3-Phase Voltage Monitor Model 201-XXX-DPDT Features:

3-Phase Voltage Monitor Model 201-XXX-DPDT Features:
3-Phase Voltage Monitor
Model 201-XXX-DPDT
Features:
•
•
•
•
•
•
•
•
•
•
•
Low voltage protection
Single-phase protection
Reverse-phase protection
Voltage unbalance protection
Two isolated Form C relays (DPDT)
Diagnostic LED
UL508 Listed
CE Marked
11-pin plug in; DIN rail or surface mount
5-year warranty
Made in the USA
The 201-XXX-DPDT is an 11-pin octal base plug-in voltage monitor
designed to protect 3-phase motors regardless of size. The 201100-DPDT is used on 95-120VAC, 50/60Hz motors and the 201200-DPDT is used on 190-240VAC, 50/60Hz motors to prevent
damage caused by incoming voltage problems. The units feature
two isolated sets of contacts that are ideal for use with two control
circuits with different voltages.
The unique microcontroller-based voltage and phase-sensing circuit
constantly monitors the voltages to detect harmful power line
conditions. When a harmful condition is detected, the MotorSaver’s
output relays are deactivated after a specified trip delay. The output
relays reactivate after power line conditions return to an acceptable
level and a specified amount of time has elapsed (restart delay). The
trip delay prevents nuisance tripping due to rapidly fluctuating
power line conditions.
This unit is also available with a shorter trip delay and faster restart
delay. The 201-XXX-DPDT-60mS has a trip delay of 0.5 seconds
and a restart delay of 60 milliseconds. See the specification table
for details.
(605) 348.5580 / (800) 843.8848 / Fax (605) 348.5685
[email protected] / [email protected]
Rev. 0809
Specifications
Functional Characteristics
Enclosure Dimensions
90% +1%
93% +1%
3
6%
4.5%
4
2
5
1
6
11
4 seconds
2 seconds
0.5 second
1.75”
(44.55)
9
8
10
7
Adjustments/Settings
Low Voltage (% of setpoint)
Trip
Reset
Voltage Unbalance
Trip
Reset
Trip Delay Times
Low voltage
Unbalanced voltage and single-phasing faults (>15%UB)
Models with -60mS option
Restart Delay Times
After a fault
After a complete power loss
Models with -60mS option
2 seconds
2 seconds
60 milliseconds
Input Characteristics
2.375”
(60.331)
Supply Voltage
201-100-DPDT
201-200-DPDT
Frequency
95-120VAC
190-240VAC
50/60 Hz (note: 50Hz will increase all delay timers by 20%)
BOTTOM
Output Characteristics
Output Contact Rating - DPDT
Pilot Duty
General Purpose
480VA @ 240VAC
10A @ 240VAC
General Characteristics
Operating Temperature (Surrounding Air)
Maximum Input Power
Relative Humidity
Terminal Torque
Wire Gauge
Standards Passed
Electrostatic Discharge (ESD)
Models with -60mS option
Radio Frequency Immunity (RFI), Radiated
Fast Transient Burst
Models with -60mS option
Surge Immunity
IEC
ANSI/IEEE
Hi-potential Test
Safety Marks
UL listed (OT11 octal socket required)
CE
Dimensions
Weight
Mounting Method
How to order:
Part Number:
-40o to 70o C (-40o to 158o F)
5W
10-95%, non-condensing per IEC 68-2-3
12 in.-lbs.
12-22 AWG Solid or stranded
4.125”
(104.65)
IEC 61000-4-2, Level 3, 6kV contact, 8kV air
IEC 61000-4-2, 3kV contact, 6kV air
150MHz, 10V/m
IEC 61000-4-4, Level 3, 3.5 kV input power and controls
IEC 61000-4-4, Level 3, 2.5kV input power and controls
IEC 61000-4-5, Level 3, 4kV line-to-line; Level 4, 4kV line-toground
C62.41 Surge and Ring Wave Compliance to a level of 6kV
line-to-line
Meets UL508 (2 x rated V + 1000V for 1 minute)
UL508 (File #E68520)
IEC 60947-6-2
2.330”H x 2.375”W x 4.125”D (with socket)
1.2 lbs.
Plugs into 11-Pin OT11 Socket (DIN rail or surface mount)
201-100-DPDT
201-200-DPDT
201-100-DPDT-60mS
201-200-DPDT-60mS
SIDE
WITH OT11* SOCKET
Auxiliary Products:
OT11-PC (11-pin octal socket)
(605) 348.5580 / (800) 843.8848 / Fax (605) 348.5685
[email protected] / [email protected]
Rev. 0809