1.5
Reset Timeout
The XR20 has a feature that requires you to enter the Programmer within 30 minutes of resetting the
panel. After 30 minutes, if you attempt to program by entering the 6653 (PROG) code, the keypad
displays: RESET PANEL. You must reset the panel and enter the program code within the next 30
minutes.
If you are already in the Programmer and do not press any keys on the programming keypad for 30
minutes, the panel terminates programming. All data entered up to that point is saved in the panel's
memory.
Using the Stop routine disarms all areas: To exit the panel's Programmer you must use the Stop
routine. The Stop routine does the following:
Disarms all areas
Clears the panel's Status List
The programming function is then terminated and the keypads return to the Status List.
XR20 Programming Guide
Page 2
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
1-INTRODUCTION
1.6
Special Keys
SELECT Keys
1
3
2
5
6
MNO
9
4
GHI
DEF
ABC
8
7
PQR
POWER
JKL
STU
0
VWX
COMMAND
YZ
COMMAND Key
ARROW Key
Figure 1: Keypad Function keys
COMMAND Key
The COMMAND key is used to advance through the programming. Pressing the COMMAND key allows
you to go forward through the programming menu and through each step of a programming section. As
you go through the programming, the keypad display shows any current programming already stored in
the panel's memory.
The COMMAND key is also used to enter information into the panel's memory such as phone numbers or
zone names. Press the COMMAND key after you've entered the information and it is being displayed
correctly on the keypad.
ARROW Key
Use the ARROW key to back up one step while in the programming menu or within a programming
section. The ARROW key also allows you to correct an error by erasing the last character entered.
SELECT Keys
The top row of keys are called the SELECT keys. When the Programmer displays an option for you to
select, such as YES or NO, you press the SELECT key under the option you want to enable.
The SELECT keys also allow you to change programming information currently in the panel's memory. As
you step through each program option, the keypad displays the current information. To change this
information, press the appropriate key under the display then enter the new information through the
keypad.
If you are changing a phone number or account number, press the SELECT key followed by the
appropriate digit keys. If entering a communication type or choosing a programming option, the keypad
displays the available response options above the SELECT keys. When there are more than four
response options available, the keypad displays the first four. Pressing the COMMAND key brings up the
next 1 to 4 options on the display. Pressing the ARROW key allows you to review the previous four
choices.
The SELECT keys are also used for selecting a section from the programming menu. This is done by
pressing any one of the SELECT keys when the name of the programming section you want is displayed.
XR20 Programming Guide
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
Page 3
1-INTRODUCTION
1.7
Entering Alpha Characters
Some options during programming require you to enter alpha characters. To enter an alpha character,
press the key that has that letter written below it. The keypad displays the number digit of the key. Next,
press the SELECT key that corresponds to the location of the letter under the key. Pressing a different
SELECT key changes the letter. When another digit key is pressed, the last letter displayed is retained
and the process is started over.
SYSTEM ON
Center Character
Left Character
Right Character
Figure 2: Keypad display and top row keys
1.8
Entering Non-Alpha Characters
To enter a space, press the 9 digit key followed by the third SELECT key. The three characters on the 9
digit key are Y, Z, and space. You can also enter the characters - (dash), . (period), * (asterisk), and #
(pound sign) using the zero key and the four SELECT keys from left to right.
1.9
Keypad Prompts Display Current Programming
Each programming prompt displayed at the keypad shows the currently selected option in the panel's
memory. These options are either shown as a number, a blank, or a NO or YES. To change a number or
blank to a new number, press any top row SELECT key. The current option is replaced with a dash. Press
the number(s) on the keypad you want to enter as the new number for that prompt.
It is not necessary to enter numbers with leading or trailing zeros. The XR20 automatically justifies the
number when you press the COMMAND key.
To change a programming prompt that requires a NO or YES response, press the top row SELECT key
under the response not selected.
For example, if the current prompt is selected as YES and you want to change it to NO, press the third
top row SELECT key from the left. The display changes to NO. Press the COMMAND key to go to the
next prompt. See Figure 3.
BELL TST
YES
NEXT
BELL TST
NO
The keypad display changes to the newly
selected option. Press COMMAND.
Press the top row select key.
Figure 3: Changing the current option selected.
XR20 Programming Guide
Page 4
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
2-INITIALIZATION
2.1
This function allows you to set the panel's programmed memory back to the factory
defaults in preparation for system programming.
INITIALIZATION
After you select YES to clear a section of memory, the panel asks if you are sure you
want to clear the memory. This is a safeguard against accidently erasing part of your
programming. No memory is cleared from the programming until you answer yes to
the SURE? YES
NO prompt.
For each section of the panel's program you can initialize, the
Programmer provides a NO or YES option.
CODES?
NO YES
Selecting YES advances you to a
confirmation prompt.
Selecting NO advances you to the
next section prompt and does not
initialize that section of the program..
SURE?
YES
NO
If you select YES, the panel initializes that section of the program and
advances you to the next section prompt.
SCHEDS?
NO YES
If you select NO, the panel advances you to the next section prompt
but does not initialize that section of the program.
A description of the Initialization selections follow:
2.2
2.3
2.4
2.5
2.6
CODES?
NO
YES
SURE?
YES
NO
SCHDS?
NO YES
SURE?
YES
EVENTS?
NO YES
SURE?
YES
ZONES?
NO YES
SURE?
YES
NO
NO
YES
CLEAR SCHEDULES - YES clears any schedules currently in the panel's
programming back to zero.
CLEAR EVENTS - YES clears all event memory currently held in the panel's Display
Events buffer.
CLEAR ZONE PROGRAMMING - YES sets all zones in the system to * UNUSED *.
NO
DEFAULTS? NO YES
SURE?
CLEAR ALL CODES - YES clears the user code memory and assigns the user code
number 99 to user number 32.
NO
CLEAR PROGRAMMING - YES sets the panel's programming back to factory default
selections. Selecting Defaults does not clear the panel's event memory, zone or user
code information, or schedules.
XR20 Programming Guide
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
Page 5
3-COMMUNICATION
3.1
COMMUNICATION
Section 3 allows you to configure the communication settings for the XR20 panel.
After choosing the Communication Type, continue through the list of options.
3.2
COMM TYPE: NONE
COMMUNICATION TYPE specifies the communication method the panel uses to
contact the receiver. Press any SELECT key to display the following communication
options:
NONE DD 4-2 M2E
NONE - For local systems. Selecting this ends communication programming.
DD - Digital Dialer communication to DMP SCS-1 Receivers.
CID
4-2 - 4-2 communication to non-DMP receivers.
M2E - Modem IIe communication to non-DMP receivers. This format sends the report
codes of the Radionics Modem IIe communication format.
CID - Contact ID communication to non-DMP receivers. This format sends the report
codes of the Ademco Contact ID communication format.
3.3
ACCOUNT NO:12 3 4 5
ACCOUNT NUMBER - Enter the account number sent to the receiver.
DD - The range of account numbers for Digital Dialer is 1 to 65,535. For account
numbers of four digits or less, you do not have to enter leading zeros. The panel
automatically right justifies the account number.
4-2, M2E, and CID - The range of account numbers for these formats is 1 to
9999.
3.4
XMIT DELAY:
00
TRANSMIT DELAY- Enter the length of time the panel waits before sending burglary
alarm reports to the receiver. The available range is 10 to 60 seconds in ten second
increments. Alarm bells and relay outputs are not delayed during this period. Burglary
Outputs in section 7.5K must be programmed for Steady.
If the area where the alarm occurred is disarmed during the Transmit Delay, only an
Abort Report is sent. Abort Reports in section 5.3 must be set to YES.
Enter zero to disable Transmit Delay.
3.5
DTMF
3.6
EVENT MGR: SEND
SND
YES
DLY
KEEP
DTMF - YES enables tone dialing. NO enables rotary dialing.
EVENT MANAGER - This option specifies when non-alarm reports are sent to the
receiver. This selection does not affect zone alarm, zone trouble, zone restoral,
supervisory, or serviceman messages. Closing reports are not delayed if you've
programmed a YES for the Bell Test option. See section 7.3.
SND - All reports are sent to the receiver as they occur.
DLY - All non-alarm reports are held until the panel's memory buffer contains 66
events or until the panel's next communication with the receiver. Modem IIe and 4-2
formats do not delay reports but send them as they occur.
Note: if BELL TEST is YES, Closing reports are not delayed.
KEEP - All non-alarm reports are held in the panel's memory buffer until they're
overwritten by new activity. You can view the contents of the buffer using the DMP
Remote Access™ software or the Display Events function in the User Menu.
Time update from the SCS-1 Receiver: The XR20 requests a time update each time (once each day
maximum) the panel contacts the receiver. The SCS-1 Receiver must have firmware version SCS/805 or
higher and the Update Time to Panel option must be set to YES in the receiver's Host Configuration
screen. In addition, the central station automation system must be configured to update the time in the
receiver at least once each day.
XR20 Programming Guide
Page 6
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
3-COMMUNICATION
3.7
TEST FREQ:
3.8
TEST
0
TEST TIME - Press COMMAND to enter the Test Time.
TIME
0:00 AM
TEST FREQUENCY - Allows you to set how often the panel's test report is sent to the
receiver. Enter from 1 to 60 days. Enter zero to disable the test report.
PM
Enter the time of day the panel sends the test report to the SCS-1 Receiver. Use
entries between 12:00 to 11:59 and then choose AM or PM.
3.9
RECEIVER 1 PROG
RECEIVER 1 PROGRAMMING - Allows you to set the options for the first receiver the
XR20 panel attempts to contact when sending reports. The XR20 supports
communication to two receivers.
3.10
ALARM
YES
ALARM REPORTS - YES enables Abort, Alarm, Alarm Restoral, Alarm Bell Silenced,
Ambush, Exit Error, and System Recently Armed reports to be sent to this receiver.
3.11
SPV/TRBL
YES
SUPERVISORY/TROUBLE REPORTS - YES enables Supervisory, Trouble, Trouble
Restoral, Force Armed, and Fault reports to be sent to this receiver.
3.12
O/C USER
YES
OPENING/CLOSING AND USER REPORTS - YES enables Opening/Closing, Door
Access, Schedule and Code Changes, Bypass, and Sensor Reset reports by user to
be sent to this receiver.
3.13
TEST RPT
YES
TEST REPORT - Enter YES to enable the Recall Test report to be sent to this
receiver. Reports are sent according to the programming in section 3.6.
3.14
BACKUP
3.15
FIRST PHONE NO.
NO
–
3.16
SECOND PHONE NO.
–
BACKUP REPORTING - YES enables this receiver to be a backup to the other
receiver in the event the other receiver cannot be contacted.
FIRST TELEPHONE NUMBER - This is the first number the panel dials when sending
reports to this receiver. Phone numbers can be up to 15 characters in length. You can
program a three second pause in the dialing sequence by entering the letter P. You
can program a dial tone detect by entering the letter D. These characters are counted
as part of the 15 allowable characters.
SECOND TELEPHONE NUMBER - The panel dials the second number when two
successive tries using the first number have failed. If the panel cannot reach the
receiver after two attempts using the second number, it returns to the first number and
makes two additional attempts. A total of ten dialing attempts are made using the first
and second phone numbers. If a second phone number is not entered, the first phone
number is used for all dialing attempts.
Each number can be up to 15 characters in length including any P or D characters
entered for pause and dial tone detect.
3.17
RECEIVER 2 PROG
RECEIVER 2 PROGRAMMING Repeat steps 3.7 through 3.14 when communicating
to a second receiver. Receiver 2 defaults are set to NO.
If you select YES for any of the Receiver 2 options, you must have at least one phone
number programmed in Receiver 2 programming.
XR20 Programming Guide
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
Page 7
3-COMMUNICATION
3.18
PAGER?
NONE
PAGER TYPE - This option allows the panel to send Alarm, Trouble, Opening and
Closing, and Late to Close reports to a customer's alphanumeric or numeric pager.
The panel uses DTMF or modem tones to generate the account and report information
sent over the pager terminal equipment.
Selecting NONE allows you to use the Receiver 2 programming to send panel reports
to a second central station receiver.
NONE NUM ALPHA
NONE - The pager reporting option is not being used.
NUMERIC - Reports are sent to the customer's numeric pager.
ALPHANUMERIC - Reports are sent to the customer's alphanumeric pager.
Caution: The XR20 communicates in a half-duplex mode with a Glenayre
alphanumeric pager terminal. The terminal modem must accept the following
parameters:
•
300 bps Bell 103 protocol
•
Carrier detect response time = 300ms
•
Delay between lost carrier and hang-up = 12.0 seconds
Instructions for using Pager Direct™ paging and cutout quick reference cards are
included in the XR20 User's Guide.
3.19 ALARM
NO
ALARM REPORTS - YES enables Abort, Alarm, Alarm Restoral, Alarm Bell Silenced,
Ambush, Exit Error, and System Recently Armed reports to be sent to this receiver.
3.20 SPV TRBL NO
SUPERVISORY/TROUBLE REPORTS - YES enables Supervisory, Trouble, Trouble
Restoral, Force Armed, and Fault reports to be sent to this receiver.
3.21 O/C USER NO
OPENING/CLOSING AND USER REPORTS - YES enables Opening/Closing, Door
Access, Schedule and Code Changes, Bypass, and Sensor Reset reports by user to
be sent to this receiver.
3.22 TEST RPT
NO
TEST REPORT - Enter YES to enable the Recall Test report to be sent to this
receiver. Reports are sent according to the programming in section 3.6.
NO
BACKUP REPORTING - YES enables this receiver to be a backup to the other
receiver in the event the other receiver cannot be contacted.
3.23
BACKUP
3.24
FIRST PHONE NO.
–
3.25
SECOND PHONE NO.
–
FIRST TELEPHONE NUMBER - This is the first number the panel dials when
sending reports to this receiver. Phone numbers can be up to 15 characters in length.
You can program a three second pause in the dialing sequence by entering the letter
P. You can program a dial tone detect by entering the letter D. These characters are
counted as part of the 15 allowable characters.
SECOND TELEPHONE NUMBER - The panel dials the second number when two
successive tries using the first number have failed. If the panel cannot reach the
receiver after two attempts using the second number, it returns to the first number and
makes two additional attempts. A total of ten dialing attempts are made using the first
and second phone numbers. If a second phone number is not entered, the first phone
number is used for all dialing attempts.
Each number can be up to 15 characters in length including any P or D characters
entered for pause and dial tone detect.
3.26
PAGER I D NUMBER
XR20 Programming Guide
PAGER IDENTIFICATION NUMBER - Enter a pager identification number if your
pager uses one. It does, the panel waits for nine seconds after having dialed the First
Phone Number before sending the Pager ID. After the Page ID has been sent, the
panel waits another three seconds before sending the actual pager message
containing the panel reports.
Page 8
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
4-REMOTE OPTIONS
4.1
4.2
REMOTE OPTIONS
RMT KEY:
This section allows you to enter the information needed for Remote Command/Remote
Programming operation. A description of the Remote Options follow:
REMOTE KEY - This option allows you to enter a code of up to eight digits for use in
verifying the authority of an alarm or service receiver to perform a remote command/
programming session. The receiver must give the correct key to the panel before
being allowed access. All panels are shipped from the factory with the Remote Key
preset as blank.
To enter a new Remote Key, press a top row SELECT key and enter any combination
of up to eight digits. The numbers you enter appear as asterisks. Press COMMAND.
4.3
MANUFACTURER AUTHORIZATION - Enter YES to allow DMP service technicians
to access the panel when required during system service or troubleshooting.
This authorization automatically expires within one hour.
MFG AUTH NO
DMP remote service is provided on a read only basis: DMP technicians can look at the system
programming and make suggestions only.
4.4
ARMED RINGS:
0
ARMED RINGS - Enter the number of rings the panel counts within a two minute
period before answering the phone line when all areas of the system are armed. Any
number from 1 to 15 can be entered. If zero is entered, the panel does not answer the
phone when all areas of the system are armed.
Answering machine bypass procedure: Entering a number greater than zero into either Armed Rings
or Disarmed Rings, allows a central station operator to connect remotely with the panel.
How it works: The operator calls the panel, rings the phone once, and then hangs up. The panel stores
this attempt to communicate. The operator then calls back within 30 seconds causing the panel to seize
the phone line and allow remote programming.
This feature does not interfere with the normal operation of the Armed Rings/Disarmed Rings function.
4.5
DISARM
4.6
ALR RCVR NO
RINGS: 0
DISARMED RINGS - Enter the number of rings the panel counts before answering the
phone line while any areas of the system are disarmed. Any number from 1 to 15 can
be entered. If zero is entered, the panel does not answer the phone when any area of
the system is disarmed.
ALARM RECEIVER AUTHORIZATION - Enter YES to enable remote commands
and programming to be accepted from the alarm SCS-1 Receiver. The Remote Key
option can also be required.
When YES is selected, the panel requests the alarm receiver key during its first alarm
communication with the first SCS-1 receiver. The panel retains this alarm receiver
key in memory and allows remote commands to be accepted from the alarm receiver.
If an alarm occurs during a remote connect, the alarm report is immediately sent to this
receiver only.
When NO is selected, remote commands and programming are not accepted from the
alarm SCS-1 receiver.
XR20 Programming Guide
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
Page 9
4-REMOTE OPTIONS
4.7
SVC RCVR
YES
SERVICE RECEIVER AUTHORIZATION - YES enables remote commands and
programming to be accepted from a secondary service receiver other than the alarm
SCS-1 Receiver. The Remote Key option can also be required.
With YES selected, the panel requests the service receiver key the first time it's
contacted by the service receiver. The panel retains this service receiver key in
memory and accepts remote commands from the service receiver.
If an alarm occurs during a remote connect, the panel disconnects from the service
receiver and calls the alarm receiver. Alarm reports are only sent to the alarm receiver.
It is important that the alarm receiver key and the service receiver key programmed
at the central station are NOT the same so the panel can determine the difference
between receivers.
When NO is selected remote commands and programming are not accepted from a
secondary service receiver.
4.8
DISARM
REMOTE DISARM - Enter YES to enable the panel to be disarmed remotely.
Selecting NO disables remote disarming.
NO
5-SYSTEM REPORTS
5.1
SYSTEM REPORTS
5.2
OPN/CLOS
5.3
ABORT
5.4
RESTORAL:
NO
YES
YES
SYSTEM REPORTS - This function allows you to select the reports the XR20 sends to
the receiver.
OPENING/CLOSING REPORTS - YES allows the panel to send opening/closing
reports by user to the receiver.
ABORT REPORT - YES allows the panel to send an alarm abort report to the receiver
any time an alarm report has also been sent and the Bell Cutoff time has not expired.
See Bell Cutoff section 7.2. The area must be disarmed and no alarmed zones can still
be armed. Yes also allows a Bell Silenced Report to be sent if the alarm bell is
silenced with a valid user code during an alarm. When the system is disarmed during
an alarm, only Abort and Opening Reports are sent.
NO
YES
D ISARM
ZONE RESTORAL REPORTS - This option allows you to specify whether the panel
sends zone restoral reports and also when they'll be sent.
NO - Restoral reports are not sent by the panel.
YES - The panel always sends zone restoral reports at the time the zone restores from
an alarm or trouble condition.
DISARM - The panel sends zone restoral reports when a zone that has restored from
an alarm or trouble is disarmed. Twenty-four hour zones send restorals immediately.
5.5
BYPASS
YES
5.6
CODE CHG NO
CODE CHANGE REPORTS - YES allows the panel to send all code additions,
changes, and deletions to the receiver. The code change report includes the user
number added or deleted and the user number of the individual making the change.
5.7
AMBUSH
AMBUSH - YES allows an ambush report to be sent anytime user code number one is
entered at a keypad. Selecting NO disables the ambush report and allows user code
number one to operate the same as all other codes.
NO
BYPASS REPORTS - YES allows the panel to send all zone bypass, reset, and force
arm reports to the receiver. The bypass report includes the zone number, zone name,
and the user number of the individual bypassing the zone.
XR20 Programming Guide
Page 10
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
6 -SYSTEM OPTIONS
6.1
SYSTEM OPTIONS
6.2
MODE: AREA SYS
AREA
A/P
SYSTEM OPTIONS - This section allows you to select system wide parameters used
in the operation of the XR20 system. A description of each System Option follows:
H/A
MODE - This configures the panel as either a four area system, an All/Perimeter
system (Perimeter/Interior), or a Home/Away system (Perimeter, Interior, and
Bedrooms). Zones must be assigned to Bedrooms for the area to be active.
6.3
CLS CODE NO
CLOSING CODE - When YES is selected, a code number is required for system
arming. If NO is selected, a code number is not required for system arming.
6.4
CLS CHK
CLOSING CHECK - Select YES to enable the panel to verify that all areas have been
armed after a schedule expires. If the Closing Check finds any areas disarmed past
the scheduled time, all keypads emit a steady beep and display CLOSING TIME!.
6.5
ENTRY DLY 1:
30
ENTRY DLY 2:
60
NO
ENTRY DELAY 1 - Enter the entry delay time for all exit type zones programmed to
use Entry Delay 1. When an armed Exit type zone is faulted, the keypad prewarn tone
begins sounding and ENTER CODE:- displays on all keypads.
The area must be disarmed before the delay expires or an alarm report is sent to the
receiver. All Burglary type zones in all areas are delayed along with the exit type zone.
Entry delay times can be from 1 to 250 seconds.
Repeat the above for Entry Delay 2 if it is being used.
6.6
EXIT DELAY:
45
EXIT DELAY - Enter the Exit Delay time for all Exit type zones. When the system is
armed, this Exit Delay time starts and all activity on Exit and Burglary zones is ignored
until the exit delay expires. The delay countdown shows on the keypad for the user.
If an exit zone is in a bad condition at the end of the exit delay:
• the alarm bell sounds for 15 seconds
• an Exit Error report is sent to the alarm receiver
• the bad exit zone is force armed
If any other zone is in a bad condition at the end of the Exit Delay, an alarm on that
zone is indicated. The Exit Delay time can be from 1 to 250 seconds. Enter zero to
disable the Exit Delay feature.
6.7
CRS ZONE TM:
0
CROSS ZONE TIME - Enter the time allowed between zone faults. When a zone
programmed for cross zoning faults, the panel begins counting down the Cross Zone
Time you enter here. If the same zone or another zone faults within this time, an alarm
report is sent to the receiver.
If the Cross Zone Time expires without the second zone fault, only a zone fault report
from the first zone is sent to the receiver. The Cross Zone Time can be from 4 to 250
seconds in one second increments.
Enter zero to disable the Cross Zone Time feature.
6.8
PWR FAIL HRS:
6.9
RST SBYP
6.10 PHON ACC
1
POWER FAIL DELAY - This option tracks the duration of an AC power failure. When
the AC power is off for the length of the programmed delay time, an AC power failure
report is sent to the receiver. The delay time can be from 1 to 9 hours. Entering a zero
sends the AC power failure report within 15 seconds.
YES
RESET SWINGER BYPASS - When YES is selected, a swinger bypassed zone is
reset if it remains in a normal condition for one hour after being bypassed. A report of
the automatic reset is sent to the receiver if Bypass Reports has been selected as
YES. See section 5.5.
NO
TELEPHONE ACCESS - YES allows the use of standard DTMF telephones to arm
and disarm and check the armed status of the XR20 panel. Refer to the XR20 User's
Guide (LT-0303) for complete information.
XR20 Programming Guide
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
Page 11
7 -OUTPUT OPTIONS
7.1
OUTPUT OPTIONS
OUTPUT OPTIONS - This function allows you to program the panel's Bell Output
functions and certain Output options. Switched Ground (open collector) outputs are
available using the 4-wire output harness on the XR20 board. Refer to the XR20
Installation Guide (LT-0229) for complete information.
A description of each output option follows:
7.2
BELL CUTOFF:
5
BELL CUTOFF TIME - Enter the maximum time the Bell Output remains on. If the Bell
Output is manually silenced or the system is disarmed, the cutoff time is reset. The
Bell Cutoff Time can be from 1 to 15 minutes.
Enter zero to provide continuous bell output.
7.3
BELL TST
NO
AUTOMATIC BELL TEST - When YES is selected, the Bell Output is turned on for
two seconds when all areas in the system are armed. In addition, the Closing Wait
feature is activated if Opening/Closing Reports is YES. See section 5.2.
Closing Wait operation
Closing Wait provides a delay time before a monitored system arms until the panel
receives an acknowledgment of the closing report from the central station receiver.
During the delay, the keypad displays DIALING . . .. Once the closing is
acknowledged, the keypad buzzes for one second and then displays the armed
message.
7.4
BELL ACTION . . . . .
BELL ACTION defines the type of Bell Output for zone alarms. Trouble conditions do
not activate the Bell Output. There are seven zone types you can program individually
for Bell Output.
To provide a steady Bell Output, enter S. For a pulsed output, enter P. For a Temporal
Code 3 output, enter T and for no Bell Output, enter N.
Below is a list of the bell action for seven of the zone types:
7.4A FIRE
TYPE: P
Defines Bell Action for Fire Type Zones. The default is set at P.
7.4B BURGLARY TYPE: S
Defines Bell Action for Burglary Type Zones. The default is set at S.
7.4C SUPRVSRY TYPE: N
Defines Bell Action for Supervisory Type Zones. The default is set at N.
7.4D PANIC
Defines Bell Action for Panic Type Zones. The default is set at N.
TYPE: N
7.4E EMERGNCY TYPE: N
Defines Bell Action for Emergency Type Zones. The default is set at N.
7.4F AUXLRY I TYPE: N
Defines Bell Action for Auxiliary 1 Type Zones. The default is set at N.
7.4G AUXLRY 2 TYPE: N
Defines Bell Action for Auxiliary 2 Type Zones. The default is set at N.
7.5
OUTPUT ACTION - This option allows you to define the operation of the four on board
annunciator outputs.
OUTPUT ACTION . . .
7.5A CO OUTS: - - - -
CUTOFF OUTPUTS - Any or all of the available outputs can be programmed here to
turn off after the time specified in OUTPUT CUTOFF TIME. See section 7.5B. To
disable this option, press any SELECT key to clear the display of output numbers and
then press COMMAND.
XR20 Programming Guide
Page 12
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
7-OUTPUT OPTIONS
7.5B
CUTOFF TIME:
0
OUTPUT CUTOFF TIME - If a Cutoff Output is assigned in section 7.5A, you can enter
a Cutoff Time of up to 15 minutes for the output to remain on. If the output is turned off
manually, the cutoff time is reset. The Cutoff Time can be from 1 to 15 minutes.
Enter zero to provide continuous output.
The Cutoff Timer is shared by all outputs. If a second output trips, the timer is not
reset. Both outputs turn off when the original time expires.
7.5C
COM FAIL OUT: 0
COMMUNICATION FAILURE OUTPUT - This output is turned on when the panel fails
to communicate with the receiver after three successive dial attempts. Enter zero to
disable this output.
7.5D
FIRE ALR
OUT: 0
FIRE ALARM OUTPUT - This output is turned on any time a fire type zone is placed in
alarm. The output is turned off using the Sensor Reset option while no additional fire
type zones are in alarm. Enter zero to disable this output.
7.5E
FIRE TRB
OUT: 0
FIRE TROUBLE OUTPUT - This output is turned on any time a fire type zone is
placed in trouble or when a supervisory type zone is placed in alarm or trouble. The
output is turned off when all fire and supervisory type zones are restored to normal.
Enter zero to disable this output.
7.5F
AMBUSH
OUT: 0
AMBUSH OUTPUT - This output is turned on any time an Ambush code is entered at
a keypad. The output is turned off using the Sensor Reset option. Enter zero to disable
this output.
7.5G
ENTRY
OUT:
0
ENTRY OUTPUT - This output is turned on at the start of the entry delay time. The
output is turned off when the area is disarmed or the entry delay time expires. Enter
zero to disable this output.
7.5H
EXIT
OUT:
0
EXIT OUTPUT - This output is turned on any time an exit delay time starts. The output
is turned off when the system arms or when the arming has been stopped. Enter zero
to disable this output.
7.5I
READY
OUT:
0
READY OUTPUT - This output is turned on whenever all disarmed zones are in a
normal state. The output is turned off when any disarmed zone is in a bad state. Enter
zero to disable this output.
7.5J
ARMED
OUT:
0
ARMED OUTPUT - This output is turned on any time an area of the system is armed.
The output is turned off when the system is completely disarmed. Enter zero to disable
this output.
7.5K
BURGLARY OUT:
0
BURGLARY OUTPUT - This output is turned on any time a burglary zone is placed in
alarm. The output is turned off when the area in which the alarm occurred is disarmed
and no other burglary zones are in alarm. Enter zero to disable this output.
7.5L
GND STRT OUT: 0
GROUND START OUTPUT - This output is turned on for 750ms any time the panel
seizes the telephone line. Enter zero to disable this output.
XR20 Programming Guide
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
Page 13
8-AREA INFORMATION
8.1
AREA INFORMATION
AREA INFORMATION - This section allows you to assign functions to individual
areas. All non-24 hour zones must be assigned to an active area. See Zone
Information in section 9.1.
You activate an area by assigning it a name. A name is given to each active area in
place of a number to assist the user during arming and disarming.
8.2
8.3
AREA NUMBER - Enter the number of the area you are programming. In an area
system, select from areas 1 to 4. In an All/Perimeter system, select INTerior or
PERIMeter. In a Home/Away system, select INTerior, PERIMeter, or BEDROOMS.
AREA NO: –
AREA NAME - In an area system, you can enter up to 16 characters for the area
name. Only those areas given names can have zones assigned to them. All others are
marked *UNUSED*. For instructions on entering alphanumeric characters. See section
1.7.
* UNUSED *
To add an area name to the system, press any SELECT key and then enter up to 16
characters for the new name. Press COMMAND to continue.
To mark an active area as unused, delete the old name by pressing a SELECT key
then press the COMMAND key. The panel automatically sets the name as *UNUSED*.
If you have already Initialized the panel, all areas will be marked as *UNUSED*. See
section 2.3.
8.4
AUTO ARM
NO
AUTOMATIC ARMING - Select YES to allow this area to arm automatically according
to the schedule.
If Closing Check is selected as YES, the automatic arming does not take place until
the expiration of a ten minute Closing Check delay. See section 6.3. If the area has
been disarmed outside a schedule, the Closing Check delay occurs one hour after the
area is disarmed.
At arming, bad zones are handled according to the option selected in section 8.5. If a
Closing report is sent, the user number is indicated as SCH on the SCS-1 Receiver.
Select NO to disable automatic arming for this area.
8.5
BAD ZONES: BYP
BYP
FORC
REF
BAD ZONES - At the time of automatic arming, some zones in the area may not be in
a normal condition. This option allows you to program the panel's response to these
bad zones. This option is not displayed if AUTO ARM is NO.
BYP - All bad zones are bypassed. A report of the bypass is sent to the receiver if
Bypass Reports has been selected as YES. See section 5.5. The report indicates SCH
as the user number.
FORC - All bad zones are force armed. Zones force armed in a bad condition are
capable of restoring into the system and reporting alarms if tripped. A report of the
force arm is sent if Bypass Reports is YES. See section 5.5. The report indicates the
user number as SCH.
REF - The automatic arming is refused and no arming takes place. A No Closing
report is sent to the receiver regardless of the Closing Check selection. See section
12.7.
8.6
AUTO DIS
NO
AUTOMATIC DISARMING - Select YES to allow this area to automatically disarm
according to a schedule. If an Opening report is sent, the user number is indicated as
SCH. Select NO to disable automatic disarming by schedule for this area.
XR20 Programming Guide
Page 14
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
9-ZONE INFORMATION
9.1
ZONE INFORMATION
ZONE INFORMATION - This allows you to define the operation of each protection
zone used in the system.
A description of each programming option follows:
9.2
9.3
ZONE NO:
ZONE NUMBER - Enter the number of the zone you intend to program. Press
COMMAND to enter a zone name. For instructions on entering alphanumeric
characters, see section 1.7.
–
* UNUSED *
ZONE NAME - Press the SELECT key and enter up to 16 characters for the zone
name. A name must be given to each zone in the system. This name can be displayed
at the keypads when the zone is bad or viewed in Display Events. The zone name is
also sent to the receiver as part of a zone event report.
A zone that is not part of the system must be marked *UNUSED*. To mark a zone
unused, delete the old name by pressing a top row SELECT key, then press the
COMMAND key. The programmer automatically programs the name as * UNUSED *.
If you selected ZONES? NO YES to clear the panel's memory during Initialization, the
zones will already be marked * UNUSED *. See section 2.3.
9.4
ZONE TYPE: BLANK
ZONE TYPE - The Zone Type defines the panel's response to the zone being opened
or shorted. See the chart in section 9.4A.
When you assign a Zone Type to a zone, responses are made automatically for the
zone. There are 11 Zone Types to choose from including Blank. The functional details
of each response are described in section 9.4A.
To enter a new Zone Type, press a top row SELECT key. The display lists the four
Zone Types shown below.
––
NT
DY
EX
Blank, Night, Day, or Exit. Press COMMAND to display additional zone types.
FI
PN
EM
SV
Fire, Panic, Emergency, or Supervisory. Press COMMAND to display additional zone
types.
A1
A2
FV
AR
Auxiliary 1, Auxiliary 2, Fire Verify, or Arming. Press the ARROW key to display the
previous zone types.
When the Zone Type you want to select is displayed, press the SELECT key beneath
its name. The chart in section 8.4A gives an outline of the Alarm Action for each Zone
Type.
If you select Blank, Night, Day, Exit, Auxiliary 1, or Auxiliary 2 as the Zone Type, the
zone must be assigned to an area.
If you select Fire, Panic, Emergency, or Supervisory as the Zone Type, these are 24
hour zones that are always armed and no area assignment is needed.
Press COMMAND to continue.
Refer to the Appendix section in this guide for zone type descriptions.
XR20 Programming Guide
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
Page 15
9-ZONE INFORMATION
9.4A
ZONE TYPE SPECIFICATIONS
Action
Message
Output
Action
Swinger
Bypass
S
P
M
F
A
L
T
-
1
to
4
S
P
M
F
A
L
T
-
1
to
4
S
P
M
F
A
L
T
-
1
to
4
S
P
M
F
N
or
Y
or
1 to 4
N
or
Y
N
or
Y
N
N
N
N
N
N
N
N
N
N
N
N
Abbr.
NIGHT
DAY
NT
DY
T
O
O
-
T
O
O
-
A
A
O
O
-
A
A
O
O
-
Y
Y
EXIT
FIRE
PANIC
EX
FI
PN
-
O
-
-
O
-
A
T
T
O
O
O
-
A
A
A
O
O
O
-
Y
N
N
A
O
EMERGENCY
1
or
2
Style
Output
1
to
4
Priority
Message
A
L
T
-
Cross Zone
Action
Armed
Short
INT
BDRM
PERIM
Assign Style for AR only
Zone Type Defaults
Armed
Open
Output
Assign Prewarn & Entry
Delay for EX only
NT
EX
PN
SV
A2
AR
Disarmed
Short
Message
-DY
FI
EM
A1
FV
Disarmed
Open
Action
Assign Area & Disarmed
condition for NT, DY, EX,
A1, A2, AR only
Area
Output
Type
Message
ZONE INFORMATION
Entry Delay
The XR20 panel contains 11 default zone types for use in configuring the system. These zone types
provide the most commonly selected functions for their applications. All zone types can be customized by
changing the variable options listed below.
EM
T O
– = This function is not enabled for this zone type.
= These zone functions are not available for this zone type.
1
N
TGL
ARM
DIS
STEP
MNT
Description of the programmable zone options
Below is a description of the various zone options shown on the table above. For additional information,
read through the Zone Information section of this manual.
Zone Type Defaults - These are complete spellings of the abbreviations used for the zone types.
Type - These are the abbreviations you'll see on the keypad for the zone types.
Area - For a ALL/PERIM or HOME/SLEEP/AWAY system, this is either Interior, Bedroom, or Perimeter.
For an AREA system, 1 to 4.
Message - A = alarm report, T = trouble report, L = local with no report, - (dash) = no report.
Output - This refers to the four XR20 relay outputs only.
Action - This selects the type of relay output: S = steady, P = pulse, M = momentary, and F = follow
Swinger Bypass - Allows the zone to be automatically shunted after three trips.
Entry Delay - Selects the entry delay timer used for this zone.
Cross Zone - Provides cross zoning for this zone.
Priority - Requires this zone to be in a normal condition before the area can be armed.
Style - These are the abbreviations you'll see on the keypad for arming zone style.
TGL = Toggle, ARM = Arm only, DIS = Disarm only, STEP = Wireless arming, MNT = Maintain
XR20 Programming Guide
Page 16
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
9-ZONE INFORMATION
9.5
AREA NO:
AREA NUMBER - If you're programming an area system, enter the area number
where this zone is being assigned.
–
AREA: PERIMETER
AREA ASSIGNMENT - For area systems, enter the area number. For All/Perimeter
systems, choose INTERIOR or PERIMETER. For Home/Away systems, choose
INTERIOR, PERIMETER, or BEDROOMS.
INT BDRM
INT (Interior) - Assigns the zone to area 2, Interior.
PERIM
BDRM (Bedroom)- Assigns the zone to area 3, Bedrooms. This option is only
displayed in Home/Away systems.
PERIM (Perimeter) - Assigns the zone to area 1, Perimeter.
9.6
AREA:
ARMING ZONE AREA NUMBER - This option specifies the areas to be armed by the
Arming Type zone. Press the appropriate number keys on the keypad to assign areas
1 to 4. When disarmed, all programmed areas are disarmed.
ARM AREA: PERIM
ARMING ZONE AREA ASSIGNMENT - For All/Perimeter systems, choose PERIM or
ALL. For Home/Away systems, choose HOME, SLEEP, or AWAY.
PERIM
PERIMETER/ALL - Specify whether the arming zone arms just the Perimeter (PERIM)
or the Perimeter and Interior areas (ALL) for All/Perimeter systems. When disarming,
all areas are disarmed.
ALL
HOME SLEEP AWAY
HOME/SLEEP/AWAY - Specify whether the arming zone arms the Perimeter
(HOME), the Perimeter and Interior (SLEEP), or all three areas (AWAY). When
disarming, all areas are disarmed.
Arming zone operation
If a bad (faulted) Priority zone is in the area being armed by an Arming zone, the
arming is stopped. If there are no Priority zones, or they are all in a normal condition,
the following applies:
When a non-Priority zone is bad when an area is armed with a keyswitch on an
Arming zone, the arming is delayed for five seconds. If, during the five second delay,
the keyswitch is turned to disarm, the arming stops. If the keyswitch is held in the
arming position for the full five seconds, the bad zone is force armed and the area is
armed.
The ability to stop the arming does not apply if a wireless arming device is being used.
See Appendix section 12.14.
XR20 Programming Guide
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
Page 17
9-ZONE INFORMATION
9.6A STYLE:
STYLE - This option specifies the style for the arming/disarming operation. The default
for STYLE: is TGL (toggle). Pressing any top row select key will display the STYLE
options. To view more style options press the command key. The following is a
description of the action for each option condition.
TGL ARM DIS STEP
MNT
TGL (Toggle) - When the zone changes from normal to shorted, the programmed
areas toggle between the armed or disarmed condition. When restored to normal, no
action occurs. When the zone is opened from a normal (disarmed) state, a trouble is
reported. When opened from a shorted (armed) state, an alarm is reported and the
zone is disabled until you disarm the area(s) from either a keypad or Remote
Access™ computer.
ARM - When the zone is shorted, the programmed areas are armed. When restored to
normal, no action occurs. When the zone is opened from a normal (disarmed) state, a
trouble is reported. When opened from a shorted (armed) state, an alarm is reported.
DIS (Disarm) - When programmed as an Area system, a short will disarm the
programmed areas. When programmed as a ALL/PERIM or HOME/AWAY system, a
short will disarm ALL areas. When restored to normal, no action occurs. When the
zone is opened from a normal (disarmed) state, a trouble is reported.
STEP - When programmed as an area system, a short will arm the areas and beep the
keypads once. When programmed as ALL/PERIM or HOME/AWAY, on the first short
HOME will arm and beep the keypad once. On the second short, SLEEP will arm and
beep the keypads twice. On the third short, AWAY will arm and beep the keypad three
times. A normal condition will cause no action. An open condition will disarm the
programmed areas and beep the keypads for one second.
Note: This arming style is designed for wireless arming pendants. When using a
arming/disarming keyswitch locate the keyswitch within the protected area.
`
MNT (Maintain) - When the zone is shorted, the programmed areas are armed. When
restored to normal, the programmed areas are disarmed and any alarm bells are
silenced. When the zone is opened from a normal (disarmed) state, a trouble is
reported. If opened from a shorted (armed) state, an alarm is reported and the zone is
disabled until you disarm the area(s) from either a keypad or Remote Access™
computer.
9.7
NEXT ZN? NO
YES
9.8
ALARM ACTION . . . .
NEXT ZONE - When YES is selected, the programming for the zone terminates and
the display returns to ZONE NO: - allowing you to enter a new zone number. To make
changes to the Alarm Action for a zone, answer the NEXT ZONE? prompt with NO.
The Alarm Action is then defined in sections 9.7 through 9.12.
ALARM ACTION - The Alarm Action section allows you to change or confirm the
default alarm characteristics of a zone type that was selected in section 9.4.
If you selected the non-24 hour zone type Blank, Night, Day, Exit, Auxiliary 1, or
Auxiliary 2, the Alarm Action programing begins with Disarmed Open.
If you selected the 24 hour zone type Fire, Panic, Emergency, or Supervisory, the
Alarm Action programming begins with Armed Open.
The Fire Verify zone type functions the same as Fire Type, with the following
exceptions: When a Fire Verify zone is placed into shorted condition, the panel
performs a Sensor Reset and does not send a report. If any Fire Verify or Fire zone
initiates an alarm within 120 seconds after the reset, an alarm is indicated. If an alarm
is initiated after 120 seconds, the cycle is repeated. If no other Fire Verify or Fire zone
is alarmed within 120 seconds, a zone fault report is sent to the receiver.
XR20 Programming Guide
Page 18
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
9-ZONE INFORMATION
9.9
DISARMED OPEN
DISARMED OPEN - Defines the action taken by the panel when the zone is opened
while the area is disarmed. There are three actions to define:
Message to Transmit
Output Number
Output Action
See sections 9.9A to 9.9C. You must also make these selections for the Disarmed
Short, Armed Open, and Armed Short zone conditions.
Press the COMMAND key to continue.
9.9A MSG: TROUBLE
A
T
L
MESSAGE TO TRANSMIT - You can send two report types to the receiver: Alarm
and Trouble. These are represented by the characters A and T. Press any top row
SELECT key to display the zone's report options.
-
ALARM - Selecting A, allows an alarm report to be sent to the receiver and the bell
output to activate according to zone type. See section 7.4, Bell Action. The zone name
appears in the panel's alarmed zones status lists.
TROUBLE - Selecting T allows a trouble report to be sent to the receiver and the zone
name to appear in the panel's alarmed zones status lists.
LOCAL - When you select L, an alarm report is NOT sent to the receiver. The bell
output still activates according to zone type and the zone name appears in the panel's
alarmed zones status lists. NOTE: If Pager is YES in Communication, the alarm report
is also sent to the designated pager.
– (dash) - When you select – , reports are NOT sent to the receiver. The bell output
does not activate and there is no display in the panel's alarmed zones status list. Only
the Output Number selected in section 9.9B activates.
9.9B OUTPUT NO: 0
OUTPUT NUMBER - You can specify any of the outputs on the XR20 to be activated
by a zone condition. The output can be activated regardless of the report to transmit
or whether or not the zone is programmed as local. An output activated by a non-24
hour armed zone is turned off when the zone's area is disarmed by a user.
To enter an Output Number, press a top row SELECT key followed by the output
number 1 to 4. Press the COMMAND key.
9.9C ACTION:
OUTPUT ACTION - Entering an Output Number in section 9.9B displays this prompt
that allows you to assign an output action to the relay.
A description of the available output actions is given below:
STD PLS MOM FOLW
STEADY - The output is turned on and remains on until the area is disarmed, an
output cutoff time expires, or the output is reset from the keypad User Menu.
PULSE - The output alternates one second on and one second off until the area is
disarmed, an output cutoff time expires, or the output is reset from the keypad User
Menu.
MOMENTARY - The output is turned on only once for one second.
FOLLOW - The output is turned on and remains on while the zone is in an off normal,
or bad condition. When the zone restores, the output is turned off.
After you've made the three selections in sections 9.9A through 9.9C, the display prompts you for the
same three selections for Disarmed Short, Armed Open, and Armed Short conditions. If the zone is a 24
hour type, only the Armed Open and Armed Short conditions are displayed. When you've programmed all
of the zone conditions, the Swinger Bypass selection is then displayed.
XR20 Programming Guide
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
Page 19
9-ZONE INFORMATION
9.10
SWGR BYP
YES
SWINGER BYPASS - YES allows the zone to be bypassed by the panel after four
alarm, trouble, or local trips within one to two hours. Selecting NO disables swinger
bypassing for this zone.
After the first trip, if the zone does not trip 3 more times before the remaining time
expires, the bypass trip counter returns to zero and the zone must trip a full 4 times
within the next hour to be automatically bypassed.
A report of a swinger bypass is sent to the receiver if Bypass Reports has been
enabled. See section 5.5.
Bypassed zones are automatically reset when the area they’re assigned to is
disarmed. All bypassed 24 hour zones are reset when the system is disarmed.
9.11
ENTRY DELAY: 1
ENTRY DELAY - Select the entry delay timer for this zone. Entry delay timers 1 and 2
are programmed in section 6.5.
9.12
CRS ZONE NO
CROSS ZONE - Select YES to enable cross zoning for this zone. Cross zoning
requires this zone to trip twice, or this zone and another cross zoned zone to trip,
within a programmed time before an alarm report is sent to the receiver.
When a cross zoned zone trips, the bell and Output action assigned to the zone
activates. See section 7.4. The cross zone time specified in System Options begins to
count down. See section 6.7. If another cross zoned zone in the system faults, or if the
first zone restores and faults again before the cross zone time expires, the panel
sends an alarm report.
If no other cross zoned zone in the system trips before the cross zone time expires,
the panel sends only a fault report from the first zone to the receiver.
Cross zoning is not compatible with Fire Verify zone types: You cannot enable cross zoning for Fire
Verify zones.
9.13
PRIORITY NO
PRIORITY - Selecting YES allows you to provide additional protection for a zone by
requiring it to be in a normal condition before its assigned area can be armed. A
priority zone cannot be bypassed.
A Priority zone not in a normal condition cannot be armed. If a user attempts to arm
the area, the keypad displays the bad zone name followed by PRIORITY ZONE and
the arming is stopped.
9.14
ZONE NO: –
ZONE NUMBER - Enter the zone number you want to program next. Return to section
9.1 and follow the descriptions of each programming prompt. If all zones are
programmed, press the ARROW key at the ZONE NO: – display to continue.
XR20 Programming Guide
Page 20
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
10-STOP
10.1
STOP
At the STOP prompt, pressing any SELECT key allows you to exit the programmer
function of the XR20 panel. When selected, the panel performs an internal reset and
exits the programmer.
The Stop function causes the following conditions to occur:
• The system is DISARMED
• The panel's Status List is CLEARED
During the Stop function, all keypad displays are momentarily blank for two seconds.
Afterwards, the programming function is terminated and the keypads return to the
Status List display.
11-SET LOCKOUT CODE
11.1
SET LOCKOUT CODE
SET LOCKOUT CODE - Pressing COMMAND at the Stop prompt displays SET
LOCKOUT CODE. This feature allows you to program a special code that will then be
required to gain access to the panel's internal Programmer through the keypad.
Changing the Lockout Code
You can change this code at any time to any combination of numbers from 1 to 5 digits
long (1 to 65535).
1. Press a SELECT key. The display changes to ENTER CODE: -.
2. Enter a 1 to 5 digit code (do not enter a number higher than 65535). Press
COMMAND.
3. Enter the new Lockout Code again. Press COMMAND. The keypad display
changes to CODE CHANGED.
Once you have changed the code, it is important that you write it down somewhere
and store it in a safe place. Lost lockout codes require the panel to be sent back into
DMP for repair.
XR20 Programming Guide
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
Page 21
12-APPENDIX
12.1
Appendix
This section of the XR20 Programming Guide provides additional zone and system information.
12.2
Status List
The Status List is the current status of the system or records of recent system events that are displayed
on the alphanumeric keypads. For example, in Home/Away systems, you might see the display SYSTEM
READY. This would be the current status of the system.
If an event were to occur on the system, such as an AC failure, the keypad would also display the AC
POWER -TRBL message. This is a system event that is placed into the Status List to alert the user to a
problem with the system.
Some Status List items remain in the display until manually cleared and some are cleared automatically
when the condition returns to normal. Below is a complete list of status and event displays the keypad
can show in the Status List:
Description
Must be manually cleared?
Fire and Supervisory zone alarms
Yes - by Sensor Reset
Fire and Supervisory zone troubles
No - clears when zone restores
Burglary zone alarms
No - clears after 8 minutes or at disarming.
All other zone alarms
No - clears when zone restores
Zone monitor displays
No - clears after 8 minutes
Day zone alerts
No - clears after 8 minutes
System monitor troubles
(AC and battery trouble)
No - clears when condition restores
Armed status display
(System On)
No
Disarmed status displays
(System Ready, System Not Ready)
No
Remote keypad messages
(Sent to the keypad by your office or
central station)
No
Each item in the list is displayed for four seconds. When there are multiple items in the list, you can use
the COMMAND or ARROW keys to scroll forward or back through the items.
12.3
False Alarm Reduction Features
System Recently Armed report
The System Recently Armed report (S78) is sent when a burglary zone is placed into alarm within five
minutes of the system being armed.
12.4
4-2 reporting operation
When using the 4-2 reporting format, the panel follows this sequence to report to the receiver.
1. The panel dials the receiver phone number and waits for a response.
2. If the panel detects it is communicating with a 4-2 compatible receiver, all reports except those
that can only be sent in SDLC are sent to the receiver.
3. If the panel detects it is communicating with a DMP SCS-1 Receiver, all reports are then sent in
SDLC format.
4. If the panel last communicated to a 4-2 compatible receiver, a SDLC event cannot initiate a call to
the receiver.
5. If the panel last communicated to a DMP SCS-1 Receiver, any reporting event can initiate a call to
the receiver.
XR20 Programming Guide
Page 22
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
12-APPENDIX
12.5
Zone type descriptions
This section describes applications for the default zone types in Zone Information programming.
NT (Night Zone) - Controlled instant zone used for perimeter doors and windows and interior devices
such as PIRs and Glassbreak detectors.
DY (Day zone) - Used for emergency doors or fire doors to sound the keypad buzzer and display the
zone name when the zone is faulted. Day zones also will send alarm reports to the receiver during the
system's armed periods.
EX (Exit zone) - Initiates the entry delay timer when its assigned area is fully armed. Also, can initiate an
exit delay timer to allow a user to exit an area after the arming process has started.
PN (Panic zone) - Used for connecting to mechanical devices that allow a user to signal an emergency
alarm. Panic zones can provide either a silent or audible alarm with or without reporting to a central
station receiver.
EM (Emergency zone) - These are used for reporting medical or other non-panic emergencies to the
central station receiver.
SV (Supervisory zone) - Used to provide 24-hour zone supervision to devices associated with fire
systems. Typical applications are tamper switches on Post Indicator Valves (PIVs), gate valves, and low
and high temperature gauges.
FI (Fire zone) - Used for any type of powered or mechanical fire detection device. Typical applications are
for smoke detectors, sprinkler flow switches, manual pull stations, and beam detectors. Cross zoning is
compatible with the Fire zone type.
FV (Fire Verify zone) - Used primarily for smoke detector circuits to verify the existence of an actual fire
condition. When a Fire Verify zone initiates an alarm, the panel performs a Fire Reset. If any Fire zone
initiates an alarm within 120 seconds after the reset, an alarm is indicated. If an alarm is initiated after 120
seconds, the cycle is repeated.
A1 and A2 (Auxiliary 1 and Auxiliary 2) - These zones are similar to a Night zone and are typically used to
protect restricted areas within a protected premises. Auxiliary 2 zones do not appear in the Status List.
AR (Arming zone) - This zone allows you to connect a keyswitch to a zone and use it to arm and disarm
the system.
12.6
Manual telephone line seizure
This feature allows you to connect with a remote receiver either by having the panel pick up the phone
line while the receiver is ringing the line or by entering a phone number for the panel to dial. This feature
is primarily used when bringing a new account on-line as it allows your office or the central station to
connect to the panel and upload a custom program.
How it works
While the panel is in the Status List, press the numbers 984 and then the COMMAND key. The keypad
display changes to NBR PICKUP.
NBR
Press the SELECT key under NBR to enter a phone number for the panel to dial. Press each number key
slowly and deliberately. The panel dials each number as it is pressed. If you make an mistake, press the
ARROW key. The panel will stop dialing and return to the NBR PICKUP display.
You can enter up to 15 characters for the phone number. To enter a # (pound sign) or * (asterisk) press
the 0 (zero) key and third SELECT key (pound) or the fourth SELECT key (asterisk).
The panel makes ten attempts to reach the receiver. If while attempting to contact the receiver, the panel
needs to send an alarm report, the dialing attempts are stopped and the panel can use the phone line to
send its report.
PICKUP
The panel immediately seizes the phone line and sends a carrier tone to the receiver.
XR20 Programming Guide
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
Page 23
12-APPENDIX
12.7
Default panel programming
This program sheets shows the XR20 panel's default program settings.
PROGRAMMING INFORMATION
For Series XR20 COMMAND PROCESSOR Panels
Name
Account Number
Address
COMMUNICATION
Communication Type
Account Number
Transmission Delay
DTMF
Events Manager
Test Frequency
Test Time
NONE DD
4-2
M2E CID
1 2 3 4 5 (1 to 65,535)
_ 0 (0 to 60 in 10 sec. increments)
NO
YES
SND
DLY
KEEP
_ 0 (0 to 60 days)
_ _ : _ _ AM PM
Receiver 1
Alarm
Supv/Trouble
O/C & User
Test Report
Backup
First Phone Number
Second Phone Number
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Receiver 2
Pager
Alarm
Supv/Trouble
O/C & User
Test Report
Backup
First Phone Number
Second Phone Number
Pager ID Number
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _
REMOTE OPTIONS
Remote Key _ _ _ _ _ _ _ _
Manufacturer Authorization
Armed Rings
Disarmed Rings
Alarm Receiver
Service Receiver
Disarm
NO
_ _
_ _
NO
NO
NO
YES
(0 to 15)
(0 to 15)
YES
YES
YES
SYSTEM REPORTS
Opening/Closing Reports
Abort Reports
Zone Restoral Reports
Bypass Reports
Code Change Reports
Ambush
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
SYSTEM OPTIONS
Mode
Closing Code
Closing Check
Entry Delay 1
Entry Delay 2
Exit Delay
Cross Zone Time
Power Fail Delay
Reset Swinger Bypass
Phone Access
Phone
City
AREA
NO
NO
_ 3 0
_ 6 0
_ 4 5
_ _ 0
1
NO
NO
DISARM
A/P
H/A
YES
YES
(0 to 250 secs.)
(0 to 250 secs.)
(0 to 250 secs.)
(0 to 250 secs.)
(0 to 9 hrs.)
YES
YES
Date
State
OUTPUT OPTIONS
Bell Cutoff Time
Automatic Bell Test
Bell Action . . . . .
Fire Zones
Burglary Zones
Supervisory Zones
Panic Zones
Emergency Zones
Auxiliary 1 Zones
Auxiliary 2 Zones
Output Action . . .
Cutoff Outputs
Cutoff Time
Communication Fail Output
Fire Alarm Output
Fire Trouble Output
Ambush Output
Entry Output
Exit Output
Ready Output
Armed Output
Burglary Output
Ground Start Output
AREA INFORMATION
Area Number
Area Name
Auto Arming
Bad zones
Auto Disarm
Zip
_ 5
NO
(0 to 15 mins.)
YES
Steady
Steady
Steady
Steady
Steady
Steady
Steady
1
_
0
0
0
0
0
0
0
0
0
0
Pulse
Pulse
Pulse
Pulse
Pulse
Pulse
Pulse
None
None
None
None
None
None
None
2 3 4
0 (0 to 15 mins.)
(0 to 4)
(0 to 4)
(0 to 4)
(0 to 4)
(0 to 4)
(0 to 4)
(0 to 4)
(0 to 4)
(0 to 4)
(0 to 4)
_ (1 to 4)
__________________
NO YES
BYP FORC REF
NO
YES
Area Number
Area Name
Auto Arming
Bad zones
Auto Disarm
_ (1 to 4)
__________________
NO YES
BYP FORC REF
NO
YES
Area Number
Area Name
Auto Arming
Bad zones
Auto Disarm
_
(1 to 4)
__________________
NO YES
BYP FORC REF
NO
YES
Area Number
Area Name
Auto Arming
Bad zones
Auto Disarm
_
(1 to 4)
__________________
NO YES
BYP FORC REF
NO
YES
LT-0302
Figure A1: XR20 Factory Default Program
XR20 Programming Guide
Page 24
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
12-APPENDIX
12.8
4-2 Reporting to Central Station Receivers
This section of the XR20 programming guide is intended to explain to installers, service technicians, and
central station personnel how the DMP 4-2 communication format operates and which hexadecimal
characters are sent for each system event.
12.9
4-2 Communication Reports
The table below contains a complete list of the hexadecimal characters sent using the DMP 4-2
communication format.
1st
Digit
1st Digit Description
2nd Digit
2nd Digit Description
1
Fire Alarm
1 to A, B, D
Zones 1 to 10, 670-A Fire Buttons, and Zones Greater than 10
2
Panic Alarm
1 to A, B, D
Zones 1 to 10, Ambush, and Zones Greater than 10
3
Burglary Alarm
1 to A, B, D
Zones 1 to 10, 670-A Police Buttons, and Zones Greater than 10
4
Emergency Alarm
1 to A, B, D
Zones 1 to 10, 670-A Emergency Buttons, and Zones Greater than 10
5
Supervisory Alarm
1 to A, D
Zones 1 to 10, and Zones Greater than 10
6
Aux 1, Aux 2, or Blank Type Alarms
1 to A, D
Zones 1 to 10, and Zones Greater than 10
7
System Report
1
Automatic Recall
7
System Report
2
Non-Alarm Overflow
7
System Report
3
Zone Alarm Overflow
7
System Report
4
System Test
7
System Report
5
Unsuccessful Remote Connect
7
System Report
6
System Recently Armed
7
System Report
7
Exit Error
7
System Report
8
Remote Programming Complete
7
System Report
9
Local Programming
7
System Report
A
Transmit Fail
7
System Report
B
System Not Armed by Scheduled Time
8
User Code Addition
1 to C, D
Users 1 to 12, 0, and User Numbers Greater than 12
8
User Code Deletion
1 to C, D
Users 1 to 12, 0, and User Numbers Greater than 12
8
User Code Change
1 to C, D
Users 1 to 12, 0, and User Numbers Greater than 12
9
not implemented
A
Zone Bypass or Force Arm
1 to A, D
Zones 1 to 10 and Zones Greater than 10
B
Disarming
1 to C, D, F
Users 1 to 12, 0, and User Numbers Greater than 12
C
Arming
1 to C, D, F
Users 1 to 12, 0, and User Numbers Greater than 12
D
Abort Received
E
Any Zone Restoral/Reset or System Restoral
1 to A, B, C, D Zones 1 to 10, Battery, AC, and Zones Greater than 12
F
Zone Trouble, Fault, Transmitter Low Battery
or Missing, or System Trouble
1 to A, B, C, D Zones 1 to 10, Battery, AC, and Zones Greater than 12
1
None
XR20 Programming Guide
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
Page 25
12-APPENDIX
12.10
How to Read this Table
The first column on the left is the first digit of the 2-digit event code sent to the receiver. The second
column is what that character represents.
The third column from the left is the second digit of the 2-digit event code sent to the receiver. The fourth
column (on the right) is what that character represents. See below:
1st
Digit
1st Digit Description
2nd Digit Description
1
Fire Alarm
1 to A, B
Zones 1 to 10 and 670-A Fire Buttons
2
Panic Alarm
1 to A, B
Zones 1 to 10 and Ambush
3
Burglary Alarm
1 to A, B
Zones 1 to 10 and 670-A Police Buttons
1st digit of event
code sent to receiver
12.11
2nd Digit
Describes the event
2nd digit of event
code sent to receiver
Defines the user number, zone
number, or other information about
the event.
4-2 Examples
The following examples are the actual event codes a central station would receive. The full report would
also include the account number and checksum.
When the central station receives this event code
12.12
It means
1A
A Fire alarm is being reported on zone 10
2B
An Ambush alarm is being reported
FB
A battery trouble is being reported
F9
A Trouble is being reported on zone nine
4-2 Communication Format Configuration
The DMP 4-2 format communicates to the central station as 4-2 with a checksum at 40 pulses per second
(pps). The XR20 panel using 4-2 communication will accept either a 1400Hz or 2300Hz acknowledgment
tone (handshake) from the receiver.
A report format sent to the receiver is defined as follows:
1234
aaaa
12.13
56
fs
7
c
a = account number
f = first digit
s = second digit
c = checksum
Numeric Pager Message Formats
The following example shows individual page display components:
Pager Display - 00128–20010
00128 = account number
2 = Message ID
0 = Always zero
010 = Zone or area number
Message ID Descriptions
1 = Zone Alarm
2 = Zone Trouble
3 = Areas Arming
4 = Areas Disarming
6 = User Check-in
The examples below show a typical display for each of the pager report options:
Zone Alarm
Zone Trouble
Areas Arming
Areas Disarming
User Check-in
00128–10003
00128–20010
00128–30123
00128–40123
00128–60008
Communication Attempts
Only one pager signal is sent to the pager terminal equipment at a time. For each pager message to be
sent, the panel dials the first phone number and follows the steps detailed in the sections 3.18 and 3.19.
XR20 Programming Guide
Page 26
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
12-APPENDIX
12.14
FA426 Wireless Operation
The FA426 is a 900MHz wireless receiver that installs in the enclosure of the XR20 Command Processor
and allows you to add up to 16 wireless expansion zones to the panel. A wire harness included with the
FA426 plugs into the receiver and connects to the keypad bus terminals on the panel.
Wireless points 2 through 16 are suitable for use with supervised wireless transmitters on doors or
windows as well as wireless smoke detectors, glassbreak detectors, and PIRs. A no response from these
points after four hours is indicated by the panel as a Missing.
Point 1 is unsupervised and designated for use with the FA113 Keychain Remote. The FA113 allows the
user to arm and disarm one or more areas of the system without using a keypad. The FA113 also
contains two ALERT buttons that allow the user to initiate a Panic alarm to the system. The unsupervised
feature of point 1 allows the FA113 to be removed from the premises without a Missing report being
generated. You can use any number of FA113 Keychain Remote devices on point 1 to allow for multiple
users.
The FA426 can communicate wireless Alarm, Trouble, Missing, and Low Battery reports to the XR20
panel. The Alarm report is received as a short condition by the panel. The Trouble report is received as
an open condition by the panel. Zone information programming in the XR20 panel must be configured for
these conditions. Missing and Low Battery reports require no special programming.
Low Battery note: If a Low Battery condition on a transmitter is corrected by replacing the battery, a
Sensor Reset must be performed on the XR20 system to clear the Low Battery message from the keypad
Status List.
FA426 connection to panel: If the connection between the FA426 and the panel is broken, zones
monitored by the FA426 will report an open condition.
12.15
FA113 User's Guide
FA113 User's Guide
These instructions guide you through the operation of the XR20 Command Processor system using the FA113 Wireless Keychain
Remote. The FA113 uses the audible output capability of the Security Command keypad to sound confirmation tones. It is
recommended that you use the FA113 within hearing distance of these keypads.
Arming a Home/Away or All/Perimeter System
1. Press the ON button once to arm the Perimeter burglary protection. The Security Command keypads emit a single beep to
confirm the arming. The Perimeter arms and all non-priority zones not in a normal condition are force armed.
2. After the single beep, press the ON button a second time to arm the Interior burglary protection. The Security Command keypads
emit two beeps to confirm the arming.
3. After the two beeps, pressing the ON button in Home/Sleep/Away systems arms the Bedrooms burglary protection. The Security
Command keypads emit three beeps to confirm the arming.
Disarming a Home/Away or All/Perimeter System
1. Press the OFF button once. The Security Command keypads emit a single 2-second beep to confirm the disarming.
Arming an Area System
1. Press the ON button once to arm the following areas:
1. ___________________
2. ___________________
3. ___________________
4. ___________________
The Security Command keypads emit a single beep to confirm the arming.
Disarming an Area System
1. Press the OFF button once to disarm the above areas. The keypads emit a single beep to confirm the disarming.
Using the ALERT Buttons
Pressing the two ALERT buttons simultaneously sends a Panic alarm to the panel. If your system is monitored by a central station,
the proper authorities will be notified of the alarm.
Cut along the dashed lines
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
Page 27
XR20 Programming Guide
NOTES:
Digital Monitoring Products
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement