null  null
Network Interface Appendix
®
Anybus CompactCom
BACnet/IP w. IT Functionality 2-Port
Doc.Id. HMSI-168-70
Rev. 1.21
Connecting DevicesTM
+$/067$'‡&+,&$*2‡.$5/658+(‡72.<2‡%(,-,1*‡0,/$12‡08/+286(‡&29(175<‡381(‡&23(1+$*(1
HMS Industrial Networks
Mailing address: Box 4126, 300 04 Halmstad, Sweden
Visiting address: Stationsgatan 37, Halmstad, Sweden
E-mail: [email protected]
Web: www.anybus.com
Important User Information
This document is intended to provide a good understanding of the functionality offered by BACnet/IP w. IT. The
document only describes the features that are specific to the Anybus CompactCom BACnet/IP w. IT Functionality
2-Port. For general information regarding the Anybus CompactCom, consult the Anybus CompactCom design
guides.
The reader of this document is expected to be familiar with high level software design, and communication systems in general. The use of advanced BACnet/IP w. IT-specific functionality may require in-depth knowledge in
BACnet/IP w. IT networking internals and/or information from the official BACnet/IP w. IT specifications. In such
cases, the people responsible for the implementation of this product should either obtain the BACnet/IP w. IT specification to gain sufficient knowledge or limit their implementation in such a way that this is not necessary.
Liability
Every care has been taken in the preparation of this manual. Please inform HMS Industrial Networks AB of any
inaccuracies or omissions. The data and illustrations found in this document are not binding. We, HMS Industrial
Networks AB, reserve the right to modify our products in line with our policy of continuous product development.
The information in this document is subject to change without notice and should not be considered as a commitment by HMS Industrial Networks AB. HMS Industrial Networks AB assumes no responsibility for any errors that
may appear in this document.
There are many applications of this product. Those responsible for the use of this device must ensure that all the
necessary steps have been taken to verify that the applications meet all performance and safety requirements including any applicable laws, regulations, codes, and standards.
HMS Industrial Networks AB will under no circumstances assume liability or responsibility for any problems that
may arise as a result from the use of undocumented features, timing, or functional side effects found outside the
documented scope of this product. The effects caused by any direct or indirect use of such aspects of the product
are undefined, and may include e.g. compatibility issues and stability issues.
The examples and illustrations in this document are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular implementation, HMS Industrial Networks AB cannot
assume responsibility for actual use based on these examples and illustrations.
Intellectual Property Rights
HMS Industrial Networks AB has intellectual property rights relating to technology embodied in the product described in this document. These intellectual property rights may include patents and pending patent applications
in the US and other countries.
Trademark Acknowledgements
Anybus ® is a registered trademark of HMS Industrial Networks AB. All other trademarks are the property of their
respective holders.
Warning:
This is a class A product. in a domestic environment this product may cause radio interference in
which case the user may be required to take adequate measures.
ESD Note: This product contains ESD (Electrostatic Discharge) sensitive parts that may be damaged if ESD
control procedures are not followed. Static control precautions are required when handling the product. Failure to observe this may cause damage to the product.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port Network Interface Appendix
Rev 1.21
Copyright© HMS Industrial Networks AB
Apr 2013 Doc Id HMSI-168-70
Table of Contents
Table of Contents
Preface
About This Document
Related Documents.................................................................................................................................. 1
Document History ................................................................................................................................... 1
Conventions & Terminology.................................................................................................................. 2
Sales and Support ..................................................................................................................................... 3
Chapter 1
About the Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
General....................................................................................................................................................... 4
Features...................................................................................................................................................... 4
Front View ................................................................................................................................................ 5
Chapter 2
Tutorial
Introduction .............................................................................................................................................. 6
Implementation ........................................................................................................................................ 6
Fieldbus Conformance Notes ................................................................................................................ 6
Certification............................................................................................................................................... 6
Chapter 3
Basic Operation
General Information................................................................................................................................ 7
Software Requirements ..................................................................................................................... 7
Device Customization ............................................................................................................................. 8
Network Identity ............................................................................................................................. 8
Web Interface................................................................................................................................... 8
Socket Interface (Advanced Users Only)........................................................................................... 8
BACnet/IP Implementation .................................................................................................................. 9
Device Object ................................................................................................................................... 9
Analog Value Object..................................................................................................................... 11
Binary Value Object...................................................................................................................... 13
Multi-State Value Object .............................................................................................................. 14
Notification Class Object ............................................................................................................... 16
Supported BACnet Services ........................................................................................................... 17
BACnet Error Codes .................................................................................................................... 18
Communication Settings ....................................................................................................................... 19
Diagnostics .............................................................................................................................................. 19
Network Data Exchange....................................................................................................................... 20
Application Data (ADIs) ............................................................................................................. 20
Translation of Data Types ............................................................................................................. 20
Mapping of BACnet Objects to Anybus CompactCom................................................................... 21
Process Data.................................................................................................................................. 22
File System............................................................................................................................................... 22
General Information....................................................................................................................... 22
System Files................................................................................................................................... 23
Chapter 4
COV Notifications, Alarms and Events
General..................................................................................................................................................... 24
COV (Change of Value) Notifications ............................................................................................... 24
Alarm/Event Functionality .................................................................................................................. 24
Setup of Alarm and Events................................................................................................................... 26
Notification Class Object ............................................................................................................... 26
Analog Value Object..................................................................................................................... 28
Binary Value Object...................................................................................................................... 29
Multi-State Value Object .............................................................................................................. 30
Chapter 5
FTP Server
General Information.............................................................................................................................. 31
User Accounts ........................................................................................................................................ 31
Session Example..................................................................................................................................... 32
Chapter 6
Web Server
General Information.............................................................................................................................. 33
Default Web Pages................................................................................................................................. 33
Network Configuration .................................................................................................................. 34
Ethernet Statistics Page.................................................................................................................. 36
Server Configuration.............................................................................................................................. 38
General Information....................................................................................................................... 38
Index Page..................................................................................................................................... 38
Default Content Types ................................................................................................................... 39
Authorization................................................................................................................................ 39
Chapter 7
E-mail Client
General Information.............................................................................................................................. 40
How to Send E-mail Messages............................................................................................................. 40
Chapter 8
Server Side Include (SSI)
General Information.............................................................................................................................. 41
Include File.............................................................................................................................................. 41
Command Functions ............................................................................................................................. 42
General Information....................................................................................................................... 42
GetConfigItem()............................................................................................................................. 43
SetConfigItem().............................................................................................................................. 44
SsiOutput().................................................................................................................................... 46
DisplayRemoteUser ....................................................................................................................... 46
ChangeLanguage() ......................................................................................................................... 47
IncludeFile()................................................................................................................................... 48
SaveDataToFile().......................................................................................................................... 49
printf() ........................................................................................................................................... 50
scanf() ............................................................................................................................................ 52
Argument Functions.............................................................................................................................. 54
General Information....................................................................................................................... 54
ABCCMessage() ........................................................................................................................... 54
SSI Output Configuration..................................................................................................................... 58
Chapter 9
Anybus Module Objects
General Information.............................................................................................................................. 59
Anybus Object (01h).............................................................................................................................. 60
Network Object (03h) ........................................................................................................................... 61
Network Configuration Object (04h) ................................................................................................. 63
Socket Interface Object (07h) .............................................................................................................. 73
SMTP Client Object (09h) .................................................................................................................... 90
File System Interface Object (0Ah) ..................................................................................................... 95
Network Ethernet Object (0Ch)........................................................................................................ 108
Chapter 10
Host Application Objects
General Information............................................................................................................................ 109
Ethernet Host Object (F9h) ............................................................................................................... 110
BACnet Host Object (EFh)................................................................................................................ 112
Appendix A Categorization of Functionality
Basic ....................................................................................................................................................... 119
Extended................................................................................................................................................ 119
Advanced ............................................................................................................................................... 119
Appendix B Implementation Details
SUP-Bit Definition............................................................................................................................... 120
Anybus Statemachine........................................................................................................................... 120
Application Watchdog Timeout Handling ....................................................................................... 120
Implemented BACnet BIBBs............................................................................................................. 121
Appendix C HICP (Anybus IPconfig)
General................................................................................................................................................... 122
Operation............................................................................................................................................... 122
Appendix D Technical Specification
Protective Earth (PE) Requirements................................................................................................. 123
Power Supply ........................................................................................................................................ 123
Environmental Specification .............................................................................................................. 123
EMC Compliance................................................................................................................................. 123
Appendix E Timing & Performance
General Information............................................................................................................................ 124
Process Data ......................................................................................................................................... 125
Overview ...................................................................................................................................... 125
Anybus Read Process Data Delay (Anybus Delay)...................................................................... 125
Anybus Write Process Data Delay (Anybus Delay) .................................................................... 125
Network System Read Process Data Delay (Network System Delay)........................................... 126
Network System Write Process Data Delay (Network System Delay).......................................... 126
Appendix F Copyright Notices
Preface
P. About This Document
For more information, documentation etc., please visit the HMS website, ‘www.anybus.com’.
P.1 Related Documents
Document
Anybus-CompactCom Software Design Guide
Anybus-CompactCom Hardware Design Guide
Anybus-CompactCom Software Driver User Guide
BACnet specification, Doc. Id. 135, 2008
Author
HMS
HMS
HMS
ASHRAE
P.2 Document History
Summary of Recent Changes ( 1.20 ..... 1.21)
Change
Updated attribute 4 in BACnet Host Object
Updated description of HICP
Page(s)
113
122
Revision List
Revision
1.00
1.10
1.11
1.12
1.13
1.20
1.21
Date
2011-04-18
2011-06-21
2011-08-08
2011-10-26
2012-04-20
2012-09-10
2013-04-04
Author(s)
KeL
KeL
KaD
KeL
KeL
KeL
KeL
Chapter(s)
All
1, 3, 9, B
6
3, 9, 10
1
3, 10, E
10, C
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Description
First release
Minor corrections and updates
Minor addition
Minor updates
Minor correction
Update and corrections
Minor updates
Doc.Id. HMSI-168-70
About This Document 2
P.3 Conventions & Terminology
The following conventions are used throughout this manual:
•
Numbered lists provide sequential steps.
•
Bulleted lists provide information, not procedural steps.
•
The terms ‘Anybus’ or ‘module’ refers to the Anybus-CompactCom module.
•
The terms ‘host’ or ‘host application’ refers to the device that hosts the Anybus module.
•
Hexadecimal values are written in the format NNNNh, where NNNN is the hexadecimal value.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
About This Document 3
P.4 Sales and Support
Sales
Support
HMS Sweden (Head Office)
E-mail:
[email protected]
E-mail:
[email protected]
Phone:
+46 (0) 35 - 17 29 56
Phone:
+46 (0) 35 - 17 29 20
Fax:
+46 (0) 35 - 17 29 09
Fax:
+46 (0) 35 - 17 29 09
Online:
www.anybus.com
Online:
www.anybus.com
HMS North America
E-mail:
[email protected]
E-mail:
[email protected]
Phone:
+1-312 - 829 - 0601
Phone:
+1-312-829-0601
Toll Free:
+1-888-8-Anybus
Toll Free:
+1-888-8-Anybus
Fax:
+1-312-629-2869
Fax:
+1-312-629-2869
Online:
www.anybus.com
Online:
www.anybus.com
HMS Germany
E-mail:
[email protected]
E-mail:
[email protected]
Phone:
+49 (0) 721-989777-000
Phone:
+49 (0) 721-989777-000
Fax:
+49 (0) 721-989777-010
Fax:
+49 (0) 721-989777-010
Online:
www.anybus.de
Online:
www.anybus.de
HMS Japan
E-mail:
[email protected]
E-mail:
[email protected]
Phone:
+81 (0) 45-478-5340
Phone:
+81 (0) 45-478-5340
Fax:
+81 (0) 45-476-0315
Fax:
+81 (0) 45-476-0315
Online:
www.anybus.jp
Online:
www.anybus.jp
E-mail:
[email protected]
E-mail:
[email protected]
Phone:
+86 (0) 10-8532-3183
Phone:
+86 (0) 10-8532-3023
Fax:
+86 (0) 10-8532-3209
Fax:
+86 (0) 10-8532-3209
Online:
www.anybus.cn
Online:
www.anybus.cn
E-mail:
[email protected]
E-mail:
[email protected]
Phone:
+39 039 59662 27
Phone:
+39 039 59662 27
Fax:
+39 039 59662 31
Fax:
+39 039 59662 31
Online:
www.anybus.it
Online:
www.anybus.it
HMS China
HMS Italy
HMS France
E-mail:
[email protected]
E-mail:
[email protected]
Phone:
+33 (0) 3 68 368 034
Phone:
+33 (0) 3 68 368 033
Fax:
+33 (0) 3 68 368 031
Fax:
+33 (0) 3 68 368 031
Online:
www.anybus.fr
Online:
www.anybus.fr
HMS UK & Eire
E-mail:
[email protected]
E-mail:
[email protected]
Phone:
+44 (0) 1926 405599
Phone:
+46 (0) 35 - 17 29 20
Fax:
+44 (0) 1926 405522
Fax:
+46 (0) 35 - 17 29 09
Online:
www.anybus.co.uk
Online:
www.anybus.com
HMS Denmark
E-mail:
[email protected]
E-mail:
[email protected]
Phone:
+45 (0) 35 38 29 00
Phone:
+46 (0) 35 - 17 29 20
Fax:
+46 (0) 35 17 29 09
Fax:
+46 (0) 35 - 17 29 09
Online:
www.anybus.com
Online:
www.anybus.com
HMS India
E-mail:
[email protected]
E-mail:
[email protected]
Phone:
+91 (0) 20 40111201
Phone:
+91 (0) 20 40111201
Fax:
+91 (0) 20 40111105
Fax:
+91 (0) 20 40111105
Online:
www.anybus.com
Online:
www.anybus.com
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Chapter 1
1. About the Anybus CompactCom BACnet/IP w.
IT Functionality 2-Port
1.1 General
The Anybus-CompactCom BACnet/IP 2-port communication module provides instant BACnet and
BACnet/IP connectivity via the patented Anybus-CompactCom host interface. Any device that supports this standard can take advantage of the features offered by the module, allowing seamless network
integration regardless of network type. The module supports linear network topology.
Furthermore, the BACnet Object can be customized, allowing the end product to appear as a vendorspecific implementation rather than a generic Anybus module.
This product conforms to all aspects of the host interface for Active modules defined in the AnybusCompactCom Hardware- and Software Design Guides, making it fully interchangeable with any other
device following that specification. Generally, no additional network related software support is needed,
however in order to be able to take full advantage of advanced network specific functionality, a certain
degree of dedicated software support may be necessary.
1.2 Features
•
Fulfills all requirements for a BACnet/IP device
•
Two BACnet/IP ports
•
Data sharing
•
Linear network topology supported
•
10/100Mbit, full/half duplex operation
•
Web server w. customizable content
•
FTP server
•
E-mail client
•
Server Side Include (SSI) functionality
•
Customizable Identity Information
•
256 ADIs available in simple mode for mapping to BACnet objects
•
A total of 2040 ADIs available in advanced mode for mapping to BACnet objects
•
Transparent Socket Interface
•
Change Of Value (COV) notification and Alarm/Event functionality supported (max 256 ADIs
available)
•
Support for Foreign Device Registration functionality
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
About the Anybus CompactCom BACnet/IP w. IT Functionality
1.3 Front View
#
1
2
3
4
5
6
Item
Network Status LED
Module Status LED
Ethernet Interface, Port 1
Ethernet Interface, Port 2
Link/Activity Port 1
Link/Activity Port 2
5
6
1
2
3
4
Network Status LED
Note: A test sequence is performed on this LED during startup.
LED State
Off
Green
Green, flashing
Red
Red, flashing
Description
No power or no IP address
• On-line, one or more BACnet messages have arrived
• Module has active COV subscriptions
• At least one value object has one or more events enabled
On-line, waiting for first BACnet message.
Duplicate IP address, FATAL error
• Connection timeout. No BACnet message has been received within the configured
‘process active timeout’ time.
• A COV or Alarm/Event notification could not be sent to its recipient.
Module Status LED
Note: A test sequence is performed on this LED during startup.
LED State
Off
Green
Red/green, alternating
Red
Red, flashing
Description
No power
Normal operation
Firmware update from file system in progress
Major fault (EXCEPTION-state, FATAL error etc.)
Recoverable fault(s)
Link/Activity LED 5/6
LED State
Off
Green
Green, flickering
Yellow
Yellow, flickering
Description
No link, no activity
Link (100 Mbit/s) established
Activity (100 Mbit/s)
Link (10 Mbit/s) established
Activity (10 Mbit/s)
Ethernet Interface
The Ethernet interface supports autonegotiation and Auto MDI-X, with 10/100Mbit, full or half duplex
operation.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Chapter 2
2. Tutorial
2.1 Introduction
This chapter is a complement to the Anybus CompactCom Implementation Tutorial. The tutorial describes and explains a simple example of an implementation with Anybus CompactCom. This chapter
includes network specific settings that are needed for a host application to be up and running and possible to test for use on BACnet/IP w. IT networks.
2.2 Implementation
It is recommended to enable attribute 7 (“Support advanced mapping”) to fully take advantage of the
functionality and flexibility of the module.
See also ...
•
“Application Data (ADIs)” on page 20
•
“Mapping of BACnet Objects to Anybus CompactCom” on page 21
•
“BACnet Host Object (EFh)” on page 112
2.3 Fieldbus Conformance Notes
•
BACnet International does not require a certification for the use of BACnet products.
•
The Anybus-CompactCom BACnet/IP has not been tested by BACnet International. However
it is recommended to test the final product for conformance with BACnet/IP.
•
To enable the product to appear as a vendor specific implementation rather than a generic Anybus module, customize the information in the BACnet Object.
2.4 Certification
HMS Industrial Networks will not certify the Anybus CompactCom BACnet/IP w. IT Functionality 2Port.
The module is implemented as a BACnet Application Specific Controller (B-ASC). Even though HMS
Industrial Networks will not certify the module, the implementation fulfills the requirements for certification as a B-ASC. See “Implemented BACnet BIBBs” on page 121 for a complete list of BACnet
BIBBs implemented in the module.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Chapter 3
3. Basic Operation
3.1 General Information
3.1.1 Software Requirements
Generally, no additional network support code needs to be written in order to support the Anybus-CompactCom BACnet/IP. However, due to the nature of the BACnet/IP networking system, certain restrictions must be taken into account:
•
There is no support for arrays of data elements in the ADIs as all data on BACnet is represented
as single units without any possibility to access data in any other way.
•
Data types UINT64 and SINT64 cannot be represented on BACnet.
•
It is not possible to map read process data.
For in-depth information regarding the Anybus-CompactCom software interface, consult the general
Anybus-CompactCom Software Design Guide.
See also...
•
Anybus-CompactCom Software Design Guide, ‘Application Data Object (FEh)’
•
“Network Object (03h)” on page 61
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Basic Operation 8
3.2 Device Customization
3.2.1 Network Identity
By default, the module uses the following identity settings:
•
Vendor Name:
“HMS Industrial Networks”
•
Vendor ID:
01E6h (HMS Industrial Networks)
•
Model Name:
“Anybus CompactCom”
•
Object Name:
“Controller”
•
Network Type:
009Ah (“BACnet/IP”)
•
Product Name:
‘Anybus-CompactCom BACnet/IP’
Optionally, it is possible to customize the identity of the module by implementing the corresponding
instance attributes in the BACnet Host Object.
See also...
•
“BACnet Host Object (EFh)” on page 112 (Host Application Object)
•
“Network Object (03h)” on page 61 (Anybus Module Object)
3.2.2 Web Interface
The web interface can be fully customized to suit a particular application. Data and web pages are stored
in a FLASH-based file system, which can be accessed using any standard FTP-client.
See also...
•
“File System” on page 22
•
“FTP Server” on page 31
•
“Web Server” on page 33
3.2.3 Socket Interface (Advanced Users Only)
The built-in socket interface allows additional protocols to be implemented on top of TCP/IP.
See also...
•
“Socket Interface Object (07h)” on page 73 (Anybus Module Object)
•
“Message Segmentation” on page 102
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Basic Operation 9
3.3 BACnet/IP Implementation
The module is implemented as a B-ASC (BACnet Application Specific Controller). It supports the following BACnet objects:
Object Name
Device object
Analog Value object
Binary Value object
Multi-state Value object
Notification Class object
Class
8
2
5
19
15
Described on page
9
11
13
14
16
Each Anybus CompactCom BACnet/IP module contains one Device object and six Notification Class
objects. These objects are fixed and can not be changed by the application.
The Analog Value, Binary Value, and Multi-State Value objects and their data are mapped against the
ADIs in the Application Data object.
The BACnet Interoperability Building Blocks (BIBBs), that are implemented in the module, are listed in
appendix B.
See also...
•
“Network Data Exchange” on page 20
•
Application Data Object (see Anybus-CompactCom Software Design Guide)
•
“Implemented BACnet BIBBs” on page 121
3.3.1 Device Object
The Device object contains information about the module as a node on a BACnet network. Apart from
the value of the Object_Identifier, the values of the properties in the object can not be changed by the
application directly. Some values can be changed by setting the corresponding attributes in the BACnet
Host object.
Property Identifier
Object_Identifier
Object_Nameb
Object_Type
System_Status
Vendor_Nameb
Vendor_Identifierb
Model_Nameb
Firmware_Revisionb
NVa Description/Comment
N/A
R/W
The instance number portion (device instance) of
this property is affected when the value attribute of
Instance 3 in the Network Configuration Object is
changed.
“Controller”
R/W*
*This property can be written to only if the Object
Name in the BACnet Host object can be set.
DEVICE
R
- NON_OPERATION R
The status of the system is reported as
AL
NON_OPERATIONAL if the Anybus CompactCom
- OPERATIONAL
module has entered the ERROR state. Otherwise
the state is reported as OPERATIONAL.
“HMS Industrial Net- R
works”
486
R
HMS Industrial Networks
Value
R/W
“”Anybus-CompactCom”
N/A
R
Application_Software_Revision N/A
Protocol_Version
1
Protocol_Revision
7
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
R
Firmware revision of the Anybus CompactCom
BACnet/IP as a string.
R
R
R
Doc.Id. HMSI-168-70
Basic Operation 10
Property Identifier
Value
R/W
Protocol_Service_Supported
1001 0100 0000 1011 R
1100
1000 0010 0000 1110
0001
Protocol_Object_Types_Suppo 0010 0100 1000 0001 R
rted
0001 0000
Object_List
NVa Description/Comment
Bit map stating what protocol services are supported in the object, see “Supported BACnet Services” on page 17.
Bit map stating what object types are supported in
the object (analog-value, binary-value, multi-state
value, device, and notification-class objects).
This list is filled based on the ADIs that are implemented in the application.
R
Max_APDU_Length_Accepted 1476
R
Segmentation_Supported
SUPPORTED_BOTH R
Segmentation supported for both Rx and Tx
APDU.
Number of maximum length APDUs that can be
received in a segmented message. This is the
maximum APDU payload in a request after segmentation.
The local time is synchronized from the application
at power up or set from the BACnet network via
the TimeSynchronization service.
The local date is synchronized from the application at power up or set from the BACnet network
via the TimeSynchronization service.
Max_Segments_Accepted
22
R
Local_Time
N/A
R
Local_Date
N/A
R
APDU_Timeouta
NV
APDU transaction timeout (ms).c
NV
Device_Address_Binding
10000 (default)
R/W
Valid range: 0 - 65535
3 (default)
R/W
Valid range: 0 - 255
N/A
R
Database_Revisiona
N/A
NV
Number of APDU transaction and/or segment
retransmission retries.
Managed by the APL layer and contains the list of
all device address bindings of active client processes inside the Anybus CompactCom BACnet/IP
module.
Incremented by 1 each time an object identifier is
changed or the name of a BACnet object is
changed.
APDU_Segment_Timeouta
5000 (default)
R/W
Valid range: 0 - 65535
R
Number_Of_APDU_Retriesa
Active_COV_Subscriptions
R
NV
APDU segment timeout (ms).c
Populated based on active COV subscription
(max. 60) entries in AE module. Registered with
SubscribeCOV service.
a. Properties that are stored in non volatile memory, keep their assigned values when the module is turned off.
b. This property can be changed by setting the corresponding attribute in the BACnet Host object, see page 112.
c. The value 0 is only valid if Number_Of_APDU_Retries = 0.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Basic Operation 11
3.3.2 Analog Value Object
The analog value object is mapped to ADIs of data types that represent analog values, e.g. UINT16.
See also ...
•
“Mapping of BACnet Objects to Anybus CompactCom” on page 21
Property Identifier
Value (default)
Object_Identifier
Object_Name
N/A
N/A
Object_Type
Present_Value
ANALOG_VALUE
N/A
Status_Flags
F, F, F, F
Event_State
NORMAL (0)
Out_Of_Service
Units
COV_Incrementa
FALSE
NO_UNITS
0
Time_Delaya
0
Notification_Classa
0
High_Limita
0
Low_Limita
0
Deadbanda
0
Limit_Enablea
F, F
Event_Enablea
F, F, F
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
R/W NVa Description/Comment
R
R
In simple mode: Analog_Value_# (# = instance
number)
In advanced mode: Corresponding ADI name
If the host application for any reason returns an error
code when the ADI name is read, the BACnet device
class error code OPERATIONAL_PROBLEM is
returned to the network.
R
R/W
Corresponding ADI value converted to Real. If the host
application for any reason returns an error code, the
BACnet device class error code
OPERATIONAL_PROBLEM is returned to the network.
R
Bit string of Status flags indicating the status of the
object.
Bit 0: IN_ALARM
Bits 1 - 3: not used. Set to FALSE.
R
Valid states:
0: NORMAL
3: HIGH_LIMIT
4: LOW_LIMIT
R
Always FALSE
R
R/W NV Min. value: 0
Max. value: Corresponding ADI data type max value.
R/W NV Time delay for an event to be triggered after occurrence (s)
Min. value: 0
Max. value: UINT32max/1000
R/W NV Min. value: 0
Max. value: 5
R/W NV Min. value: Min. value of the ADI’s data type
R/W NV Max. value: Max. value of hte ADI’s data type
R/W NV Min. value: 0
Max. value: Corresponding ADI data type max value
R/W NV Bit string that determines what TO event limits are enabled
Bit 0: LOW_LIMIT_ENABLE
Bit 1: HIGH_LIMIT_ENABLE
R/W NV Bit string that determines what TO events that are enabled
Bit 0: TO-OFFNORMAL
Bit 1: not used. Set to FALSE.
Bit 2: TO-NORMAL
Doc.Id. HMSI-168-70
Basic Operation 12
Property Identifier
Value (default)
Notify_Typea
Alarm
Acked_Transitionsb
T, T, T
Event_Time_Stampsb N/A
R/W NVa Description/Comment
R/W NV Specifies the classification of an TO event that is sent
by this object.
0: ALARM
1: EVENT
R
Bit string that determines what TO events has been
acknowledged by a BACnet recipient.
Bit 0: TO-OFFNORMAL
Bit 1: TO-FAULT
Bit 2: TO-NORMAL
R
Array of BACnetTimeStamp that specifies the last TO
event stamp that was triggered.
(ArrayIdx 0: Number of elements)
ArrayIdx 1: TO-OFFNORMAL
ArrayIdx 2: TO-FAULT
ArrayIdx 3: TO-NORMAL
a. Properties that are stored in non volatile memory, keep their assigned values when the module is turned off. The
properties are only available if the corresponding ADI is mapped on the write process data channel and will be set
to default at a change in the write process data map. See also “Communication Settings” on page 19 and “Alarm/
Event Functionality” on page 24.
b. Only available if the corresponding ADI is mapped on the write process data channel.
Non volatile properties are kept in non volatile memory until the write process data map changes. After
a change to the write process data map, the BACnet object properties will be set to their default values.
Non volatile properties are saved to non volatile memory immediately after they are changed.
The Present_Value property is linked to the Value attribute of the corresponding ADI. A successful read
request from the network will return a value that will be converted to a BACnet Real value and returned
to the network. If an error is returned from the application, the BACnet device class error code
OPERATIONAL_PROBLEM is returned to the network.
When the Present_Value property is written from the network, the BACnet Real value is converted to
the data type of the corresponding ADI. For all data types, except FLOAT, all decimal precision is lost.
If error code Out of range or Attribute not settable is returned, the corresponding BACnet error code
will be returned to the network. Any other error code will be translated to
OPERATIONAL_PROBLEM.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Basic Operation 13
3.3.3 Binary Value Object
The binary value object is mapped to ADIs of data type BOOL.
See also ...
•
“Mapping of BACnet Objects to Anybus CompactCom” on page 21
Property Identifier
Value (default)
Object_Identifier
Object_Name
N/A
N/A
Object_Type
Present_Value
Status_Flags
BINARY_VALUE
N/A
F, F, F, F
Event_State
NORMAL
Out_Of_Service
Time_Delay
FALSE
0
Notification_Classa
0
Alarm_Valuea
INACTIVE (0)
Event_Enablea
N/A
Notify_Typea
Alarm
Acked_Transitionsb
T, T, T
a
Event_Time_Stampsb N/A
R/W NVa Description/Comment
R
R
In simple mode: Binary_Value_# (# = instance number)
In advanced mode: Corresponding ADI name
If read request for any reason returns a error code from
the application, the BACnet device class error code
OPERATIONAL_PROBLEM is returned to the network.
R
R/W
Corresponding ADI value
R
Bit string of Status flags indicating the status of the
object.
Bit 0: IN_ALARM
Bits 1 - 3: not used. Set to FALSE.
R
Valid states:
0: NORMAL
2: OFF_NORMAL
R
Always FALSE
R/W NV Time delay for an event to be triggered after occurrence (s)
R/W NV Min. value: 0
Max. value: 5
R/W NV
R/W NV Bit string that determines what TO event is enabled
Bit 0: TO-OFFNORMAL
Bit 1: not used. Set to FALSE.
Bit 2: TO-NORMAL
R/W NV Specifies the classification of an TO event that is sent
by this object.
0: ALARM
1: EVENT
R
Bit string that determines what TO events have been
acknowledged by a BACnet recipient.
Bit 0: TO-OFFNORMAL
Bit 1: TO-FAULT
Bit 2: TO-NORMAL
R
Array of BACnetTimeStamp that specifies the last TO
event stamp that was triggered.
(ArrayIdx 0: Number of elements)
ArrayIdx 1: TO-OFFNORMAL
ArrayIdx 2: TO-FAULT
ArrayIdx 3: TO-NORMAL
a. Properties that are stored in non volatile memory, keep their assigned values when the module is turned off. The
properties are only available if the corresponding ADI is mapped on the write process data channel and will be set
to default at a change in the write process data map. See also “Communication Settings” on page 19 and “Alarm/
Event Functionality” on page 24.
b. Only available if the corresponding ADI is mapped on the write process data channel.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Basic Operation 14
Non volatile properties are kept in non volatile memory until the write process data map changes. After
a change to the write process data map, the BACnet object properties will be set to their default values.
Non volatile properties are saved to non volatile memory immediately after they are changed.
The Present_Value property is linked to the Value attribute of the corresponding ADI. A successful read
request from the network will return a value that will be converted to a BACnet BinaryPV value and
returned to the network. If an error is returned from the application, the BACnet device class error code
OPERATIONAL_PROBLEM is returned to the network.
When the Present_Value property is written from the network, the BACnet BinaryPV value is converted
to Bool. If error code Out of range or Attribute not settable is returned, the corresponding BACnet error
code will be returned to the network. Any other error code will be translated to
OPERATIONAL_PROBLEM.
3.3.4 Multi-State Value Object
The multi-state value object is mapped to ADIs of data type ENUM.
See also ...
•
“Mapping of BACnet Objects to Anybus CompactCom” on page 21
Time_Delaya
R/W NVa Description/Comment
N/A
R
N/A
R
In simple mode: Multistate_Value_# (# = instance number)
In advanced mode: Corresponding ADI name
If a read request returns an error code from the application,
the BACnet device class error code
OPERATIONAL_PROBLEM is returned to the network.
MULTISTATE_VALUE R
N/A
R/W
Corresponding ADI value
F, F, F, F
R
Bit string of Status flags indicating the status of the object.
Bit 0: IN_ALARM
Bit 1: FAULT
Bits 2 - 3: not used. Set to FALSE.
NORMAL
R
Valid states:
0: NORMAL
1: FAULT
2: OFF_NORMAL
FALSE
R
Always FALSE
N/A
R
Corresponding ADI Max_Value + 1. If an error occurs when
reading the Max_value, this property will be set to 256.
0
R/W NV Time delay for an event to be triggered after occurrence (s)
Notification_Class
0
Alarm_Valuesa
Empty list
R/W NV Min. value: 0
Max. value: 5
R/W NV
Fault_Valuesa
Empty list
R/W NV
Event_Enablea
N/A
Notify_Typea
Alarm
R/W NV Bit string that determines what TO event is enabled
Bit 0: TO-OFFNORMAL
Bit 1: TO-FAULT
Bit 2: TO-NORMAL
R/W NV Specifies the classification of an TO event that is sent by this
object.
0: ALARM
1: EVENT
Property Identifier
Object_Identifier
Object_Name
Object_Type
Present_Value
Status_Flags
Event_State
Out_Of_Service
Number_Of_States
Value
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Basic Operation 15
R/W NVa Description/Comment
T, T, T
R
Bit string that determines the TO events that have been
Acked_Transitionsb
acknowledged by a BACnet recipient.
Bit 0: TO-OFFNORMAL
Bit 1: TO-FAULT
Bit 2: TO-NORMAL
b N/A
R
Array
of BACnetTimeStamp that specifies the last TO event
Event_Time_Stamps
stamp that was triggered.
(ArrayIdx 0: Number of elements)
ArrayIdx 1: TO-OFFNORMAL
ArrayIdx 2: TO-FAULT
ArrayIdx 3: TO-NORMAL
State_Text
N/A
R
This property is mapped against the module’s
Get_Enum_String service
b
NO_FAULT_DETECTE
R
Object reliability
Reliability
D
0: NO_FAULT_DETECTED
9: MULTI_STATE_FAULT
Property Identifier
Value
a. Properties that are stored in non volatile memory, keep their assigned values when the module is turned off. The
properties are only available if the corresponding ADI is mapped on the write process data channel and will be set
to default at a change in the write process data map. See also “Communication Settings” on page 19 and “Alarm/
Event Functionality” on page 24.
b. Only available if the corresponding ADI is mapped on the write process data channel.
Non volatile properties are kept in non volatile memory until the write process data map changes. After
a change to the write process data map, the BACnet object properties will be set to their default values.
Non volatile properties are saved to non volatile memory immediately after they are changed.
The Present_Value property is linked to the Value attribute of the corresponding ADI. A successful read
request from the network will return a value that will be converted to a BACnet Unsigned value, incremented by one1 and returned to the network. If an error is returned from the application, a BACnet device class error code OPERATIONAL_PROBLEM is returned to the network.
When the Present_Value property is written from the network, the BACnet Unsigned value is decremented by one. If error code Out of range or Attribute not settable is returned, the corresponding BACnet error code will be returned to the network. Any other error code will be translated to
OPERATIONAL_PROBLEM.
The State_Text property is linked to the Get_Enum_String service of the ADI. The property is an array
property, where array index 0 returns the number of states (see property Number_Of_States). All other
indices return the corresponding state text. Multistate states begin at 1, so the value is decremented by
1 and a Get_Enum_String command is sent to the corresponding ADI. If an error is returned from the
application, a BACnet device class error code OPERATIONAL_PROBLEM is returned to the network.
1. The ENUM ADI is zero based in the Anybus CompactCom, but the first state of a multistate value object
on BACnet is one.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Basic Operation 16
3.3.5 Notification Class Object
An Anybus CompactCom BACnet/IP module always contain 6 (0 - 5) instances of this object. Each
instance contains a list of devices that need to be informed about certain events and alarms.
See also ...
•
“COV Notifications, Alarms and Events” on page 24
Property Identifier
Value
R/W
Object_Identifier
N/A
Default: Notification_Class_#
(# = instance number)
NOTIFICATION_CLASS
N/A
Default: {3, 0, 0, 0}
Values 0 - 255 are allowed, a
lower value has higher priority than a higher value.
R
RW
Object_Namea
Object_Type
Notification_Class
a
Priority
R
R
Index 0: R
Index 1-3:
R/W
Ack_Requireda
Default: {0, 0, 0}
(0 = not set)
R/W
Recipient_Lista
N/A
R/W
Vendor property 600: Default: {0, 0, 0, ...}
Recipient_Error_Field (0 = not set)
R
NVa Description/Comment
NV BACnet Char string (only ANSIX34 supported).
Max. 30 characters
Equal to instance number
NV BACnet array of Unsigned values:
0: Number of Elements
1: TO-OFFNORMAL
2: TO-FAULT
3: TO-NORMAL
NV BACnet Bit string of 3 bits:
Bit 0: TO-OFFNORMAL
Bit 1: TO-FAULT
Bit 2: TO-NORMAL
NV BACnet list of BACnetDestination primitives.
There are 60 list entries available to be configured among the 6 Notification Class instances.
BACnet Bit string of a maximum of 60 bits.
The string has one bit per element present in
the Recipient_List. If a bit is set an event notification error is present for the corresponding
recipient entry in the Recipient_List property.
a. Non volatile. The default values of these properties are assigned by the Anybus CompactCom module the first
time the module is started. When a BACnet user requests to write any of these properties the data is saved to non
volatile memory directly after the validation of the service write request.
The Recipient_List specifies one or more recipients that a notification event should be sent to. In total
there are 60 list entries available to be divided among the 6 Notification Class object instances. These
are managed on a “pool” basis, and when all have been assigned to the Notification object instances, an
error is issued (CLASS_SERVICES, CODE_NO_SPACE_TO_ADD_LIST_ELEMENT).
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Basic Operation 17
3.3.6 Supported BACnet Services
The following services are supported by the Anybus CompactCom BACnet/IP w. IT Functionality 2Port.
Service
ReadProperty
ReadPropertyMultiple
WriteProperty
WritePropertyMultiple
Who-Is
Who-Has
I-Am
DeviceCommunicationControl
ReinitializeDevice
TimeSynchronization
SubscribeCOV
GetAlarmSummary
GetEventSummary
AcknowledgeAlarm
Description
Reads a single property from a BACnet object
Reads multiple properties from a BACnet object
Writes a single property to a BACnet object
Writes multiple properties to a BACnet object
Upon receipt of a Who-Is request the module will return an I-Am response containing its BACnet device object instance number.
The service is used to find out which devices are present on the network, and their addresses.
This service is used to find out what devices in a network are implementing a specific object.
The service uses either the object identifier or the object name for lookup.
Upon a receipt of a Who_Has request the module will return an I-Have response, if it implements the requested object.
This service is sent by the module in response to a matching Who-Is request. It is used to
locate BACnet devices based on the device object instance number.
Turns off the BACnet communication of the module. Once communication is disabled the module will only respond to DeviceCommunicationControl requests and ReinitializeDevice messages. If only initiation instead of all communication is disabled, the module will also respond to
Who-Is requests.
Resets devices over BACnet. A cold start results in a hardware reset. A warm start results in a
restart of the BACnet stack and data mapping will not be affected.
Synchronizes the current time and date of the module.
Subscribes for changes of value with a BACnet object. The ADI corresponding to the object
has to be mapped on write process data.
Responds with a list containing information about all active alarms.
Responds with a list containing information about all active alarms and events.
Acknowledges an active alarm.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Basic Operation 18
3.3.7 BACnet Error Codes
Device Class Error Codes
Error Code
OPERATIONAL_PROBLEM
Indicates
The application has generated a not expected response, e.g. reading the value attribute
of an ADI failed when performing ReadProperty on a value object.
Property Class Error Codes
Error Code
WRITE_ACCESS_DENIED
READ_ACCESS_DENIED
PROPERTY_IS_NOT_AN_ARRAY
INVALID_DATA_TYPE
VALUE_OUT_OF_RANGE
UNKNOWN_PROPERTY
INVALID_ARRAY_INDEX
CHARACTER_SET_NOT_SUPPORTED
DUPLICATE_NAME
OTHER
Indicates
Trying to write a non-writable property.
Trying to read a non-readable property.
Trying to read or write an array index of a property that is not an array.
Trying to write a property using the wrong data type.
The value written to a property is either too large or too small.
Trying to read a non-existent property.
Trying to read or write an array index that does not exist for the property.
Writing a char string property with a character set not supported by the
Anybus CompactCom module.
The value written to an Object_Name property already exists as an object
name for another object.
The Anybus CompactCom module encountered a general error.
Service Class Error Codes
Error Code
INCONSISTENT_PARAMETERS
INVALID_EVENT_STATE
INVALID_TIME_STAMP
SERVICE_REQUEST_DENIED
CHARACTER_SET_NOT_SUPPORTED
COMMUNICATION_DISABLED
COV_SUBSCRIPTION_FAILED
Indicates
Something went wrong while parsing the data in a WriteProperty request.
The event state supplied in an AcknowledgeAlarm request is not correct.
The time stamp supplied in an AcknowledgeAlarm request is not correct.
Generic error occurred for an AcknowledgeAlarm request
Wrong character set used for the password supplied with a ReinitializeDevice
or DeviceCommunicationControl request.
Received an invalid request for the current DeviceCommunicationControl
state.
• a SubscribeCOV request could not be completed due to lack of
resources
or
• it is not possible to set up the object for COV notification due to properties not being mapped on process-write data.
Object Class Error Codes
Error Code
UNKNOWN_OBJECT
NO_ALARM_CONFIGURED
OTHER
ABORT_BUFFER_OVERFLOW
UNKNOWN_OBJECT
OTHER
Indicates
The requested object does not exist in the Anybus CompactCom module.
There is no alarm or event to acknowledge for the event state supplied with
the AcknowlegeAlarm request.
Generic error during object request
Response APDU is too large.
The requested object does not exist in the Anybus CompactCom module.
The Anybus CompactCom module encountered a general error.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Basic Operation 19
Security Class Error Codes
Error Code
PASSWORD_FAILURE
Indicates
Wrong password for ReinitializeDevice or DeviceCommunicationControl
service.
3.4 Communication Settings
As with other Anybus-CompactCom products, network related communication settings are grouped in
the Network Configuration Object (04h).
In this case, this includes...
•
UDP
All data to and from the module is transported via UDP
•
TCP/IP settings
These settings must be set properly in order for the module to be able to participate on the network.
The module supports DHCP, which may be used to retrieve the TCP/IP settings from a DHCPserver automatically. DHCP is enabled by default, but can be disabled if necessary.
•
Physical Link Settings
By default, the module uses auto-negotiation to establish the physical link settings, however it is
possible to force a specific setting if necessary.
The parameters in the Network Configuration Object (04h) are available from the network through the
built-in web server.
See also...
•
“Web Server” on page 33
•
“Network Configuration Object (04h)” on page 63 (Anybus Module Object)
•
“HICP (Host IP Configuration Protocol)” on page 122
3.5 Diagnostics
Major unrecoverable faults are reported in the Diagnostic Object
See also...
•
“Diagnostic Object (02h)” on page 64 (Anybus Module Object)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Basic Operation 20
3.6 Network Data Exchange
3.6.1 Application Data (ADIs)
ADIs are represented through the BACnet objects. The properties of the BACnet objects are mapped
to instances in the Application Data Object on the host application side.
There are two mapping schemes, one simple and one advanced. The application decides what scheme
to use by implementing an attribute (#7, Support advanced mapping) in the BACnet Host Object. Accessible range of ADIs for the simple mapping scheme is 1 to 256. In the advanced mapping scheme,
there are 2040 analog value objects, 2040 binary value objects and 2040 multi-state value objects that can
be mapped to ADIs in any order. It is recommended to use advanced mapping to fully take advantage
of the functionality and flexibility of the module.
See also...
•
“Simple Mapping” on page 21
•
“Advanced Mapping” on page 21
•
“BACnet Host Object (EFh)” on page 112
3.6.2 Translation of Data Types
The Anybus data types are translated to BACnet standard and vice versa as follows:
Anybus Data Type
BOOL
ENUM
SINT8
UINT8
SINT16
UINT16
SINT32
UINT32
FLOAT
CHAR
BACnet Object Name
Binary Value Object
Multi-state Value Object
Analog Value Object
Analog Value Object
Analog Value Object
Analog Value Object
Analog Value Object
Analog Value Object
Analog Value Object
Analog Value Object
Comments
Each ADI element of this type occupies one byte.
Each ADI element of this type occupies two bytes.
Each ADI element of this type occupies four bytes.
Each ADI element of this type occupies one byte.
If an ADI of a size that doesn’t match the size of the Present Value property in a Value Object, is
mapped to a Value object, it will result in FAULT or in OPERATIONAL_PROBLEM when accessed.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Basic Operation 21
3.6.3 Mapping of BACnet Objects to Anybus CompactCom
Simple Mapping
In the simple mapping schema, that is implemented by default, the module will scan the first 256 implemented instances of the application data object during initialization. It will read the data type attribute
and based on the data type BACnet objects will be created in a sequential order, starting with 0. Anybus
CompactCom data types will be mapped to BACnet objects according to the table above. This mapping
will stay fixed. For an example see the figure below:
BV: Binary Value object
AV: Analog Value object
MSV: Multi-state Value object
BV#
0
1
2
3
ADI#
1 - BOOL
2 - BOOL
3 - UINT16
4 - BOOL
10 - UINT16
11 - UINT32
20 - BOOL
AV#
0
1
2
21 - ENUM
22 - ENUM
MSV#
0
1
Advanced Mapping
If the “Advanced mapping supported” attribute in the BACnet Host object is true, the user can create
almost any type of mapping of BACnet objects to Anybus CompactCom ADIs. This mapping can be
designed to closely match the application and it is up to the application to keep track of the ADI - BACnet object relationships. The services of the BACnet host object are then used to implement this mapping on BACnet. Valid range of object identifier number is 0 - 2039 for each value object type. For an
example see the figure below:
BV: Binary Value object
AV: Analog Value object
MSV: Multi-state Value object
BV#
100
200
ADI#
201
300
1 - BOOL
2 - BOOL
3 - UINT16
4 - BOOL
10 - UINT16
11 - UINT32
20 - BOOL
AV#
100
200
300
21 - ENUM
22 - ENUM
MSV#
100
801
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Basic Operation 22
3.6.4 Process Data
The Anybus CompactCom BACnet/IP supports COV (Change Of Value) notification and Alarm/
Event functionality, see “COV Notifications, Alarms and Events” on page 24. To be able to use these
features for a BACnet object, the corresponding ADI must be mapped on write process data. If not, the
module has no way of detecting any changes in the value of the ADI. Also, if an ADI is mapped on write
process data, the properties used for COV notifications and Alarms/Events will be accessible to the corresponding BACnet object. If the mapping is changed, all COV and Alarm/Event information, that has
been stored in non volatile memory, will be cleared.
No read process data is passed from the module to the application.
3.7 File System
3.7.1 General Information
Category: Extended
The built-in file system hosts 1.43 MByte of non volatile storage, which can be accessed by the HTTP
and FTP servers, the e-mail client, and the host application.
The file system uses the following conventions:
•
‘\’ (backslash) is used as a path separator
•
A ‘path’ originates from the system root and as such must begin with a ‘\’
•
A ‘path’ must not end with a ‘\’
•
Names may contain spaces (‘ ’) but must not begin or end with one.
•
Names must not contain one of the following characters: ‘\ / : * ? “ < > |’
•
Names cannot be longer than 48 characters
•
A path cannot be longer than 255 characters (filename included)
See also...
•
“FTP Server” on page 31
•
“Web Server” on page 33
•
“E-mail Client” on page 40
•
“Server Side Include (SSI)” on page 41
•
“File System Interface Object (0Ah)” on page 95
IMPORTANT: The file system is located in flash memory. Due to technical reasons, each flash segment can be erased
approximately 100000 times before failure, making it unsuitable for random access storage.
The following operations will erase one or more flash segments:
•
Deleting, moving or renaming a file or directory
•
Writing or appending data to an existing file
•
Formatting the file system
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Basic Operation 23
3.7.2 System Files
The file system contains a set of files used for system configuration. These files, known as “system files”,
are regular ASCII files which can be altered using a standard text editor (such as Notepad in Microsoft
Windows™). The format of these files are, with a few exceptions, based on the concept of ‘keys’, where
each ‘key’ can be assigned a value, see below.
Example:
[Key1]
value of Key1
[Key2]
value of Key2
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Chapter 4
4. COV Notifications, Alarms and Events
4.1 General
The Anybus CompactCom BACnet/IP supports COV (Change Of Value) notification and Alarm/
Event functionality. These features can only be used for a BACnet object if the corresponding ADI is
mapped on write process data. see “General” on page 24.
Note: If the mapping of the ADIs is changed, all COV and Alarm/Event information, that has been
stored in non volatile memory, will be cleared.
4.2 COV (Change of Value) Notifications
A BACnet device can subscribe for a COV (Change of value) notification from another BACnet device
on the network. The first device uses the service SubscribeCOV to send the identifier of the desired object to the second device to activate the notification. A change in the Present_value property will then
trigger a COV notification to the first BACnet device.
Each Value object is mapped to an ADI in the Anybus-CompactCom module, and the property
Present_value corresponds to the Value attribute in the ADI. If the ADI is not mapped on the write
process data area any change in the value will go unnoticed and a subscribeCOV service will return the
error code COV_SUBSCRIPTION_FAILED.
In Binary Value and Multi-State Value objects any change in the present value will cause a notification
to be sent. In Analog Value objects a property, COV_increment, is used to decide how much a present
value needs to change in order for a notification to be sent.
4.3 Alarm/Event Functionality
A change in the present value of an object can also be used to trigger an alarm or an event.
Each value object is associated to a Notification Class object instance. Each instance contains a list of
all recipients of a specific Alarm/Event notification. Alarms and events are handled in the same way by
the value objects. If an alarm or an event is to be issued is decided by the application in the property
Notify_Type in the value object and the choice indicates the severity of the notification to the recipient.
Alarms/events are issued every time a value object changes state. The reasons for changing states are
specific to each of the three value objects as described below. The possibility to issue an alarm or an
event has to be enabled in each object. It is also possible to delay an alarm/event using the Time_Delay
property of the object. As previously mentioned this functionality is only available if the ADIs are
mapped to write process data.
Notification Class Object Functionality
The Notification Class object is used to configure certain constraints in the functionality and the recipient list that is common to all objects that are associated to an instance of the Notification Class Object.
The Anybus CompactCom BACnet/IP w. IT module supports 6 instances of this object.
There are three object notifications (or events) that each indicate a transition from one state to another:
TO-OFFNORMAL, TO-FAULT, and TO-NORMAL. Every alarm/event triggered by a value object,
is represented as one of these. The interpretation depends on which value object was the origin of the
notification.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
COV Notifications, Alarms and Events 25
Analog Value Object Alarm/Event Functionality
An Analog Value object has three possible states: NORMAL, LOW_LIMIT and HIGH_LIMIT. The
LOW_LIMIT state is entered when the present value, object property Present_value, falls below the value in the object property Low_limit. The HIGH_LIMIT state is entered when the present value rises
above the value in the property High_limit. When the present value returns above or below the given
limit, the object returns to the NORMAL state.The OFF_NORMAL bit in the property Event_enable
must be set, to allow transitions to other states than the NORMAL state. The LOW_LIMIT and
HIGH_LIMIT bits in the property Limit_Enable must be set to allow transitions to the corresponding
state.
A change of state will result in either a TO-NORMAL event or a TO-OFFNORMAL event issued to
the Notification Class object instance. A TO-OFFNORMAL event indicates that the value of the property value has increased above the defined high limit or decreased below the defined low limit. A TONORMAL event indicates a return to the NORMAL state.
Binary Value Object Alarm/Event Functionality
A Binary Value Object has two states, NORMAL and OFF_NORMAL. An alarm value can be set and
when the property Present_Value is changed to this value, the object changes from the NORMAL state
to the OFF_NORMAL state. The corresponding bit(s) must be set in the property Event_Enable for
this functionality to be available.
A change of state will result in either a TO-NORMAL event or a TO-OFFNORMAL event issued to
the Notification Class object instance. A TO-OFFNORMAL event indicates that the value of the property value has changed to equal the alarm value. A TO-NORMAL event indicates a return to the NORMAL state.
Multi-State Value Object Alarm/Event Functionality
The Multi-State Value object contains one list for alarm values and one for fault values. When the property Present_Value is changed to a value that is present in the alarm value list, the object enters the
OFF_NORMAL state and a TO-OFFNORMAL event is issued. If the value is present in the fault values list, the object enters the FAULT state and a TO-FAULT event is issued. A TO-NORMAL event
is issued when the object returns to the NORMAL state from any of the other two states. The corresponding bit(s) must be set in the property Event_Enable for the functionality to be available.
Summary of states and events for the value objects.
Object
Analog Value Object
Binary Value Object
Multi State Value Object
State
NORMAL
HIGH_LIMIT
LOW_LIMIT
NORMAL
OFF_NORMAL
NORMAL
FAULT
OFF_NORMAL
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Possible events
TO-OFFNORMAL
TO-NORMAL
TO-OFFNORMAL
TO-NORMAL
TO-FAULT
TO-OFFNORMAL
TO-NORMAL
TO-OFFNORMAL
TO-NORMAL
TO-FAULT
Doc.Id. HMSI-168-70
COV Notifications, Alarms and Events 26
4.4 Setup of Alarm and Events
This section gives a short guide to what properties in the BACnet objects need to be setup and monitored when implementing the BACnet alarm/event functionality.
4.4.1 Notification Class Object
BACnet object notifications are classified as either TO-OFFNORMAL, TO-FAULT, or TO-NORMAL. Any event triggered by a BACnet value object is interpreted as one of these three.
See also...
•
“Notification Class Object” on page 16
Priority
This property defines how to prioritize the three different kinds of notifications/events that can be issued by an object. A lower value has priority over a higher value, e.g. setting Priority arrayidx 2 to 1 and
the other entries in the array to 5 and 76 will give TO-FAULT priority over the other notifications.
If all three events are given the same priority in the property, they will receive the following priority by
default:
1. TO-NORMAL
2. TO-FAULT
3. TO-OFFNORMAL
I.e. TO-NORMAL has the highest priority.
Ack Required
This property specifies if an acknowledgement is required from the recipients of a specific TO event.
Every TO event sent is flagged to tell the recipient whether an acknowledgement is required or not,
based on the corresponding TO bit in the bit string in this property.
Recipient List
This list specifies the BACnet recipients that shall receive a notification of an alarm/event associated
with the notification class. The list is a sequence of BACnetDestination primitives, where each entry
consists of the following elements:
Element
Transitions
IssueConfirmedNotifications
ProcessIdentifier
Recipient
Description
Bit string that determines what TO events shall be sent to this recipient.
Boolean that specifies if a ConfirmedEventNotification or UnConfirmedEventNotification request
shall be sent to the recipient.
Unsigned32 value that specifies the process identifier that is linked to the notification event. If an
acknowledgement is required for the specific event (see Ack_Required) the acknowledgement
source has to have a valid value of a recipient process identifier to successfully acknowledge the
alarm/event.
BACnetRecipient primitive that can either be a DeviceInstanceNumber or a BACnetMAC
address. The primitive will be added to the DAB (Device Address Binding) lookup mechanism of
the BACnet APL layer and who-is/I-am BACnet UnConfirmedServices will be used to probe for
the recipient device on BACnet. When a valid lookup is found the event notifications will be sent
to that device. If no valid probe is found the corresponding bit in VendorProperty: 600, BACnetRecipientErrorField will be set in the notification class.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
COV Notifications, Alarms and Events 27
Element
ToTime
FromTime
ValidDays
Description
BACNetTime primitive that specifies the ending time for when the recipient will accept event notifications. The contents must match the local RTC time or no event notifications will be sent to this
recipient entry.
BACNetTime primitive that specifies the starting time for when the recipient will accept event notifications. The contents must match the local RTC time or no event notifications will be sent to this
recipient entry.
BACnetDaysOfWeek that specifies the valid days of the week for when the recipient will accept
event notifications. The contents must match the local RTC time or no event notifications will be
sent to this recipient entry.
Vendor Property: 600, Recipient_Error_Field
This vendor specific property, added by HMS, holds a bit string that is used for diagnostics to determine
if a recipient has notification errors present or not. Bit 0 in the bit string represents recipient 1 in the
RecipientList property, bit 1 represents recipient 2, and so on.
If the bit for a recipient is set, one of the following error events are present:
•
The recipient device was not found on the BACnet network.
•
A ConfirmedEventNotification request sent to the recipient returns a negative acknowledge response or an internal timeout.
If a bit has been set, as a result of an error, the bit will be cleared when a successful notification event
has been sent or when the Recipient_List property has been updated with a new list of recipients.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
COV Notifications, Alarms and Events 28
4.4.2 Analog Value Object
Available TO events are TO-NORMAL and TO-OFFNORMAL. The object has three states, NORMAL, LOW_LIMIT and HIGH_LIMIT, but the TO events only reflect transitions to and from a normal state to a not normal state.
Object Properties to Setup:
Property
Notification Class
Event Enable
NotifyType
Limit Enable
High Limit
Low Limit
Deadband
Time Delay
Description
Unsigned value that specifies which Notification Class the alarm/event notification of this object is
associated to.
Bit string that defines what TO events will be enabled to send alarm/event notifications.
Enumeration that decides if a notification shall be an EVENT or an ALARM.
Bit string that enables/disables HIGH_LIMIT and LOW_LIMIT guarding.
BACnet real value (float) that specifies the upper limit of the normal value span where a
TO_OFFNORMAL event will be issued.
BACnet real value (float) that specifies the lower limit of the normal value span where a
TO_OFFNORMAL event will be issued.
BACnet real value (float) that specifies the deadband for the high and low limits
Unsigned value that specifies the time (ms) that will elapse before an event notification is triggered to be sent to its recipient.
Object Properties to Monitor:
Property
Event State
Event Time Stamps
Acked Transitions
Status Flags
Description
BACnet enum of the event state that specifies the current state of the object.
BACnet array of time stamps indicating when the last triggered events of each of the 3 different
TO states, occurred.
Bit string that specifies the TO event transitions that have been acknowledged by a notification
class recipient. It is enough if one recipient acknowledges an event for the corresponding TO bit
to be set. If no acknowledgement is required for the notification class the corresponding TO bit
will be set automatically.
Bit string of the status flags of the objects. If a TO-OFFNORMAL event is active the IN_ALARM
bit will be set.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
COV Notifications, Alarms and Events 29
4.4.3 Binary Value Object
Available TO events are TO-NORMAL and TO-OFFNORMAL.
Object Properties to Setup:
Property
Notification Class
Event Enable
NotifyType
Alarm Value
Time Delay
Description
Unsigned value that specifies which Notification Class the alarm/event notification of this object is
associated to.
Bit string that defines what TO events will be enabled to send alarm/event notifications.
Enumeration that decides if a notification shall be an EVENT or an ALARM.
BACnet BinaryPV enumeration that specifies when Present_Value is OFF_NORMAL, either 0
(inactive) or 1 (active).
Unsigned value that specifies the time (ms) that will elapse before an event notification is triggered to be sent to its recipient.
Object Properties to Monitor:
Property
Event State
Event Time Stamps
Acked Transitions
Status Flags
Description
BACnet enum of the event state that specifies the current state of the object.
BACnet array of time stamps indicating when the last triggered events of each of the2 different
TO states, occurred.
Bit string that specifies the TO event transitions that have been acknowledged by a notification
class recipient. It is enough if one recipient acknowledges an event for the corresponding TO bit
to be set. If no acknowledgement is required for the notification class the corresponding TO bit
will be set automatically.
Bit string of the status flags of the objects. If a TO-OFFNORMAL event is active the IN_ALARM
bit will be set.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
COV Notifications, Alarms and Events 30
4.4.4 Multi-State Value Object
Available TO events are TO-NORMAL, TO-OFFNORMAL, and TO-FAULT.
Object Properties to Setup:
Property
Notification Class
Event Enable
NotifyType
Alarm Valuesa
Fault Valuesa
Time Delay
Description
Unsigned value that specifies which Notification Class the alarm/event notification of this object is
associated to.
Bit string that defines what TO events will be enabled to send alarm/event notifications.
Enumeration that decides if a notification shall be an EVENT or an ALARM.
BACnet list of unsigned values that will trigger a TO-OFFNORMAL event.
BACnet list of unsigned values that will trigger a TO-FAULT event.
Unsigned value that specifies the time (ms) that will elapse before an event notification is triggered to be sent to its recipient.
a. If the same value is specified for the Alarm Values property as for the Fault Values property, both a
TO_OFFNORMAL and a TO_FAULT will be triggered.
Note: Any valid value, that is not listed in the Alarm Values and Fault Values properties, can generate a
TO-NORMAL event.
Object Properties to Monitor:
Property
Event State
Event Time Stamps
Acked Transitions
Status Flags
Reliability
Description
BACnet enum of the event state that specifies the current state of the object.
BACnet array of time stamps indicating when the last triggered events of each of the 3 different
TO states, occurred.
Bit string that specifies the TO event transitions that have been acknowledged by a notification
class recipient. It is enough if one recipient acknowledges an event for the corresponding TO bit
to be set. If no acknowledgement is required for the notification class the corresponding TO bit
will be set automatically.
Bit string of the status flags of the objects. If a TO-OFFNORMAL event is active the IN_ALARM
bit will be set. If a TO-FAULT event is active the FAULT bit will be set.
BACnet enumeration that is set to 9 (multi_state_fault) if a TO-FAULT event is active and 0
(no_fault_detected) otherwise.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Chapter 5
5. FTP Server
5.1 General Information
Category: extended
The built-in FTP-server makes it easy to manage the file system using a standard FTP client.
By default, the following port numbers are used for FTP communication:
•
TCP, port 20 (FTP data port)
•
TCP, port 21 (FTP command port)
The FTP server supports up to 8 concurrent connections.
5.2 User Accounts
User accounts are stored in the configuration file '\ftp.cfg'. This file holds the usernames, passwords,
and home directory for all users. Users are not able to access files outside of their home directory.
File Format:
User1:Password1:Homedir1
User2:Password2:Homedir2
User3:Password3:Homedir3
Optionally, the UserN:PasswordN-section can be replaced by a path to a file containing a list of users
as follows:
File Format (‘\ftp.cfg’):
User1:Password1:Homedir1
User2:Password2:Homedir2
\path\userlistA:HomedirA
\path\userlistB:HomedirB
The files containing the user lists shall have the following format:
File Format:
User1:Password1
User2:Password2
User3:Password3
Notes:
•
Usernames must not exceed 15 characters in length.
•
Passwords must not exceed 15 characters in length.
•
Usernames and passwords must only contain alphabetic characters and/or numbers.
•
If ‘\ftp.cfg’ is missing or cannot be interpreted, all user name/password combinations will be
accepted and the home directory will be the FTP root (i.e. ‘\ftp\’).
•
The home directory for a user must also exist in the file system if they should be able to log in,
just adding the user information to the 'ftp.cfg' file it is not enough.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
FTP Server 32
•
If ‘Admin Mode’ has been enabled in the Ethernet Object, all user name/password combinations
will be accepted and the user will have unrestricted access to the file system (i.e. the home directory will be the system root).
•
It is strongly recommended to have at least one user with root access (‘\’) permission. If not,
‘Admin Mode’ must be enabled each time a system file needs to be altered (including ‘\ftp.cfg’).
5.3 Session Example
The Windows Explorer features a built-in FTP client which can easily be used to access the file system
as follows:
1. Open the Windows Explorer by right-clicking on the ‘Start’-button and selecting ‘Explorer’
2. In the address field, type FTP://<user>:<password>@<address>
- Substitute <address> with the IP address of the Anybus module
- Substitute <user> with the username
- Substitute <password> with the password
3. Press enter. The Explorer will now attempt to connect to the Anybus module using the specified
settings. If successful, the file system will be displayed in the Explorer window.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Chapter 6
6. Web Server
6.1 General Information
Category: extended
The built-in web server provides a flexible environment for end-user interaction and configuration purposes. The powerful combination of SSI and client-side scripting allows access to objects and file system
data, enabling the creation of advanced graphical user interfaces.
The web interfaces are stored in the file system, which can be accessed through the FTP server. If necessary, the web server can be completely disabled in the Ethernet Host Object.
The web server supports up to 20 concurrent connections and communicates through port 80.
See also...
•
“FTP Server” on page 31
•
“Server Side Include (SSI)” on page 41
•
“Ethernet Host Object (F9h)” on page 110
6.2 Default Web Pages
The default web interface consists of a set of virtual files; these virtual files may be replaced, but not
permanently erased, by placing files with the same name in the same location (i.e. the web root).
The files can be used as-is or called
from a customized web environment.
index.htm
The files are:
<WebRoot>\style.css
<WebRoot>\arrow_red.gif
<WebRoot>\index.htm
<WebRoot>\netinfo.htm
<WebRoot>\netconfig.htm
<WebRoot>\netstat.htm
<WebRoot>\parameter.htm
<WebRoot>\language.htm
language.htm
parameter.htm
netinfo.htm
netconfig.htm
netstat.htm
Note: If none of these files are used, it is recommended to completely disable the virtual file system
altogether in the File System Interface Object.
See also...
•
“File System” on page 22
•
“File System Interface Object (0Ah)” on page 95
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Web Server 34
6.2.1 Network Configuration
The network configuration page provides an interface for changing TCP/IP and SMTP settings in the
Network Configuration Object.
Available editable settings will be explained on the next page.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Web Server 35
IP configuration
Name
IP address
Subnet mask
Gateway
Host name
Domain name
DNS 1
DNS 2
DHCP
Description
The TCP/IP settings of the module
Default values: 0.0.0.0
Value ranges: 0.0.0.0 - 255.255.255.255
The module needs a reset for the changes to take effect
IP address or name
Max 64 characters
Changes will take effect immediately
IP address or name
Max 48 characters
Changes will take effect immediately
Primary and secondary DNS server, used to resolve host name
Default values: 0.0.0.0
Value ranges: 0.0.0.0 - 255.255.255.255
Changes will take effect immediately
Checkbox for enabling or disabling DHCP
Default value: enabled
The module needs a reset for the changes to take effect
SMTP Settings
Changes to these settings will take effect immediately.
Name
SMTP Server
SMTP User
SMTP Pswd
Description
IP address or name
Max 64 characters
Max 64 characters
Max 64 characters
Ethernet Configuration
Changes to these settings will take effect immediately.
Name
Comm 1
Comm 2
Description
Ethernet speed/duplex settings
Default value: auto
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Web Server 36
6.2.2 Ethernet Statistics Page
The Ethernet statistics web page contains the following information:
Ethernet Link
Port 1
Port 2
Description
Speed:
The current link speed.
Duplex:
The current duplex configuration.
Speed:
The current link speed.
Duplex:
The current duplex configuration.
BACnet/IP Statistics
Description
SvrUnConfRxReqRecv
Number of UnConfirmed server requests received
SvrUnConfTxReqSent
Number of UnConfirmed server request sent
lCltUnConfTxReqSent
Number of UnConfirmed client request sent
BACnet APL (application layer)
Statistics
Description
TrActive
Active server transactions
(Available for both client and server transactions.=
TrActiveMax
Max active server transactions
TrTxSegSent
Number of tx segments sent
TrTxSegAckRecv
Number of tx ack received
TrTxSegNegAckRecv
Number of negative tx ack received
TrRxSegRecv
Number of rx segments received
TrRxSegAckSent
Number of rx segments ack sent
TrRxSegDupAckSent
Number of rx segments dup ack sent
TrRxSegNegAckSent
Number of rx segments neg ack sent
TrRxAPDURecv
Number of Confirmed trans received
TrTxAPDUSent
Number of Confirmed trans sent
TrTxSegTimeout
Number of tx segment timeouts
TrRxSegTimeout
Number of rx segment timeouts
TrImpDelete
Number of implicit deletes
TrTxTmoDelete
Number of tx timeout deletes
TrRxTmoDelete
Number of rx timeout deletes
TrRxAbortsRecv
Number of rx aborts received
TrTxAbortsRecv
Number of tx aborts received
TrAbortsSent
Number of transaction aborts sent
TrRejectsSent
Number of transaction rejects sent
TrErrorsSent
Number of transaction errors sent
BACnet AE (Alarm and Event)
Module statistics.
Description
iActiveCOVEntry
Number of active COV subscriptions
iMaxActiveCOVEntry
The maximum number of active COV subscriptions ever present since startup.
lCOVLifeEntryRefCnt
Number of COV subscriptions that have a lifetime enabled. When the lifetime elapses they will be automatically deleted,
lCOVTrAllocResumes
APL client transactions (confirmed requests) resource allocation resumes.
A needed resource was unavailable and a resume of the COV update process was scheduled.
lCOVNwMsgAllocResums
NWL client message resource allocation resumes.A needed resource was
unavailable and a resume of the COV update process was scheduled.
lCOVConfNotifys
Number of confirmed COV notifications sent.
iCOVUnConfNotifys
Number of unconfirmed COV notifications sent
iCOVConfNotifyErrors
Number of confirmed COV notification errors. A negative acknowledgement
or/and in timeout was returned to a confirmed COV to notify request.
iACtiveAEEvents
Number of currently active AE module events
iACtiveNCRecip
Number of active NC recipients assigned to a notification class
lAETrAllocResumes
APL client transactions (confirmed requests) resource allocation resumes.
A needed resource was unavailable and a resume of the AE update process was scheduled.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Web Server 37
BACnet/IP Statistics
Description
lAENwMsgAllocResumes
NWL client message resource allocation resumes.
lAEConfNotifys
Number of confirmed AE notifications sent
lAEUnConfNotifys
Number of unconfirmed AE notifications sent
lAEConfNotifyErrors
Number of confirmed AE notification errors. A negative acknowledgement
or/and an internal timeout was returned to a confirmed AE notify request.
lAEDABLookupErrors
Number of DAB (Device Address Binding) lookup errors. When an AE event
is about to be sent to a BACnet recipient and we don’t have an active binding against it (managed by who-is/i-am negotiations by the APL layer) this
error is issued every time a notification could not be sent.
Interface Counters
Description
In Octets:
Received bytes.
In Ucast Packets:
Received unicast packets.
In NUcast packets:
Received non-unicast packets (broadcast and multicast).
In Discards:
Received packets discarded due to no available memory buffers.
In Errors:
Received packets discarded due to reception error.
In Unknown Protos:
Received packets with unsupported protocol type.
Out Octets:
Sent bytes.
Out Ucast packets:
Sent unicast packets.
Out NUcast packets:
Sent non-unicast packets (broadcast and multicast).
Out Discards:
Outgoing packets discarded due to no available memory buffers.
Out Errors:
Transmission errors.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Web Server 38
6.3 Server Configuration
6.3.1 General Information
Category: advanced
Basic web server configuration settings are stored in the system file ‘\http.cfg’. This file holds the root
directory for the web interface, content types, and a list of file types which shall be scanned for SSI.
File Format:
•
The web server cannot access files outside this directory.
[WebRoot]
\web
[FileTypes]
FileType1:ContentType1
FileType2:ContentType2
...
FileTypeN:ContentTypeN
[SSIFileTypes]
FileType1
FileType2
...
FileTypeN
Web Root Directory
•
Content Types
A list of file extensions and their reported content
types.
See also...
- “Default Content Types” on page 39
•
SSI File Types
By default, only files with the extension ‘shtm’ are
scanned for SSI. Additional SSI file types can be
added here as necessary.
The web root directory determines the location of all files related to the web interface. Files outside of
this directory and its subdirectories cannot be accessed by the web server.
6.3.2 Index Page
The module searches for possible index pages in the following order:
1. <WebRoot>\index.htm
2. <WebRoot>\index.html
3. <WebRoot>\index.shtm
4. <WebRoot>\index.wml
Note 1: Substitute <WebRoot> with the web root directory specified in ‘\http.cfg’.
Note 2: If no index page is found, the module will default to the virtual index file (if enabled).
See also...
•
“Default Web Pages” on page 33
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Web Server 39
6.3.3 Default Content Types
By default, the following content types are recognized by their file extension:
File Extension
htm, html, shtm
gif
jpeg, jpg, jpe
png
js
bat, txt, c, h, cpp, hpp
zip
exe, com
wml
wmlc
wbmp
wmls
wmlsc
xml
pdf
css
Reported Content Type
text/html
image/gif
image/jpeg
image/x-png
application/x-javascript
text/plain
application/x-zip-compressed
application/octet-stream
text/vnd.wap.wml
application/vnd.wap.wmlc
image/vnd.wap.wbmp
text/vnd.wap.wmlscript
application/vnd.wap.wmlscriptc
text/xml
application/pdf
text/css
Content types can be added or redefined by adding them to the server configuration file, see “General
Information” on page 38.
6.3.4 Authorization
Directories can be protected from web access by placing a file called ‘web_accs.cfg’ in the directory to
protect. This file shall contain a list of users that are allowed to access the directory and its subdirectories.
File Format:
Username1:Password1
Username2:Password2
...
UsernameN:PasswordN
•
List of approved users.
•
Optionally, a login message can be specified by including the
key [AuthName]. This message will be displayed by the web
browser upon accessing the protected directory.
[AuthName]
(message goes here)
The list of approved users can optionally be redirected to one or several other files.
Example:
In this example, the list of approved users will be loaded from ‘here.cfg’ and ‘too.cfg’.
[File path]
\i\put\some\over\here.cfg
\i\actually\put\some\of\it\here\too.cfg
[AuthName]
Howdy. Password, please.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Chapter 7
7. E-mail Client
7.1 General Information
Category: extended
The built-in e-mail client allows the application to send e-mail messages through an SMTP-server. Messages can either be specified directly in the SMTP Client Object, or retrieved from the file system. The
latter may contain SSI, however note that for technical reasons, certain commands cannot be used (specified separately for each SSI command).
The client supports authentication using the ‘LOGIN’ method. Account settings etc. are stored in the
Network Configuration Object.
See also...
•
“Network Configuration Object (04h)” on page 63
•
“SMTP Client Object (09h)” on page 90
7.2 How to Send E-mail Messages
To be able to send e-mail messages, the SMTP-account settings must be specified.
This includes...
•
A valid SMTP-server address
•
A valid user name
•
A valid password
To send an e-mail message, perform the following steps:
1. Create a new e-mail instance using the ‘Create’-command (03h)
2. Specify the sender, recipient, topic and message body in the e-mail instance
3. Issue the ‘Send Instance E-mail’-command (10h) towards the e-mail instance
4. Optionally, delete the e-mail instance using the ‘Delete’-command (04h)
Sending a message based on a file in the file system is achieved using the ‘Send E-mail from File’-command. For a description of the file format, see “Command Details: Send E-mail From File” on page 93.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Chapter 8
8. Server Side Include (SSI)
8.1 General Information
Category: advanced
Server Side Include functionality, or SSI, allows data from files and objects to be represented on web
pages and in e-mail messages.
SSI are special commands embedded within the source document. When the Anybus module encounters such a command, it will execute it, and replace it with the result specified operation (if applicable).
By default, only files with the extension ‘shtm’ are scanned for SSI.
8.2 Include File
This function includes the contents of a file. The content is scanned for SSI.
Note: This function cannot be used in e-mail messages.
Syntax:
<?--#include file="filename"-->
filename-Source file
Default Output:
Scenario
Success
Default Output
(contents of file)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Server Side Include (SSI) 42
8.3 Command Functions
8.3.1 General Information
Command functions executes commands and includes the result.
General Syntax:
<?--#exec cmd_argument='command'-->
command-Command function, see below.
Command Functions:
Command
GetConfigItem()
SetConfigItem()
SsiOutput()
DisplayRemoteUser
ChangeLanguage()
IncludeFile()
SaveDataToFile()
printf()
scanf()
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Valid for E-mail Messages
Yes
No
Yes
No
No
Yes
No
Yes
No
Page
43
44
46
46
47
48
49
50
52
Doc.Id. HMSI-168-70
Server Side Include (SSI) 43
8.3.2 GetConfigItem()
This command returns specific information from a file in the file system.
File Format:
The source file must have the following format:
[key1]
value1
[key2]
value2
...
[keyN]
valueN
Syntax:
<?--exec cmd_argument='GetConfigItem("filename", "key",
"separator")'-->
filename-Source file to read from.
key
-Source [key] in file.
separator-Optional; specifies line separation characters (e.g. “<br>”).
(default is CRLF).
Default Output:
Scenario
Success
Authentication Error
File open error
Key not found
Default Output
(value of specified key)
“Authentication error ”
“Failed to open file “filename” “
“Tag (key) not found ”
Example:
The following SSI...
<?--exec cmd_argument='GetConfigItem("\fruit.cnf", "Lemon")'-->
... in combination with the following file (‘\fruit.cnf’)...
[Apple]
Green
[Lemon]
Yellow
[Banana]
Blue
... returns the string ‘Yellow’.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Server Side Include (SSI) 44
8.3.3 SetConfigItem()
This function stores an HTML-form as a file in the file system.
Note: This function cannot be used in e-mail messages.
Syntax:
<?--#exec cmd_argument='SetConfigItem("filename" [, Overwrite])'-->
filename-Destination file. If the specified file does not exist, it will be created
(provided that the path is valid).
Overwrite-Optional; forces the module to create a new file each time the command
is issued. The default behaviour is to modify the existing file.
File Format:
Each form object is stored as a [tag], followed by the actual value.
[form object name 1]
form object value 1
[form object name 2]
form object value 2
[form object name 3]
form object value 3
...
[form object name N]
form object value N
Note: Form objects with names starting with underscore (‘_’) will not be stored.
Default Output:
Scenario
Success
Authentication Error
File open error
File write error
Default Output
“Configuration stored to “filename” ”
“Authentication error ”
“Failed to open file “filename” “
“Could not store configuration to “filename” “
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Server Side Include (SSI) 45
Example:
The following example demonstrates how to use this function. The resulting page sends a form
to itself, which is then evaluated by the SetConfigItem command.
<HTML>
<HEAD><TITLE>SetConfigItem Test</TITLE></HEAD>
<BODY>
<?--#exec cmd_argument='SetConfigItem("\food.txt")'-->
<FORM action="test.shtm">
<P>
<LABEL for="Name">Name: </LABEL><BR>
<INPUT type="text" name="Name"><BR><BR>
<LABEL for="_Age">Age: </LABEL><BR>
<INPUT type="text" name="_Age"><BR><BR>
<LABEL for="Food">Food: </LABEL><BR>
<INPUT type="radio" name="Food" value="Cheese"> Cheese<BR>
<INPUT type="radio" name="Food" value="Sausage"> Sausage<BR><BR>
<LABEL for="Drink">Drink: </LABEL><BR>
<INPUT type="radio" name="Drink" value="Wine"> Wine<BR>
<INPUT type="radio" name="Drink" value="Beer"> Beer<BR><BR>
<INPUT type="submit" name="_submit">
<INPUT type="reset" name="_reset">
</P>
</FORM>
</BODY>
</HTML>
The resulting file (‘\food.txt’) may look somewhat as follows:
[Name]
Cliff Barnes
[Food]
Cheese
[Drink]
Beer
Note: In order for this example to work, the HTML-file must be named ‘test.shtm’.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Server Side Include (SSI) 46
8.3.4 SsiOutput()
This command temporarily modifies the SSI output of the following command function.
Syntax:
<?--#exec cmd_argument='SsiOutput("success", "failure")'-->
success- String to use in case of success
failure - String to use in case of failure
Default Output:
(this command produces no output on its own)
Example:
The following example illustrates how to use this command.
<?--#exec cmd_argument='SsiOutput ("Parameter stored", "Error")'-->
<?--#exec cmd_argument='SetConfigItem("File.cfg", Overwrite)'-->
See also...
•
“SSI Output Configuration” on page 58
8.3.5 DisplayRemoteUser
This command stores and returns the user name for an authentication session.
Note: This command cannot be used in e-mail messages.
Syntax:
<?--#exec cmd_argument='DisplayRemoteUser'-->
Default Output:
Scenario
Success
Default Output
(current user)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Server Side Include (SSI) 47
8.3.6 ChangeLanguage()
This command changes the language setting based on an HTML form object.
Note: This command cannot be used in e-mail messages.
Syntax:
<?--#exec cmd_argument='ChangeLanguage( "source" )'-->
source -Name of form object which contains the new language setting.
The passed value must be a single digit as follows:
Form value
“0”
“1”
“2”
“3”
“4”
Language
English
German
Spanish
Italian
French
Default Output:
Scenario
Success
Error
Default Output
“Language changed”
“Failed to change language “
Example:
The following example demonstrates how to use this function. The resulting page sends a form
to itself, which is then evaluated by the ChangeLanguage() command.
<HTML>
<HEAD><TITLE>ChangeLanguage Test</TITLE></HEAD>
<BODY>
<?--#exec cmd_argument='ChangeLanguage("lang")'-->
<FORM action="test.shtm">
<P>
<LABEL for="lang">Language(0-4): </LABEL><BR>
<INPUT type="text" name="lang"><BR><BR>
<INPUT type="submit" name="_submit">
</P>
</FORM>
</BODY>
</HTML>
Note: In order for this example to work, the HTML-file must be named ‘test.shtm’.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Server Side Include (SSI) 48
8.3.7 IncludeFile()
This command includes the content of a file. Note that the content is not scanned for SSI.
Syntax:
<?--#exec cmd_argument='IncludeFile("filename" [, separator])'-->
filename-Source file
separator-Optional; specifies line separation characters (e.g. “<br>”).
Default Output:
Scenario
Success
Authentication Error
File open error
Default Output
(file contents)
“Authentication error”
“Failed to open file “filename” “
Example:
The following example demonstrates how to use this function.
<HTML>
<HEAD><TITLE>IncludeFile Test</TITLE></HEAD>
<BODY>
<H1> Contents of ‘info.txt’:</H1>
<P>
<?--#exec cmd_argument='IncludeFile("info.txt")'-->.
</P>
</BODY>
</HTML>
Contents of ‘info.txt’:
Neque porro quisquam est qui dolorem ipsum quia dolor sit amet,
consectetur, adipisci velit...
When viewed in a browser, the resulting page should look somewhat as follows:
See also...
•
“Include File” on page 41
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Server Side Include (SSI) 49
8.3.8 SaveDataToFile()
This command stores data from an HTML-form as a file in the file system. Contents from the different
form objects are separated by a blank line (2*CRLF).
Note: This command cannot be used in e-mail messages.
Syntax:
<?--#exec cmd_argument='SaveDataToFile("filename" [, "source"],
Overwrite|Append)'-->
filename-Destination file. If the specified file does not exist, it will be created
(provided that the path is valid).
source - Optional; by specifying a form object, only data from that particular form
object will be stored. Default behaviour is to store data from all form
objects except the ones where the name starts with underscore (‘_’).
Overwrite|Append-Specifies whether to overwrite or append data to existing files.
Default Output:
Scenario
Success
Authentication Error
File write error
Default Output
“Configuration stored to “filename” ”
“Authentication error ”
“Could not store configuration to “filename” “
Example:
The following example demonstrates how to use this function. The resulting page sends a form
to itself, which is then evaluated by the SaveDataToFile command.
<HTML>
<HEAD><TITLE>SaveDataToFile Test</TITLE></HEAD>
<BODY>
<?--#exec cmd_argument='SaveDataToFile("\stuff.txt", “Meat”, Overwrite)'-->
<FORM action="test.shtm">
<P>
<LABEL for="Fruit">Fruit: </LABEL><BR>
<INPUT type="text" name="Fruit"><BR><BR>
<LABEL for="Meat">Meat: </LABEL><BR>
<INPUT type="text" name="Meat"><BR><BR>
<LABEL for="Bread">Bread: </LABEL><BR>
<INPUT type="text" name="Bread"><BR><BR>
<INPUT type="submit" name="_submit">
</P>
</FORM>
</BODY>
</HTML>
The resulting file (‘\stuff.txt’) will contain the value specified for the form object called ‘Meat’.
Note: In order for this example to work, the HTML-file must be named ‘test.shtm’.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Server Side Include (SSI) 50
8.3.9 printf()
This function returns a formatted string which may contain data from the Anybus module and/or application. The formatting syntax used is similar to that of the standard C-function printf().
The function accepts a template string containing zero or more formatting tags, followed by a number
of arguments. Each formatting tag corresponds to a single argument, and determines how that argument
shall be converted to human readable form.
Syntax:
<?--#exec cmd_argument='printf("template" [, argument1, ..., argumentN])'-->
template-
Template which determines how the arguments shall be represented. May
contain any number of formatting tags which are substituted by subsequent arguments and formatted as requested. The number of format tags
must match the number of arguments; if not, the result is undefined.
Formatting tags are written as follows:
%[Flags][Width][.Precision][Modifier]type
See also...
•
argument-
“Formatting Tags” on page 51
Source arguments; optional parameters which specify the actual source of
the data that shall be inserted in the template string. The number of arguments must match the number of formatting tags; if not, the result is undefined.
At the time of writing, the only allowed argument is ABCCMessage().
See also...
•
“ABCCMessage()” on page 54
Default Output:
Scenario
Success
ABCCMessage error
Default Output
(printf() result)
ABCCMessage error string ( “Errors” on page 57)
Example:
See also...
- “ABCCMessage()” on page 54
- “Example (Get_Attribute):” on page 56
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Server Side Include (SSI) 51
Formatting Tags
•
Type (Required)
The Type-character is required and determines the basic representation as follows:
Type Character
c
d, i
e, E
f
g, G
o
s
u
x, X
%
•
1065
Text
4242
4e7f
%
Meaning
Left-justify the result within the give width (default is right justification)
Always include a ‘+’ or ‘-’ to indicate whether the number is positive or negative
If the number does not start with a ‘+’ or ‘-’, prefix it with a space character instead.
Pad the field with zeroes instead of spaces
For %e, %E, and %f, forces the number to include a decimal point, even if no digits follow.
For %x and %X, prefixes 0x or 0X, respectively.
Width (Optional)
Width
number
*
•
Example
b
565
5.6538e2
565.38
565.38
Flags (Optional)
Flag Character
+
(space)
0 (zero)
#
•
Representation
Single character
Signed decimal integer.
Floating-point number in exponential notation.
Floating-point number in normal, fixed-point notation.
%e or %E is used if the exponent is less than -4 or greater than or equal to the
precision; otherwise %f is used. Trailing zeroes/decimal point are not printed.
Unsigned octal notation
String of characters
Unsigned decimal integer
Hexadecimal integer
Literal %; no assignment is made
Meaning
Specifies the minimum number of characters to be printed.
If the value to be printed is shorter than this number, the result is padded to make up the
field width. The result is never truncated even if the result is larger.
The width is not specified in the format string, it is specified by an integer value preceding
the argument that has to be formatted.
.Precision (Optional)
The exact meaning of this field depends on the type character:
Type Character
d, i, o, u, x, X
e, E, f
g, G
s
c
•
Meaning
Specifies the minimum no. of decimal digits to be printed. If the value to be printed is
shorter than this number, the result is padded with space. Note that the result is never truncated, even if the result is larger.
Specifies the no. of digits to be printed after the decimal point (default is 6).
Specifies the max. no. of significant numbers to be printed.
Specifies the max. no. of characters to be printed
(no effect)
Modifier
Modifier Character Meaning
h
Argument is interpreted as SINT8, SINT16, UINT8 or UINT16
l
Argument is interpreted as SINT32 or UINT32
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Server Side Include (SSI) 52
8.3.10 scanf()
This function is very similar to the printf() function described earlier, except that it is used for input rather than output. The function reads a string passed from an HTML form object, parses the string as specified by a template string, and sends the resulting data to the specified argument. The formatting syntax
used is similar to that of the standard C-function scanf().
The function accepts a source, a template string containing zero or more formatting tags, followed by a
number of arguments. Each argument corresponds to a formatting tag, which determines how the data
read from the HTML form shall be interpreted prior sending it to the destination argument.
Note: This command cannot be used in e-mail messages.
Syntax:
<?--#exec cmd_argument='scanf("source", "template" [,
argument1, ..., argumentN])'-->
source -
Name of the HTML form object from which the string shall be extracted.
template-
Template which specifies how to parse and interpret the data. May contain
any number of formatting tags which determine the conversion prior to
sending the data to subsequent arguments. The number of formatting tags
must match the number of arguments; if not, the result is undefined.
Formatting tags are written as follows:
%[*][Width][Modifier]type
See also...
•
argument-
“Formatting Tags” on page 53
Destination argument(s) specifying where to send the interpreted data.
The number of arguments must match the number of formatting tags; if
not, the result is undefined.
At the time of writing, the only allowed argument is ABCCMessage().
See also...
•
“ABCCMessage()” on page 54
Default Output:
Scenario
Success
Parsing error
Too much data for argument
ABCC Message error
Default Output
“Success”
“Incorrect data format ”
“Too much data ”
ABCCMessage error string ( “Errors” on page 57)
Example:
See also...
- “ABCCMessage()” on page 54
- “Example (Set_Attribute):” on page 56
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Server Side Include (SSI) 53
Formatting Tags
•
Type (Required)
The Type-character is required and determines the basic representation as follows:
Type
c
d
Argument Data Type
CHAR
SINT8
SINT16
SINT32
i
Accepts a signed or unsigned decimal integer. May be given as decimal, hex- SINT8/UINT8
adecimal or octal, determined by the initial characters of the input data:
SINT16/UINT16
Initial Characters:Format:
SINT32/UINT32
0x Hexadecimal
0 Octal
1... 9 Decimal
u
Accepts an optionally signed decimal integer.
UINT8
UINT16
UINT32
o
Accepts an optionally signed octal integer.
SINT8/UINT8
SINT16/UINT16
SINT32/UINT32
x, X
Accepts an optionally signed hexadecimal integer.
SINT8/UINT8
SINT16/UINT16
SINT32/UINT32
e, E,
Accepts an optionally signed floating point number. The input format for float- FLOAT
f,
ing-point numbers is a string of digits, with some optional characteristics:
g, G
- It can be a signed value
- It can be an exponential value, containing a decimal rational number followed by an exponent field, which consists of an ‘E’ or an ‘e’ followed by an
integer.
n
Consumes no input; the corresponding argument is an integer into which
SINT8/UINT8
scanf writes the number of characters read from the object input.
SINT16/UINT16
SINT32/UINT32
s
Accepts a sequence of non-whitespace characters
STRING
[scanset] Accepts a sequence of non-whitespace characters from a set of expected
STRING
bytes specified by the scanlist (e.g ‘[0123456789ABCDEF]’)
A literal ‘]’ character can be specified as the first character of the set. A caret
character (‘^’) immediately following the initial ‘[’ inverts the scanlist, i.e.
allows all characters except the ones that are listed.
%
Accepts a single ‘%’ input at this point; no assignment or conversion is done. The complete conversion specification should be ‘%%’.
•
Input
Single character
Accepts a signed decimal integer
* (Optional)
Data is read but ignored. It is not assigned to the corresponding argument.
•
Width (Optional)
Specifies the maximum number of characters to be read.
•
Modifier (Optional)
Specifies a different data size.
Modifier Meaning
h
SINT8, SINT16, UINT8 or UINT16
l
SINT32 or UINT32
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Server Side Include (SSI) 54
8.4 Argument Functions
8.4.1 General Information
Argument functions are supplied as parameters to certain command functions.
General Syntax:
(Syntax depends on context)
Argument Functions:
Function
ABCCMessage()
Description
-
Page
54
8.4.2 ABCCMessage()
This function issues an object request towards an object in the module or in the host application.
Syntax:
ABCCMessage(object, instance, command, ce0, ce1,
msgdata, c_type, r_type)
object -Specifies the Destination Object
instance- Specifies the Destination Instance
command- Specifies the Command Number
ce0
- Specifies CmdExt[0] for the command message
ce1
- Specifies CmdExt[1] for the command message
msgdata- Specifies the actual contents of the MsgData[] subfield in the command
•
Data can be supplied in direct form (format depends on c_type)
•
The keyword “ARG” is used when data is supplied by the parent
command (e.g. scanf()).
c_type - Specifies the data type in the command (msgdata)
See also...
•
“Command Data Types (c_type)” on page 55
r_type - Specifies the data type in the response (msgdata)
See also...
•
“Response Data Types (r_type)” on page 55
Numeric input can be supplied in the following formats:
Decimal (e.g. 50)-(no prefix)
Octal (e.g. 043)- Prefix 0 (zero)
Hex (e.g. 0x1f)- Prefix 0x
See also...
•
“Example (Get_Attribute):” on page 56
•
“Example (Set_Attribute):” on page 56
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Server Side Include (SSI) 55
•
Command Data Types (c_type)
For types which support arrays, the number of elements can be specified using the suffix ‘[n]’,
where ‘n’ specifies the number of elements. Each data element must be separated by a space.
•
Type
BOOL
SINT8
SINT16
SINT32
UINT8
UINT16
UINT32
CHAR
STRING
Supports Arrays
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
FLOAT
NONE
Yes
No
Data format (as supplied in msgdata)
1
-25
2345
-2569
245
40000
32
A
“abcde”
Note: Quotes can be included in the string if preceded by backslash(‘\’)
Example: “We usually refer to it as \”the Egg\” “
5.6538e2
Command holds no data, hence no data type
Response Data Types (r_type)
For types which support arrays, the number of elements can be specified using the suffix ‘[n]’,
where ‘n’ specifies the number of elements.
Type
BOOL
Supports Arrays
Yes
SINT8
SINT16
SINT32
UINT8
Yes
Yes
Yes
Yes
UINT16
UINT32
CHAR
STRING
ENUM
Yes
Yes
Yes
No
No
FLOAT
NONE
Yes
No
Comments
Optionally, it is possible to exchange the BOOL data with a message
based on the value (true or false). In such case, the actual data type
returned from the function will be STRING.
Syntax: BOOL<true><false>
For arrays, the format will be BOOL[n]<true><false>.
This type can also be used when reading ENUM data types from an
object. In such case, the actual ENUM value will be returned.
When using this data type, the ABCCMessage() function will first read
the ENUM value. It will then issue a ‘Get Enum String’-command to
retrieve the actual enumeration string. The actual data type in the
response will be STRING.
Response holds no data, hence no data type
IMPORTANT: It is important to note that the message will be passed transparently to the addressed object. The SSI
engine performs no checks for violations of the object addressing scheme, e.g. a malformed Get_Attribute request which
(wrongfully) includes message data will be passed unmodified to the object, even though this is obviously wrong. Failure to
observe this may cause loss of data or other undesired side effects.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Server Side Include (SSI) 56
Example (Get_Attribute):
This example shows how to retrieve the IP address using printf() and ABCCMessage().
<?--#exec cmd_argument='printf( "%u.%u.%u.%u",
ABCCMessage(4,3,1,5,0,0,NONE,UINT8[4] ) )'-->
Variable
object
instance
command
ce0
ce1
msgdata
c_type
r_type
Value
4
3
1
5
0
0
NONE
UINT8[4]
Comments
Network Configuration Object (04h)
Instance #3 (IP address)
Get_attribute
Attribute #5
Command message holds no data
Array of 4 unsigned 8-bit integers
See also...
- “printf()” on page 50
Example (Set_Attribute):
This example shows how to set the IP address using scanf() and ABCCMessage(). Note the special parameter value ‘ARG’, which instructs the module to use the passed form data (parsed by
scanf() ).
<?--#exec cmd_argument='scanf("IP", "%u.%u.%u.%u",
ABCCMessage(4,3,2,5,0,ARG,UINT8[4],NONE ) )'-->
Variable
object
instance
command
ce0
ce1
msgdata
c_type
r_type
Value
4
3
2
5
0
ARG
UINT8[4]
NONE
Comments
Network Configuration Object (04h)
Instance #3 (IP address)
Set_attribute
Attribute #5
Use data parsed by scanf() call
Array of 4 unsigned 8-bit integers
Response message holds no data
See also...
- “scanf()” on page 52
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Server Side Include (SSI) 57
Errors
In case an object request results in an error, the error code in the response will be evaluated and translated to the following text strings:
Error Code
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16... 255
Output
“Unknown error”
“Unknown error”
“Invalid message format”
“Unsupported object”
“Unsupported instance”
“Unsupported command”
“Invalid CmdExt[0]”
“Invalid CmdExt[1]”
“Attribute access is not set-able”
“Attribute access is not get-able”
“Too much data in msg data field”
“Out of range”
“Invalid state”
“Out of resources”
“Segmentation failure”
“Segmentation buffer overflow”
“Unknown error”
See also...
•
“SSI Output Configuration” on page 58
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Server Side Include (SSI) 58
8.5 SSI Output Configuration
Optionally, the SSI output can be permanently changed by adding the file ‘\output.cfg’.
File format:
[ABCCMessage_X]
0:"Success string"
1:"Error string 1"
2:"Error string 2"
...
16:"Error string 16"
[GetConfigItem_X]
0:"Success string"
1:"Authentication error string"
2:"File open error string"
3:"Tag not found string"
•
Each error code corresponds to a dedicated
output string, labelled from 1 to 16.
See also...
- “Errors” on page 57
•
Use ‘%s” to include the name of the file.
[SetConfigItem_X]
0:"Success string"
1:"Authentication error string"
2:"File open error string"
3:"File write error string"
•
Use ‘%s” to include the name of the file.
[IncludeFile_X]
0:"Success string"
1:"Authentication error string"
2:"File readS error string"
•
Use ‘%s” to include the name of the file.
[scanf_X]
0:"Success string"
1:"Parsing error string"
[ChangeLanguage_X]
0:"Success string"
1:"Change error string"
All content above can be included in the file multiple times changing the value ‘X’ in each tag for different languages. The module will then select the correct output string based on the language settings. If
no information for the selected language is found, it will use the default SSI output.
Value of X
0
1
2
3
4
Language
English
German
Spanish
Italian
French
See also...
•
“SsiOutput()” on page 46
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Chapter 9
9. Anybus Module Objects
9.1 General Information
This chapter specifies the Anybus Module Object implementation and how they correspond to the functionality in the Anybus-CompactCom BACnet/IP.
Standard Objects:
•
“Anybus Object (01h)” on page 60
•
“Network Object (03h)” on page 61
•
“Network Configuration Object (04h)” on page 63
Network Specific Objects:
•
“Socket Interface Object (07h)” on page 73
•
“SMTP Client Object (09h)” on page 90
•
“File System Interface Object (0Ah)” on page 95
•
“Network Ethernet Object (0Ch)” on page 19
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
60
9.2 Anybus Object (01h)
Category
Basic
Object Description
This object assembles all common Anybus data, and is described thoroughly in the general AnybusCompactCom Software Design Guide.
Supported Commands
Object:
Get_Attribute
Instance:
Get_Attribute
Set_Attribute
Get_Enum_String
Object Attributes (Instance #0)
(Consult the general Anybus-CompactCom Software Design Guide for further information.)
Instance Attributes (Instance #1)
Basic
#
1
2... 11
Name
Module type
-
Access
Get
-
Type
UINT16
-
12
LED colors
Get
13... 15
-
-
struct of:
UINT8(LED1A)
UINT8(LED1B)
UINT8(LED2A)
UINT8(LED2B)
-
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Value
0401h (Standard Anybus-CompactCom)
Consult the general Anybus-CompactCom
Software Design Guide for further information.
Value:Colour:
01h Green
02h Red
01h Green
02h Red
Consult the general Anybus-CompactCom
Software Design Guide for further information.
Doc.Id. HMSI-168-70
61
9.3 Network Object (03h)
Category
Basic
Object Description
For more information regarding this object, consult the general Anybus-CompactCom Software Design
Guide.
Supported Commands
Object:
Get_Attribute
Instance:
Get_Attribute
Set_Attribute
Get_Enum_String
Map_ADI_Write_Area
Note: It is not possible to map read process data in the Anybus CompactCom BACnet/IP w. IT Functionality 2-Port, thus the standard command Map_ADI_Write_Area is not supported.
Object Attributes (Instance #0)
(Consult the general Anybus-CompactCom Software Design Guide for further information.)
Instance Attributes (Instance #1)
Basic
#
1
2
3
4
5
Name
Network type
Network type string
Data format
Parameter data support
Write process data size
6
Read process data size Get
7
Exception Information
8... 10 -
Access
Get
Get
Get
Get
Get
Get
-
Type
UINT16
Array of CHAR
ENUM
BOOL
UINT16
UINT16
UINT8
-
Value
009Ah
‘BACnet/IP’
01h (MSB first)
True
Current write process data size (in bytes)
Updated on every successful Map_ADI_Write_Areaa
Current read process data size (in bytes). Always
zero as it is not possible to map read process data.
See table below
Consult the general Anybus-CompactCom Software
Design Guide for further information.
a. Consult the general Anybus-CompactCom Software Design Guide for further information.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
62
Exception Information
Value
00h
01h
02h
03h
04h
Meaning
No information
The Get_All_BACnet_Object_Instances serves request for analog value objects failed
The Get_All_BACnet_Object_Instances serves request for binary value objects failed
The Get_All_BACnet_Object_Instances serves request for multistate value objects failed
An ADI mapped on process data could not be resolved as a BACnet object during start up.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
63
9.4 Network Configuration Object (04h)
Category
Extended, Advanced
Object Description
This object holds network specific configuration parameters that may be set by the end user. A reset
command (factory default) issued towards this object will result in all instances being set to their default
values.
If the settings do not match the configuration used, the Status LED of the module will flash red to indicate a minor error.
See also...
•
“Communication Settings” on page 19
•
“E-mail Client” on page 40
Supported Commands
Object:
Get_Attribute
Reset
Instance:
Get_Attribute
Set_Attribute
Get_Enum_String
Object Attributes (Instance #0)
(Consult the general Anybus-CompactCom Software Design Guide for further information.)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
64
Instance Attributes (Instance #3, Device Instance)
Changes are valid after reset.
Advanced
#
1
2
3
4
5
Name
a
Name
Data type
Number of elements
Descriptor
Value
Access
Get
Type
Description
Array of CHAR ‘Device inst’
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
UINT32
06h (= UINT32)
01h (one element)
07h (read/write/shared access)
Min = 0, max = 3FFFFEh, default = (module serial number
& 3FFFFEh)
a. Multilingual, see “Multilingual Strings” on page 72.
Instance Attributes (Instance #4, Ethernet Port)
Changes are valid after reset.
Advanced
#
1
2
3
4
5
Name
Namea
Data type
Number of elements
Descriptor
Value
Access
Get
Type
Description
Array of CHAR ‘UDP port’
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
UINT16
05h (= UINT16)
01h (one element)
07h (read/write/shared access)
Min = 1, max = 65535, default = BAC0h
a. Multilingual, see “Multilingual Strings” on page 72.
Instance Attributes (Instance #5, Process Active Timeout)
Changes have immediate effect.
Advanced
#
1
Name
Name
Access
Get
2
3
4
5
Data type
Number of elements
Descriptor
Value
Get
Get
Get
Get/Set
a
Type
Description
Array of CHAR ‘Process tmo’ (Specifies the process active timeout in milliseconds))
UINT8
05h (= UINT16)
UINT8
01h (one element)
UINT8
07h (read/write/shared access)
UINT16
The value is stored in non volatile memory (Default = 0)
a. Multilingual, see “Multilingual Strings” on page 72.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
65
Instance Attributes (Instance #6, IP Address)
Changes are valid after reset.
Advanced
#
1
2
3
4
5
Name
a
Name
Data type
Number of elements
Descriptor
Value
Access
Get
Type
Description
Array of CHAR ‘IP address’
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
Array of UINT8
04h (= UINT8)
04h (four elements)
07h (read/write/shared access)
Valid range: 0.0.0.0 - 255.255.255.255 (Default =0.0.0.0)
a. Multilingual, see “Multilingual Strings” on page 72.
Instance Attributes (Instance #7, Subnet Mask)
Changes are valid after reset.
Advanced
#
1
2
3
4
5
Name
a
Name
Data type
Number of elements
Descriptor
Value
Access
Get
Type
Description
Array of CHAR ‘Subnet mask’
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
Array of UINT8
04h (= UINT8)
04h (four elements)
07h (read/write/shared access)
Valid range: 0.0.0.0 - 255.255.255.255 (Default =0.0.0.0)
a. Multilingual, see “Multilingual Strings” on page 72.
Instance Attributes (Instance #8, Gateway Address)
Changes are valid after reset.
Advanced
#
1
2
3
4
5
Name
Namea
Data type
Number of elements
Descriptor
Value
Access
Get
Type
Description
Array of CHAR ‘Gateway’
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
Array of UINT8
04h (= UINT8)
04h (four elements)
07h (read/write/shared access)
Valid range: 0.0.0.0 - 255.255.255.255 (Default =0.0.0.0)
a. Multilingual, see “Multilingual Strings” on page 72.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
66
Instance Attributes (Instance #9, DHCP)
Changes are valid after reset.
Extended
#
1
2
3
4
5
Name
a
Access
Get
Type
Description
Array of CHAR ‘DHCP’
Valuea
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
ENUM
Name
Data type
Number of elements
Descriptor
08h (= ENUM)
01h (one element)
07h (read/write/shared access)
Value:Enum. String:Meaning:
00h ‘Disable’ DHCP disabled
01h ‘Enable’ DHCP enabled (default)
a. Multilingual, see “Multilingual Strings” on page 72.
Instance Attributes (Instance #10, Ethernet Communication Settings 1)
Changes have immediate effect.
Advanced
#
1
2
3
4
5
Name
a
Access
Get
Type
Description
Array of CHAR ‘Comm 1’
Valuea
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
ENUM
Name
Data type
Number of elements
Descriptor
08h (= ENUM)
01h (one element)
07h (read/write/shared access)
Value:Enum. String:Meaning:
00h ‘Auto’ Auto negotiation (default)
01h ‘10 HDX’ 10Mbit, half duplex
02h ‘10 FDX’ 10Mbit, full duplex
03h ‘100 HDX’ 100Mbit, half duplex
04h ‘100 HDX’ 100Mbit, full duplex
a. Multilingual, see “Multilingual Strings” on page 72.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
67
Instance Attributes (Instance #11, Ethernet Communication Settings 2)
Changes have immediate effect.
Advanced
#
1
2
3
4
5
Name
a
Access
Get
Type
Description
Array of CHAR ‘Comm 2’
Valuea
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
ENUM
Name
Data type
Number of elements
Descriptor
08h (= ENUM)
01h (one element)
07h (read/write/shared access)
Value:Enum. String:Meaning:
00h ‘Auto’ Auto negotiation (default)
01h ‘10 HDX’ 10Mbit, half duplex
02h ‘10 FDX’ 10Mbit, full duplex
03h ‘100 HDX’ 100Mbit, half duplex
04h ‘100 HDX’ 100Mbit, full duplex
a. Multilingual, see “Multilingual Strings” on page 72.
Instance Attributes (Instance #12, DNS1)
This instance holds the address to the primary DNS server. Changes have immediate effect.
Advanced
#
1
2
3
4
5
Name
Namea
Data type
Number of elements
Descriptor
Value
Access
Get
Type
Description
Array of CHAR ‘DNS1’
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
Array of UINT8
04h (= UINT8)
04h
07h (read/write/shared access)
Valid range: 0.0.0.0 - 255.255.255.255 (Default =0.0.0.0)
a. Multilingual, see “Multilingual Strings” on page 72.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
68
Instance Attributes (Instance #13, DNS2)
This instance holds the address to the secondary DNS server. Changes have immediate effect.
Advanced
#
1
2
3
4
5
Name
a
Name
Data type
Number of elements
Descriptor
Value
Access
Get
Type
Description
Array of CHAR ‘DNS2’
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
Array of UINT8
04h (= UINT8)
04h
07h (read/write/shared access)
Valid range: 0.0.0.0 - 255.255.255.255 (Default =0.0.0.0)
a. Multilingual, see “Multilingual Strings” on page 72.
Instance Attributes (Instance #14, Host name)
This instance holds the host name of the module. Changes have immediate effect.
Advanced
#
1
2
3
4
5
Name
a
Name
Data type
Number of elements
Descriptor
Value
Access
Get
Type
Description
Array of CHAR ‘Host name’
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
Array of CHAR
07h (= CHAR)
40h
07h (read/write/shared access)
Host name, 64 characters (pad with spaces to full length)
a. Multilingual, see “Multilingual Strings” on page 72.
Instance Attributes (Instance #15, Domain name)
This instance holds the domain name. Changes have immediate effect.
Advanced
#
1
2
3
4
5
Name
Namea
Data type
Number of elements
Descriptor
Value
Access
Get
Type
Description
Array of CHAR ‘Domain name’
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
Array of CHAR
07h (= CHAR)
30h
07h (read/write/shared access)
Domain name, 48 characters (pad with space to full length)
a. Multilingual, see “Multilingual Strings” on page 72.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
69
Instance Attributes (Instance #16, SMTP Server)
This instance holds the SMTP server address. Changes have immediate effect.
Advanced
#
1
2
3
4
5
Name
a
Name
Data type
Number of elements
Descriptor
Value
Access
Get
Type
Description
Array of CHAR ‘SMTP Server’
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
Array of CHAR
07h (= CHAR)
40h
07h (read/write/shared access)
Dotted decimal format or server name
a. Multilingual, see “Multilingual Strings” on page 72.
Instance Attributes (Instance #17, SMTP User)
This instance holds user name for the SMTP account. Changes have immediate effect
Advanced
#
1
2
3
4
5
Name
a
Name
Data type
Number of elements
Descriptor
Value
Access
Get
Type
Description
Array of CHAR ‘SMTP User’
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
Array of CHAR
07h (= CHAR)
40h
07h (read/write/shared access)
SMTP account user name, 64 characters
(pad with spaces to full length)
a. Multilingual, see “Multilingual Strings” on page 72.
Instance Attributes (Instance #18, SMTP Password)
This instance holds the password for the SMTP account. Changes have immediate effect.
Advanced
#
1
2
3
4
5
Name
a
Name
Data type
Number of elements
Descriptor
Value
Access
Get
Type
Description
Array of CHAR ‘SMTP Pswd’
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
Array of CHAR
07h (= CHAR)
40h
07h (read/write/shared access)
SMTP password, 64 characters
(pad with space to full length)
a. Multilingual, see “Multilingual Strings” on page 72.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
70
Instance Attributes (Instance #19, Foreign Device Registration IP
Address)
This instance holds the IP address of the BACnet Broadcast Management Device (BBMD) that the
module can register as a foreign device on. Changes have immediate effect.
When a valid value is written to this instance, the module will unregister with the current BBMD (if any)
and send a request to register a foreign device (Register-Foreign-Device) to the new BBMD.
Advanced
#
1
2
3
4
5
Name
a
Name
Data type
Number of elements
Descriptor
Value
Access
Get
Type
Description
Array of CHAR ‘FDR IP address’
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
Array of UINT8
04h (= UINT8)
04h
07h (read/write/shared access)
Valid range: 0.0.0.0 - 255.255.255.255 (Default =0.0.0.0).
The value is stored in non volatile memory.
a. Multilingual, see “Multilingual Strings” on page 72.
Instance Attributes (Instance #20, Foreign Device Registration Ethernet
Port)
This instance holds the UDP port to use for foreign device registration. Changes have immediate effect.
When a valid value is written to this instance, the module will unregister with the current BBMD (if any)
and send a request to register a foreign device (Register-Foreign-Device) to the new BBMD. This will
only be done if the value attribute (#5) of instance #19 is set to a valid value.
Advanced
#
1
2
3
4
5
Name
Namea
Data type
Number of elements
Descriptor
Value
Access
Get
Type
Description
Array of CHAR ‘FDR UDP port’
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
UINT16
05h (= UINT16)
01h
07h (read/write/shared access)
Min = 0, max = FFFFh, default = BAC0h. The value is
stored in non volatile memory.
a. Multilingual, see “Multilingual Strings” on page 72.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
71
Instance Attributes (Instance #21, Foreign Device Registration Time to
Live Value)
This instance holds the time to live value for the foreign device registration. Changes have immediate
effect.
When a valid value is written to this instance, the module will send a send a request to register a foreign
device (Register-Foreign-Device) with the new time to live value. This will only be done if the value attribute (#5) of instance #19 is set to a valid value.
Advanced
#
1
2
3
4
5
Name
a
Name
Data type
Number of elements
Descriptor
Value
Access
Get
Type
Description
Array of CHAR ‘FDR TTL value’
Get
Get
Get
Get/Set
UINT8
UINT8
UINT8
UINT16
05h (= UINT16)
01h
07h (read/write/shared access)
Min = 0 s, max = FFFFh s, default = 0 s. The value is stored
in non volatile memory.
a. Multilingual, see “Multilingual Strings” on page 72.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
72
Multilingual Strings
The instance names and enumeration strings in this object are multi-lingual, and are translated based on
the current language settings as follows:
Instance
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
English
Device inst
UDP port
Process tmo
IP address
Subnet mask
Gateway
DHCP
Enable
Disable
Comm 1
Auto
10 HDX
10 FDX
100 HDX
100 FDX
Comm 2
Auto
10 HDX
10 FDX
100 HDX
100 FDX
DNS1
DNS2
Host name
Domain name
SMTP Server
SMTP User
SMTP Pswd
FDR IP address
FDR UDP port
FDR TTL value
German
Geraetenummer
UDP Port
Prozess Tmo
IP-Adresse
Subnetzmaske
Gateway
DHCP
Einschalten
Ausschalten
Komm 1
Auto
10 HDX
10 FDX
100 HDX
100 FDX
Komm 2
Auto
10 HDX
10 FDX
100 HDX
100 FDX
DNS 1
DNS 2
Host name
Domain name
SMTP Server
SMTP User
SMTP PSWD
FDR IP-Adr.
FDR UDP-Port
FDR TTL-Wert
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Spanish
Istanc.Dispos
Puerto UDP
Tout Proceso
Dirección IP
Masac. subred
Pasarela
DHCP
Activado
Desactivado
Comu 1
Auto
10 HDX
10 FDX
100 HDX
100 FDX
Comu 2
Auto
10 HDX
10 FDX
100 HDX
100 FDX
DNS Primaria
DNS Secunda.
Nombre Host
Nombre Domain
Servidor SMTP
Usuario SMTP
Clave SMTP
Dir. IP FDR
Puerto UDP FDR
Valor FDR TTL
Italian
Dispositivo
Porta UDP
Tout Processo
Indirizzo IP
Sottorete
Gateway
DHCP
Abilitato
Disabilitato
Connessione 1
Auto
10 HDX
10 FDX
100 HDX
100 FDX
Connessione 2
Auto
10 HDX
10 FDX
100 HDX
100 FDX
DNS1
DNS2
Nome Host
Nome Dominio
Server SMTP
Utente SMTP
Password SMTP
Indir. IP FDR
Porta UDP FDR
Val. TTL FDR
French
Inst produit
Port UDP
Process tmo
Adresse IP
Sous-réseau
Passerelle
DHCP
Activé
Désactivé
Comm 1
Auto
10 HDX
10 FDX
100 HDX
100 FDX
Comm 2
Auto
10 HDX
10 FDX
100 HDX
100 FDX
DNS1
DNS2
Nom hôte
Nom Domaine
SMTP serveur
SMTP utilisa.
SMTP mt passe
Adresse IP FDR
Port UDP FDR
Valeur TTL FDR
Doc.Id. HMSI-168-70
73
9.5 Socket Interface Object (07h)
Category
Advanced
Object Description
This object provides direct access to the TCP/IP stack socket interface, enabling custom protocols to
be implemented over TCP/UDP.
Note that some of the commands used when accessing this object may require segmentation. For more
information, see “Message Segmentation” on page 102.
IMPORTANT: The use of functionality provided by this object should only be attempted by users who are already familiar with socket interface programming and who fully understands the concepts involved in TCP/IP programming.
Supported Commands
Object:
Get_Attribute
Create (See “Command Details: Create” on page 75)
Delete (See “Command Details: Delete” on page 76)
Instance:
Get_Attribute
Set_Attribute
Bind (See “Command Details: Bind” on page 77)
Shutdown (See “Command Details: Shutdown” on page 78)
Listen (See “Command Details: Listen” on page 79)
Accept (See “Command Details: Accept” on page 80)
Connect (See “Command Details: Connect” on page 81)
Receive (See “Command Details: Receive” on page 82)
Receive_From (See “Command Details: Receive_From” on page 83)
Send (See “Command Details: Send” on page 84)
Send_To (See “Command Details: Send_To” on page 85)
IP_Add_membership (See “Command Details: IP_Add_Membership” on page 86)
IP_Drop_membership (See “Command Details: IP_Drop_Membership” on page 87)
DNS_Lookup (See “Command Details: DNS_Lookup” on page 88)
Object Attributes (Instance #0)
#
1
2
3
4
11
Name
Name
Revision
Number of instances
Highest instance no.
Max. no. of instances
Access
Get
Get
Get
Get
Get
Data Type
Array of CHAR
UINT8
UINT16
UINT16
UINT16
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Value
‘Socket interface’
01h
0008h
Doc.Id. HMSI-168-70
74
Instance Attributes (Sockets #1...8)
Advanced
#
1
Name
Socket type
Access
Get
Type
UINT8
2
3
4
5
Port
Host IP
Host port
TCP State
Get
Get
Get
Get
UINT16
UINT32
UINT16
UINT8
6
7
8
TCP RX bytes
TCP TX bytes
Reuse address
Get
Get
Get/Set
UINT16
UINT16
BOOL
9
Keep alive
Get/Set
BOOL
10 IP Multicast TTL
Get/Set
UINT8
11 IP Multicast Loop
Get/Set
BOOL
12 Ack delay time
Get/Set
UINT16
13 TCP No Delay
Get/Set
BOOL
14 TCP Connect
Timeout
Get/Set
UINT16
Description
Value:Socket Type:
00h SOCK_STREAM, NON-BLOCKING (TCP)
01h SOCK_STREAM, BLOCKING (TCP)
02h SOCK_DGRAM, NON-BLOCKING (UDP)
03h SOCK_DGRAM, BLOCKING (UDP)
Local port that the socket is bound to
Host IP address, or 0 (zero) if not connected
Host port number, or 0 (zero) if not connected
State (TCP sockets only):
Value:State:Description:
00h CLOSED Closed
01h LISTEN Listening for connection
02h SYN_SENT Active, have sent SYN
03h SYN_RECEIVED Have sent and received SYN
04h ESTABLISHED Established.
05h CLOSE_WAIT Received FIN, waiting for close
06h FIN_WAIT_1 Have closed, sent FIN
07h CLOSING Closed exchanged FIN; await FIN ACK
08h LAST_ACK Have FIN and close; await FIN ACK
09h FIN_WAIT_2 Have closed, FIN is acknowledged
0Ah TIME_WAIT Quiet wait after close
Number of bytes in RX buffers (TCP sockets only)
Number of bytes in TX buffers (TCP sockets only)
Socket can reuse local address
Value:Meaning:
1 Enabled
0 Disabled (default)
Protocol probes idle connection (TCP sockets only)
Value:Meaning:
1 Enabled
0 Disabled (default)
IP Multicast TTL value (UDP sockets only).
Default = 1.
IP multicast loop back (UDP sockets only)a
Value:Meaning:
1 Enable (default)
0 Disable
Time for delayed ACKs in ms (TCP sockets only)
Default = 200msb
Don’t delay send to coalesce packets (TCP).
Value:Meaning:
1 Delay (default)
0 Don’t delay (turn off Nagle’s algorithm on socket)
TCP Connect timeout in seconds (default = 75s)
a. Must belong to group in order to get the loop backed message
b. Resolution is 50ms, i.e. 50...99 = 50ms, 100...149 = 100ms, 199 = 150ms etc.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
75
Command Details: Create
Category
Advanced
Details
Command Code.:
03h
Valid for:
Object Instance
Description
This command creates a socket.
Note: This command is only allowed in WAIT_PROCESS, IDLE and PROCESS_ACTIVE states.
•
Command Details
Field
Contents
CmdExt[0] (reserved, set to zero)
CmdExt[1] Value:Socket Type:
00h SOCK_STREAM, NON-BLOCKING (TCP)
01h SOCK_STREAM, BLOCKING (TCP)
02h SOCK_DGRAM, NON-BLOCKING (UDP)
03h SOCK_DGRAM, BLOCKING (UDP)
•
Response Details
Field
Data[0]
Data[1]
Contents
Instance number (low)
Instance number (high)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Comments
Instance number of the created socket.
Doc.Id. HMSI-168-70
76
Command Details: Delete
Category
Advanced
Details
Command Code.:
04h
Valid for:
Object Instance
Description
This command deletes a previously created socket and closes the connection (if connected).
•
If the socket is of TCP-type and a connection is established, the connection is terminated with
the RST-flag.
•
To gracefully terminate a TCP-connection, it is recommended to use the ‘Shutdown’-command
(see “Command Details: Shutdown” on page 78) before deleting the socket, causing the connection to be closed with the FIN-flag instead.
•
Command Details
Field
Contents
CmdExt[0] Instance number to delete (low)
CmdExt[1] Instance number to delete (high)
•
Comments
Instance number of socket that shall be deleted.
Response Details
(no data)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
77
Command Details: Bind
Category
Advanced
Details
Command Code.:
10h
Valid for:
Instance
Description
This command binds a socket to a local port.
•
Command Details
Field
Contents
CmdExt[0] Requested port number (low)
CmdExt[1] Requested port number (high)
•
Comments
Set to 0 (zero) to request binding to any free port.
Response Details
Field
Contents
CmdExt[0] Bound port number (low)
CmdExt[1] Bound port number (high)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Comments
Actual port that the socket was bound to.
Doc.Id. HMSI-168-70
78
Command Details: Shutdown
Category
Advanced
Details
Command Code.:
11h
Valid for:
Instance
Description
This command closes a TCP-connection using the FIN-flag. Note that the response does not indicate
if the connection actually shut down, which means that this command cannot be used to poll non-blocking sockets, nor will it block for blocking sockets.
•
Command Details
Field
Contents
CmdExt[0] (reserved, set to zero)
CmdExt[1] Value:Mode:
00h Shutdown receive channel
01h Shutdown send channel
02h Shutdown both receive- and send channel
•
Response Details
(no data)
The recommended sequence to gracefully shut down a TCP connection is described below.
Application initiates shutdown:
1. Send shutdown with CmdExt[1] set to 01h. This will send FIN-flag to host shutting down the
send channel, note that the receive channel will still be operational.
2. Receive data on socket until error message Object specific error (EDESTADDRREQ (14)) is
received, indicating that the host closed the receive channel. If host does not close the receive channel use a timeout and progress to step 3.
3. Delete the socket instance. If step 2 timed out, RST-flag will be sent to terminate the socket.
Host initiates shutdown:
1. Receive data on socket, if zero bytes received it indicates that the host closed the receive channel
of the socket.
2. Try to send any unsent data to the host.
3. Send shutdown with CmdExt[1] set to 01h. This will send FIN-flag to host shutting down the
receive channel.
4. Delete the socket instance.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
79
Command Details: Listen
Category
Advanced
Details
Command Code.:
12h
Valid for:
Instance
Description
This command puts a TCP socket in listening state. Backlog queue length is the number of unaccepted
connections allowed on the socket. When backlog queue is full, further connections will be refused with
RST-flag.
•
Command Details
Field
Contents
CmdExt[0] (reserved)
CmdExt[1] Value:Backlog queue length:
00h 1
01h 2
02h 4
•
Comments
(set to zero)
-
Response Details
(no data)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
80
Command Details: Accept
Category
Advanced
Details
Command Code.:
13h
Valid for:
Instance
Description
This command accepts incoming connections on a listening TCP socket. A new socket instance is created for each accepted connection. The new socket is connected with the host and the response returns
its instance number.
NON-BLOCKING mode:
This command must be issued repeatedly (polled) for incoming connections. If no incoming
connection request exists, the module will respond with error code 0006h (EWOULDBLOCK).
BLOCKING mode:
This command will block until a connection request has been detected.
Note: This command will only be accepted if there is a free instance to use for accepted connections.
For blocking connections, this command will reserve an instance.
•
Command Details
(no data)
•
Response Details
Field
Data[0]
Data[1]
Data[2]
Data[3]
Data[4]
Data[5]
Data[6]
Data[7]
Contents
Instance number for the connected socket (low)
Instance number for the connected socket (high)
Host IP address byte 3 (low)
Host IP address byte 2
Host IP address byte 1
Host IP address byte 0 (high)
Host port number (low)
Host port number (high)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
81
Command Details: Connect
Category
Advanced
Details
Command Code.:
14h
Valid for:
Instance
Description
For SOCK_DGRAM sockets, this command specifies the peer with which the socket is to be associated
(to which datagrams are sent and the only address from which datagrams are received).
For SOCK_STREAM sockets, this command attempts to establish a connection to a host.
SOCK_STREAM sockets may connect successfully only once, while SOCK_DGRAM-sockets may use
this service multiple times to change their association. SOCK_DGRAM sockets may dissolve their association by connecting to IP address 0.0.0.0, port 0 (zero).
NON-BLOCKING mode:
This command must be issued repeatedly (polled) until a connection is connected, rejected or
timed out. The first connect-attempt will be accepted, thereafter the command will return error
code 22 (EINPROGRESS) on poll requests while attempting to connect.
BLOCKING mode:
This command will block until a connection has been established or the connection request is
cancelled due to a timeout or a connection error.
•
Command Details
Field
CmdExt[0]
CmdExt[1]
Data[0]
Data[1]
Data[2]
Data[3]
Data[4]
Data[5]
•
Contents
(reserved)
Contents
(set to zero)
Host IP address byte 3 (low)
Host IP address byte 2
Host IP address byte 1
Host IP address byte 0 (high)
Host port number (low)
Host port number (high)
-
Response Details
(no data)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
82
Command Details: Receive
Category
Advanced
Details
Command Code.:
15h
Valid for:
Instance
Description
This command receives data from a connected socket. Message segmentation may be used to receive up
to 1472 bytes (see “Message Segmentation” on page 102).
For SOCK-DGRAM-sockets, the module will return the requested amount of data from the next received datagram. If the datagram is smaller than requested, the entire datagram will be returned in the
response message. If the datagram is larger than requested, the excess bytes will be discarded.
For SOCK_STREAM-sockets, the module will return the requested number of bytes from the received
data stream. If the actual data size is less than requested, all available data will be returned.
NON-BLOCKING mode:
If no data is available on the socket, the error code 0006h (EWOULDBLOCK) will be returned.
BLOCKING mode:
The module will not issue a response until the operation has finished.
If the module responds successfully with 0 (zero) bytes of data, it means that the host has closed the
connection. The send channel may however still be valid and must be closed using ‘Shutdown’ and/or
‘Delete’.
•
Command Details
Field
CmdExt[0]
CmdExt[1]
Data[0]
Data[1]
•
Contents
(reserved)
Segmentation Control bits
Receive data size (low)
Receive data size (high)
Notes
(set to zero)
see “Command Segmentation” on page 103
Only used in the first segment
Response Details
Note: The data in the response may be segmented (see “Message Segmentation” on page 102).
Field
CmdExt[0]
CmdExt[1]
Data[0...n]
Contents
(reserved)
Segmentation Control bits
Received data
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Notes
(set to zero)
see “Response Segmentation” on page 104
-
Doc.Id. HMSI-168-70
83
Command Details: Receive_From
Category
Advanced
Details
Command Code.:
16h
Valid for:
Instance
Description
This command receives data from an unconnected SOCK_DGRAM-socket. Message segmentation
may be used to receive up to 1472 bytes (see “Message Segmentation” on page 102).
The module will return the requested amount of data from the next received datagram. If the datagram
is smaller than requested, the entire datagram will be returned in the response message. If the datagram
is larger than requested, the excess bytes will be discarded.
The response message contains the IP address and port number of the sender.
NON-BLOCKING mode:
If no data is available on the socket, the error code 0006h (EWOULDBLOCK) will be returned.
BLOCKING mode:
The module will not issue a response until the operation has finished.
•
Command Details
Field
CmdExt[0]
CmdExt[1]
Data[0]
Data[1]
•
Contents
(reserved)
Segmentation Control bits
Receive data size (low)
Receive data size (high)
Notes
(set to zero)
see “Command Segmentation” on page 103
Only used in the first segment
Response Details
Note: The data in the response may be segmented (see “Message Segmentation” on page 102).
Field
CmdExt[0]
CmdExt[1]
Data[0]
Data[1]
Data[2]
Data[3]
Data[4]
Data[5]
Data[6...n]
Contents
(reserved)
Segmentation Control bits
Host IP address byte 3 (low)
Host IP address byte 2
Host IP address byte 1
Host IP address byte 0 (high)
Host port number (low)
Host port number (high)
Received data
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Notes
(set to zero)
see “Response Segmentation” on page 104
The host address/port information is only included
in the first segment. All data thereafter will start at
Data[0]
Doc.Id. HMSI-168-70
84
Command Details: Send
Category
Advanced
Details
Command Code.:
17h
Valid for:
Instance
Description
This command sends data on a connected socket. Message segmentation may be used to send up to 1472
bytes (see “Message Segmentation” on page 102).
NON-BLOCKING mode:
If there isn’t enough buffer space available in the send buffers, the module will respond with error code 0006h (EWOULDBLOCK)
BLOCKING mode:
If there isn’t enough buffer space available in the send buffers, the module will block until there
is.
•
Command Details
Note: To allow larger amount of data (i.e. >255 bytes) to be sent, the command data may be
segmented (see “Message Segmentation” on page 102).
Field
CmdExt[0]
CmdExt[1]
Data[0...n]
•
Contents
(reserved)
Segmentation Control
Data to send
Notes
(set to zero)
see “Command Segmentation” on page 103
-
Response Details
Field
CmdExt[0]
CmdExt[1]
Data[0]
Data[1]
Contents
(reserved)
Notes
(ignore)
Number of sent bytes (low)
Number of sent bytes (high)
Only valid in the last segment
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
85
Command Details: Send_To
Category
Advanced
Details
Command Code.:
18h
Valid for:
Instance
Description
This command sends data to a specified host on an unconnected SOCK-DGRAM-socket. Message segmentation may be used to send up to 1472 bytes (see “Message Segmentation” on page 102).
•
Command Details
Note: To allow larger amounts of data (i.e. >255 bytes) to be sent, the command data may be
segmented (see “Message Segmentation” on page 102).
Field
CmdExt[0]
CmdExt[1]
Data[0]
Data[1]
Data[2]
Data[3]
Data[4]
Data[5]
Data[6...n]
•
Contents
(reserved)
Segmentation Control
Host IP address byte 3 (low)
Host IP address byte 2
Host IP address byte 1
Host IP address byte 0 (high)
Host port number (low)
Host port number (high)
Data to send
Notes
(set to zero)
see “Command Segmentation” on page 103
The host address/port information shall only be
included in the first segment. All data thereafter
must start at Data[0]
Response Details
Field
CmdExt[0]
CmdExt[1]
Data[0]
Data[1]
Contents
(reserved)
Notes
(ignore)
Number of sent bytes (low)
Number of sent bytes (high)
Only valid in the last segment
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
86
Command Details: IP_Add_Membership
Category
Advanced
Details
Command Code.:
19h
Valid for:
Instance
Description
This command assigns to the socket an IP multicast group membership. The module always joins the
‘All hosts group’ automatically, however this command may be used to specify up to 20 additional memberships.
•
Command Details
Field
CmdExt[0]
CmdExt[1]
Data[0]
Data[1]
Data[2]
Data[3]
•
Contents
(reserved)
Notes
(set to zero)
Group IP address byte 3 (low)
Group IP address byte 2
Group IP address byte 1
Group IP address byte 0 (high)
-
Response Details
(no data)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
87
Command Details: IP_Drop_Membership
Category
Advanced
Details
Command Code.:
1Ah
Valid for:
Instance
Description
This command removes the socket from an IP multicast group membership.
•
Command Details
Field
CmdExt[0]
CmdExt[1]
Data[0]
Data[1]
Data[2]
Data[3]
•
Contents
(reserved)
Notes
(set to zero)
Group IP address byte 3 (low)
Group IP address byte 2
Group IP address byte 1
Group IP address byte 0 (high)
-
Response Details
(no data)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
88
Command Details: DNS_Lookup
Category
Advanced
Details
Command Code.:
1Bh
Valid for:
Object Instance
Description
This command resolves the given host name and returns the IP address.
•
Command Details
Field
Contents
CmdExt[0] (reserved)
CmdExt[1]
Data[0... N] Host name
•
Notes
(set to zero)
Host name to resolve
Response Details (Success)
Field
CmdExt[0]
CmdExt[1]
Data[0]
Data[1]
Data[2]
Data[3]
Contents
(reserved)
Notes
(set to zero)
IP address byte 3 (low)
IP address byte 2
IP address byte 1
IP address byte 0 (high)
IP address of the specified host
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
89
Socket Interface Error Codes (Object Specific)
The following object-specific error codes may be returned by the module when using the socket interface object.
Error Code
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
28
101
Name
ENOBUFS
ETIMEDOUT
EISCONN
EOPNOTSUPP
ECONNABORTED
EWOULDBLOCK
ECONNREFUSED
ECONNRESET
ENOTCONN
EALREADY
EINVAL
EMSGSIZE
EPIPE
EDESTADDRREQ
ESHUTDOWN
(reserved)
EHAVEOOB
ENOMEM
EADDRNOTAVAIL
EADDRINUSE
(reserved)
EINPROGRESS
ETOOMANYREFS
Command aborted
Meaning
No internal buffers available
A timeout event occurred
Socket already connected
Service not supported
Connection was aborted
Socket cannot block because unblocking socket type
Connection refused
Connection reset
Socket is not connected
Socket is already in requested mode
Invalid service data
Invalid message size
Error in pipe
Destination address required
Socket has already been shutdown
Out of band data available
No internal memory available
Address is not available
Address already in use
Service already in progress
Too many references
If a command is blocking on a socket, and that socket is closed using the
Delete command, this error code will be returned to the blocking command.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
90
9.6 SMTP Client Object (09h)
Category
Advanced
Object Description
This object groups functions related to the SMTP-client.
See also...
•
“File System” on page 22
•
“E-mail Client” on page 40
•
“Instance Attributes (Instance #16, SMTP Server)” on page 69
•
“Instance Attributes (Instance #17, SMTP User)” on page 69
•
“Instance Attributes (Instance #18, SMTP Password)” on page 69
Supported Commands
Object:
Get_Attribute
Create
Delete
Send e-mail from file( “Command Details: Send E-mail From File” on page 93)
Instance:
Get_Attribute
Set_Attribute
Send e-mail( “Command Details: Send E-mail” on page 94)
Object Attributes (Instance #0)
#
1
2
3
4
11
12
13
Name
Name
Revision
Number of instances
Highest instance no.
Max. no. of instances
Success count
Error count
Access
Get
Get
Get
Get
Get
Get
Get
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Data Type
Array of CHAR
UINT8
UINT16
UINT16
UINT16
UINT16
UINT16
Value
‘SMTP Client’
01h
0006h
Reflects the no. of successfully sent messages
Reflects the no. of messages that could not be delivered
Doc.Id. HMSI-168-70
91
Instance Attributes
Advanced
Instances are created dynamically by the application.
#
1
2
3
4
Name
From
To
Subject
Message
Access
Get/Set
Get/Set
Get/Set
Get/Set
Type
Array of CHAR
Array of CHAR
Array of CHAR
Array of CHAR
Description
e.g. “[email protected]”
e.g. “[email protected]”
e.g. “Important notice”
e.g. “Duck and cover”
Command Details: Create
Category
Advanced
Details
Command Code.:
03h
Valid for:
Object
Description
This command creates an e-mail instance.
•
Command Details
Field
CmdExt[0]
CmdExt[1]
•
Contents
(reserved, set to zero)
Comments
-
Response Details
Field
CmdExt[0]
CmdExt[1]
MsgData[0]
MsgData[1]
Contents
(reserved, ignore)
Comments
-
Instance number
low byte
high byte
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
92
Command Details: Delete
Category
Advanced
Details
Command Code.:
04h
Valid for:
Object
Description
This command deletes an e-mail instance.
•
Command Details
Field
CmdExt[0]
CmdExt[1]
•
Contents
(reserved, ignore)
Comments
-
Response Details
(no data)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
93
Command Details: Send E-mail From File
Category
Advanced
Details
Command Code.:
11h
Valid for:
Object
Description
This command sends an e-mail based on a file in the file system.
File format:
The file must be a plain ASCII-file in the following format:
[To]
recipient
[From]
sender
[Subject]
e-mail subject
[Headers]
extra headers, optional
[Message]
actual e-mail message
•
Command Details
Field
Contents
CmdExt[0]
(reserved, set to zero)
CmdExt[1]
MsgData[0... n] Path + filename of message file
•
Comments
-
Response Details
(no data)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
94
Command Details: Send E-mail
Category
Advanced
Details
Command Code.:
10h
Valid for:
Instance
Description
This command sends the specified e-mail instance.
•
Command Details
(no data)
•
Response Details
(no data)
Object Specific Error Codes
Error Codes
1
2
3
4
5
6
255
(other)
Meaning
SMTP server not found
SMTP server not ready
Authentication error
SMTP socket error
SSI scan error
Unable to interpret e-mail file
Unspecified SMTP error
(reserved)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
95
9.7 File System Interface Object (0Ah)
Category
Advanced
Object Description
This object provides an interface to the built-in file system. Each instance represents a handle to a file
stream and contains services for file system operations.
Supported Commands
Object:
Get_Attribute
Create( “Command Details: Create” on page 97)
Delete( “Command Details: Delete” on page 98)
Format Disc( “Command Details: Format Disc” on page 107)
Instance:
Get_Attribute
File Open( “Command Details: File Open” on page 98)
File Close( “Command Details: File Close” on page 99)
File Delete( “Command Details: File Delete” on page 99)
File Copy( “Command Details: File Copy” on page 100)
File Rename( “Command Details: File Rename” on page 101)
File Read( “Command Details: File Read” on page 102)
File Write( “Command Details: File Write” on page 103)
Directory Open( “Command Details: Directory Open” on page 103)
Directory Close( “Command Details: Directory Close” on page 104)
Directory Delete( “Command Details: Directory Delete” on page 104)
Directory Read( “Command Details: Directory Read” on page 105)
Directory Create( “Command Details: Directory Create” on page 106)
Directory Change( “Command Details: Directory Change” on page 106)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
96
Object Attributes (Instance #0)
#
1
2
3
4
11
12
13
14
15
Name
Name
Revision
Number of instances
Highest instance no.
Max. no. of instances
Disable virtual file system
Total disc size
Free space
Disc CRC
Access
Get
Get
Get
Get
Get
Get
Get
Get
Get
Data Type
Array of CHAR
UINT8
UINT16
UINT16
UINT16
BOOL
Array of UINT32
Array of UINT32
Array of UINT32
Value
‘File System Interface’
01h
0004h
False
-
Description
Value:Type:
00h Reserved
01h File instance
02h Directory instance
File size in bytes (zero for directories)
Path where instance operates
Instance Attributes
Advanced
#
1
Name
Instance type
Access
Get
Type
UINT8
2
3
File size
Path
Get
Get
UINT32
Array of CHAR
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
97
Command Details: Create
Category
Advanced
Details
Command Code.:
03h
Valid for:
Object
Description
This command creates a file operation instance.
•
Command Details
Field
Contents
CmdExt[0] (reserved, set to zero)
CmdExt[1]
•
Comments
-
Response Details
Field
Contents
CmdExt[0] (reserved, ignore)
CmdExt[1]
MsgData[0] Instance number
MsgData[1]
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Comments
low byte
high byte
Doc.Id. HMSI-168-70
98
Command Details: Delete
Category
Advanced
Details
Command Code.:
04h
Valid for:
Object
Description
This command deletes a file operation instance.
•
Command Details
Field
Contents
CmdExt[0] (reserved, ignore)
CmdExt[1]
•
Comments
-
Response Details
(no data)
Command Details: File Open
Category
Advanced
Details
Command Code.:
10h
Valid for:
Instance
Description
This command opens a file for reading, writing, or appending.
•
Command Details
Field
CmdExt[0]
Contents
Mode
CmdExt[1]
(reserved, set to zero)
MsgData[0... n] Path + filename
•
Comments
Value:Mode:
00h Read mode
01h Write mode
02h Append mode
Relative to current path
Response Details
(no data)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
99
Command Details: File Close
Category
Advanced
Details
Command Code.:
11h
Valid for:
Instance
Description
This command closes a previously opened file.
•
Command Details
(no data)
•
Response Details
Field
CmdExt[0]
CmdExt[1]
MsgData[0]
MsgData[1]
MsgData[2]
MsgData[3]
Contents
(reserved, ignore)
Comments
-
File size
low byte, low word
high byte, high word
Command Details: File Delete
Category
Advanced
Details
Command Code.:
12h
Valid for:
Instance
Description
This command permanently deletes a specified file from the file system.
•
Command Details
Field
Contents
CmdExt[0]
(reserved, set to zero)
CmdExt[1]
MsgData[0... n] Path + filename
•
Comments
Relative to current path
Response Details
(no data)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
100
Command Details: File Copy
Category
Advanced
Details
Command Code.:
13h
Valid for:
Instance
Description
This command makes a copy of a file.
•
Command Details
Field
Contents
CmdExt[0]
(reserved, set to zero)
CmdExt[1]
MsgData[0... n] Source path + filename
NULL
Destination path + filename
•
Comments
Relative to current path, separated by NULL
Response Details
(no data)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
101
Command Details: File Rename
Category
Advanced
Details
Command Code.:
14h
Valid for:
Instance
Description
This command renames or moves a file.
•
Command Details
Field
Contents
CmdExt[0]
(reserved, set to zero)
CmdExt[1]
MsgData[0... n] Old path + filename
NULL
New path + filename
•
Comments
Relative to current path, separated by NULL
Response Details
(no data)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
102
Command Details: File Read
Category
Advanced
Details
Command Code.:
15h
Valid for:
Instance
Description
Reads data from a file previously opened for reading.
•
Command Details
Field
CmdExt[0]
CmdExt[1]
•
Contents
Bytes
(reserved, set to zero)
Comments
no. of bytes to read
-
Response Details
Field
Contents
CmdExt[0]
(reserved, ignore)
CmdExt[1]
MsgData[0... n] Data
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Comments
Data read from file
Doc.Id. HMSI-168-70
103
Command Details: File Write
Category
Advanced
Details
Command Code.:
16h
Valid for:
Instance
Description
Writes data to a file previously opened for writing or appending.
•
Command Details
Field
Contents
CmdExt[0] (reserved, set to zero)
CmdExt[1]
Data[0... n] Data
•
Comments
Data to write to file
Response Details
Field
Contents
CmdExt[0] Bytes
CmdExt[1] (reserved, ignore)
Comments
no. of bytes written
-
Command Details: Directory Open
Category
Advanced
Details
Command Code.:
20h
Valid for:
Instance
Description
This command opens a directory.
•
Command Details
Field
Contents
CmdExt[0] (reserved, set to zero)
CmdExt[1]
Data[0... n] Path + name of directory
•
Comments
Relative to current path
Response Details
(no data)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
104
Command Details: Directory Close
Category
Advanced
Details
Command Code.:
21h
Valid for:
Instance
Description
This command closes a previously opened directory.
•
Command Details
(no data)
•
Response Details
(no data)
Command Details: Directory Delete
Category
Advanced
Details
Command Code.:
22h
Valid for:
Instance
Description
This command permanently deletes an empty directory from the file system.
•
Command Details
Field
Contents
CmdExt[0]
(reserved, set to zero)
CmdExt[1]
MsgData[0... n] Path + name of directory
•
Comments
Relative to current path
Response Details
(no data)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
105
Command Details: Directory Read
Category
Advanced
Details
Command Code.:
23h
Valid for:
Instance
Description
This command reads the contents of a directory previously opened for reading.
The command returns information about a single directory entry, which means that the command must
be issued multiple times to retrieve the complete contents of a directory. When the last entry has been
read, the command returns an “empty” response (i.e. a response where the data size is zero).
•
Command Details
(no data)
•
Response Details
Field
CmdExt[0]
CmdExt[1]
MsgData[0]
MsgData[1]
MsgData[2]
MsgData[3]
MsgData[4]
Contents
(reserved, ignore)
Comments
-
Size of entry
Low byte, low word
High byte, high word
Bit:Meaning:
0 Entry is a directory
1 Entry is read-only
2 Entry is hidden
3 Entry is a system entry
-
Flags
MsgData[5... n] Name of entry
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
106
Command Details: Directory Create
Category
Advanced
Details
Command Code.:
24h
Valid for:
Instance
Description
This command creates a directory.
•
Command Details
Field
Contents
CmdExt[0]
(reserved, set to zero)
CmdExt[1]
MsgData[0... n] Path + name of directory
•
Comments
Relative to current path
Response Details
(no data)
Command Details: Directory Change
Category
Advanced
Details
Command Code.:
25h
Valid for:
Instance
Description
This command changes the current directory/path for an instance.
•
Command Details
Field
Contents
CmdExt[0]
(reserved, set to zero)
CmdExt[1]
MsgData[0... n] Path + name of directory
•
Comments
Relative to current path
Response Details
(no data)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
107
Command Details: Format Disc
Category
Advanced
Details
Command Code.:
30h
Valid for:
Object
Description
This command formats the file system.
•
Command Details
Field
CmdExt[0]
CmdExt[1]
•
Contents
(reserved, set to zero)
Comments
-
Response Details
(no data)
Object Specific Error Codes
Error Codes
1
2
3
4
5
6
7
8
9
10
11
12
Meaning
Failed to open file
Failed to close file
Failed to delete file
Failed to open directory
Failed to close directory
Failed to create directory
Failed to delete directory
Failed to change directory
Copy operation failure (could not open source)
Copy operation failure (could not open destination)
Copy operation failure (write failed)
Unable to rename file
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
108
9.8 Network Ethernet Object (0Ch)
Category
Extended
Object Description
This object provides Ethernet-specific information to the application.
Supported Commands
Object:
Get_Attribute
Instance:
Get_Attribute
Object Attributes (Instance #0)
#
1
2
3
4
Name
Name
Revision
Number of instances
Highest instance no.
Access
Get
Get
Get
Get
Data Type
Array of CHAR
UINT8
UINT16
UINT16
Value
‘Network Ethernet’
01h
-
Instance Attributes (Instance #1)
Extended
#
1
Name
MAC Address
Access
Get
Type
Description
Array of UINT8 Current MAC address.
See also “Ethernet Host Object (F9h)” on page 110)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Chapter 10
10. Host Application Objects
10.1 General Information
This chapter specifies the host application object implementation in the module. The objects listed here
may optionally be implemented within the host application firmware to expand the BACnet/IP implementation.
Standard Objects:
•
Application Object (see Anybus-CompactCom Software Design Guide)
•
Application Data Object (see Anybus-CompactCom Software Design Guide)
Network Specific Objects:
•
“BACnet Host Object (EFh)” on page 112
•
“Ethernet Host Object (F9h)” on page 110
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
110
10.2 Ethernet Host Object (F9h)
Category
Basic, extended
Object Description
This object implements Ethernet features in the host application.
Supported Commands
Object:
Get_Attribute
Instance:
Get_Attribute
Set_Attribute
Object Attributes (Instance #0)
#
1
2
3
4
Name
Name
Revision
Number of instances
Highest instance no.
Access
Get
Get
Get
Get
Data Type
Array of CHAR
UINT8
UINT16
UINT16
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Value
‘Ethernet’
01h
0001h
0001h
Doc.Id. HMSI-168-70
111
Instance Attributes (Instance #1)
Basic
#
Name
Access
1
MAC addressb
Get
Defaulta Comment
Array of UINT8 6 byte physical address value; overrides the
pre-programmed MAC address. Note that the
new MAC address value must be obtained
from the IEEE.
Type
a. If an attribute is not implemented, the module will use this value instead
b. The module is pre-programmed with a valid MAC address. To use that address, do not implement this attribute.
Extended
#
Name
Access
Type
2
Enable HICP
Get
BOOL
3
Enable Web Server
Get
BOOL
5
Enable Web ADI access Get
BOOL
6
Enable FTP server
Get
BOOL
7
Enable admin mode
Get
BOOL
8
Network Status
Set
UINT16
Defaulta Comment
True
Value:Meaning:
True HICP enabled
False HICP disabled
(see “HICP (Host IP Configuration Protocol)”
on page 122)
True
Value:Meaning:
True web server enabled
False web server disabled
(see “Web Server” on page 33)
True
Value:Meaning:
True web ADI access enabled
False web ADI access disabled
(see “Web Server” on page 33)
True
Value:Meaning:
True FTP server enabled
False FTP server disabled
(see “FTP Server” on page 31)
False
Value:Meaning:
True FTP Admin mode enabled
False FTP Admin mode disabled
(see “FTP Server” on page 31)
See “Network Status” on page 111
a. If an attribute is not implemented, the module will use this value instead
Network Status
This attribute holds a bit field which indicates the overall network status as follows:
Bit
0
Contents
Link
1
IP established
2... 15 (reserved)
Description
Value:Meaning:
True Link sensed
False No link
Value:Meaning:
True IP address established
False IP address not established
(mask off and ignore)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
112
10.3 BACnet Host Object (EFh)
Category
Basic, extended, advanced
Object Description
This object implements BACnet specific features in the host application. If attribute #7 (Support Advanced Mapping) is enabled, the application can define the ADI mapping of the module to suit the application.
The implementation of this object is optional; the host application can support none, some, or all of the
attributes specified below. The module will attempt to retrieve the values of these attributes during startup; if an attribute is not implemented in the host application, simply respond with an error message (06h,
“Invalid CmdExt[0]”). In such cases, the module will use its default value.
If the module attempts to retrieve a value of an attribute not listed below, respond with an error message
(06h, “Invalid CmdExt[0]”).
See also...
•
Anybus CompactCom Software Design Guide, “Error Codes”
Supported Commands
Object:
Get_ADI_By_BACnet_Object_Instance
(See “Command Details: Get_ADI_By_BACnet_Object” on page 115)
Get_ADI_By_BACnet_Name
(See “Command Details: Get_ADI_By_BACnet_Name” on page 116)
Get_All_BACnet_Object_Instances
(See “Command Details: Get_All_BACnet_Object_Instances” on page 117)
Get_BACnet_Object_Instance_By_ADI
(See “Command Details: Get_BACnet_Object_Instance_By_ADI” on page 118)
Instance:
-
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
113
Object Attributes (Instance #0)
#
1
2
3
4
Name
Name
Revision
Number of instances
Highest instance no.
Access
Get
Get
Get
Get
Data Type
Array of CHAR
UINT8
UINT16
UINT16
Value
‘BACnet’
01h
0001h
0001h
Instance Attributes (Instance #1)
Basic
#
1
Name
Object Name
Access Type
Default Value
a Array of CHAR “Controller”
Get/Set
2
Vendor Name
Get
3
4
Vendor Identifier
Model Name
Get
Get
5
Firmware Revision
Get
6
Application_Software_ Get
Version
Current date and time:b Get/Set Struct of:-
8
Year
Month
Day
Hour
Minute
Second
Comment
Any change in the values of these
attributes will change the corresponding property of the BACnet Device
Object.
Array of CHAR “HMS Industrial Networks”
UINT16
01E6h
Array of CHAR “Anybus-CompactCom” Any change in the values of this
attribute will change the corresponding
property of the BACnet Device Object.
A change will also affect the product
name displayed on the web pages and
in HICP responses (Fieldbus type
value).
Array of CHAR Anybus CompactCom Any change in the values of these
firmware revision
attributes will change the corresponding property of the BACnet Device
Array of CHAR “ “
Object.
UINT16
UINT8
UINT8
UINT8
UINT8
UINT8
0 (if the attribute is not
implemented)
Current year, e.g. 2011
Current month, e.g. 05
Current day, e.g. 14
Current hour, e.g. 15
Current minute, e.g. 54
Current second, e.g. 21
a. The application decides whether it will be allowed to set the Object Name attribute or not.
b. This attribute is used if the host application has a real time clock implemented. It is read by the module at startup
and written by the module when a TimeSynchronization is received on BACnet to sync the time in the host application. Both get and set access are optional. If set is supported, then get is required. If invalid values are detected
at startup, all elements will be set to 0.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
114
Extended
#
7
Name
Support
advanced mapping
Access Type
Get
BOOL
Default Value
False
Comment
If true, the application supports advanced
BACnet to ADI mapping schema and must
support all related services.
See:
- “Command Details:
Get_ADI_By_BACnet_Object” on page
115
- “Command Details:
Get_ADI_By_BACnet_Name” on page
116
- “Command Details:
Get_BACnet_Object_Instance_By_ADI”
on page 118
- “Command Details:
Get_All_BACnet_Object_Instances” on
page 117
Advanced
#
9
Name
Password
Access Type
Default Value
Get
Array of CHAR “Admin”
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Comment
Password used for ReinitializeDevice and
DeviceCommunicationControl services.
Max 20 bytes.
Doc.Id. HMSI-168-70
115
Command Details: Get_ADI_By_BACnet_Object
Category
Extended
Details
Command Code.:
10h
Valid for:
Object Instance
Description
By setting the ‘Support advanced mapping’-attribute (#7), all requests to BACnet data objects will be
translated to ADIs using this service.
The service is used to translate from BACnet addressing to Anybus CompactCom addressing. Request
to supported BACnet object classes are forwarded to the application, so that it can return the corresponding ADI.
For information about BACnet object classes, see “BACnet/IP Implementation” on page 9.
•
Command Details
Field
CmdExt[0]
CmdExt[1]
MsgData[0,1]
MsgData[2... 5]
•
Contents
(reserved)
Notes
BACnet Object
BACnet Instance
BACnet object class
-
Response Details
Field
CmdExt[0]
CmdExt[1]
MsgData[0,1]
Contents
(reserved)
Notes
ADI
ADI that corresponds to the requested BACnet Object
Instance
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
116
Command Details: Get_ADI_By_BACnet_Name
Category
Extended
Details
Command Code.:
11h
Valid for:
Object Instance
Description
By setting the ‘Support advanced mapping’-attribute (#7), all requests to BACnet data objects by name
will be translated to ADIs using this service.
The service is used to translate from BACnet addressing to Anybus CompactCom addressing. Request
to supported BACnet object classes are forwarded to the application, so that it can return the corresponding ADI.
For information about BACnet object classes, see “BACnet/IP Implementation” on page 9.
•
Command Details
Field
CmdExt[0]
CmdExt[1]
MsgData[0.... N]
•
Contents
(reserved)
Notes
BACnet Object_Name
This field holds a string containing the BACnet object name
Response Details
Field
CmdExt[0]
CmdExt[1]
MsgData[0,1]
Contents
(reserved)
Notes
ADI
MsgData[2,3]
BACnet object class
MsgData[4... 7]
BACnet Instance
ADI that corresponds to the requested BACnet Object
Name
The BACnet object class that corresponds to the BACnet
Object_Name requested
The BACnet Instance that corresponds to the BACnet
Object_Name requested.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
117
Command Details: Get_All_BACnet_Object_Instances
Category
Extended
Details
Command Code.:
12h
Valid for:
Object Instance
Description
If the ‘Support advanced mapping’-attribute (#7) is set, the Object_List attribute in the Device Object
will be populated during initialization using this service. The response returns a bit array of 2040 entries.
A set bit indicates that the corresponding instance is implemented within the application.
Example:
This example shows the first two bytes in the application response. Instances
1, 4, 10, 12, and 13 are implemented in the application.
Byte
0
1
•
Value
12h (0001 0010b)
34h (0011 0100b)
Command Details
Field
CmdExt[0]
CmdExt[1]
MsgData[0, 1]
•
Contents
(reserved)
Notes
BACnet Object
BACnet object class
Response Details
Field
CmdExt[0]
CmdExt[1]
MsgData[0... 254]
Contents
(reserved)
Notes
Object List
Bit array indicating implemented BACnet objects corresponding to the requested BACnet object class.
For information about BACnet object classes, see “BACnet/IP Implementation” on page 9.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
118
Command Details: Get_BACnet_Object_Instance_By_ADI
Category
Extended
Details
Command Code.:
13h
Valid for:
Object Instance
Description
If the ‘Support advanced mapping’-attribute (#7) is set, this service must be implemented. When the
mapping of write process data has been performed, it is not possible for the module to know which ADI
corresponds to which BACnet object identifier. This service finds that information by translating from
an ADI to a BACnet object identifier.
For information about BACnet object classes, see “BACnet/IP Implementation” on page 9.
•
Command Details
Field
CmdExt[0]
CmdExt[1]
MsgData[0, 1]
•
Contents
(reserved)
Notes
ADI
The ADI for which the application wants to find the BACnet
object identifier.
Response Details
Field
CmdExt[0]
CmdExt[1]
MsgData[0, 1]
Contents
(reserved)
Notes
BACnet object class
MsgData[2... 5]
BACnet Instance
The BACnet object class used for the ADI supplied in the
command. (UINT16)
The BACnet instance corresponding to the ADI supplied in
the command. (UINT32)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Appendix A
A. Categorization of Functionality
The objects, including attributes and services, of the Anybus CompactCom and the application are divided into three categories: basic, advanced and extended.
A.1 Basic
This category includes objects, attributes and services that are mandatory to implement or to use. They
will be enough for starting up the Anybus CompactCom and sending/receiving data with the chosen
network protocol. The basic functions of the industrial network are used.
Additional objects etc, that will make it possible to certify the product also belong to this category.
A.2 Extended
Use of the objects in this category extends the functionality of the application. Access is given to the
more specific characteristics of the industrial network, not only the basic moving of data to and from
the network. Extra value is given to the application.
A.3 Advanced
The objects, attributes and services that belong to this group offer specialized and/or seldom used functionality. Most of the available network functionality is enabled and accessible. Access to the specification of the industrial network is normally required.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Appendix B
B. Implementation Details
B.1 SUP-Bit Definition
The supervised bit (SUP) indicates that the network participation is supervised by another network device. In the case of BACnet/IP, this means that the SUP-bit is set when the time (ms) elapsed since the
last BACnet request is less than the parameter “Process Active Timeout” value, if this parameter value
is greater than zero.
B.2 Anybus Statemachine
The table below describes how the Anybus Statemachine relates to the BACnet/IP network.
Anybus State
WAIT_PROCESS
Implementation
The module stays in this state until a BACnet
request arrives.
ERROR
IP conflict
PROCESS_ACTIVE BACnet request(s) addressed to this module
have been received within the last “Process
Active Timeout” time.
Comment
-
IDLE
N/A
-
EXCEPTION
Unexpected error, e.g. watchdog timeout etc.
MS LED turns red (to indicate a major fault)
NS LED is off
• If no process active timeout value is specified (i.e. the parameter is set to 0), the module will remain in this state after the first
BACnet request has been received.
• The supervised bit is set when the module is
in this state.
B.3 Application Watchdog Timeout Handling
Upon detection of an application watchdog timeout, the module will cease network participation and
shift to state ‘EXCEPTION’. No other network specific actions are performed.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Implementation Details 121
B.4 Implemented BACnet BIBBs
The Anybus CompactCom BACnet/IP w. IT Functionality 2-Port is implemented as a BACnet Application Specific Controller (B-ASC). To make the module eligible for certification as a B-ASC, the following BIBBs (BACnet Interoperability Building Blocks) are implemented:
BIBB
Data Sharing-ReadProperty-B (DS-RP-B)
Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)
Data Sharing-WriteProperty-B (DS-WP-B)
Data Sharing-WritePropertyMultiple-B (DS-WPM-B)
Data Sharing-COV-B (DS-COV-B)
Alarm and Event-Notification Internal-B (AE-N-I-B)
Alarm and Event-ACK-B (AE-ACK-B)
Alarm and Event-Alarm Summary-B (AE-ASUM-B)
Alarm and Event-Information-B (AE-INFO-B)
Device Management-Dynamic Device Binding-A (DM-DDB-A)
Device Management-Dynamic Device Binding-B (DM-DDB-B)
Device Management-Dynamic Object Binding-B (DM-DDB-B)
Device Management-Device Communication Control-B (DM-DCC-B)
Device Management-TimeSynchronization-B (DM-TS-B)
Device Management-ReinitializeDevice-B (DM-RD-B)
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Corresponding BACnet Service(s)
ReadProperty (Execute)
ReadPropertyMultiple (Execute)
WriteProperty (Execute)
WritePropertyMultiple (Execute)
SubscribeCOV (Execute)
ConfirmedCOVNotification (Initiate)
UnConfirmedCOVNotification (Initiate)
ConfirmedEventNotification (Initiate)
UnConfirmedEventNotification (Initiate)
AcknowledgeAlarm (Execute)
GetAlarmSummary (Execute)
GetEventInformation (Execute)
Who-Is (Initiate)
I-Am (Execute)
Who-Is (Execute)
I-Am (Initiate)
Who-Has (Execute)
I-Have (Initiate)
DeviceCommunicationControl (Execute)
TimeSynchronization (Execute)
ReinitializeDevice (Execute)
Doc.Id. HMSI-168-70
Appendix C
C. HICP (Host IP Configuration Protocol)
C.1 General
The module supports the HICP protocol used by the Anybus IPconfig utility for changing settings, e.g.
IP address, subnet mask, and enable/disable DHCP. Anybus IPconfig can be downloaded free of charge
from the HMS website. The utility may be used to access the network settings of any Anybus product
connected to the network via UDP port 3250.
C.2 Operation
Upon starting the program, the network is scanned for Anybus products. The network can be rescanned at any time by clicking ‘Scan’.
To alter the network settings of the module, doubleclick on its entry in the list. A window will appear,
containing the settings for the module.
Validate the new settings by clicking ‘Set’, or click
‘Cancel’ to cancel all changes.
Optionally, the configuration can be protected from
unauthorized access by a password. To enter a password, click on the ‘Change password’ checkbox, and
enter the password under ‘New password’.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Appendix D
D. Technical Specification
D.1 Protective Earth (PE) Requirements
In order to ensure proper EMC behaviour, the module must be properly connected to protective earth
via the PE pad / PE mechanism described in the general Anybus-CompactCom Hardware Design
Guide.
HMS Industrial Networks does not guarantee proper EMC behaviour unless these PE requirements are
fulfilled.
D.2 Power Supply
Supply Voltage
The module requires a regulated 3.3V power source as specified in the general Anybus-CompactCom
Hardware Design Guide.
Power Consumption
The Anybus-CompactCom BACnet/IP is designed to fulfil the requirements of a Class B module. For
more information about the power consumption classification used on the Anybus-CompactCom platform, consult the general Anybus-CompactCom Hardware Design Guide.
The current hardware design consumes up to 380 mA1.
D.3 Environmental Specification
Consult the Anybus-CompactCom Hardware Design Guide for further information.
D.4 EMC Compliance
Consult the Anybus-CompactCom Hardware Design Guide for further information.
1. Note that in line with HMS policy of continuous product development, we reserve the right to change the
exact power requirements of this product without prior notification. Note however that in any case, the
Anybus-CompactCom BACnet/IP will remain a Class B module.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Appendix E
E. Timing & Performance
E.1 General Information
This chapter specifies timing and performance parameters that are verified and documented for the Anybus CompactCom BACnet/IP w. IT Functionality 2-Port.
The following timing aspects are measured:
Category
Startup Delay
NW_INIT Delay
Telegram Delay
Command Delay
Parameters
T1, T2
T3
T4
T5
Note
These parameters are equivalent
for all Anybus CompactCom modules. Please consult the Anybus
CompactCom Software Design
Guide, App. B. for times measured.
Anybus Read Process Data Delay (Anybus Delay)
Anybus Write Process Data Delay (Anybus Delay)
T6, T7, T8
T12, T13, T14
Not supported, see page 125
See page 125
Network System Read Process Data Delay (Network System Delay) T9, T10, T11
Network System Write Process Data Delay (Network System Delay) T15, T16, T17
Not supported, see page 126
See page 126
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Timing & Performance 125
E.2 Process Data
E.2.1 Overview
Host Application
Application
software
Anybus
Host
interface
software
HMS Driver
Network Master
Network
specific
software
Network
specific
hardware
Network Media
Event
Anybus Delay
Network System Delay
E.2.2 Anybus Read Process Data Delay (Anybus Delay)
The Read Process Data Delay (labelled ‘Anybus delay’ in the figure above) is defined as the time measured from just before new data is buffered and available to the Anybus host interface software, to when
the data is available to the host application (just after the new data has been read from the driver).
No read process data can be mapped in the Anybus CompactCom BACnet module, thus parameters T6,
T7 and T8 are not measured.
Please consult the Anybus CompactCom Software Design Guide, Appendix B, for more information.
E.2.3 Anybus Write Process Data Delay (Anybus Delay)
The Write Process Data Delay (labelled ‘Anybus delay’ in the figure) is defined as the time measured
from the point the data is available from the host application (just before the data is written from the
host application to the driver), to the point where the new data has been forwarded to the network buffer
by the Anybus host interface software.
In BACnet, this timing parameter measures the time for a COV notification and/or an alarm event to
reach the network buffer.
Parameter
T12
T13
T14
Description
Anybus Write Process Data delay, 8 ADIs (single UINT8)
Anybus Write Process Data delay, 16 ADIs (single UINT8)
Anybus Write Process Data delay, 32 ADIs (single UINT8)
Typ.
390
410
520
Min.
260
300
360
Max.
610
660
760
Unit.
μs
μs
μs
Please consult the Anybus CompactCom Software Design Guide, Appendix B, for more information.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Timing & Performance 126
E.2.4 Network System Read Process Data Delay (Network System Delay)
The Network System Read Process Data Delay (labelled ‘Network System Delay in the figure), is defined
as the time measured from the point where an event is generated at the network master to when the
corresponding data is available to the host application (just after the corresponding data has been read
from the driver).
No read process data can be mapped in the Anybus CompactCom BACnet module, thus parameters T9,
T10 and T11 are not measured.
E.2.5 Network System Write Process Data Delay (Network System Delay)
The Network System Write Process Data Delay (labelled ‘Network System Delay in the figure), is defined as the time measured from the time after the new data is available from the host application (just
before the data is written to the driver) to when this data generates a corresponding event at the network
master.
In BACnet, this timing parameter measures the time for a COV notification and/or an alarm event to
generate a corresponding event at the network master.
Parameter
T15
T16
T17
Description
Network System Write Process Data delay, 8 ADIs (single UINT8)
Network System Write Process Data delay, 16 ADIs (single UINT8)
Network System Write Process Data delay, 32 ADIs (single UINT8)
Typ.
15
15.6
16
Min.
8.4
8
8
Max.
27.2
41.6
58
Unit.
ms
ms
ms
Conditions:
Parameter
Application CPU
Timer system call interval
Driver call interval
No.of ADIs (single UINT8) mapped to Process Data
Communication
Telegram types during measurement period
Bus load, no. of nodes, baud rate etc.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Conditions
1 ms
0.2... 0.3 ms
8, 16 and 32
Parallel
Process Data only
Normal
Doc.Id. HMSI-168-70
Appendix F
F. Copyright Notices
This product includes software developed by Carnegie Mellon, the Massachusetts Institute of Technology, the University of California, and RSA Data Security:
*****************************************************************************
Copyright 1986 by Carnegie Mellon.
*****************************************************************************
Copyright 1983,1984,1985 by the Massachusetts Institute of Technology
*****************************************************************************
Copyright (c) 1988 Stephen Deering.
Copyright (c) 1982, 1985, 1986, 1992, 1993
The Regents of the University of California. All rights reserved.
This code is derived from software contributed to Berkeley by Stephen Deering of Stanford University.
Redistribution and use in source and binary forms, with or without modification, are permitted provided that the
following conditions are met:
•
Redistributions of source code must retain the above copyright notice, this list of conditions and the following disclaimer.
•
Redistributions in binary form must reproduce the above copyright notice, this list of conditions and the
following disclaimer in the documentation and/or other materials provided with the distribution.
•
Neither the name of the University nor the names of its contributors may be used to endorse or promote
products derived from this software without specific prior written permission.
THIS SOFTWARE IS PROVIDED BY THE REGENTS AND CONTRIBUTORS ``AS IS'' ANDANY EXPRESS OR
IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE REGENTS OR CONTRIBUTORS BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL,
EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF
SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION)
HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY,
OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS
SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.
*****************************************************************************
Copyright (C) 1990-2, RSA Data Security, Inc. All rights reserved.
License to copy and use this software is granted provided that it is identified as the "RSA Data Security, Inc. MD4
Message-Digest Algorithm" in all material mentioning or referencing this software or this function.
License is also granted to make and use derivative works provided that such works are identified as "derived from
the RSA Data Security, Inc. MD4 Message-Digest Algorithm" in all material mentioning or referencing the derived
work.
RSA Data Security, Inc. makes no representations concerning either the merchantability of this software or the
suitability of this software for any particular purpose. It is provided "as is" without express or implied warranty of
any kind.
These notices must be retained in any copies of any part of this documentation and/or software.
*****************************************************************************
Copyright (C) 1991-2, RSA Data Security, Inc. Created 1991. All rights reserved.
License to copy and use this software is granted provided that it is identified as the "RSA Data Security, Inc. MD5
Message-Digest Algorithm" in all material mentioning or referencing this software or this function.
License is also granted to make and use derivative works provided that such works are identified as "derived from
the RSA Data Security, Inc. MD5 Message-Digest Algorithm" in all material mentioning or referencing the derived
work.
RSA Data Security, Inc. makes no representations concerning either the merchantability of this software or the
suitability of this software for any particular purpose. It is provided "as is" without express or implied warranty of
any kind.
These notices must be retained in any copies of any part of this documentation and/or software.
Anybus CompactCom BACnet/IP w. IT Functionality 2-Port
Doc.Rev. 1.21
Doc.Id. HMSI-168-70
Was this manual useful for you? yes no