datasheet for 713200115 by SenGenuity

datasheet for 713200115 by SenGenuity
SM-S4xx-G
Wireless SAW Temperature Sensor Module
6 Sensor System
Key Features
Typical Applications
• Temperature Range: -20°C ... +120°C
• Center Frequency: 429.503 to 436.503 MHz
• Temperature Coefficient of Frequency: 17.35 ppm/K
• Switchgear where Bolt mounting is desired
• Applications where access is limited or restricted
• Applications where providing power to sensors is difficult
Measurement Conditions
•
•
•
•
Ambient Temperature:
Wireless Reader Tx Level:
Wireless Reader Tx Antenna Gain:
Wireless Reader Rx Threshold1:
25°C
-6 dBm
0 dBi
0 dB
Performance Specifications2
Parameter
Minimum Signal Strength1
(Reader Hardware Rx Readout)
Typical Value
Tolerance/Limit
22 dB
min. 15 dB
Centre frequency [fs]
(Reader hardware frequency readout)
± 75 kHz
SM-S429-G
SM-S431-G
SM-S432-G
SM-S433L-G
SM-S435-G
SM-S436-G
Time Domain Slope3
429.503 MHz
430.903 MHz
432.303 MHz
433.703 MHz
435.103 MHz
436.503 MHz
1.3 dB/μs
-
Operating Temperature Range [OTR]
-
-200C to 1200C
Storage Temperature Range
-
-400C to 1200C
4
Temperature Coefficient of Frequency [TCf ]
17.35 ppm/K
-
Temperature Error due to Aging5 within OTR
0.29 K
max. -2K to 2K
Notes:
1. In reference to internal reader signal level.
2. Under conditions specified in the Measurement Environment (see following pages). Specifications for the sensor have been established by using the SenGenuity WSR-T2 Wireless SAW Reader. See reader specification sheet
for information on standard set up of reader hardware.
3. Decay of time domain response envelope, measured with 4MHz span around center (resonant) frequency.
4. Δf[Hz] = TCf(ppm/K) x (T - To) x fS[MHz]
5. For 1000h continuous operation at maximum operating temperature.
Page 1 of 4
Telefilter GmbH, Potsdamer Strasse 18, 14513 Teltow, Germany | Phone: (+49) 3328 4784-0 | E-Mail: tft@telefilter.com
|
www.sengenuity.com
Typical Temperature Error (Maximum Operating Temperature)
Sensor Characteristics (Temperature Characteristics and Time Domain Response)
Page 2 of 4
Telefilter GmbH, Potsdamer Strasse 18, 14513 Teltow, Germany | Phone: (+49) 3328 4784-0 | E-Mail: tft@telefilter.com
|
www.sengenuity.com
Dimensions in mm
Marking example
SM-S429-G
D26
SENGENUITY
Item#
SM-S429-G
Datecode: Year + Week
D
2013
E
2014
F
2015
Description & Ordering code
Marking
1
713200113 Sensormodul-SM-S433L-G-Standard (Bolt Mount 2)
SM-S433L-G
2
713200114 Sensormodul-SM-S436-G-Standard (Bolt Mount 2)
SM-S436-G
3
713200115 Sensormodul-SM-S435-G-Standard (Bolt Mount 2)
SM-S435-G
4
713200116 Sensormodul-SM-S432-G-Standard (Bolt Mount 2)
SM-S432-G
5
713200117 Sensormodul-SM-S431-G-Standard (Bolt Mount 2)
SM-S431-G
6
713200118 Sensormodul-SM-S429-G-Standard (Bolt Mount 2)
SM-S429-G
Circuit Diagram
Page 3 of 4
Telefilter GmbH, Potsdamer Strasse 18, 14513 Teltow, Germany | Phone: (+49) 3328 4784-0 | E-Mail: tft@telefilter.com
|
www.sengenuity.com
Stability Characteristics and Reliability
After the following tests the sensor shall meet the whole specification:
•
Shock:
500g, 1 ms, half sine wave, 3 shocks each plane;
DIN IEC 68 T2 - 27
•
Vibration:
10 Hz to 500 Hz, 0,35 mm or 5 g respectively, 1 octave per min, 10 cycles per plan, 3 plans;
DIN IEC 68 T2 - 6
•
Change of temperature:
-55 °C to 125°C / 15 min. each / 100 cycles;
DIN IEC 68 part 2 – 14 Test N
•
ESD:
MIL-STD-883E using coupling network of ISO 10605 and EN 6100-4-2;
HBM:250V
•
Impact Strength:
1J , rod pendulum, impact at upper edge of sensor module cap
(may occur only once in sensor module lifetime)
This sensor is RoHS compliant (2011/65/EU)
Measurement Environment
Specified electrical properties shall be measured under the following test conditions
1.
Ambient temperature:
25°C
2.
Humidity:
30% - 60%
3.
Distance sensor antenna to reader antenna:
80cm (signal path shall have minimum free 1st Fresnel zone)
4.
Anechoic environment:
Reflected RF signals (multipath echos) should be attenuated minimum 25 dB in
reference to direct signal between reader / sensor module
5.
Inband interferer:
Outside signals in the measured frequency range shall be attenuated by 40 dB in
reference to reader Tx signal power
6.
Sensor mounting:
Sensor module has to be mounted on a ground plane perpendicular to sensor
module antenna rotation axis
7.
Antenna alignment:
Rotation axis of sensor module and reader antenna have to be parallel and
perpendicular to transmission path
The frequency and signal level is influenced by reactive interaction to materials within the reactive near field, approximately 17.5 cm. For
a description of an example implementation of these requirements see application note Sensor Module Test Setup.
History
Version
Changes
Name
Date
A
B
C
generation of sensor module specification
updated sensor module marking in construction section
consolidate all 6 frequencies for -G sensor modules, low limit storage temp. to -40°C
T.Martens
T.Martens
R.Pfitzinger
30-06-2011
11-11-2011
30-09-2013
Product status and specifications are subject to change.
DISCLAIMER
Vectron International reserves the right to make changes to the product(s) and or information contained herein without notice. No liability is assumed as a result of their use or application.
No rights under any patent accompany the sale of any such product(s) or information.
REV. C
Page 4 of 4
Telefilter GmbH, Potsdamer Strasse 18, 14513 Teltow, Germany | Phone: (+49) 3328 4784-0 | E-Mail: tft@telefilter.com
|