RIBXG Series Datasheet

RIBXG Series Datasheet
Functional Devices, Inc.
•
p: 800.888.5538
•
f: 765.883.7505
RIBXG Series
•
www.functionaldevices.com
•
sales@functionaldevices.com
AC Sensors Low-Voltage-Switching
Enclosed Split Core AC Sensors
Wire Clamp
2.000”
.52” x .52”
Load Wire Opening
LED 2
LED 1
(if present)
Threshold Adjust
2.520”
RIBXGA
2.000”
RIBXGTF
1.100”
1.750”
Load Wire
Load Wire
Made in USA
Meets
“Buy American”
of ARRA 2009
Wht/Yel
Removable Mounting Tab
Wht/Yel
Specifications
Operating Temperature:
Humidity Range:
Max Sense Voltage:
Approvals:
-30 to 140° F
5 to 95% (noncondensing)
600 Vac
UL Listed, UL916, UL864, C-UL,
California State Fire Marshal, CE, RoHS
Mounting/Installation: Removable mounting tab provided.
The wire clamp locks against the load
wire, securing the unit in place.
Sensor Output: Current below threshold: Open
Current above threshold: Closed
Self-Calibrating AC Sensors
Sensor Output:
• Solid State Contact
• 30 Vac/dc, .4 Amp Max.
• When current sensor status is off (open), leakage
<30 uA @ 30Vac/dc
• When current sensor status is on (closed), voltage drop
< .3 Vac/dc @ .1 Amp
< 1.6 Vac/dc @ .4 Amp
(Models with -SCAL Suffix)
-SCAL LED Table
LED Off
No Current
Two Winks
Current Below Range
Three Winks
Current In Range
Four Winks
Current Above Range
Continuous Winks
Calibration in Progress
LED 1
RIBXGA-SCAL
DIP Switch
The SCAL unit begins the 30 second self-calibration process the first time current is applied in the operating range. The
threshold is permanently set. Subsequent calibrations may be performed by moving SW1 to the position opposite of
its current position with or without current applied (hands can be safely away from live voltage). Once current begins
flowing, or if it already is, the calibration process will begin. At the end of the 30 seconds, amperage will be read and set
as the threshold. SW2 in the ON position provides a 15% (+/-3%) differential, in the OFF position it provides a 25% (+/-3%)
differential. SW2 can be selected at anytime and does not affect the threshold setting. Current in-range closes the status
contacts. Current above or below range opens the status contacts. Ex. With a current of 10 amps set as the threshold and
a 15% differential, status contacts will be closed between 8.5 amps and 11.5 amps and open outside of this range. A small
amount of hysteresis is provided to prevent dithering near the differential limits.
RIBXGTA-SCAL
Made in USA
Meets
“Buy American”
of ARRA 2009
RIBXG Series Selection Guide
Model#
Range
Type
Threshold
RIBXGF
.35-150 Amp
Split Core
Fixed, .35 Amp
Solid State Switch SPST ; 30 Vac/dc ; .4 Amps Max (Wht/Yel 16˝ 18 AWG Wire Leads)
RIBXGFL*
.75-150 Amp
Split Core
Fixed, .75 Amp
Solid State Switch SPST ; 30 Vac/dc ; .4 Amps Max (Wht/Yel 16˝ 18 AWG Wire Leads)
RIBXGTF
.35-150 Amp
Split Core
Fixed, .35 Amp
Solid State Switch SPST ; 30 Vac/dc ; .4 Amps Max (Terminal Strip, Accepts #14-22 AWG Wire)
RIBXGTFL*
.75-150 Amp
Split Core
Fixed, .75 Amp
Solid State Switch SPST ; 30 Vac/dc ; .4 Amps Max (Terminal Strip, Accepts #14-22 AWG Wire)
Over Trip Point
RIBXGA
.75-150 Amp
Split Core
Adjustable
Solid State Switch SPST ; 30 Vac/dc ; .4 Amps Max (Wht/Yel 16˝ 18 AWG Wire Leads)
Over Trip Point
Under Trip Point
RIBXGTA
.75-150 Amp
Split Core
Adjustable
Solid State Switch SPST ; 30 Vac/dc ; .4 Amps Max (Terminal Strip, Accepts #14-22 AWG Wire)
Over Trip Point
Under Trip Point
RIBXGA-SCAL
3-150 Amp
Split Core
Self-Cal.
Solid State Switch SPST ; 30 Vac/dc ; .4 Amps Max (Wht/Yel 16˝ 18 AWG Wire Leads)
See -SCAL Table
RIBXGTA-SCAL
3-150 Amp
Split Core
Self-Cal.
Solid State Switch SPST ; 30 Vac/dc ; .4 Amps Max (Terminal Strip, Accepts #14-22 AWG Wire)
See -SCAL Table
* = Not approved by California State Fire Marshal
Sensor Output
LED 1
LED 2
Over Trip Point