Siemens SIRIUS Modular System

Siemens SIRIUS Modular System
SIRIUS Modular System
Highly flexible system-based switching, protecting and starting
siemens.com/sirius
Answers for industry.
Contents
Everything for the electrical cabinet:
SIRIUS Modular System.
SIRIUS Modular System Components
Switching and Protection Device Combinations
Comfortable Power Infeed and Distribution
Electromechanical Switching Devices for the Fuseless
Assembly of Load Feeders up to 7.5 kW
Size S00 Selection and Ordering Data:
Master control room
Press Shop
Final Assembly
Body Shop
Power
distribution
Paint Shop
Pressing, equipping, transporting.
These functions run in many automated
production environments. You’ll find
everything that you need to switch, protect
and start motors with the extensive portfolio
of the modular SIRIUS system.
Everything. Easy. SIRIUS
4
8
9
Powertrain/
Assembly
Circuit Breaker, Contactor with Overload Relay
Circuit Breaker, Contactor with Current Monitoring Relay
10
10
Circuit Breaker, Soft Starter with Current Monitoring Relay
Circuit Breaker, Solid-State Switching Device
with Current Monitoring Relay
13
13
Electromechanical Switching Devices for the Fuseless
Assembly of Load Feeders up to 18.5 kW
Size S0 Selection and Ordering Data:
16
Circuit Breaker, Contactor, Overload Relay
Circuit Breaker, Contactor with Current Monitoring Relay
17
17
Circuit Breaker, Soft Starter with Current Monitoring Relay
18
Assembly of Direct-On-Line and Reversing Starters up to 22 kW
Size S2 Selection and Ordering Data
20
Assembly of Direct-On-Line and Reversing Starters up to 45 kW
Size S3 Selection and Ordering Data
22
Size S6, S10 and S12
Selection and Ordering Data
24
Fuseless Load Feeders
Selection and Ordering Data:
Direct-On-Line Starters
(Completely Pre-Assembled Load Feeders, Compact Starters)
Reversing Starters
(Completely Pre-Assembled Load Feeders, Compact Starters)
Communication Connection
(IO-Link / AS-Interface masters, contactors, function modules
for Mounting on 3RT2 Contactors and for Connection to the Control,
Compact Starters)
Infeed Systems
For Compact Starters, Load Feeders,
3-Phase Busbars, 8US Busbar Adapters
26
27
28
31
Accessories
Selection and Ordering Data:
Circuit Breakers
Contactors
Overload Relays, Current Monitoring Relays
34
36
40
Service & Support
42
Everything. System-based.
SIRIUS Modular System.
The permanent advancement and continuous
innovation of SIRIUS optimally prepare our customers for current and future requirements and
provide them with efficient solutions. All components of the SIRIUS modular system are characterized by their space-saving design and high
degree of flexibility. Configuration, installation,
wiring and maintenance can be realized easily and
in minimum time. No matter whether you want
to assemble load feeders with circuit breakers or
overload relays, contactors / solid-state contactors,
reversing contactors or soft starters – SIRIUS offers
the suitable product for every application.
How to realize fast, easy, flexible and space-saving control cabinet assembly? With the unique
SIRIUS modular system, which offers everything required for the switching, protection and
starting of motors and systems. It comprises a modular range of standard components up to
250 kW / 400 V in only seven optimally matched sizes which can be easily combined and utilize
largely identical accessories. Switching technology made easy!
Thanks to the latest innovations of sizes S00 and
S0 up to 40 A, the new SIRIUS modular system now
offers even more functional diversity:
Circuit breakers
In addition to the innovated basic components
(such as contactors, circuit breakers and overload
relays), the innovated SIRIUS modular system offers
unprecedented highlights:
SENTRON 3VL
• Feeder combinations which can be completely
plug-connected without tools thanks to consistently implemented spring-loaded connection
system
• 2- and 3-phase 3RR2 current monitoring relays
for direct mounting on contactors
• 3RA27 and 3RA28 function modules which can
be plugged onto contactors for the easy assembly of direct-on-line, reversing and star-delta
starters and for connection to the control via
AS-Interface or IO-Link with minimized wiring
Contactors
Overload relays
Soft starters
S00
S0
S2
S3
S6
S10
S12
3
4
Overview of the Numerous Advantages
Offered by the SIRIUS Modular System.
With its manifold components, the SIRIUS modular system covers various functions
for control cabinet applications and offers numerous advantages in terms of
assembly and handling, application monitoring, connection to the control as well
as planning and configuration.
Assembly and handling:
Application control:
Connection to the control:
Planning and configuration:
• Load feeders: Easy realization
with standard devices up to
250 kW / 400 V
• Maintenance: Extremely long service
life, low maintenance and reliability
• Communication: Standardized
connection to AS-Interface, IO-Link
and PROFIBUS DP possible
• Configuration: Easy and fast thanks
to comprehensive CAx data provision
Reduced wiring expenditures and fault
avoidance – with maximum flexibility
• Modular system: All components
are matched and can be combined
• Versions and sizes: Efficiency and
flexibility with 7 compact sizes
• Accessories:
Minimum variance with integrated
accessories
Improved operational reliability and
system availability
• Application monitoring: Flexibly
integrated in the feeder thanks to
current monitoring relay
Optimum integration in the
automation environment
Eased system planning and
documentation
• Service: Short delivery periods also
for spare parts thanks to worldwide
logistics network
• Environment: Environmentally
compatible production and materials,
recyclability
• Design: Clear and ergonomic, awarded
with the iF Product Design Award
• Assembly: Fast commissioning, short
setup times, easy wiring
• Configurator: For easy product
selection, incl. accessories
• Mounting: Permanently safe
mounting with screw-type or easy
plug-in connection system
• Global applicability: Thanks to
comprehensive approvals
• Spring-loaded connection system:
Fast and safe connection, vibrationproof and with zero maintenance
• Reduced wiring: Considerably
reduced number of line connections
thanks to plug-in connection system
and IO-Link or AS-Interface
Switching. Protecting. Starting.
The components of the SIRIUS Modular System.
Far more than ON/OFF:
SIRIUS 3RV circuit breakers
Rugged and reliable:
SIRIUS 3RT contactors
SIRIUS 3RV circuit breakers (MSP)
are compact, current-limiting
circuit breakers. They guarantee
safe reliable shutdown when
short circuits occur and protect loads and plants against
overload. Furthermore, they
are suitable for operationally
switching load feeders with a
low operating frequency and
safely disconnecting the plant
or system from the line supply
when service is been carried
out or changes are being made.
SENTRON 3VL circuit breakers are
suitable for applications above
100 A. As infeed and load feeder
breaker, they protect plants and
motors against short circuit and
overload.
Due to their extremely high ruggedness and optimum contact
reliability, our contactors switch
with supreme confidence.
Furthermore, compact electrical cabinets can be configured
with high packing densities. The
reason for this is that the auxiliary switch blocks and solenoid
protective circuitry are located
within the envelope contours
of the contactors. This makes it
easier to expand the system and
saves considerable space in the
electrical cabinet. With size S00
and S0 contactors, the auxiliary
switches are already integrated in the enclosure.
Tripping when things get
tough: SIRIUS 3RU and 3RB
overload relays
Easy application monitoring:
SIRIUS 3RR2 current monitoring
relays
The overload relays of the
SIRIUS family, available as either
thermal or solid-state versions,
protect loads connected to the
main circuit, as a function of the
current, and also protect other
switching and protective devices
in the particular load feeder. The
solid-state SIRIUS 3RB2 overload
relays guarantee seamless motor
and plant protection from 0.1 A
to 630 A. Due to the wide setting ranges, the current range is
covered with a minimum number
of versions.
The SIRIUS current monitoring
relays not only monitor the
motor, but the entire system or
driven process for overcurrent
and undercurrent, cable breakage and phase failure.
For example, load shedding or
overload of an application is
promptly detected and signaled
at an early stage. Sizes S00 and
S0 of the 3RR2 current monitoring relay are directly integrated
in the load feeder. They simply
have to be plugged onto the
contactor: Click ’n’ go.
Gentle starting:
SIRIUS 3RW soft starters
SIRIUS 3RW soft starters offer a
seamless range that covers all
standard and high-feature motor
starting applications. They can be
used in the widest range of applications to exploit the advantages
of soft starting for the easy and
efficient realization of optimum
machine concepts. The compact
two-phase-controlled 3RW30
facilitates efficient and spacesaving soft starting up to 55 kW
(with 400 V). The 3RW40 additionally offers soft stopping as
well as integrated intrinsic device
and motor protection functions,
thanks to which an additional
overload relay is unnecessary.
Device versions up to a rating of
55 kW (with 400 V) are available:
Thermistor motor protection
evaluation, 400–600 V.
5
6
Switching. Protecting. Starting.
The components of the SIRIUS Modular System.
SIRIUS contactor
screw connection
Competent control of high
switching frequencies: SIRIUS 3RF
solid-state contactors
Compact switching and protection
with comprehensive additional
functions: 3RA6 compact starters
SIRIUS solid-state contactors (size S0)
for motor switching offer an
almost unlimited service life – even
under harsh conditions and with
high switching frequencies. The
three-phase solid-state contactors
switch motors up to 7.5 kW in an absolutely noise-free manner. A special
reversing contactor version facilitates direction of rotation changes
of motors up to 3 kW. The compact
devices in 45 or 90 mm width can be
combined with our circuit breakers,
current monitoring relays or solidstate overload relays. This supports
the fast and easy assembly of fuseless and fused motor feeders.
Equipped with the functions of a
circuit breaker, a contactor and a
solid-state overload relay, the compact starter offers maximum reliability
and minimum variance as direct-online or reversing starter up to 32 A.
Safe disconnection upon the starter‘s
end of service life offers an additional
advantage in terms of system availability. Reduced wiring in the main circuit
thanks to the brilliantly simple infeed
system, incl. PE connection, and in
the control circuit thanks to optional
AS-Interface connection or integrated
IO-Link interface supports the rapid
assembly of complete feeder groups.
The devices‘ incorporation in the
Totally Integrated Automation concept and pre-defined icon blocks for
visualization facilitate the output of
significant device diagnostics without
the normally required configuration
expenditures.
SIRIUS contactor
spring-loaded connection
SIRIUS contactor
ring cable lug connection
Fast, reliable and user-friendly: spring-loaded technology
For the first time, the entire S00/S0 range is available with spring-loaded
connection system both in the main and control circuit. This accelerates device connection and offers maximum operational reliability. The outstanding
ease of wiring ensures rapid mounting. The gas-tight clamp connection‘s
vibration resistance represents a further advantage. In addition, this connection system offers maximum contact reliability – even under the harshest
­of conditions. The frequently required re-tightening of connection terminals
is thus done away with.
A special bonus: Also the connecting modules for direct-on-line, reversing
and star-delta starters are available with spring-loaded connection system to
support the mounting of complete feeders without tools.
Maximum connection flexibility
Of course, all components of the SIRIUS modular system are also available
with the screw-type connection system – largely even with ring cable lug –
for special requirements, e.g. mechanical engineering applications in the
semiconductor industry.
Switching. Protecting. Starting.
The components of the SIRIUS Modular System.
Straight ahead:
The 3RA11 direct starter
Ready for immediate use:
Pre-wired SIRIUS load feeders
Load feeders start loads using a combination
of protective and switching functions. Generally, a multiple number of components is
required to implement every type of starter.
In order to reduce time and costs – and especially to minimize downtimes – we offer you
a wide range of pre-wired starter solutions:
Phases interchanged:
The 3RA12 reversing starter
Two stages – one start:
The 3RA14 star-delta
combination
• Direct starters up to 22 kW – the optimum starter
combination for all motors. For high switching frequencies
with solid-state contactors up to 7.5 kW.
• Reversing starters up to 11 kW – the matching
combination for reversing motors. Solid-state reversing
contactors can be used for applications with high
switching frequencies up to 3 kW.
• Wye-delta* combinations up to 75 kW – the solution for
running-up motors in stages.
• Soft starters – when soft starting and stopping is required
(soft ramp-down as of 3RW40).
An almost unlimited number of further tested combinations
can be easily assembled from the individual components.
The SIRIUS Configuration manual offers selection support:
Available under order number 3ZX1012-0RA21-1AC0 or for
download via www.siemens.com/industrial-controls/support
7
Combination of switching and protective devices
Electromechanical
controls
Fuse with contactor
and overload relay
For details, see:*
Motor starter protector
for motor protection
and contactor
8
Motor starter protector Starter motor starter
for motor protection
protector, contactor
with overload relay
and overload relay
function and contactor
See p. 12, 17, 26
See p. 11, 17
Compact Starter
Motor starter protector
for motor protection,
contactor and current
monitoring relay
See p. 26, 27, 30
See p. 12, 17
Motor starter protector for
motor protection with
overload relay function,
contactor and current
Short circuit
Switching
Overload /
Monitoring
M
M
M
M
Fuse-protected
M
I
I
M
M
Non-fused
Electronic
controls
Motor starter protector
for motor protection,
soft starter and current
monitoring relay
Starter motor starter
protector, soft starter
and current
monitoring relay
For details, see:*
See p. 14, 19
See p. 19
Fuse and soft starter
Fuse and solid-state
switching device
Fuse, solid-state
switching device and
current monitoring
relay
Motor starter protector
for motor protection
and solid-state
switching device
Motor starter protector for
motor protection, solid-state
switching device and current
monitoring device
See p. 15
See p. 15
Short circuit
Switching
Overload /
Monitoring
M
M
Non-fused
* Fur further details and solutions not listed here, refer to the IC10 catalog
M
M
Fuse-protected
M
M
M
Non-fused
Comfortable Power Infeed and Distribution:
SIRIUS 3RV29 and 3RA68 Infeed Systems.
Efficient and flexible power
distribution
The components of the SIRIUS modular system offer maximum wiring
flexibility. They can be connected
easily via the corresponding SIRIUS
3RV29 infeed system or the 3RA68
infeed system in conjunction with
the compact starter. Both systems
are respectively available for devices
with screw-type and spring-loaded
connection system. For connection,
individual circuit breakers, complete
load feeders or compact starters are
simply clicked into the respective
infeed system. Doing away
with laborious wiring and fault risks,
a complete feeder group is thus
supplied with power: Click ’n’ go!
Design highlights
Alternatively, also conventional
wiring is supported:
Via parallel wiring, 3-phase busbar or
the 8US busbar adapter with which
the SIRIUS load feeders can be directly
mounted on a 60 mm busbar system.
These manifold combination options
facilitate the effortless realization
of your individual control cabinet
solution – perfectly matched to your
application.
• Outstanding flexibility for assembly and expansions
• Reduced space requirements in the control cabinet thanks
to very compact design
• Infeed optionally from the left or right with conductor
cross sections of up to 70 mm2
• Optional wiring duct between the feeders
• Additional integration of further 1-, 2- or 3-pole components
via terminal block
• Maximum current carrying capacity of 100 A
• Integration of load feeders with screw-type and spring-loaded
connection system
• High vibration resistance, particularly with switching devices
featuring the spring-loaded connection system
• Time savings in terms of mounting thanks to easy plug-in
connection system
• Also PE connection option with the 3RA68 infeed
9
Design up to 7.5 kW (S00)
,
Starter combinations of motor starter protector and contactor
with overload relay
Type
Screw connection
Spring-loaded connection
Type
Screw connection
Spring-loaded connection
3RA1921-1DA00
3RA2911-2AA00
Motor starter protector*
3RA1921-1DA00
10
Starter combinations of motor starter protector and
contactor with optional current monitoring relay
Motor starter protector*
Link module
Non-fused, electromechanical switching design
3RA2911-2AA00
Link module
Contactor (AC / DC)*
Contactor (AC / DC)*
Overload relay*
Overload relay*
* For order numbers of basic components see tabular overview on page 11
* For order numbers of basic components see tabular overview on page 12
Starter combinations: motor starter
protector, contactor with overload relay
M
Motor starter protector for starter protection
Contactor
Three-phase
motor
400 V/AC-3
Setting range of Order no.
thermal overload
release
CLASS 10
Auxiliary Order no.
contacts
[kW]
[A]
[A]
0.04
0.16
–
0.06
0.2
–
0.06
0.25
–
0.09
0.32
–
0.09
0.4
–
0.12
0.5
–
0.18
0.63
–
0.18
0.8
–
0.25
1
–
0.37
1.25
–
0.55
1.6
–
0.75
2
–
0.75
2.5
–
1.1
3.2
–
1.5
4
–
1.5
5
–
2.2
6.3
–
3
8
–
4
10
–
–
5.5
12.5
–
–
7.5
16
–
–
1)
Direct mounting on contactor, screw and
spring-loaded connection possible
Overload relay 1)
Order no.
Control supply voltage
DC 24 V
AC 230 V, 50/60 Hz
Setting
range
CLASS 10
Order no.
Thermal
Order no.
Electronic
CLASS 10
[A]
3RV2311-0DC 0
0.11 – 0.16 3RU2116-0A 0
0.14 – 0.2 3RU2116-0B 0
0.18 – 0.25 3RU2116-0C 0
0.22 – 0.32 3RU2116-0D 0
3RV2311-0FC 0
0.35 – 0.5
3RV2311-0AC 0
3RV2311-0BC 0
3RV2311-0CC 0
0.28 – 0.4
3RV2311-0EC 0
3RV2311-0GC 0
3RV2311-0HC 0
3RV2311-0JC
0
3RV2311-0KC 0
3RV2311-1AC 0
1NC
1NO
3RV2311-1BC 0
3RT2015- BB42
3RT2015- BB41
3RT2015- AP02
3RT2015- AP01
1.1 – 1.6
1.4 – 2
3RV2311-1CC 0
1.8 – 2.5
3RV2311-1EC 0
2.8 – 4
3RV2311-1GC 0
4.5 – 6.3
3RV2311-1DC 0
2.2 – 3.2
3RV2311-1FC 0
3.5 – 5
3RV2311-1HC 0
5.5 – 8
0
1NC
3RV2311-1KC 0
1NC
3RV2311-4AC 0
1NC
3RV2311-1JC
Screw connection: 1
Spring-loaded
connection: 2
1NO
1NO
1NO
3RU2116-1A 0
3RU2116-1B 0
3RU2116-1C 0
3RU2116-1D 0
3RU2116-1F 0
3RU2116-1G 0
3RU2116-1H 0
7 – 10
3RU2116-1J
3RT2017- BB42
3RT2017- AP02
9 – 12.5
3RU2116-1K 0
3RT2018- AP02
11 – 16
3RU2116-4A 0
3RT2017- BB41
3RT2018- BB42
3RT2018- BB41
Screw connection: 1
Spring-loaded
connection: 2
Ring cable lug
4
connection:
3RT2017- AP01
3RT2018- AP01
3RB3016-1P
(1 – 4 A)
0
3RB3016-1S
(3 – 12 A)
0
3RB3016-1T
(4 – 16 A)
0
3RU2116-1E 0
3RT2016- AP02
3RT2016- AP01
3RB3016-1N 0
(0.32 – 1.25 A)
3RU2116-0K 0
3RT2016- BB42
3RT2016- BB41
0
3RU2116-0E 0
3RU2116-0F 0
0.45 – 0.63 3RU2116-0G 0
0.55 – 0.8 3RU2116-0H 0
0.7 – 1
3RU2116-0J 0
0.9 – 1.25
3RB3016-1R
(0.1 – 0.4 A)
Screw connection: B
Spring-loaded
connection: C
Ring cable lug
connection: J
0
Screw connection: B
Spring-loaded
connection: E
11
Starter combinations:
motor starter protector,
contactor with optional current
monitoring relay
Three-phase
motor
400 V/AC-3
[kW]
I
M
[A]
Motor starter protector for motor protection
Contactor
Setting range
of thermal
overload
release
CLASS 10
Auxiliary Order no.
contacts
0.04
0.16
0.11 – 0.16
0.2
0.14 – 0.2
0.06
0.25
0.18 – 0.25
0.09
0.32
0.22 – 0.32
0.09
0.4
0.28 – 0.4
0.12
0.5
0.35 – 0.5
0.18
0.63
0.45 – 0.63
0.18
0.8
0.55 – 0.8
0.25
1
0.7 – 1
0.37
1.25
0.9 – 1.25
0.55
1.6
1.1 – 1.6
0.75
2
1.4 – 2
0.75
2.5
1.8 – 2.5
1.1
3.2
2.2 – 3.2
1.5
4
2.8 – 4
1.5
5
3.5 – 5
2.2
6.3
4.5 – 6.3
3
8
5.5 – 8
4
10
7 – 10
7.5
12.5
16
9 – 12.5
11 – 16
DC 24 V
Size S0
Size S2
Measurement
range
AC 230 V, 50/60 Hz
Order no.
Basic (analog
setting)
Order no.
Standard
(digital setting)
3RR2141- A 30
3RR2241- F 30
[A]
3RV2011-0AA 0
3RV2011-0BA 0
3RV2011-0CA 0
3RV2011-0DA 0
3RV2011-0EA 0
3RV2011-0FA 0
3RV2011-0GA 0
3RV2011-0HA 0
3RV2011-0JA
0
3RV2011-0KA 0
3RV2011-1AA 0
1NC
1NO
3RT2015- BB42 3RT2015- AP02
3RT2015- BB41 3RT2015- AP01
3RV2011-1BA 0
3RV2011-1CA 0
3RV2011-1DA 0
3RV2011-1EA 0
3RV2011-1FA 0
1.6 – 16
3RV2011-1GA 0
3RV2011-1HA 0
3RV2011-1JA
0
3RV2011-1KA 0
3RV2011-4AA 0
Screw connection: 1
Spring-loaded
connection: 2
Ring cable lug
connection: 4
Size S00
Order no.
Control supply voltage
[A]
0.06
5.5
Order no.
Current monitoring relay
Size S3
1NC
1NO
1NC
1NO
1NC
1NO
3RT2016- BB42 3RT2016- AP02
3RT2016- BB41 3RT2016- AP01
3RT2017- BB42 3RT2017- AP02
3RT2017- BB41 3RT2017- AP01
3RT2018- BB42 3RT2018- AP02
3RT2018- BB41 3RT2018- AP01
Screw connection: 1
Spring-loaded
connection: 2
Ring cable lug
connection: 4
Size S6, S10, S12
Screw connection: 1
Spring-loaded
connection: 2
AC/DC 24 V: A
AC/DC 24 –240 V: W
Fuseless Load Feeders
Communication
Feeder Combinations
Infeed System
12
Accessories
Design up to 7.5 kW (S00)
Non-fused, electronic switching design
Starter combinations:
motor starter protector, soft starter with optional
current monitoring relay (for stand-alone mounting)
Starter combinations:
motor starter protector, solid-state switching
device with optional current monitoring relay
Type
Screw
connection
Spring-loaded
connection
Type
Motor starter
protector *
Link module
Motor starter
protector *
3RA2921-1BA00
3RA2911-2GA00
Link module
3RU2916-3AA01
3RA2921-1BA00
Solid-state
contactor /
solid-state
reversing
contactor *
Soft starter *
Adapter for
stand-alone
assembly
Screw
connection
3RU2916-3AC01
Current
monitoring
relay *1)
Adapter for
stand-alone
assembly
* For order numbers of basic components see tabular
overview on page 14
Current
monitoring
relay *1)
3RU2916-3AA01
* For order numbers of basic components see tabular
overview on page 15
1) An adapter for stand-alone assembly is required for the
application of a 3RR2 current monitoring relay on a 3RW30/40
soft starter. The current monitoring relay must not be active
during the start-up and ramp-down phase (phase control).
For 3RW30: The 3RR2 monitoring relay is to be enabled via an
upstream timing relay after soft start-up completion.
For 3RW40: The 3RR2 monitoring relay is to be enabled/disabled
via the BYPASS output (start-up detection).
An adapter for stand-alone assembly is required for the
application of a 3RR2*41 current monitoring relay of size S00.
1) 13
14
Starter combinations: motor
starter protector, soft starter
with optional current monitoring
relay (for stand-alone mounting)
Motor starter protector
Soft starter 1)
Current monitoring relay
Three-phase
motor
400 V/AC-3
Setting range
of thermal
overload
release
CLASS 10
Rated
Order no.
Order no.
operating
current
Control supply voltage
Measurement
range
[kW]
[A]
[A]
AC/DC 24 V
[A]
3.6
3RW3013-
BB04
3RW3013-
BB14
3RV2011-1FA^ 0
6.5
3RW3014-
BB04
3RW3014-
BB14
3RV2011-1HA^ 0
9
3RW3016-
BB04
3RW3016-
BB14
0.04
0.06
0.06
0.09
0.09
0.12
0.18
0.18
0.25
0.32
0.4
0.5
0.63
0.8
0.11 – 0.16
3RV2011-0BA^ 0
0.22 – 0.32
3RV2011-0DA^ 0
0.35 – 0.5
3RV2011-0FA^ 0
0.55 – 0.8
3RV2011-0HA^ 0
0.18 – 0.25
0.28 – 0.4
0.45 – 0.63
3RV2011-0GA^ 0
0.55
1.6
1.1 – 1.6
3RV2011-1AA^ 0
1.8 – 2.5
3RV2011-1CA^ 0
2.8 – 4
3RV2011-1EA^ 0
3RV2011-1GA^ 0
0.75
1.1
1.5
1.5
2
2.5
3.2
4
5
1.4 – 2
2.2 – 3.2
3.5 – 5
2.2
6.3
4.5 – 6.3
3
8
5.5 – 8
4
5.5
7.5
Rated operating voltage 200 ... 480 V
10
12.5
16
7 – 10
9 – 12.5
11 – 16
3RR2141-
3RR2241- F 30
3RV2011-0EA^ 0
3RV2011-0JA^
0.9 – 1.25
Order no.
Standard (digital
setting)
3RV2011-0CA^ 0
0.7 – 1
1.25
AC/DC 110 – 230 V
Order no.
Basic (analog
setting)
3RV2011-0AA^ 0
0.14 – 0.2
1
0.75
1)
0.16
0.2
0.25
0.37
M
[A]
Order no.
0
3RV2011-0KA^ 0
3RV2011-1BA^ 0
3RV2011-1DA^ 0
3RV2011-1JA^
0
3RV2011-1KA^ 0
3RV2011-4AA^ 0
Screw connection: 1
Spring-loaded
connection: 2
Ring cable lug
connection: 4
12.5
17.6
3RW3017-
3RW3018-
BB04
BB04
Screw connection: 1
Spring-loaded
connection: 2
3RW3017-
3RW3018-
1.6 – 16
A 30
BB14
BB14
Screw connection: 1
Spring-loaded
connection: 2
AC/DC 24 V: A
AC/DC 24 –240 V: W
Starter combinations: motor
starter protector, soft starter
with optional current monitoring
relay (for stand-alone mounting)
Three-phase
motor
400 V/AC-3
[kW]
M
[A]
2)
Solid-state contactor 2)
Setting range
of thermal
overload
release
CLASS 10
Rated
operating
current
Order no.
[A]
DC 24 V
Order no.
[A]
0.04
0.16
0.11 – 0.16
0.06
0.2
0.14 – 0.2
0.06
0.25
0.18 – 0.25
0.09
0.32
0.22 – 0.32
0.09
0.4
0.28 – 0.4
0.12
0.5
0.35 – 0.5
0.18
0.63
0.45 – 0.63
0.18
0.8
0.55 – 0.8
0.25
1
0.7 – 1
0.37
1.25
0.9 – 1.25
0.55
1.6
1.1 – 1.6
0.75
2
1.4 – 2
0.75
2.5
1.8 – 2.5
1.1
3.2
2.2 – 3.2
1.5
4
2.8 – 4
1.5
5
3.5 – 5
2.2
6.3
4.5 – 6.3
Current monitoring relay Order no.
Control supply voltage
AC 110 – 230 V, 50/60 Hz
Measurement
range
Order no.
Basic (analog
setting)
Order no.
Standard (digital
setting)
1.6 – 16
3RR2141- A 30
3RR2241- F 30
4 – 16
3RR2142- A 303) 3RR2242- F 303)
[A]
3RV2011-0AA^ 0
3RV2011-0BA^ 0
3RV2011-0CA^ 0
3RV2011-0DA^ 0
3RV2011-0EA^ 0
3RV2011-0FA^ 0
3RV2011-0GA^ 0
3RV2011-0HA^ 0
3RV2011-0JA^
0
5.2
3RF3405- BB04
3RF3405- BB24
3RV2011-0KA^ 0
3RV2011-1AA^ 0
3RV2011-1BA^ 0
3RV2011-1CA^ 0
3RV2011-1DA^ 0
3RV2011-1EA^ 0
3
8
5.5 – 8
4
10
7 – 10
5.5
12.5
9 – 12.5
7.5
16
11 – 16
Overall width 90 mm
Rated operating voltage Ue 48 ... 480 V
3)
Can be directly mounted on solid-state contactor
with screw connection
1)
Motor starter protector
3RV2011-1FA^ 0
3RV2011-1GA^ 0
3RV2011-1HA^ 0
3RV2011-1JA^
0
3RV2011-1KA^ 0
3RV2011-4AA^ 0
9.2
12.5
16
Screw connection: 1
Spring-loaded connection: 2
Ring cable lug connection: 4
3RF3410- BB041)
3RF3410- BB241)
3RF3412- BB041)
3RF3412- BB241)
3RF3416- BB041)
3RF3416- BB241)
Screw connection: 1
Spring-loaded
connection: 2
Solid-state reversing contactor 2)
3.8
5.4
7.4
3RF3403-1BD04
3RF3405-1BD04
3RF3410-1BD041)
3RF3403-1BD24
3RF3405-1BD24
3RF3410-1BD241)
Screw connection: 1
Spring-loaded
connection: 2
AC/DC 24 V: A
AC/DC 24 –240 V: W
15
Size S00
Size S0
Size S2
Size S3
Size S6, S10, S12
Fuseless Load Feeders
Communication
Feeder Combinations
Infeed System
Accessories
Design up to 18.5 kW (S0)
Non-fused, electromechanical switching design
Starter combinations:
motor starter protector,
contactor and overload
relay
Starter combinations:
motor starter protector, contactor with
optional current monitoring relay
1
1
2
2
3
3
4
4
Type
Screw connection
1
Motor starter protector *
2
Link module AC
DC
3
4
Spring-loaded connection
Type
1
Motor starter protector *
2
Link module1)AC
DC
Contactor *
3
Contactor *
Overload relay *
4
Current monitoring relay *
1)
3RA2921-1AA00
3RA2921-1BA00
3RA2921-2AA00
3RA2921-2AA00
* For order numbers of basic components see tabular overview on page 17
1)
Only suitable up to 32 A
Screw connection
Spring-loaded connection
3RA2921-1AA00
3RA2921-1BA00
3RA2921-2AA00
3RA2921-2AA00
* For order numbers of basic components see tabular overview on page 17
1)
Only suitable up to 32 A
16
Starter combinations:
motor starter protector,
contactor and overload relay
M
Motor starter protector for
starter protection
Contactor
Three-phase
motor
400V/AC-3
Order no.
[kW]
[A]
Thermal
overload
release
Aux.
contacts
7.5
16
–
3RV2321-4AC 0
7.5
20
–
3RV2321-4BC 0
11
22
–
3RV2321-4CC 0
11
25
–
3RV2321-4DC 0
15
28
–
3RV2321-4NC 0
15
32
–
3RV2321-4EC 0
18.5
36
–
3RV2321-4PC10
18.5
40
–
3RV2321-4FC10
I
M
2)
4)
Size S00
Size S0
AC 230 V
1NO+1NC 3RT2027- BB40 3RT2027- AP00 3RT2027- N 30 1NO+1NC 3RT2028- BB40 3RT2028- AP00 3RT2028- N 30
Three-phase
motor
400V/AC-3
Order no.
[kW]
[A]
Thermal
overload
release
Aux.
contacts
7.5
16
11 – 16
3RV2021-4AA 0
7.5
20
14 – 20
3RV2021-4BA 0
11
22
17 – 22
3RV2021-4CA 0
11
25
20 – 25
3RV2021-4DA 0
15
28
23 – 28
3RV2021-4NA 0
15
32
27– 32
3RV2021-4EA 0
18.5
36
30 – 36
3RV2021-4PA10
18.5
40
34 – 40
3RV2021-4FA10
UC (AC 50/60 Hz/DC)
1NO+1NC 3RT2026- BB40 3RT2026- AP00 3RT2026- N 30 Contactor
[A]
Order no.
Control supply voltage
DC 24 V
Motor starter protector f. motor protection
Size S2
Order no.
Screw connection: 1
Spring-loaded
connection: 2
Ring cable lug
connection 4): 4
Screw connection: 1
Spring-loaded
connection 2): 2
Ring cable lug connection 2): 4
Max. 32 A
Voltages on request
Order no.
1NO+1NC 3RT2025- BB40 3RT2025- AP00 3RT2025- N 30
Screw connection: 1
Spring-loaded connection 2): 2
Starter combinations:
motor starter protector,
contactor with optional
current monitoring relay
Overload relay
Setting Order no.
range
Thermal
CLASS 10
[A]
11 – 16
3RU2126-4A 0
14 – 20
3RU2126-4B 0
17 – 22
3RU2126-4C 0
20 – 25
3RU2126-4D 0
23 – 28
3RU2126-4N 0
27 – 32
3RU2126-4E 0
30 – 36
3RU2126-4P 0
34 – 40
3RU2126-4F 0
UC 21 – 28 V: B
UC 95 – 130 V: F
UC 200 – 280 V: P
Setting Order no.
range
Electronic
CLASS 10
[A]
6 – 25
3RB3026 -1Q 0
10 – 40
3RB3026- 1V 0
Screw connection: B
Spring-loaded
connection: C
Ring cable lug
connection: J
Screw connection: B
Spring-loaded
connection: E
Current monitoring relay
Order no.
Order no.
Order no.
Control supply voltage
DC 24 V
AC 230 V
UC (AC 50/60 Hz/DC)
Measurement
range
Order no.
Basic
(analog setting)
Order no.
Standard
(digital setting)
4 – 40
3RR2142- A 30
3RR2242- F 30
[A]
1NO+1NC 3RT2025- BB40 3RT2025- AP00 3RT2025- N 30
1NO+1NC 3RT2026- BB40
3RT2026- AP00
1NO+1NC 3RT2027- BB40
3RT2027- AP00 3RT2027- N 30
3RT2026- N 30
1NO+1NC 3RT2028- BB40 3RT2028- AP00 3RT2028- N 30
Screw connection: 1
Spring-loaded
connection: 2
Ring cable lug connection 4): 4
Size S3
Size S6, S10, S12
UC 21 – 28 V: B
UC 95 – 130 V: F
UC 200 – 280 V: P
Screw connection: 1
Spring-loaded connection: 2
AC/DC 24 V: A
AC/DC 24 – 240 V: W
Fuseless Load Feeders
Communication
Feeder Combinations
Infeed System
17
Accessories
Design up to 18.5 kW (S0)
Non-fused, electronic switching design
Starter combinations:
motor starter protector, 3RW30 soft starter with optional current monitoring relay
(for stand-alone mounting)
Starter combinations:
motor starter protector, 3RW40 soft starter (integrated electronic overload relay)
with optional current monitoring relay (for stand-alone mounting)
Type
1
1
Motor starter
protector *
2
Link module1)
3
Soft starter *
4
Adapter for
stand-alone
assembly
5
Current
monitoring
relay *2)
2
Screw
connection
3RA2921-1BA00
3RU2926-3AA01
Spring-loaded
connection
3RA2921-2GA00
Type
1
3RU2916-3AC01
2
2
Link module1)
3
Soft starter *
4
Adapter for
stand-alone
assembly
5
Current
monitoring
relay *2)
Spring-loaded
connection
3RA2921-1BA00
3RA2921-2GA00
3RU2926-3AA01
3RU2916-3AC01
3
4
5
Motor starter
protector *
Screw
connection
* For order numbers of basic components see tabular
overview on page 19
* For order numbers of basic components see tabular
overview on page 19
3
1
18
4
1) Only suitable up to 32 A
2) An adapter for stand-alone assembly is required for the
application of a 3RR2 current monitoring relay on a 3RW30/40 soft
starter. The current monitoring relay must not be active during the
start-up and ramp-down phase (phase control).
For 3RW30: The 3RR2 monitoring relay is to be enabled via an
upstream timing relay after soft start-up completion.
For 3RW40: The 3RR2 monitoring relay is to be enabled/disabled
via the BYPASS output (start-up detection).
5
1) Only suitable up to 32 A
2) An adapter for stand-alone assembly is required for the
application of a 3RR2 current monitoring relay on a 3RW30/40 soft
starter. The current monitoring relay must not be active during the
start-up and ramp-down phase (phase control).
For 3RW30: The 3RR2 monitoring relay is to be enabled via an
upstream timing relay after soft start-up completion.
For 3RW40: The 3RR2 monitoring relay is to be enabled/disabled
via the BYPASS output (start-up detection).
Starter combinations: motor
starter protector,
3RW30 soft starter with optional current
monitoring relay (for stand-alone mounting:
see combination options on page 18)
Three-phase
motor
400 V/AC-3
Soft starter 1)
Setting range,
thermal
overload
release
CLASS 10
Rated
Order no.
operating
current
[kW]
[A]
[A]
11
22
17 – 22
11
25
20 – 25
15
28
23 – 28
15
32
27 – 32
18.5
M
Motor starter protector for motor protection
18.5
18.5
36
40
40
Order no.
Measurement
range
[A]
AC/DC 24 V
AC/DC 110 – 230 V
3RV2021-4CA 0
25
3RW3026- BB04
3RW3026- BB14
3RV2021-4NA 0
32
3RW3027- BB04
3RW3027- BB14
38 3RW3028- BB04
3RW3028- BB14
45
3RW3036- BB04
3RW3036- BB14
3RV2021-4EA 0
3RV2021-4PA10
3RV2021-4FA10
3RV2021-4FA10
34 – 40
34 – 40
Order no.
Order no.
Basic
(analog setting)
Order no.
Standard
(digital setting)
Control supply voltage
3RV2021-4DA 0
30 – 36
Current monitoring relay
[A]
4 – 40
3RR2142- A 30 3RR2242- F 30
Starter combinations: motor starter protector,
3RW40 soft starter (integrated electronic
overload relay) with optional current monitoring
relay (for stand-alone mounting: see combination
options on page 18)
Three-phase
motor
400 V/AC-3
Setting range
of thermal
overload
release
CLASS 10
Rated
Order no.
operating
current
[A]
[A]
5.5
12.5
–
7.5
16
20
–
–
3RV2321-4AC 0
3RV2321-4BC 0
3RV2321-4CC 0
15
28
–
15
32
3RV2321-4NC 0
18.5
18.5
Size S0
3RV2311-1KC 0
–
25
–
3RV2321-4DC 0
3RV2321-4EC 0
3RV2321-4PC10
3RV2321-4FC10
36
40
Screw connection: 1
Spring-loaded
connection: 2
up to 32 A
Size S2
Current monitoring relay
Order no.
Measurement
range
Order no.
Basic
(analog setting)
Order no.
Standard
(digital setting)
Control supply voltage
22
Operating voltage 200 – 480 V
Size S00
Order no.
11
11
1)
Soft starter 1)
[kW]
7.5
M
Motor starter protector for starter protection
Size S3
[A]
AC/DC 24 V
AC/DC 110 – 230 V
12.5
3RW4024- BB04
3RW4024- BB14
25
3RW4026- BB04
3RW4026- BB14
32
3RW4027- BB04
3RW4027- BB14
38
3RW4028- BB02
Screw connection: 1
Spring-loaded
connection: 2
Size S6, S10, S12
[A]
4 – 40
3RR2142- A 30 3RR2242- F 30
–
Screw connection: 1
Spring-loaded connection: 2
AC/DC 24 V: A
AC/DC 24 – 240 V: W
Fuseless Load Feeders
Communication
Feeder Combinations
Infeed System
19
Accessories
Design S2 up to 22 kW
Direct start
20
4
Hutschienenadapter
3RA19 32-1AA00
Leistungsschalter
Baugröße
1
S2
Reversing
start
6
1
40 mm: 3RA19 33-1C
60 mm: 3RA19 33-1D
comprising:
8
5
Verbindungs2
baustein
für AC:
3RA19 31-1AA00
für DC:
3RA19 31-1BA00
Assembly kit
for busbar mounting
7
9
4
5
1 wiring kit
6
1 busbar adapter
7
1 controlgear support
9
1 side module
8
2
3
Assembly kit
for rail mounting
5
3
Schütz
Baugröße
S2
2 link wedges
2
3RA19 33-1B
comprising:
1 wiring kit
1 rail adapter
5
8
2 side modules
4 link wedges
Type
1
Size S2 circuit breaker
2
Link module
3
Size S2 contactors
Version
AC
DC
3RA19 31-1AA00
3RA19 31-1BA00
For busbar mounting (alternative)
Busbar adapter
40 mm
60 mm
8US10 61-5FP08
8US12 61-5FP08
For rail mounting (diagram)
4
Rail adapter
Type
Order no.
3RA19 32-1AA00
1
Size S2 circuit breaker
2
2 Size S2 contactors
3
Mechanical interlock
4
Link module
5
Wiring kit:
upper link module,
lower link module
Version
Order no.
3RA19 24-2B
AC
DC
3RA19 31-1AA00
3RA19 31-1BA00
For busbar mounting (diagram)
6
Controlgear support
40 mm
60 mm
8US10 60-5AP00
8US12 60-5AP00
7
Busbar adapter
40 mm
60 mm
8US10 61-5FP08
8US12 61-5FP08
8
Link wedges (1 Order no. = 100 wedges)
8US19 98-1AA00
9
Side module
8US19 98-2MB00
For rail mounting (alternative)
Rail adapter
3RA19 32-1AA00
Link wedges (1 Order no. = 100 wedges)
8US19 98-1AA00
S2 selection and ordering data
Circuit breakers (MSP)
Contactor
Threephase
motor
400 V/AC-3
Setting Order no.
range
CLASS 10
Aux.
contacts
[kW]
[A]
[A]
15
29
22 – 32
18.5
22
22
35
41
41
Control supply
voltage
Soft starters 1)
Order no.
Control
supply
voltage
Overload relays
Rated
operating
current
Order no.
Ie [A]
28 – 40
36 – 45
40 – 50
3RV1031-4EA10
3RV1031-4FA10
3RV1031-4GA10
3RV1031-4HA10
–
AC 230 V, 50/60 Hz 3RT1034-1AL20
–
DC 24 V
–
–
–
–
3RT1034-1BB40
AC 230 V, 50/60 Hz 3RT1035-1AL20
DC 24 V
3RT1035-1BB40
AC 230 V, 50/60 Hz 3RT1036-1AL20
DC 24 V
3RT1036-1BB40
AC/DC 110–230 V
45
3RW3036-1BB14
45
3RW3036-1BB04
AC/DC 24 V
AC/DC 110–230 V
45
3RW4036-1BB14
45
3RW4036-1BB04
AC/DC 24 V
Setting
Order no.
range
Thermal
CLASS 10
Setting
range
[A]
[A]
22 – 32
3RU1136-4EB0
28 – 40
3RU1136-4FB0
36 – 45
3RU1136-4GB0
40 – 50
Order no.
Electronic2)
CLASS 10
12.5 – 50 3RB2 3 - UB0
3RU1136-4HB0
CLASS 10 0
CLASS 20 0
CLASS 5...30* 1
6
6
3
1
2
4
* With ground-fault detection
(activatable) and electrical
remote reset
Operating voltage 200 – 480 V
1) For using tripping CLASS 20, please refer to the information contained in the
“SIRIUS Engineering – Fuseless Load Feeders” configuration brochure and in the
catalog
2) 21
Size S00
Size S0
Size S2
Size S3
Size S6, S10, S12
Fuseless Load Feeders
Communication
Feeder Combinations
Infeed System
Accessories
Design S3 up to 45 kW
22
Direct start
Reversing start
5
4
6 7
1
Assembly kit
for rail mounting
5
3RA19 43-1B
comprising:
1
7
4
2
7
8
6
2
8
1 wiring kit
5
2 rail adapters
6
3 side modules
7
6 link wedges
7
2
3
3
8
Type
1
Size S3 circuit breaker
2
Link module
3
Size S3 contactor
4
Rail adapter
Version
AC
DC
Type
Order no.
3RA19 41-1AA00
3RA19 41-1BA00
3RA19 42-1A
1
Size S3 circuit breaker
2
2 Size S3 contactors
3
Mechanical interlock
Version
Order no.
AC
DC
3RA19 41-1AA00
3RA19 41-1BA00
3RA19 24-2B
4
Link module
5
Rail adapter
6
Side modules for rail adapters
(1 Order no. = 10 adapters)
3RA19 02-1B
7
Link wedges (1 Order no. = 100 wedges)
8US19 98-1AA00
8
Wiring kit:
upper link module,
lower link module
3RA19 43-2A
S3 selection and ordering data
Threephase
motor
400 V/AC-3
Circuit breakers (MSP)
Contactor
Setting Order no.
range
CLASS 10
Aux.
contacts
Control supply
voltage
–
AC 230 V, 50/60 Hz 3RT1044-1AL20
–
DC 24 V
[kW]
[A]
[A]
30
55
42 – 63
37
45
45
1)
2)
67
80
80
57 – 75
70 – 90
3RV1041-4JA10
3RV1041-4KA10
3RV1041-4LA10
80 – 100 3RV1041-4MA10
–
–
–
–
Soft starters1)
Order no.
3RT1044-1BB40
AC 230 V, 50/60 Hz 3RT1045-1AL20
DC 24 V
3RT1045-1BB40
AC 230 V, 50/60 Hz 3RT1046-1AL20
DC 24 V
3RT1046-1BB40
Control
supply
voltage
Overload relays
Rated
Order no.
operating
current
Setting
Order no.
range
Thermal
CLASS 10
Setting
range
Ie [A]
[A]
[A]
AC/DC 110–230 V
80
3RW3046-1BB14
80
3RW3046-1BB04
AC/DC 24 V
AC/DC 110–230 V
80
3RW4046-1BB14
80
3RW4046-1BB04
AC/DC 24 V
45 – 63
3RU1146-4JB0
57 – 75
3RU1146-4KB0
70 – 90
3RU1146-4LB0
80 – 100
25 – 100
3RU1146-4MB0
Order no.
Electronic2)
CLASS 10
3RB2 4 - EB0
CLASS 10 0 61
CLASS 20 0 62
CLASS 5...30* 1 34
* With ground-fault detection
(activatable) and electrical
remote reset
Operating voltage 200 – 480 V
or using tripping CLASS 20, please refer to the information contained in the
F
“SIRIUS Engineering – Fuseless Load Feeders” configuration brochure and in the
catalog
23
Size S00
Size S0
Size S2
Size S3
Size S6, S10, S12
Fuseless Load Feeders
Communication
Feeder Combinations
Infeed System
Accessories
S6, S10, S12 selection and ordering data
S6
Contactor
Threephase
motor
400 V/AC-3
Electromagnetic
operating
mechanism
[kW]
[A]
55
115
90
150
185
Overload relay2)
Aux.
Control
switches supply
voltage
Order no.
contactor
Order no.
Vacuum
contactor
[AC/DC V]
Conventional
Electronic
75
24
Setting
range
Order no.
Solid-state
Overload relay
Soft starter
Version
2NO + 2NC
220 – 240
3RT1054-1AP36
–
3RT1054-1NP36
–
3RT1054-1QP35
–
– for 24 V DC PLC output
2NO + 2NC
200 – 277
1NO + 1NC
200 – 277
– with AS-i interface and RLT3)
1NO + 1NC
200 – 277
Conventional
2NO + 2NC
220 – 240
3RT1055-6AP36
–
3RT1055-6NP36
–
50 – 200
3RB2 5 - FW2 with straight-through
transformer
3RT1055-6QP35
–
50 – 200
3RB2 5 - FC2
3RT1054-1PP35
–
– for 24 V DC PLC output
2NO + 2NC
200 – 277
– for 24 V DC PLC output w/RLT3)
1NO + 1NC
200 – 277
– with AS-i interface and RLT3)
1NO + 1NC
200 – 277
Conventional
2NO + 2NC
220 – 240
3RT1056-6AP36
–
– for 24 V DC PLC output
2NO + 2NC
200 – 277
– for 24 V DC PLC output w/RLT3)
1NO + 1NC
200 – 277
3RT1056-6NP36
–
– with AS-i interface and RLT3)
1NO + 1NC
200 – 277
3RT1056-6QP35
–
Electronic
3RT1055-6PP35
3RT1056-6PP35
Rated
Order no.
operating
current
Ie [A]
[A]
– for 24 V DC PLC output w/RLT3)
Electronic
Control
supply
voltage
–
–
with busbar
connection
CLASS 10 0 61
CLASS 20 0 62
CLASS 5...30* 1 34
* With ground-fault detection (activatable)
and electrical remote reset
AC 230 V
134
3RW4055-6BB44
AC 115 V
134
3RW4055-6BB34
AC 230 V
162
3RW4056-6BB44
AC 115 V
162
3RW4056-6BB34
S6
110
Contactor
225
Conventional
Electronic
132
160
265
300
S12
220
3RT1064-6AP36
3RT1264-6AP36
3RT1064-6NP36
3RT1264-6NP36
3RT1064-6QP35
–
AC 230 V
230
3RW4073-6BB44
– for 24 V DC PLC output
2NO + 2NC
200 – 277
1NO + 1NC
200 – 277
– with AS-i interface and RLT3)
1NO + 1NC
200 – 277
Conventional
2NO + 2NC
220 – 240
3RT1065-6AP36
3RT1265-6AP36
AC 115 V
230
3RW4073-6BB34
– for 24 V DC PLC output
2NO + 2NC
200 – 277
200 – 277
3RT1265-6NP36
280
1NO + 1NC
3RT1065-6NP36
AC 230 V
– for 24 V DC PLC output w/RLT3)
3RW4074-6BB44
– with AS-i interface and RLT3)
1NO + 1NC
200 – 277
3RT1065-6QP35
–
AC 115 V
280
3RW4074-6BB34
Conventional
2NO + 2NC
220 – 240
3RT1066-6AP36
3RT1266-6AP36
– for 24 V DC PLC output
2NO + 2NC
200 – 277
– for 24 V DC PLC output w/RLT3)
1NO + 1NC
200 – 277
3RT1066-6NP36
3RT1266-6NP36
CLASS 10 0 61
CLASS 20 0 62
CLASS 5...30* 1 34
– with AS-i interface and RLT3)
1NO + 1NC
200 – 277
3RT1066-6QP35
–
* With ground-fault detection (activatable)
and electrical remote reset
AC 230 V
356
3RW4075-6BB44
AC 115 V
356
3RW4075-6BB34
AC 230 V
432
3RW4076-6BB44
AC 115 V
432
3RW4076-6BB34
Electronic
Electronic
3RT1064-6PP35
3RT1065-6PP35
3RT1066-6PP35
–
–
Conventional
500
–
3RB2 6 - GC2
with busbar
connection
Overload relay2)
2NO + 2NC
220 – 240
3RT1075-6AP36
3RT1275-6AP36
3RT1075-6NP36
3RT1275-6NP36
3RT1075-6QP35
–
– for 24 V DC PLC output
2NO + 2NC
200 – 277
– for 24 V DC PLC output w/RLT3)
1NO + 1NC
200 – 277
– with AS-i interface and RLT3)
1NO + 1NC
200 – 277
Conventional
2NO + 2NC
220 – 240
3RT1076-6AP36
3RT1276-6AP36
– for 24 V DC PLC output
2NO + 2NC
200 – 277
– for 24 V DC PLC output w/RLT3)
1NO + 1NC
200 – 277
3RT1076-6NP36
3RT1276-6NP36
– with AS-i interface and RLT3)
1NO + 1NC
200 – 277
Electronic
55 – 250
160 – 630 3RB2 6 - MC2 with busbar
connection
Contactor
400
Soft starter
220 – 240
– for 24 V DC PLC output w/RLT3)
Electronic
250
Overload relay2)
2NO + 2NC
3RT1075-6PP35
3RT1076-6PP35
3RT1076-6QP35
For applications above 100 A, SIRIUS contactors can be combined with SENTRON 3VL circuit breakers.
For more detailed information please refer to the engineering brochure “Engineering SIRIUS fuseless load feeders.”
–
Soft starter
160 – 630 3RB2 6 - MC2 with busbar
connection
CLASS 10 0 61
CLASS 20 0 62
CLASS 5...30* 1 34
–
* With ground-fault detection
(activatable) and electrical remote reset
–
1)
or rated device operating voltage Ue: 200–460 V
F
(see catalog for Ue: 400–600 V)
2)
or using tripping CLASS 20, please refer to the information
F
contained in the “SIRIUS Engineering – Fuseless Load Feeders”
configuration brochure and in the catalog
3)
RLT: Remaining lifetime indication
SENTRON 3VL circuit breakers are suitable for the
fuseless short-circuit and overload protection of soft
starters of size S6 or larger. For further information,
please refer to the catalog.
25
Size S00
Size S0
Size S2
Size S3
Size S6, S10, S12
Fuseless Load Feeders
Communication
Feeder Combinations
Infeed System
Accessories
Fuseless load feeders up to 15 kW
26
Direct starter,
fully preassembled,
electromechanical
3RA21 direct-on-line starter
Threephase
motor
400 V/AC-3
M
[kW]
[A]
[A]
0.06
0.20
0.14 – 0.2
0.06
0.25
0.18 – 0.25
0.09
0.32
0.22 – 0.32
0.09
0.40
0.28 – 0.4
0.12
0.50
0.35 – 0.5
0.18
0.63
0.45 – 0.63
0.18
0.80
0.55 – 0.8
0.25
1.0
0.7 – 1
0.37
1.25
0.9 – 1.25
0.55
1.6
1.1 – 1.6
0.75
2.0
1.4 – 2
0.75
2.5
1.8 – 2.5
1.1
3.2
2.2 – 3.2
1.5
4.0
2.8 – 4
1.5
5.0
3.5 – 5
2.2
6.3
4.5 – 6.3
3
8
5.5 – 8
4
10
7 – 10
5.5
12.5
9 – 12.5
7.5
16
11 – 16
7.5
20
14 – 20
11
22
17 – 22
11
25
20 – 25
15
32
27 – 32
1)
PS: Control and protective switching
C
device, IEC/EN 60947-6-2
2)
If used in the 3RA68 Infeed system, please
use 3 instead of 2.
3)
Setting range
of thermal
overload
release
Not available with spring-loaded connection system
Coordination type 1
3RA21 direct-on-line starter
3RA61 Compact Starter
Coordination type 2
Setting range
of thermal
overload
release
3RA2110-0B 15-1
S00
3RA2110-0D 15-1
S00
S00
S00
S00
S00
S00
S03)
S03)
Coordination
type 2 CPS1)
[A]
3RA2110-0B 15-1
S00
3RA2110-0D 15-1
S00
S00
S00
S00
S00
S00
S00
S00
3RA2110-0C 15-1
3RA2110-0E 15-1
3RA2110-0F 15-1
3RA2110-0G 15-1
3RA2110-0H 15-1
3RA2110-0J
15-1
3RA2110-0K 15-1
3RA2110-1A 15-1
3RA2110-1B 15-1
3RA2110-1C 15-1
3RA2110-1D 15-1
3RA2110-1E 15-1
3RA2110-1F 15-1
3RA2110-1G 15-1
3RA2110-1H 15-1
3RA2110-1J
16-1
3RA2110-1K 17-1
3RA2110-4A 18-1
3RA2120-4B 26-0
3RA2120-4C 27-0
3RA2120-4D 27-0
3RA2120-4E 27-0
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S0
S0
S00
S0
S0
Screw connection (for mounting onto DIN rail):
Spring-loaded connection
(for mounting onto DIN rail):
Screw connection (busbar adapter):
Spring-loaded connection (busbar adapter):
3RA2110-0C 15-1
3RA2110-0E 15-1
3RA2110-0F 15-1
3RA2110-0G 15-1
3RA2110-0H 15-1
3RA2110-0J
15-1
3RA2110-0K 15-1
3RA2110-1A 15-1
3RA2110-1B 15-1
3RA2110-1C 15-1
3RA2110-1D 15-1
3RA2110-1E 15-1
3RA2120-1F 24-0
3RA2120-1G 24-0
3RA2120-1H 24-0
3RA2120-1J
26-0
3RA2120-1K 26-0
3RA2120-4A 26-0
3RA2120-4B 26-0
3RA2120-4C 27-0
3RA2120-4D 27-0
3RA2120-4E 27-0
A
E
D
H
S00
S00
S00
S00
S00
S00
S00
S03)
S0
S0
S0
S0
3RA6120- A 3 0.32 – 1.25
3RA6120- B 3 1 – 4
3RA6120- C 3 3– 12
3RA6120- D 3 8 – 32
3RA6120- E 3 3)
S03)
S0
S0
24 V AC/DC: B B 4
230 V AC: A P 0
0.1 – 0.4
Without terminals: 0
With screw connection: 1
With spring-loaded connection: 2
24 V AC/DC: B
AC 110 ... 240 V AC/DC: P
0
2
2
2)
2)
Reversing starter,
fully preassembled
M
Three-phase
motor
400 V/AC-3
Setting
range
of thermal
overload
release
[kW]
[A]
[A]
0.06
0.20
0.14 – 0.2
0.06
0.25
0.18 – 0.25
0.09
0.32
0.22 – 0.32
0.09
0.40
0.28 – 0.4
0.12
0.50
0.35 – 0.5
0.18
0.63
0.45 – 0.63
0.18
0.80
0.55 – 0.8
0.25
1.0
0.7 – 1
0.37
1.25
0.9 – 1.25
0.55
1.6
1.1 – 1.6
0.75
2.0
1.4 – 2
0.75
2.5
1.8 – 2.5
1.1
3.2
2.2 – 3.2
1.5
4.0
2.8 – 4
1.5
5.0
3.5 – 5
2.2
6.3
4.5 – 6.3
3
8
5.5 – 8
4
10
7 – 10
5.5
12.5
9 – 12.5
7.5
16
11 – 16
7.5
20
14 – 20
11
22
17 – 22
11
25
20 – 25
15
28
23 – 28
15
32
27 – 32
1)
PS: Control and protective switching
C
device, IEC/EN 60947-6-2
2)
If used in the 3RA68 Infeed system, please
use 3 instead of 2.
3)
Not available with spring-loaded connection system
Size S00
Size S0
3RA22 reversing starter
3RA22 reversing starter
3RA62 Compact Starter
Coordination type 1
Coordination type 2
Setting range
of thermal
overload
release
Coordination
type 2 CPS 1)
[A]
3RA2210-0B 15-2
S00
3RA2210-0D 15-2
S00
S00
S00
S00
S00
S00
S00
S00
3RA2210-0C 15-2
3RA2210-0E 15-2
3RA2210-0F 15-2
3RA2210-0G 15-2
3RA2210-0H 15-2
3RA2210-0J
15-2
3RA2210-0K 15-2
3RA2210-1A 15-2
3RA2210-1B 15-2
3RA2210-1C 15-2
3RA2210-1D 15-2
3RA2210-1E 15-2
3RA2210-1F 15-2
3RA2210-1G 15-2
3RA2210-1H 15-2
3RA2210-1J
16-2
3RA2210-1K 17-2
3RA2210-4A 18-2
3RA2220-4B 26-0
3RA2220-4C 27-0
3RA2220-4D 27-0
3RA2220-4N 28-0
3RA2220-4E 28-0
S00
S00
S00
S00
S00
S00
S00
S00
S00
S00
S0
S0
S00
S0
S0
S0
Screw connection (for mounting onto DIN rail) S00:
Screw connection (for mounting onto DIN rail) S0:
Spring-loaded connection (for mounting onto DIN rail) S00:
Spring-loaded connection (for mounting onto DIN rail) S0:
Screw connection (busbar adapter):
Spring-loaded connection (busbar adapter):
Size S2
Size S3
3RA2210-0B 15-2
S00
3RA2210-0D 15-2
S00
S00
S00
S00
S00
S00
S03)
S03)
3RA2210-0C 15-2
3RA2210-0E 15-2
3RA2210-0F 15-2
3RA2210-0G 15-2
3RA2210-0H 15-2
3RA2210-0J
15-2
3RA2210-0K 15-2
3RA2210-1A 15-2
3RA2210-1B 15-2
3RA2210-1C 15-2
3RA2210-1D 15-2
3RA2210-1E 15-2
3RA2220-1F 24-2
3RA2220-1G 24-0
3RA2220-1H 24-0
3RA2220-1J
26-0
3RA2220-1K 26-0
3RA2220-4A 26-0
3RA2220-4B 26-0
3RA2220-4C 27-0
3RA2220-4D 27-0
3RA2220-4N 28-0
3RA2220-4E 28-0
A
B
E
F
D
H
S00
S00
S00
S00
S00
S00
S00
S03)
S0
S0
S0
S0
Size S6, S10, S12
3RA6250- A 3 0.32 – 1.25
3RA6250- B 3 1 – 4
3RA6250- C 3 3– 12
3RA6250- D 3 8 – 32
3RA6250- E 3 3)
S03)
S0
S0
S0
24 V AC/DC: B B 4
230 V AC: A P 0
0.1 – 0.4
Without terminals: 0
With screw connection: 1
With spring-loaded
connection: 2
24 V AC/DC B
AC 110 ... 240 V AC/DC P
Fuseless Load Feeders
0
2
2
Communication
Feeder Combinations
Infeed System
2)
2)
27
Accessories
Communications – general information and contactors
28
Interfacing load feeders to the control system requires function modules for IO-Link or AS-i which are mounted
on contactors (24 V DC) with a communication interface. Depending on the version, they communicate with an
IO-Link interface group or any AS-i Master.
Motor
Starter
Protection
Typical layout in the
environment of IO-Link
PROFIBUS
or
PROFINET/Ethernet
IO-Link
IO-Link
Version
ET 200S electronic module, 4SI IO-Link (with 4 ports
for 4 load feeders each)
or
ET 200S electronic module, 4SI SIRIUS (with 4 ports
for 4 load feeders each)
ET 200S terminal module (15 mm wide)
– With screw terminal
– With spring-loaded terminal
– With Fast Connect
ET 200S interface module for interfacing to
PROFIBUS and PROFINET and more system
accessories
Contactor
Order no.
6ES7 138-4GA50-0AB0
3RK1005-0LB00-0AA0
TM-E15S26-A1 6ES7
TM-E15C26-A1 6ES7
TM-E15N26-A1 6ES7
see the Industry Mall or
the IKPI Catalog
Mounting principle of function modules on contactors
S00 contactor with communication interface
Typical layout in the
environment of AS-Interface
AS-Interface
AS-Interface
Version
CP 343-2P communication processor for interfacing
SIMATIC S7-300 to AS-Interface (AS-i Spec.3.0) for
max. 62 load feeders
Front connector, 20-pin with screw contacts
Front connector, 20-pin with spring-loaded contacts
DP/AS-i LINK Advanced, gateway between
PROFIBUS DP and AS-Interface
– Single master for max. 62 load feeders
– Double master for max. 124 load feeders
IE/AS-i LINK PN IO, gateway between PROFINET and
AS-Interface
Single master for max. 62 load feeders
Double master for max. 124 load feeders
AS-Interface power supply unit IP20
– 120/230 V AC 3A
– 24 V DC 3A
– 120/230 V AC 5A
– 120/230 V AC 8A
For more system components for AS-Interface
Order no.
6GK7343-2AH11-0XA0
6ES7392-1AJ00-0AA0
6ES7392-1BJ00-0AA0
Three-phase motor
400 V/AC-3
[kW]
[A]
Auxiliary
contacts
Control supply voltage
Order no.
3
7
1NC
3RT2015- BB42-0CC0
4
9
1NC
5.5
12
1NC
7.5
16
1NC
1NO
3RT2015- BB41-0CC0
3RT2016- BB42-0CC0
1NO
3RT2016- BB41-0CC0
3RT2017- BB42-0CC0
1NO
6GK1415-2BA10
6GK1415-2BA20
DC 24 V
3RT2017- BB41-0CC0
3RT2018- BB42-0CC0
1NO
3RT2018- BB41-0CC0
S0 contactor with communication interface
5.5
12
6GK1411-2AB10
6GK1411-2AB20
7.5
16
1NO+1NC
1NO+1NC
11
25
1NO+1NC
15
32
1NO+1NC
3RX9501-0BA00
3RX9501-1BA00
3RX9502-0BA00
3RX9503-0BA00
see the Industry Mall or
the IKPI Catalog
18.5
38
1NO+1NC
3RT2024- BB40-0CC0
3RT2025- BB40-0CC0
3RT2026- BB40-0CC0
3RT2027- BB40-0CC0
3RT2028- BB40-0CC0
Screw connection: 1
Spring-loaded
connection: 2
Function modules for mounting on 3RT2 contactors and for interfacing the control system
Parallel
wiring
Direct-on-line start
Reversing start
Order no.
ON delay
OFF delay
(with auxiliary voltage)
3RA2811- CW10
3RA2812- DW10
Star-delta start
Wiring kit for contactors
S00
Wiring kit for contactors with screw
connection
S0
Order no.
3RA2913-2AA 3RA2923-2AA Order no.
3RA2816-0EW20
Function module 4)
Wiring kit for contactors 1)
S00
3RA2913-2BB Wiring kit for contactors 1)
S0
3RA2923-2BB IO-Link
Direct-on-line start 1)
Reversing start 1) 2) 3)
2)
Star-delta start 1) 2) 4)
Order no.
Function module
3RA2711- AA00
Order no.
Function module
Wiring kit for contactors
S00
Wiring kit for contactors
S0
Order no.
3RA2711- BA00
Function module
3RA2913-2AA Wiring kit for contactors
S00
Wiring kit for contactors
S0
3RA2923-2AA 3RA2711- CA00
3RA2913-2BB 3RA2923-2BB AS-Interface
Direct-on-line start 1)
Reversing start 1) 2) 3)
2)
Star-delta start 1) 2) 4)
Order no.
Function module
3RA2712- AA00
Order no.
Function module
Wiring kit for contactors
S00
Wiring kit for contactors
S0
Screw connection: 1
Spring-loaded connection: 2
Order no.
3RA2712- BA00
Function module
3RA2913-2AA Wiring kit for contactors
S00
Wiring kit for contactors
S0
3RA2923-2AA Screw connection: 1
Spring-loaded connection: 2
3RA2712- CA00
3RA2913-2BB 3RA2923-2BB Screw connection: 1
Spring-loaded connection: 2
The above shown contactor assemblies can be combined with motor starter protector, overload and current monitoring relay (see the descriptions on previous pages)
The wiring modules for control circuit are not required when using function modules with communications interface
The contactor upon which the basic module is fitted must be selected as a communication contactor (see page 28)
3)
Consisting of 1 basic module and 1 interface module
4)
Consisting of 1 basic module and 2 interface modules
1)
2)
29
Communications – Compact Starter
IO-Link
Setting range
of thermal
overload release
[A]
0.1 – 0.4
0.32 – 1.25
3RA65 reversing starter
Coordination type 2 / CPS
Coordination type 2 / CPS
1)
3 – 12
8 – 32
3RA2711-0EE02
Module connector, 14-pin, 21 cm,
for wider gaps between two contactors
3RA2711-0EE03
3RA6500- BB42
Control module,
(incl. enabling chip and blanking cover)
3RA6935-0A
3RA6500- DB42
Connecting cable for
control module
3RA6933-0A
AC/DC 24 V
3RA6400- AB42
3RA6500- AB42
3RA6400- CB42
3RA6500- CB42
3RA6400- DB42
3RA6400- EB42
Accessories for Compact Starter with IO-Link and 3RA27 function module
Ribbon cable, 14-pin, 8 cm,
for small gaps between two contactors
AC/DC 24 V
3RA6400- BB42
1–4
M
3RA64 direct-on-line starter
1)
3RA6500- EB42
AS-Interface
+
Setting range
of thermal
overload release
[A]
0.1 – 0.4
0.32 – 1.25
1–4
M
1)
3 – 12
8 – 32
PS: Control and
C
protective switching device,
IEC/EN 60947-6-2
=
3RA61 direct-on-line starter
3RA62 reversing starter
Coordination type 2 / CPS
Coordination type 2 / CPS
1)
Accessories for AS-Interface
1)
3RK1904-2AB01
AS-i addressing unit
AC/DC 24 V
AC/DC 24 V
AS-Interface add-on modules for 3RA6 Compact Starter (DC 24 V)
3RA6120- AB34
3RA6250- AB34
3RA6120- CB34
3RA6250- CB34
Without additional inputs/outputs
With two local inputs
With two unassigned external inputs
With one unassigned external input and output each
With two unassigned external outputs
For on-site control
3RA6120- BB34
3RA6120- DB34
3RA6120- EB34
3RA6250- BB34
3RA6250- DB34
3RA6250- EB34
3RA6970-3A
3RA6970-3B
3RA6970-3C
3RA6970-3D
3RA6970-3E
3RA6970-3F
Screw connection: 1
Spring-loaded
connection: 2
30
Size S00
Size S0
Size S2
Size S3
Size S6, S10, S12
Fuseless Load Feeders
Communication
Feeder Combinations
Infeed System
Accessories
3RA68 Infeed system (Compact Starter)
1
2
1
3
4
5
8
2
NSB0_01878
7
4
6
Items 6 and 9 already included in the scope of delivery
Terminal type
Order no.
Screw feeding 25/35 mm² left
with fixed-mounted triple expansion module
Screw connection
3RA6812-8AB
Screw feeding 25/35 mm² left
with fixed-mounted triple expansion module
Spring-loaded
connection
3RA6812-8AC
Screw feeding 50–70 mm² left
with fixed-mounted triple expansion module
Screw connection
3RA6813-8AB
Screw feeding 50–70 mm² left
with fixed-mounted triple expansion module
Spring-loaded
connection
3RA6813-8AC
3-phase feeders
3RA6830-5AC
Spring-loaded feeding 25/35 mm²
left or right up to 63 A
9
3
10
Type
5
6
7
Expansion module
Dual expansion module with 2 slots
Screw connection
3RA6822-0AB
Triple expansion module with 3 slots
Screw connection
3RA6823-0AB
Dual expansion module with 2 slots
Spring-loaded connection
3RA6822-0AC
Triple expansion module with 3 slots
Spring-loaded connection
3RA6823-0AC
Expansion plug
Expansion plug between 2 expansion modules (already included in the
delivery scope of the expansion modules)
PE supply
PE supply 25/35 mm²
Screw connection
3RA6860-6AB
PE supply 25/35 mm²
Spring-loaded connection
3RA6860-5AC
PE tap 6/10 mm²
Screw connection
3RA6870-4AB
PE tap 6/10 mm²
Spring-loaded connection
PE tap
PE expansion plug
3RA6870-3AC
3RA6890-0EA
8
Link wedge (already included in the scope of supply of 2 and 3 )
9
Cover cap of the energy bus (already included in the scope of supply of 1 )
10
Adapter for SIRIUS 3RV2 motor starter protector
3RA6890-0BA
Adapter 45 mm for 3RV2
for motor starter protector with screw connection
3RA6890-1AA
Expansion plug for SIRIUS 3RV19 Infeed system
Terminal block to integrate 1-, 2- or 3-pole
components
Spring-loaded connection
3RV1917-5D
31
3RV29 Infeed system (motor starter protector and load feeder)
32
Type
Version
Size for
3RV20,
3RV23
motor starter
protectors
Order no.
For 2 motor starter
protectors
S00, S0
3RV2917-1A
For 2 motor starter
protectors
S00, S0
3RV2917-1E
For 2 motor starter
protectors
S00, S0
3RV2917-4A
For 3 motor starter
protectors
S00, S0
3RV2917-4B
S00
3RV2917-5CA00
Spring-loaded 1 pc.
S00
connection
10 pcs. S00
3RV2917-5AA00
7
3
8
1
1
2
9
2
6
3
3-phase busbars
with infeed on the left
incl. end cover
3RV2917-6A
with infeed on the right
incl. end cover
3RV2917-6A
For system expansion
incl. expansion plug
3RV2917-5BA00
For system expansion
incl. expansion plug
3RV2917-5BA00
Connector
For contacting the motor
starter protectors
Screw
connection
Screw
connection
5
NSB0_02078
4
4
5
6
7
Accessories
8
9
Expansion plug
End cover
10 pcs. S00
1 pc.
S0
10 pcs. S0
Spring-loaded 1 pc.
S0
connection
10 pcs. S0
Contactor base for building up direct-on-line
or reversing starters
Terminal block to integrate 1-, 2- or 3-pole
components
DIN rail, 45 mm, to integrate other
devices into the system, such as
5SY motor starter protectors
Wider expansion plug
Spare parts
1 pc.
1 pc.
S00, S0
3RV2917-5C
3RV2917-5A
3RV1927-5AA00
3RV1927-5A
3RV2927-5AA00
3RV2927-5A
3RV2927-7AA00
3RV2917-5D
3RV1917-7B
3RV2917-5E
3RV2917-5BA00
3RV2917-6A
3-phase comb busbars / 8US busbar adapters for supply
Type
1
Size
Order no.
3-phase comb busbars
2
1
For supplying several 3RV2
motor starter protectors
(screw-connected) mounted
side by side on DIN rails,
safe to touch
For 2 motor starter protectors
For 4 motor starter protectors
For 3 motor starter protectors
3
Modular
spacing
55 mm
Modular
spacing
63 mm
S00, S0
3RV1915-1AB
3RV1915-2AB
3RV1915-3AB
S00, S0
3RV1915-1CB
3RV1915-2CB
3RV1915-3CB
S00, S0
For 5 motor starter protectors
S00, S0
3-phase supply terminals
6
Modular
spacing
45 mm
Connection from the top
S00, S0
Connection from the bottom
S00, S0
3RV1915-1BB
3RV1915-1DB
3RV1915-2BB
3RV1915-2DB
–
–
3RV2925-5AB
3RV2915-5B
3-phase supply terminals to build up “type E starters”
Connection from the top
S00, S0
3RV2925-5EB
Cover caps for connecting lugs
Touch protection for unassigned slots
S00, S0
3RV1915-6AB
Accessories
Type
Size
Version
(Length)
Order no.
S00
200 mm
8US1251-5DS10
S0
260 mm
8US1251-5NT10
S00, S0
260 mm
8US1251-5DT11
S0
260 mm
8US1251-5NT11
200 mm
8US1250-5AS10
260 mm
8US1250- 5AT10
200 mm
8US1998-2BJ10
Busbar adapter for 60 mm system
4
For load feeders
Rated current 16 A for screw connection
For load feeders
Rated current 32 A for screw connection
For load feeders
Rated current 16 A for spring-loaded connection
For load feeders
Rated current 32 A for spring-loaded connection
5
Accessories
Support
for side mounting on busbar adapter, 45 mm wide
Support
for side mounting on busbar adapter, 45 mm wide
Side module
to widen the busbar adapter, 9 mm wide
Spacer
Fixes the load feeder on the adapter
Vibration/shock kit
To compensate strain from higher vibration and shock
8US1998-1BA10
8US1998-1CA10
33
Size S00
Size S0
Size S2
Size S3
Size S6, S10, S12
Fuseless Load Feeders
Communication
Feeder Combinations
Infeed System
Accessories
Accessories for 3RV2 motor starter protector (S00, S0)
Type
34
Version
Order no.
Order no.
Screw connection Spring-loaded
connection
Order no.
Ring cable
lug connection
1CO
3RV2901-1D
–
–
2NO
3RV2901-1F
3RV2901-2F
7
Accessories for 3RV2 motor starter protector, size S00, S0
Auxiliary and signaling contacts
1
Front-mounted auxiliary block
3
2
Auxiliary switch suited for electronic components
2
4
3
5
1
6
Side-mounted auxiliary block
with 2 contacts
1NO + 1NC
3RV2901-1E
3RV2901-2E
3RV2901-1G
–
–
2NO
3RV2901-1B
3RV2901-2B
–
1NO + 1NC
2NC
Side-mounted auxiliary block with 4 contacts 2NO +2NC
3RV2901-1A
3RV2901-1C
3RV2901-1J
3RV2921-1M
3RV2901-2A
3RV2901-2C
–
3RV2921-2M
3RV2901-4A
–
–
3RV2921-4M
4
Signaling switch
5
Shunt trip1)
AC/DC 20 – 70 V
3RV2902-1DB0
3RV2902-2DB0
–
6
Undervoltage release1)
AC 230 V
3RV2902-1AP0
3RV2902-2AP0
3RV2902-4AP0
Undervoltage release
with leading auxiliary contacts
AC 230 V
3RV2922-1CP0
3RV2922-2CP0
–
7
Auxiliary release
AC 210 – 240 V
AC 400 V
AC 400 V
Disconnector module and terminal blocks
3RV2902-1DP0
3RV2902-1AV0
3RV2922-1CV0
3RV2922-1CV1
3RV2902-2DP0
3RV2902-2AV0
3RV2922-2CV0
3RV2922-2CV1
–
3RV2902-4AV0
–
3RV2922-4CV1
Disconnector module
3RV2928-1A
–
–
Phase barriers
for higher creepage distances and air clearances
3RV2928-1K
–
–
Terminal block type E
for higher creepage distances and air clearances
3RV2928-1H
Type
Rotary door-coupling operating mechanisms
Rotary door-coupling operating mechanism (black) with
Extension shaft
Extension shaft
–
Extension shaft
Extension shaft
Molded-plastic housing
–
Version 2)
Order no.
130 mm
3RV2926-0B
330 mm
EMERGENCY STOP rotary door-coupling operating mechanism (red/yellow) with
130 mm
330 mm
3RV2926-0K
3RV2926-0C
3RV2926-0L
3RV1923-1CA00
For motor starter protector (+ Side-mounted auxiliary block)
54 mm
72 mm
3RV1923-1DA00
Molded-plastic housing with EMERGENCY STOP rotary door-coupling operating mechanism
For motor starter protector (+ Side-mounted auxiliary block)
For motor starter protector (+ Side-mounted auxiliary block + auxiliary release)
54 mm
72 mm
3RV1923-1FA00
3RV1923-1GA00
For motor starter protector (+ Side-mounted auxiliary block + auxiliary release)
More versions on request
2)
Only available as screw-connected versions
–
1CO
AC 415 V
1)
3RV2901-4E
Accessories for 3RV1 circuit breakers (S2, S3)
Type
Version
For size
Order no.
1W
S2, S3
3RV1901-1D
1NO + 1NC
S2, S3
3RV1901-1E
2NO
S2, S3
3RV1901-1F
1NO + 1NC
S2, S3
3RV1901-1A
2NO
S2, S3
3RV1901-1B
2NC
S2, S3
3RV1901-1C
Transverse auxiliary switch
with 4 contacts
2NO + 2NC
S2, S3
3RV1901-1J
Shunt release
AC 230 V
S2, S3
3RV1902-1DP0
Undervoltage release
AC 230 V
S2, S3
3RV1902-1AP0
Undervoltage release
with leading auxiliary switches
AC 230 V
S2, S3
3RV1922-1CP0
Signal switch
S2, S3
3RV1921-1M
Isolator module
S2
3RV1938-1A
8
Accessories for 3RV1 circuit breakers (S2, S3)
2
Auxiliary and signaling switches
4
7
1
2
6
3
4
5
6
1
7
8
Transverse auxiliary switch
with 2 contacts
NSB0_02184
3
Transverse auxiliary switch
5
35
Size S00
Size S0
Size S2
Size S3
Size S6, S10, S12
Fuseless Load Feeders
Communication
Feeder Combinations
Infeed System
Accessories
Accessories for 3RT201 contactors (S00)
5
Front mounting auxiliary
contacts for
13
6
2
7
10
Version
1 3RT2 contactors
Standard
2 1-pole auxiliary contact block,
cable entry from the top
1NO
Communication
1NC
2-pole auxiliary contact block,
cable entry from the top
3
1NO + 1NC
2NO
1-pole auxiliary contact block,
cable entry from the bottom
8
1NO
1NC
3 2-pole auxiliary contact block,
cable entry from the bottom
1
4
4
1
11
36
1NO + 1NC
2NO
4-pole auxiliary contact blocks1),
(in compliance with DIN EN 50 012
and DIN EN 50 005)
1NC
8
10
5
6
7
8
1NO + 1NC
2NO
2Ö
–
–
3RH2911-1LA20
3RH2911-1BA10
3RH2911-1BA01
3RH2911-1MA11
3RH2911-1MA20
–
–
–
–
–
–
–
–
–
–
–
3RH2911-1HA01
3RH2911-2HA01
3RH2911-4HA01
3RH2911-1HA11
3RH2911-2HA11
3RH2911-4HA11
3RH2911-1HA10
3RH2911-1HA20
3RH2911-1NF11
3RH2911-1NF20
3RH2911-1NF02
3RH2911-2HA02
3RH2911-2HA22
3RH2911-2HA10
3RH2911-2HA20
3RH2911-2NF11
3RH2911-2NF20
3RH2911-2NF02
3RH2911-4HA02
3RH2911-4HA22
3RH2911-4HA10
3RH2911-4HA20
–
–
–
3RH2911-1DA20
3RH2911-2DA20
–
2NC
3RH2911-1DA02
3RH2911-2DA02
–
3RH2911-1DA11
3RH2911-2DA11
3RH2911-4DA11
1NO + 1NC
–
3RH2911-2DE11
–
Soldering pin adapter for contactors
with 4-pole auxiliary contact block
For 4 contactors
(pack)
3RT1916-4KA2
–
–
10 Soldering pin adapter for contactors
For 4 contactors
(pack)
3RT1916-4KA1
–
–
AC 127–240 V
3RT2916-1BD00
3RT2916-1BD00
3RT2916-1BD00
AC-3/400 V: 20 A
3RT1916-4RD01
–
–
3RA2913-3K
–
11 Surge suppressor, e.g. varistor (AC 230 V)2)
without LED
with LED
or further surge suppressors, refer to the Industry Mall
F
or the IC 10 catalog
3RH2911-1LA11
–
2NO
1NO + 1NC
Auxiliary contact block suited for electronic
components for side mounting (on the right)
(in compliance with DIN EN 50 012 and
DIN EN 50 005)
2)
–
3RH2911-1AA01
see page 17 (Function modules for mounting on contactors and for interfacing the control system)
9 Auxiliary contact blocks for side
mounting
(in compliance with DIN EN 50 012
and DIN EN 50 005)
More auxiliary contact blocks on request
–
see page 16
3RH2911-1HA22
Size-specific accessories for 3RT201 contactors (S00)
1)
3RH2911-1AA10
see tabular overview on page 5ff.
2NO + 2NC
2NO
Auxiliary contact blocks suitable for
electronic components
(2-pole)
(in compliance with DIN EN 50 005)
Order no. Ring cable
lug connection
3RH2911-1HA02
1NO
9
Order no. Springloaded connection
2NC
1NO + 1NC
12
Order no.
Screw connection
12 Terminal module for contactor with
screw connection
13 3-phase supply terminal
Adapter
Plug
AC 127–240 V
Conductor cross
section: 6 mm
3RT2916-1JL00
3RT1900-4RE01
3RT2916-1JL00
–
3RT2916-1JL00
–
–
Accessories for 3RT202 contactors (S00)
5
Front mounting auxiliary
contacts for
13
5
5
9
1
3RT2 contactors
2
1-pole auxiliary contact block,
cable entry from the top
12
Order no.
Order no.
Screw connection Spring-loaded
connection
Standard
see tabular overview on page 5ff.
Communication see page 16
1NO
3RH2911-1AA10
–
3RH2911-1AA01
–
1NO + 1NC
3RH2911-1LA11
–
2NO
3RH2911-1LA20
–
1NO
3RH2911-1BA10
–
1NC
3RH2911-1BA01
–
1NO + 1NC
3RH2911-1MA11
2NO
3RH2911-1MA20
1NC
3RH2911-1HA01
3RH2911-2HA01
2NC
3RH2911-1HA02
3RH2911-2HA02
1NO + 1NC
3RH2911-1HA11
3RH2911-2HA11
2NO + 2NC
3RH2911-1HA22
3RH2911-2HA22
1NO
3RH2911-1HA10
3RH2911-2HA10
2NO
3RH2911-1HA20
3RH2911-2HA20
1NO + 1NC
3RH2911-1NF11
3RH2911-2NF11
2NO
3RH2911-1NF20
3RH2911-2NF20
2NC
3RH2911-1NF02
3RH2911-2NF02
1-pole auxiliary contact block,
cable entry from the bottom
1
2
4
5
3
2-pole auxiliary contact block,
cable entry from the bottom
4
4-pole auxiliary contact block1)
(in compliance with DIN EN 50 012
and DIN EN 50 005)
10
6
13
11
7
Auxiliary contact blocks suitable
for electronic components (2-pole)
(in compliance with DIN EN 50 005)
8
5
6
7
8
9
10
11
12
13
1)
More auxiliary contact blocks on request
2)
or further surge suppressors, refer to the Industry
F
Mall or the IC 10 catalog
Size S00
Version
2-pole auxiliary contact block,
cable entry from the top
1
3
Comment
Size S0
Size S2
Size S3
see page 17 (Function modules for mounting on contactors and for interfacing the controller)
Size-specific accessories for 3RT2 contactors
Auxiliary contact blocks
acc. to DIN EN
for side mounting (on the right)
50 005
(in compliance
with DIN EN
50 012 and
DIN EN 50 005)
Auxiliary contact block for side
acc. to
mounting (on the right), suitable DIN EN
for electronic components
50 005
Overvoltage limiter, e.g. varistor (AC 230 V)
without LED
AC 127–240 V
with LED
AC 127–240 V
Terminal module for contactor
Adapter
with screw connection
Plug
Pneumatic delay block
0.1 – 30 s
(in compliance with
1 – 60 s
DIN EN 50 005)
0.1 – 30 s
1NO + 1NC
1 – 60 s
Coil terminal module
Connection from the top
Connection from the bottom
Diagonal connection
Size S6, S10, S12
Order no.
Ring cable lug
connection
–
–
–
–
–
–
3RH2911-4HA01
3RH2911-4HA02
3RH2911-4HA11
3RH2911-4HA22
3RH2911-4HA10
3RH2911-4HA20
–
–
–
2NO
1NO + 1NC
2NC
3RH2921-1DA20
3RH2921-1DA11
3RH2921-1DA02
3RH2921-2DA20
3RH2921-2DA11
3RH2921-2DA02
–
3RH2921-4DA11
–
1NO + 1NC
–
3RH2921-2DE11
–
3RT2926-1BD00
3RT2926-1JL00
3RT1926-4RD01
3RT1900-4RE01
3RT2926-2PA01
3RT2926-2PA11
3RT2926-2PR01
3RT2926-2PR11
3RT2926-1BD00
3RT2926-1JL00
–
3RT2926-1BD00
3RT2926-1JL00
–
–
–
–
–
–
–
–
–
3RT2926-4RA11
3RT2926-4RB11
3RT2926-4RC11
3RT2926-4RA12
3RT2926-4RB12
3RT2926-4RC12
–
–
–
400 V/AC-3:
25 A
ON delay
OFF delay
Fuseless Load Feeders
Communication
Feeder Combinations
Infeed System
Accessories
37
Accessories for 3RT1 contactors (S2 to S3)
38
2
3
9
2
Solid-state time-delay block,
ON delay
Solid-state time-delay block,
OFF delay
Auxiliary switch block, solid-state time-delay
ON delay
OFF delay
2-pole auxiliary switch block,
cable entry from above
2-pole auxiliary switch block,
cable entry from below
4-pole auxiliary switch block,
(terminal designations acc. to
DIN EN 50 012 or DIN EN 50 005)
Link for paralleling (star jumper), 3-pole,
without terminal
3
4
8
1
10
Contactor, size S2 (example)
control supply voltage
10
14
1
5
6
7
4
8
7
13
9
5
17
6
14
11
18
1)
or further surge suppressors, refer to the Industry Mall
F
or the IC 10 catalog
Version
7.5 kW/400 V
230 V 50 Hz
For size
Order no.
3RT10 25-1AP00
For sizes S2 to S3
15
16
1
0.5 – 10 s
3RT19 26-2CH21
0.5 – 10 s
3RT19 26-2DH21
0.5 – 10 s
0.5 – 10 s
1NO + 1NC
3RT19 26-2ED21
3RT19 26-2FL21
3RH19 21-1LA11
1NO + 1NC
3RH19 21-1MA11
–
3RH19 21-1HA11
S2
S3
3RT19 36-4BA31
3RT19 46-4BA31
1NO + 1NC
S2
S3
S2 – S12
3RT19 36-4BB31
3RT19 46-4BB31
3RH19 21-1DA11
1NO
1NC
–
–
S2 – S3
S2 – S3
S2 – S3
S2 – S3
3RH19 21-1CA10
3RH19 21-1CA01
3RA19 24-2B
3RA19 24-1A
–
–
–
–
S2
S2
S3
S2 – S3
3RA19 23-2A
3RA19 33-2A
3RA19 43-2A
3RT19 26-1BD00
–
S2 – S3
3RT19 26-3AB31
–
AC/DC 24
AC/DC 110
AC/DC 230
S2 – S3
S2
S2
S2
3RT19 26-1QT00
3RT19 26-3AB31
3RT19 26-3AF31
3RT19 26-3AP31
2NO + 2NC
Link for paralleling, 3-pole, with terminal
10 2-pole auxiliary switch block, can be laterally
mounted (left or right), (terminal designations
acc. to DIN EN 50 012 or DIN EN 50 005)
11 1-pole auxiliary switch block
(up to 4 can be snapped on)
12 Mechanical interlock, can be laterally mounted
13 Mechanical interlock, can be mounted
at the front
14 Wiring connectors at the top and bottom
(reversing operation)
15 Surge suppressor (varistor, RC coupling,
diode combination), can be mounted
at the top or bottom
16 Interface for mounting directly onto the
contactor coil
17 LED module to indicate contactor operation
18 Mechanical latching
Accessories for 3RT1 contactors (S6 to S12)
1
79
8
12
2
13
18
10
63
45
3
11
9
4
14
2
1
4
Version
Order no.
– 2nd block (left/right), DIN EN 50 012
1NO + 1NC
3RH1921-1JA11
2NO
3RH1921-1KA20
– 2nd block (left/right), DIN EN 50 005
11
1
Type
2-pole auxiliary switch block, can be laterally mounted
5
6
15
56
4-pole auxiliary switch block, can be mounted at the front
37
10
8
7
8
9
Schütze
Baugrössen S6 bis S12 mit Zubehör
2NO + 2NC
3RH1921-1XA22-0MA0
1-pole auxiliary switch block, can be mounted at the front
1NO
1NC
1NO + 1NC
3RH1921-1CA10
3RH1921-1CA01
3RH1921-1LA11
– with classification No. 1…4, DIN EN 50 012
2-pole auxiliary switch block, can be mounted at the front,
cable entry from above, DIN EN 50 005
2-pole auxiliary switch block, can be mounted at the front,
cable entry from below, DIN EN 50 005
Auxiliary switch block, solid-state time-delay
– OFF delay, AC 200–240 V
12 Parallelschaltverbindung (Sternpunktbrücke),
(ansprech- oder rückfallverzögert oder Stern-Dreieck-Funktion)
3-polig, mit Durchgangsloch, unterschiedlich für
Baugrössen S6 und S10/S12
4 4-poliger Hilfsschalterblock
5
6
7
8
(Anschlussbezeichnungen nach DIN EN 50 012 oder DIN EN 50 005)
2-poliger Hilfsschalterblock, Leitungseinführung von oben
2-poliger Hilfsschalterblock, Leitungseinführung von unten
1-poliger Hilfsschalterblock (max. 4 aufschnappbar)
2-poliger Hilfsschalterblock, seitlich rechts oder links anbaubar
(Anschlussbezeichnungen nach DIN EN 50 012 oder DIN EN 50 005)
(gleich für S0 bis S12)
6
Überspannungsbegrenzer
(RC-Glied) oben an Einschubspule ansteckbar
Mechanische Verriegelung, seitlich anbaubar
Verdrahtungsbausteine oben und unten (Reversierbetrieb)
13 Anschlussabdeckung für Kabelschuh- und
Schienenanschluss unterschiedlich für
Baugrössen S6 und S10/S12
14 Klemmenabdeckung für Rahmenklemme
unterschiedlich für Baugrössen S6 und S10/S12
15 Rahmenklemmenblock, unterschiedlich für
Baugrössen S6 und S10/S12
9
Operating
mechanism types
10
33
11
44
1
RC element, AC 127–240 V 1)
Wiring connectors
top and bottom
2
55
22
11
5
5
Size S00
Size S0
Terminal cover for cable lug and busbar connection
11
Mechanical interlock
Size
3RT12 vacuum contactor, Sizes S10
and S12
3
Withdrawable coils for contactors
with conventional operating
mechanism 3RT1…-.A..
4
Withdrawable coils for contactors
with electronic operating
mechanism 3RT1…-.N..
5
10
3RT10 and 3RT14 air contactors,
Sizes S6, S10 and S12
S6
S10
Withdrawable coils and laterally
mounted module (can be plugged
in) for contactors with electronic
operating mechanism and remaining lifetime signal 3RT1…-.P.. and
2RT1…-.Q
S12
1)
Size S2
Size S3
1NO + 1NC
1NO + 1NC
3RH1921-1HA22
3RH1921-1MA11
0 ... 10 s
3RH1926-2ED21
for S6
3RA1953-2M
for S12
3RA1973-2A
for S10
Connection cover for box terminals
Gleiches Zubehör für Baugrössen S0 bis S12
Gleiches Zubehör für Baugrössen S6 bis S12
Zubehör unterschiedlich je nach Baugrösse
2NO + 2NC
0.5 ... 10 s
1 Luftschütz 3RT10 und 3RT14, Baugrössen S6, S10 und S12
3 Hilfsschalterblock, elektronisch verzögert
3RH1921-1KA11
– with classification No. 5…8, DIN EN 50 012
– ON delay, AC 200–240 V
11
1NO + 1NC
for S6
for S10/S12
for S6
for S10/S12
3RH1926-2FL21
3RT1956-1CD00
3RA1963-2A
3RT1956-4EA2
3RT1966-4EA2
3RT1956-4EA2
3RT1966-4EA2
3RA1954-2A
3-phasemotor
400 V/AC-3
Contactor without
coil
Withdrawable coil for operating mechanism
AC/DC 220...240 V
AC/DC 200...277 V
kW
Order no.
Order no.
Order no.
55
3RT1054-1LA06
3RT1955-5AP31
3RT1955-5NP31
75
3RT1055-6LA06
90
3RT1056-6LA06
110
3RT1064-6LA06
3RT1965-5AP31
3RT1965-5NP31
132
3RT1065-6LA06
160
3RT1066-6LA06
200
3RT1075-6LA06
3RT1975-5AP31
3RT1975-5NP31
250
3RT1076-6LA06
conventional
electronic
control supply voltage
or further surge suppressors, refer to the Industry Mall
F
or the IC 10 catalog
Size S6, S10, S12
Fuseless Load Feeders
39
Communication
Feeder Combinations
Infeed System
Accessories
Accessories for 3RU21 thermal overload relay, 3RB30/31 solid-state overload relay,
3RR21 analog current monitoring relay and 3RR22 digital current monitoring relay (S00, S0)
Version
For size
Order no.
Can be combined with the following overload
and current monitoring relays
3RU2
Relay base for stand-alone mounting
For mounting the overload relays separately
S00
3RU2916-3A 01
For screw and snap-on mounting on TH 35 DIN rail
S0
3RU2926-3A 01
Reset slide, holder and funnel
S00, S0
3RU2900-1A
Reset slide, holder and funnel
S00, S0
3RB3980-0A
Push button with elongated stroke (12 mm),
IP65, Ø 22 mm
S00, S0
3SB3000-0EA11
Extension tappet to even out the spacing between a push
button and the reset button of the relay
S00, S0
3SX1335
Mechanical RESET consisting of:
Cable release with holder for RESET for bores Ø 6.5 mm in the control panel
Length 400 mm
S00, S0
3RU2900-1B
Length 400 mm
S00, S0
3RB3980-0B
Length 600 mm
S00, S0
3RU2900-1C
Length 600 mm
S00, S0
3RB3980-0C
For covering the setting components
S00, S0
3RV2908-0P
For covering the setting components
S00, S0
3RB3984-0
For covering the setting components
S00, S0
3RR2940
AC/DC 24 ... 30 V
S00, S0
3RU1900-2AB71
AC/DC 110 ... 127 V
S00, S0
3RU1900-2AF71
AC/DC 220 ... 250 V
S00, S0
3RU1900-2AM71
Sealable cover for 3RB20/21, transparent
Modules for remote reset
Screw connection:
Spring-loaded
connection:
40
A
C
3RB3
3RR21
3RR22
Accessories for 3RU11 thermal overload relay
and 3RB20/21 solid-state overload relay
Version
Accessories for motor starters
For size
Order no.
S2
3RU1936-3AA01
S3
3RU1946-3AA01
1 Resetting plunger, holder and former
S2 – S10/S12
3RU1900-1A
2 Push button with extended stroke (12 mm),
IP65, Ø 22 mm
S2 – S10/S12
3SB3000-0EA11
S2 – S10/S12
3SX1335
Terminal support for stand-alone assembly for 3RU11
for separately mounting the overload relays,
screw-type and snap-on fastening on TH 35 DIN rails,
size S3 also for TH 75 DIN rails
3-phase
motor
400 V/AC-3
[kW]
Enclosure for direct starters Size
Order no.
22
Moulded-plastic enclosure
for wall mounting IP65
degree of protection
with actuator elements
S2
3RE1933-1CB3
Order no.
Qty.
Contactor
3RT10 3
1
Thermal or
solid-state overload relay
3RU11 36 resp.
2RB10 36
1
Lateral auxiliary switch 1NO/1NC
3RH1021-1DA11
1
Mechanical RESET for 3RU11 and 3RB20/21
comprising:
1
2
Extension plunger for compensation of the distance
between a push button and the relay‘s release button
Cable release with holder for RESET 3RU11 and 3RB20/21
for holes 6.5 mm diameter in the panel; max. panel thickness 8 mm
Length 400 mm
S2 – S10/S12
3RU1900-1B
Length 600 mm
S2 – S10/S12
3RU1900-1C
S2 – S10/S12
3RB2984-0
S3
3RT1946-4EA1
S6
3RT1956-4EA1
Components
required
Sealable cover, transparent for 3RB20/21
to cover the setting elements
Terminal covers for 3RU11 and 3RB20/21
Cover for cable lug and busbar connection
Cover for box terminals
Cover for the screw connection between the contactor and
overload relay without box terminals (1x is required for each
combination)
S10/S12
3RT1966-4EA1
S2
3RT1936-4EA2
S3
3RT1946-4EA2
S6
3RT1956-4EA2
S10/S12
3RT1966-4EA2
S6
3RT1956-4EA3
S10/S12
3RT1966-4EA3
S6
3T1955-4G
S6
3T1956-4G
S10/S12
3T1966-4G
Box terminal block
for round and ribbon cables
up to 70 mm2
up to 120 mm
2
up to 240 mm2
41
Size S00
Size S0
Size S2
Size S3
Size S6, S10, S12
Fuseless Load Feeders
Communication
Feeder Combinations
Infeed System
Accessories
42
Support
Product information
As competent and reliable partner, we not only offer tried-and-tested products
and systems, but also comprehensive support – from initial information to planning,
configuration and ordering, down to commissioning, ongoing operation and
technical service:
■■Access to all important and up-to-date information: From the website to the newsletter, down to the download of complete brochures
■■Ordering and information platform for all products and systems
■■Efficient tools for increased productivity, e.g. CAx Data for your configuration
process
■■Service & Support Portal for comprehensive technical information on configuration
and system documentation
Promotion website
Newsletter portal
Information and Download Center
Industry Mall
Software
for Industrial Controls
Product
information
Newsletter: always up to date
Constantly updated information on
the subjects of Industrial Controls
www.siemens.com/
industrial-controls/
newsletter
Product selection
Easy download of catalogs and
information material
Our Information and Download
Center offers all current
■■ Catalogs
■■ Customer magazines
■■ Brochures
for download
www.siemens.com/
industrial-controls/
infomaterial
Industry Mall: platform for
e-business and product
information
Benefit from 24/7 access to our
comprehensive information and
ordering platform for the complete
Industrial Controls portfolio,
including:
■■ Selection tools, product and
system configurators
■■ Availability check
■■ Order tracking
www.siemens.com/
industrial-controls/
mall
Product selection
Product selection
Product & system engineering
Service & Support Portal
CAx-Data
www.siemens.com/
sirius
Product information
Service
Operation
Commissioning
Ordering
Configuration
Planning
Information
We thus provide you with a comfortable basis for optimizing your processes.
In short: Support for improved efficiency!
Comprehensive information on
Industrial Controls
Amongst others, rapid and targeted
provision of information on:
■■ SIRIUS Industrial Controls
Ensure your success with our
trendsetting system solutions!
Product documentation
Image database
SITRAIN Portal
Product training
Technical Assistance
Product hotline
www.siemens.com/
industrial-controls/
configurators
Product & system engineering
Product training
Software for Industrial Controls:
easy, fast and safe
Our software supports you
throughout all project phases – from
planning to parametrization, down
to operation.
■■ Parametrization and Configuration
with SIRIUS Industrial Controls
■■ Planning and Dimensioning
of electrical power distribution
systems with SIMARIS
www.siemens.com/
industrial-controls/
mall
www.siemens.com/
simaris
Product documentation
Online support: full-range
technical product information
24/7 access to comprehensive
technical information on our products
and systems to support you from the
planning to the configuration down to
the operation phase.
■■ Product data sheets, manuals/
operating instructions
■■ Certificates, characteristic curves,
downloads
■■ FAQs
www.siemens.com/
industrial-controls/
support
Technical Product Data for CAx Applications: immediate availability
of configuration-relevant CAx data
types for your CAD/CAE system
This DVD provides you with a comprehensive pool of configurationrelevant CAx data types.
■■ Commercial and technical product
master data
■■ 2-D dimension drawings, isometric
illustrations and 3-D models
■■ Product data sheets
■■ Tender specifications
CAx OnlineGenerator:
Easy download of
product image material
Our image database contains all
current
■■ Product images
■■ 2-D dimension drawings, isometric
illustrations and 3-D models
■■ Internal circuit diagrams
■■ Symbols
in diverse versions for free
download.
www.siemens.com/
industrial-controls/
picdb
Training: knowledge expansion
Our training offer both comprises
an overview as well as detailed
competencies regarding selected
products and systems. Amongst
others, you can expand your product
and system know-how of SIRIUS.
www.siemens.com/
sitrain
Or contact us
personally via the
information hotline:
via telephone:
+49 (911) 895 7575
via fax:
+49 (911) 895 7576
via e-mail:
[email protected]
www.siemens.com/
industrial-controls/
support
CAx-DVD:
Order no. E86060D1000-A207-A7-6300
(Industry Mall)
Product hotline
Technical Assistance:
competent Industrial Controls
expert consulting
We support you with all technical
enquiries regarding our products
and systems – both before and after
delivery.
■■ Product selection
■■ Old/new conversions, competitor
conversions
■■ Special versions, special
requirements
■■ Commissioning, operation
Tip: the Service & Support Portal,
including the FAQ database, can
be called up via www.siemens.
com/industrial-controls/technicalassistance. You can also directly
submit your support request to a
technical consultant.
www.siemens.com/
industrial-controls/
technical-assistance
Personally from
Mo. through Fr.
8.00 am to 5.00 pm
(CET)
via telephone:
+49 911 895 5900
via e-mail:
[email protected]
siemens.com
via fax:
+49 911 895 5907
43
Siemens AG
Industry Sector
Control Components and
Systems Engineering
P.O. Box 23 55
90713 FÜRTH
GERMANY
Subject to changes 08/13
Order No.: E20001-A380-P302-V8-7600
Dispo 27601
WÜ MP.R3.CL.0000.00.3.28 WS 08133.0
Printed in Germany
© Siemens AG 2012
The information provided in this brochure contains merely general descriptions or
characteristics of performance which in case of actual use do not always apply as
described or which may change as a result of further development of the products.
An obligation to provide the respective characteristics shall only exist if expressly
agreed in the terms of contract.
All product designations may be trademarks or product names of Siemens AG or
supplier companies whose use by third parties for their own purposes could violate
the rights of the owners.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement