WebRelay-Quad Users Manual TM Covers:

WebRelay-Quad Users Manual TM Covers:
WebRelay-QuadTM
Users Manual
Revision: 2.2 - June 8, 2007
Covers:
X-WR-4R1-5
X-WR-4R1-I
X-WR-4R1-E
TM
a division of...
Xytronix Research & Design, Inc.
North Logan, Utah, USA
(c) 2006-2007 Xytronix Research & Design, Inc.
Revision 2.2b
WebRelay-QuadTM Users Manual
Contents
Trademark and Copyright Information
Warranty
FCC Statement
Installation Guidelines (Read Before Installing)
Section 1: Introduction
1.1 Features
1.2 WebRelay-QuadTM Models Available
1.3 Connectors & Indicators
1.4 Example Configurations and Applications
1.4.1 Basic Setup
1.4.2 Controlling High Power Devices
1.4.3 Using WebRelay-QuadTM Without a Computer
Section 2: Installation and Setup
2.1 Mounting
2.1.1 Wall Mounting
2.1.2 DIN-Rail Mounting
2.2 Connection
2.2.1 Power Supply Connection
2.2.2 Network Connection
2.2.3 Relay Connection
2.3 Establishing Communications for Setup
2.3.1 Option 1: Assign a temporary IP address to WebRelay-QuadTM
2.3.2 Option 2: Assign a temporary IP address to configuration computer
2.3.3 Open Configuration Web Page
2.4 Web-Based Setup
2.4.1 Main Setup Page
2.4.2 Network Setup Page
2.4.3 Password Setup Page
2.4.4 Relay Setup Pages
Section 3: Operation
3.1 Browser Operation
3.2 XML Operation
3.3 Modbus Operation
3.3.1 Read Coils (Modbus Function Code 01 (0x01))
3.3.2 Write Single Coil (Modbus Function Code 05 (0x05))
3.3.3 Write Multiple Coils (Modbus Function Code 15 (0x0F))
3.3.4 Write Multiple Registers (Modbus Function Code 16 (0x10))
Appendix A:
Appendix B:
Appendix C:
Appendix D:
Restoring Factory Default Settings
Specifications
Mechanical Information
Open TCP Legal Notice
Xytronix Research & Design, Inc.
page 1
Revision 2.2b
WebRelay-QuadTM Users Manual
Trademark and Copyright Information
This document is Copyright ©2005-2007 by Xytronix Research & Design, Inc. All rights reserved.
WebRelay-QuadTM and ControlByWebTM are Trademarks of Xytronix Research & Design, Inc. 2005-2007.
Portions of the software used in WebRelay-QuadTM are open source and appropriate copyright and legal notices are
listed at the end of this manual. All other parts of the software are property of Xytronix Research & Design, Inc.
©2005-2007. The hardware design, schematics, PCB layout, concept, graphics, users manual, etc., are property of
Xytronix Research & Design, Inc. ©2005-2007. WebRelay-QuadTM may not be opened, dis-assembled, copied or
reverse engineered.
No part of this manual may be reproduced or transmitted in any form or by any means, electronic or mechanical,
including photocopying or scanning, for any purpose other than the personal use by the purchaser of this product.
Xytronix Research & Design, Inc., assumes no responsibility for any errors that may appear in this document.
Whereas effort has been made to make the information in this document as useful and accurate as possible, Xytronix
Research & Design, Inc. assumes no responsibility for the application, usefulness, or completeness of the information
contained herein. Under no circumstance will Xytronix Research & Design, Inc. be responsible or liable for any
damages or losses including direct, indirect, special, incidental, or consequential damages or losses arising from
either the use of any information contained within this manual or the use of any products or services referenced in
this manual.
Xytronix Research & Design, Inc. reserves the right to change any product’s features, specifications, documentation,
warranties, fee schedules, and conditions at any time and without notice.
Warranty
This Xytronix Research & Design, Inc. product has a warranty against defects in material and workmanship for a
period of one year from the date of shipment. During the warranty period, Xytronix Research & Design, Inc. will, at
its option, either repair or replace products that prove to be defective. This warranty is extended to the original
purchaser of the equipment only.
For warranty service or repair, the product must be properly packaged, and returned to Xytronix Research & Design,
Inc. The purchaser shall prepay all charges for shipping to Xytronix Research & Design, Inc., and Xytronix Research
& Design, Inc. will pay the shipping charges to return the product to the purchaser as long as the product is shipped
within the United States. If the product is shipped outside of the United States, the purchaser shall pay all shipping
charges, duties, and taxes.
Limitation
The foregoing warranty shall not apply to defects or damage resulting from improper use or misuse, unauthorized
repair, tampering, modification, improper connection, or operation outside the electrical/environmental specifications
for the product. Further, the warranty does not cover Acts of God, such as fire, flood, hurricanes, and tornadoes.
This warranty does not cover damage to property, equipment, direct, indirect, consequential, or incidental damage
(including damage for loss of business profit, business interruption, loss of data, and the like) arising out of the use or
misuse of this product. UNDER NO CIRCUMSTANCES WILL THE LIABILITY OF XYTRONIX RESEARCH &
DESIGN, INC. TO THE PURCHASER OR ANY OTHER PARTY EXCEED THE ORIGINAL PURCHASE
PRICE OF THE PRODUCT, REGARDLESS OF THE FORM OF THE CLAIM. No other warranty is expressed or
implied. Xytronix Research & Design, Inc. specifically disclaims the implied warranties or merchantability and
fitness for a particular purpose. Some jurisdictions may not allow the exclusion of limitation of liability for
consequential or incidental damage.
Xytronix Research & Design, Inc.
page 2
Revision 2.2b
WebRelay-QuadTM Users Manual
FCC Statement
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
• This device may not cause harmful interference.
• This device must accept any interference received, including interference that may cause undesired operation.
Warning: This equipment has been tested and found to comply with the limits for a Class B (Class A for POE
model) digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable
protection. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause interference to radio communications. However, there is no guarantee
that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio
or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
Notice: Changes or modification not expressly approved by the party responsible for compliance could void the
user’s authority to operate the equipment.
Installation Guidelines (Read Before Installing)
- Do not open the WebRelay-QuadTM enclosure. This will void the warranty.
- This unit must be installed by qualified personnel.
- This unit must not be installed directly outdoors.
- This unit must not be used for medical, life saving purposes, or for any purpose where its failure could cause serious
injury or the loss of life.
Notes about security:
By design, WebRelay-QuadTM is very secure. It does not support terminal or file transfer programs such as telnet, ftp,
ssh, etc. This means that it is not possible for someone to ‘break in’ to WebRelay-QuadTM and access other devices on
your local network. WebRelay-QuadTM does not support remote firmware updates which means that it is not possible
for someone to remotely install malicious software. The simplicity of WebRelay-QuadTM makes it a very secure
device. As with any device to be installed on a network, there are some security precautions that should be observed.
If WebRelay-QuadTM is installed on the Internet, it is recommended that passwords be enabled for the control page.
Make sure secure passwords are used. Passwords should be at least 8 characters in length and should be a
combination of upper case letters, lower case letters, and numbers. Don’t use passwords that would be easy to guess.
For additional security, a firewall may be used to limit access only to selected IP addresses. Another option may be
to set up a Virtual Private Network (VPN) between the network where WebRelay-QuadTM resides and the client
machine (web browser, second WebRelay-QuadTM, etc.).
Final installation note. This ControlByWebTM product supports connection to 10Mbps and 100Mbps networks.
Although 100Mbps networks are faster, the amount of data transferred to and from this device is very minimal and
little if any performance increase will be gained by setting it to 100Mbps. There are advantages however, to operate
this device at 10Mbps. At 10Mbps, less power is required, the unit runs cooler, and the lifetime of the product will be
extended.
Xytronix Research & Design, Inc.
page 3
Revision 2.2b
WebRelay-QuadTM Users Manual
Section 1: Introduction
WebRelay-QuadTM is a compact, four-relay module with a built in web server. It can be controlled and/or monitored
over any IP network including private networks, IP-based industrial control networks, and the Internet. Users can
operate WebRelay-QuadTM using a web browser or a custom application. Computers, PLCs, or automation controllers
may control and monitor WebRelay-QuadTM without user intervention. This works by sending text commands over
the network and reading XML status pages from WebRelay-QuadTM, or by using Modbus/TCP protocol.
WebRelay-QuadTM has many applications and is only limited by imagination. It works very well as a stand-alone
device that can be controlled using a web browser or as a convenient way to add I/O to a computer. It can be used in
industrial applications to control motors, lights, coils, pumps, valves, etc.
1.1 Features
WebRelay-QuadTM is very simple but has many features. Some features include...
•
No programming required
•
Easy to use as a stand alone device or as part of a large control system
•
Built-in web server provides simple, web based configuration and control
•
Control page can be customized with appropriate text and buttons
•
10/100 Ethernet connectivity
•
Four, 24Volt 1-Amp relays
•
Removable terminal connectors (included) simplifies wiring and service
•
Custom applications can control WebRelay-QuadTM with simple text commands and read XML formatted
status.
•
Modbus/TCP protocol support provides inter-interoperability with devices/software from other
manufacturers.
•
Password protection
•
Selectable TCP ports
•
On/Off or pulse mode
•
DIN-Rail or Wall Mount
1.2 WebRelay-QuadTM Models Available
WebRelay-QuadTM is currently available in three models. The only difference between the three models is the power
supply requirements.
Part Number
Power Supply Requirements
X-WR-4R1-5
5VDC
X-WR-4R1-I
9-28VDC
X-WR-4R1-E
Power Over Ethernet or 5VDC
1.3 Connectors & Indicators
WebRelay-QuadTM has a removable terminal connector and an Ethernet connector. The terminal connector is used to
provide power to the internal web server, and is used to connect external electrical loads to the relay contacts.
There are seven LED indicators on WebRelay-QuadTM. The Power LED (green) indicates that the unit is powered.
Four LEDs (green) labeled Relay 1-4 which indicate that the corresponding relay coil is energized. When the relay
coils are energized, the NO (Nornally Open) contacts are closed and the NC (Normally Closed) contacts are open.
The load device that is connected to the relay contacts may be on or off when the coil is energized depending on how
it is wired. The LINK (green) LED indicates that WebRelay-QuadTM is properly connected to an Ethernet network.
The ACK LED (amber) flashes when there is network activity. Note that the LINK and ACT LEDs are located on
the Ethernet connector.
Xytronix Research & Design, Inc.
page 4
Revision 2.2b
WebRelay-QuadTM Users Manual
Removable
Terminal Strip
Relay
Status
Indicator
Lights
Power
Indicator
Light
Network
Activity
Light
Network
Link
Light
Ethernet
Connector
1.4 Example Configurations and Applications
WebRelay-QuadTM is very versatile and can be used in many applications. Several basic installation schemes are
illustrated in this section.
Xytronix Research & Design, Inc.
page 5
Revision 2.2b
WebRelay-QuadTM Users Manual
1.4.1 Basic Setup
The illustration below shows a simple WebRelay-QuadTM application. The example shows how a 3-color
industrial light tower can be controlled remotely over an Ethernet network. The three lights are connected to
three of the relays so each light can be controlled individually. The lights can be connected directly to the
relay contacts because they are low power lights (LEDs). The controller can be a web browser, a custom
control application running on a computer, a PLC, or an embedded industrial controller. Commands are sent
to WebRelay-QuadTM over the Ethernet network using standard IP protocols so the controller can be placed
physically next to the light tower or a distance away.
Power Supply for WebRelayQuad
Device to be
Controlled
(Light Tower)
WebRelay-Quad
Vin+
Vin-
1C
2C
1NO
2NO
ht
Lig
1
Li
gh
t2
Light
3
3C
3N
O
COM
Computer, PLC, Industrial
Controller, etc.
IP
Network
Note that a single power supply could be
used to power both WebRelay-Quad and
Light Tower.
Power Supply
for Light Tower
+V
COM
Xytronix Research & Design, Inc.
page 6
Revision 2.2b
WebRelay-QuadTM Users Manual
1.4.2 Controlling High Power Devices
WebRelay-QuadTM can be used to control high power devices by using an external relay. In this
configuration, WebRelay-QuadTM does not control the load directly, but controls the external relay and the
external relay controls the load. This is illustrated below.
Neutral
Power Supply
(Powers WebRelay)
(5VDC or 9-28VDC)
Device to be
Controlled
240V
AC Power
Source
Line
25 Amp
Solid State Relay
WebRelay-Quad
Vin+
Vin-
Computer, PLC, Industrial Controller, etc.
1C
1NO
-
Input
+
IP
Network
Xytronix Research & Design, Inc.
page 7
Revision 2.2b
WebRelay-QuadTM Users Manual
1.4.3 Using WebRelay-QuadTM Without a Computer
WebRelay-QuadTM can be used in conjunction with other ControlByWeb products such as WebRelayTM or
the Five- Input Module. This allows users to control devices at a remote location by using switches or
buttons instead of using a computer. The illustration below shows how three switches can remotely control
three indicator lights in a light tower at a remote location. This configuration offers many possibilities in
security and remote control. The inputs can be driven by switches, sensors, or digital outputs from a PLC or
automation controller.
Power Supply for
Five Input Module
Power Supply for WebRelayQuad
Light Tower
Switches
Five Input Module
Light 2
In2+
Vin+
Vin1NO
2NO
t1
h
Lig
3NO
In3+
IP
Network
To 1C,
Light 3
COM
+5
In1+
WebRelay-Quad
Vin+
VinGnd
In1In2In3-
Li
gh
t
Ligh 2
t3
Light 1
3C
2C, and
Power Supply
for Light Tower
+V
COM
Xytronix Research & Design, Inc.
page 8
Revision 2.2b
WebRelay-QuadTM Users Manual
Section 2: Installation and Setup
Installation consists of mounting WebRelay-QuadTM, connecting to an IP network, providing power, configuring via a
web browser, and wiring relay contacts to the device that will be controlled.
2.1 Mounting
WebRelay-QuadTM can be be wall mounted or DIN rail mounted. It should be mounted in a clean dry location where
it is protected from the elements. Ventilation is recommended for installations where ambient air temperature is
expected to be high.
2.1.1 Wall Mounting
WebRelay-QuadTM includes two keyholes in the rear of its enclosure for wall mounting. Mount to a wall by
using two #8 screws. Attach the screws to the wall vertically spaced exactly 2.5 inches apart. The head of
the screws should be about 1/10 inch away from the wall. See Appendix C for mechanical details.
2.1.2 DIN-Rail Mounting
WebRelay-QuadTM can be mounted to a standard (35mm by 7.55mm) DIN rail. Attach WebRelay-QuadTM to
the DIN rail by hooking the top hook on the back of the enclosure to the DIN rail and then snap the bottom
hook into place. Remove WebRelay-QuadTM from DIN rail using a flat-head screwdriver. Insert the
screwdriver into the notch in the release tab and pry against the enclosure to release the bottom hook.
Xytronix Research & Design, Inc.
page 9
Revision 2.2b
WebRelay-QuadTM Users Manual
2.2 Connection
CAUTION: MAKE SURE POWER IS SHUT OFF BEFORE WIRING!
Two removable terminal connectors are provided for simple wiring to WebRelay-QuadTM. The correct wiring
procedure is as follows;
1. Make sure power is turned off.
2. Remove terminal connectors from WebRelay-QuadTM and make wiring connections to the terminals.
3. Reconnect terminal connectors.
4. Apply power.
It is recommended that the load (device to be controlled) not be connected to WebRelay-QuadTM until after
WebRelay-QuadTM has been configured and tested. By doing this, wiring and configuration mistakes will not cause
the load device to turn on unexpectedly.
IMPORTANT: MAKE SURE WIRES ARE PROPERLY ATTACHED TO THE TERMINALS!
Bad Connector Example.
Strand(s) of wire are loose
Wires are stripped too far back
Good Connector Example.
Wires are stripped correct
amount and there are no loose
strands that can cause shorts
Xytronix Research & Design, Inc.
page 10
Revision 2.2b
WebRelay-QuadTM Users Manual
14-pin connector pinout:
Pin
VIN+
Description
Power supply input. Connect to the positive side of the appropriate power supply. DO NOT
EXCEED MAXIMUM POWER SUPPLY VOLTAGE.
Model X-WR-4R1-5
5VDC Power supply
Model X-WR-4R1-I
9~28VDC Power supply
Model X-WR-4R1-E
Power Over Ethernet model. These units do not require a power supply to be connected to this
pin when the unit is connected to an 802.3af compliant network. Alternatively, this model can be
powered using a 5VDC power supply.
VIN1C
Power supply ground (-) connection.
Relay 1 Common Contact
1NC
Relay 1 Normally Closed Contact
1NO
Relay 1 Normally Open Contact
2C
Relay 2 Common Contact
2NC
Relay 2 Normally Closed Contact
2NO
Relay 2 Normally Open Contact
3C
Relay 3 Common Contact
3NC
Relay 3 Normally Closed Contact
3NO
Relay 3 Normally Open Contact
4C
Relay 4 Common Contact
4NC
Relay 4 Normally Closed Contact
4NO
Relay 4 Normally Open Contact
2.2.1 Power Supply Connection
WebRelay-QuadTM requires power for its internal logic circuits. Connect appropriate power supply to the
Vin+ and Vin- terminals. Alternatively, WebRelay-QuadTM units with the Power Over Ethernet option may
be powered through the Ethernet connection instead of using an external power supply.
Multiple WebRelay-QuadTM units may be connected to a single power supply by connecting the power
supply input terminals in parallel. The power supply must have a high enough current rating to power all
units connected (see specifications for current requirements for a specific model number).
WebRelay-QuadTM units with the Power Over Ethernet option may be connected to an 802.3af compliant
Ethernet port instead of connecting an external power supply. In this case, WebRelay-QuadTM is powered
through the network port. In an 802.3af compliant network, a 48 Volt power source is injected into the
Ethernet line. This power source is provided by an 802.3af compliant hub, switch, or power injector which
may be located in a utility closet which could be a distance away from WebRelay-QuadTM. This option is
very useful for installations where local power is not available. The power injector may inject the 48 Volt
power source through the data lines or the spare lines in the Ethernet cable. DO NOT USE A POWER
INJECTOR THAT APPLIES A VOLTAGE TO BOTH THE DATA LINES AND THE SPARE LINES.
Xytronix Research & Design, Inc.
page 11
Revision 2.2b
WebRelay-QuadTM Users Manual
2.2.2 Network Connection
Connect the Ethernet port to a 10 Base T or 10/100 Base T Ethernet connection. This typically connects to
an Ethernet hub, switch, or router. For configuration, WebRelay-QuadTM may be connected directly to the
Ethernet port on a computer using a “crossover” cable. Otherwise for connection through a hub or router, a
standard “straight-thru” cable should be used.
2.2.3 Relay Connection
The relay contacts internally connect directly to the 14-pin connector. No internal fuse is provided. The
relay contacts are rated at 1 Amp max (28V max). For larger loads, an external relay may be used to control
the load.
2.3 Establishing Communications for Setup
WebRelay-QuadTM is set up using a web browser. The first task is to establish communications between a computer
and the WebRelay-QuadTM device so that the browser-based configuration can begin. To do this, the computer and
WebRelay-QuadTM must be physically connected to the same network and both must have IP addresses on the same
network. There are two ways to set up the computer and WebRelay-QuadTM so that they are on the same network.
The first way (Option 1), is to change the IP address of WebRelay-QuadTM to an address that is on the same network
as the computer. The second way (Option 2) is to change the IP address of the computer to an address that is on the
same network that WebRelay-QuadTM is set to by default.
2.3.1 Option 1: Assign a temporary IP address to WebRelay-QuadTM
This option is used to TEMPORARILY assign an IP address to WebRelay-QuadTM without the need to
change the IP address of the configuration computer. Note that WebRelay-QuadTM will only use this IP
address as long as power is maintained. Once power is lost and restored, WebRelay-QuadTM will use the IP
address assigned in the setup page and not the temporary address assigned here. This means that once
communications are established, the desired IP address should be entered into the network setup page using
the browser.
To assign the temporary IP address...
1.
Make sure WebRelay-QuadTM and the configuration computer are connected to the same physical
network. This will not work through routers or gateways.
2.
Assign the address as follows...
Windows:
Open a Command Prompt (on Windows XP, select START, then RUN, then type “cmd”).
Type...
arp -s {new IP address} {serial number of WebRelay-QuadTM }
Note: IP address format is: xxx.xxx.xxx.xxx
Serial number format is: ss-ss-ss-ss-ss-ss
For example, to set a WebRelay-QuadTM device (with serial number 00-0C-C8-01-00-01 )
to 10.10.10.40 the following command would be used.
arp -s 10.10.10.40 00-0c-c8-01-00-01
Next, type...
ping -l 102 {new IP address}
For example, if the new IP address is 10.10.10.40, the following command would be
used.
ping -l 102 10.10.10.40
Xytronix Research & Design, Inc.
page 12
Revision 2.2b
WebRelay-QuadTM Users Manual
Linux/Unix:
Open a terminal, change to root user (su -, then enter root password).
Type...
arp -s {new IP address} {serial number of WebRelay-QuadTM }
Note: IP address format is: xxx.xxx.xxx.xxx
Serial number format is: ss:ss:ss:ss:ss:ss
For example, to set a WebRelay-QuadTM device (with serial number 00-0C-C8-01-00-01 )
to 10.10.10.40 the following command would be used.
arp -s 10.10.10.40 00:0c:c8:01:00:01
Next, type...
ping -s 102 {new IP address}
For example, if the new IP address is 10.10.10.40, the following command would be
used.
ping -s 102 10.10.10.40
Mac OS X
Open a terminal,
Note that the terminal is in the “Utilities” directory which is in “Applications” directory.
type
sudo arp -s {new IP address} {serial number of WebRelay-QuadTM }
Note: Administrator password is required.
IP address format is: xxx.xxx.xxx.xxx
Serial number format is: ss:ss:ss:ss:ss:ss
For example, to set a WebRelay-QuadTM device (with serial number 00-0C-C8-01-00-01 )
to 10.10.10.40 the following command would be used.
sudo arp -s 10.10.10.40 00:0c:c8:01:00:01
Next, type...
ping -s 102 {new IP address}
For example, if the new IP address is 10.10.10.40, the following command would be
used.
ping -s 102 10.10.10.40
2.3.2 Option 2: Assign a temporary IP address to configuration computer
If the first option above is not used, you can use this option to communicate with WebRelay-QuadTM . By
default, WebRelay-QuadTM comes from the factory with an IP address of 192.168.1.2. Communications with
WebRelay-QuadTM may be established by assigning an IP address to the configuration computer that is on
the same network as WebRelay-QuadTM (for example the configuration computer could be assigned to
192.168.1.5) .
Xytronix Research & Design, Inc.
page 13
Revision 2.2b
WebRelay-QuadTM Users Manual
Instructions for changing the IP address of the computer that will be used for WebRelay-QuadTM
configuration are given here. Note that these instructions are specifically for computers with the Windows
XP operating system. For setup using other operating systems, refer to the appropriate users manual.
Step 1: Open the control panel by clicking on the start menu and then clicking on Control Panel. (Note that
control panel shown is in “Classic View”. If control panel is in “Category View” select the “Classic View”
option before proceeding.)
Xytronix Research & Design, Inc.
page 14
Revision 2.2b
WebRelay-QuadTM Users Manual
Step 2: Double click on the icon labeled Network Connections. The following menu will pop up.
Step 3: Right click on the icon labeled Local Area Connection. Another menu will appear. Select the option
at the bottom of the menu labeled Properties. The Local Area Connection Properties window will appear.
Step 4: On the Local Area Connection Properties page scroll down to Internet Protocol (TCP/IP), select it,
and then click the button labeled properties.
Xytronix Research & Design, Inc.
page 15
Revision 2.2b
WebRelay-QuadTM Users Manual
Step 5: Before making any changes to the network settings, write down the current settings so they can
be restored once WebRelay-QuadTM is configured. Next, select the radio button labeled “Use the following
IP address,” and type in the IP address 192.168.1.50. Type in a subnet mask of 255.255.255.0. Leave the
default gateway field blank. Click OK to apply settings.
2.3.3 Open Configuration Web Page
Once the network is set up, open the configuration setup page by typing the following URL into the browser:
http://192.168.1.2/setup.html (note that if option 1 above was used for initial configuration, replace the IP
address given here with the newly assigned IP address). A password is required to change any parameters.
The default password is ‘webrelay’ (do not include quotes, password is case sensitive).
2.4 Web-Based Setup
WebRelay-QuadTM is fully configurable through HTML 4.0 compliant web browsers such as Internet Explorer and
Mozilla Firefox. It’s easy to use tab based menu system has been designed to allow the unit to be configured easily.
Note that in this chapter, the default IP address of 192.168.1.2 is used in all examples. If the IP address has been
changed, substitute the new IP address for the address shown in the examples.
Before proceeding, make sure a network connection has been established between the computer and WebRelayQuadTM. This is done by typing the following URL into the web browser: http://192.168.1.2/setup.html. Another
way to check communications is to ping WebRelay-QuadTM (from the command prompt (type ping 192.168.1.2)).
Each setup page is described below.
Xytronix Research & Design, Inc.
page 16
Revision 2.2b
WebRelay-QuadTM Users Manual
2.4.1 Main Setup Page
This is the initial page that appears when the URL http://192.168.1.2/setup.html is entered into the web
browser. It provides basic information about the WebRelay-QuadTM unit.
Navigating between setup pages is done by clicking on the tabs at the top of the page. All setup pages
require a password. The default password is ‘webrelay’ (no quotes, all lower case) and no user name
is required.
Each setup page has a “Submit” button and a “Reset” button at the bottom of the page. After entering the
desired parameters into each page, the “Submit” button must be pressed before any parameters will be
saved. If a mistake is made in entering the parameters, the “Reset” button may be used to restore all
parameters on the page to their current settings. The “Reset” button is only effective before the “Submit”
button is pressed.
2.4.2 Network Setup Page
The network parameters are changed on this page. Note that if multiple WebRelay-QuadTM units are used on
the same network, install one unit at a time and set the IP address of each unit before connecting the next
Xytronix Research & Design, Inc.
page 17
Revision 2.2b
WebRelay-QuadTM Users Manual
unit to the network. This avoids having multiple WebRelay-QuadTM units installed on the network with the
same factory default IP address at the same time. It may be necessary to clear the arp cache each time you
swap WebRelay-QuadTM units on the network (this is because each unit has the same default IP address but
different mac address). This is done by typing arp -d in the command prompt of a Windows computer
(arp -d -a as super user on Apple OSX). Also note that the unit must be power-cycled (power
disconnected, then
reconnected) before network settings take effect. No other setup page requires power-cycling for the
settings take effect.
1. IP Address:
WebRelay-QuadTM requires a static IP address. This is a unique address that identifies
WebRelay-QuadTM on the network. Dynamic IP address assignment is not supported. The
lack of dynamic IP addressing support is intentional because a dynamically changing the
IP address would make it difficult for a client to access the web server built into
WebRelay-QuadTM. The IP address is specific to the network where WebRelay-QuadTM
will be installed, and must be obtained from the network administrator.
This guide is not meant to be a tutorial on IP addressing, however a few comments about IP
addressing are given here.
If WebRelay-QuadTM will be used over the Internet, the IP address must be a routable address
assigned by the upstream Internet Service Provider (ISP).
In cases where the ISP only provides a single routable IP address for the entire network (this is
Xytronix Research & Design, Inc.
page 18
Revision 2.2b
WebRelay-QuadTM Users Manual
typical with ISPs such as cable providers), a proxy server (or gateway router) may be used. A
proxy server allows multiple devices to connect to the Internet using a single routable IP address.
Many small routers from LinkSys, Dlink, and Netgear perform proxy server functions. If a proxy
server is used, WebRelay-QuadTM will not be accessible from the Internet until the proxy server is
properly configured (forward proper port to WebRelay-QuadTM). This information is mentioned for
convenience but details of setting up a configuration such as this is beyond the scope of this
manual.
If WebRelay-QuadTM is used on a private network only and is NOT used over the Internet, a
routable IP address is not necessary. This may be the case when WebRelay-QuadTM is used to
control (or monitor) a device in another room or a nearby building.
If WebRelay-QuadTM will be installed on a simple, private network that does not connect to the
Internet, the default IP address may be used as long as no other device on the network uses the
same address. If multiple WebRelay-QuadTM units are installed on the same network, each unit
must have its own unique IP address. For example, WebRelay-QuadTM comes from the factory
with a default IP address of 192.168.1.2. If multiple units are used, change the IP address for each
unit (192.168.1.3, 192.168.1.4, 192.168.1.5 etc.).
2. Netmask:
This specifies the size of the local network. This must be obtained from the network
administrator. By default, the netmask is set to 255.255.255.0.
3. Broadcast:
This specifies the broadcast address. This must be obtained from the network
administrator. By default, this is set to 192.168.1.255.
4. Gateway:
This specifies the IP address of the gateway router. This must be obtained from the
network administrator. By default, this is set to 192.168.1.1.
5. TCP Port:
This specifies the TCP port used for communications with WebRelay-QuadTM. By default,
the port is set to 80 which is the standard http port. It is recommended that the port not be
changed without an understanding of TCP/IP and ports.
Changing the port can be useful for accessing multiple WebRelay-QuadTM devices which
are installed behind a gateway router on a private network that uses non-routable IP
addresses (192.168.x.x, 10.x.x.x, and 172.16.x.x through 172.31.x.x are non-routable or
private IP addresses). In this case, each WebRelay-QuadTM unit would be assigned a
different port (for example 8000, 8001, 8002, etc). The gateway router would be set up to
forward all traffic for each of the assigned ports to the IP address of the WebRelay-QuadTM
unit which uses that port. The WebRelay-QuadTM units could then be accessed from
outside the private network by entering the IP address of the gateway and the port for the
desired WebRelay-QuadTM unit. Note that whenever any port is assigned other than port
80, all communications with that WebRelay-QuadTM device must include the port. For
example, if WebRelay-QuadTM is assigned port 8000, access to the setup page would
require the following URL to be entered; http://192.168.1.2:8000/setup.html.
Xytronix Research & Design, Inc.
page 19
Revision 2.2b
WebRelay-QuadTM Users Manual
An example screenshot of a gateway router configuration is given below. This setup
allows seven ControlByWebTM products to be accessed on a private network behind a
gateway router. Note that this screenshot is simply an example of a typical router setup
page. Routers will vary.
In the example, the seven ControlByWebTM products are assigned IP addresses of
10.10.10.41 to 10.10.10.47. The first device labeled WebRelay-Quad 1 has an IP address
of 10.10.10.41 and is assigned port 8001. Note that in the WebRelay-QuadTM setup page
(under Network settings tab), TCP Port 8001 must be specified for this device. The
second device, labeled WebRelay-Quad 2 has an IP address of 10.10.10.42 and is assigned
port 8002. This WebRelay-QuadTM must have its TCP Port set to 8002 in it's network
settings page. This pattern continues through 10.10.10.77 which is assigned the port 8007.
To access the ControlByWebTM units from the Internet, enter the IP address of the gateway
plus the port number of the desired device.
6. Modbus Port:
This specifies the port used for Modbus/TCP communications with WebRelay-QuadTM.
By default this is set to port 502 which is the standard Modbus port. For users not familiar
with Modbus, Modbus is a messaging structure protocol used in industrial manufacturing
control and automation. It is an open protocol and offers interoperability with software
and devices from other manufacturers. If Modbus is not used, this setting can be ignored.
Modbus communications are disabled whenever the control password is enabled.
7. Speed:
This option sets the data rate of the Ethernet port. Both 10Mbps and 100Mbps can be
selected. The 100Mbps option offers faster communications but the amount of data to and
from WebRelay-QuadTM is so small that users will not likely notice much of a difference.
When WebRelay-QuadTM is set to 10Mbps, it draws less power and runs a little cooler
which translate into a longer product life. IT IS RECOMMENDED THAT THIS
SETTING BE LEFT AT 10MBPS UNLESS THE USER HAS A SPECIFIC REASON TO
USE 100MBPS.
Xytronix Research & Design, Inc.
page 20
Revision 2.2b
WebRelay-QuadTM Users Manual
8. Mode:
This option allows the Ethernet port to be set to Half Duplex or Full Duplex. Legacy
Ethernet operates in Half Duplex mode which means that devices can either send data or
receive data, but not both at the same time. Full duplex means that devices can send and
receive data at the same time.
2.4.3 Password Setup Page
The password setup page is used to change and enable passwords. A password is required for the setup
pages but is optional for the control page. The password is enabled or disabled for the control page by using
the Yes or No radio buttons. Enabling the control page password also enables the requirement for a
password when reading/writing XML pages. Enabling the control page password also disables the ability to
communicate with WebRelay-QuadTM using Modbus. Note that when the password is changed, the password
may be displayed in the browser’s history in clear text. It is advisable to clear the browsers history after
setting the password. Passwords may be up to 10 characters.
2.4.4 Relay Setup Pages
These pages are used to set up the function of each of the four relays, and how each relay is represented on
the control page. All four pages are identical, with the exception of the Relay 1 page which also includes a
field for the main header text on the control page, the option to automatically refresh the control page, and
the time duration for auto refresh.
The following settings (1-3) are only included on the Relay 1 setup page and not on Relay 2,3 or 4 setup
pages.
1. Main Header Text:
This text will be displayed in the main header area of the control page. This field can be up to 25 characters
in length.
2. Auto Refresh Page:
Web pages traditionally display static information. The WebRelay-QuadTM control page, however, displays
Xytronix Research & Design, Inc.
page 21
Revision 2.2b
WebRelay-QuadTM Users Manual
information that is dynamic. Each time the control page is loaded to the browser, it displays a snapshot of
the current status of the unit. If the state of the unit changes, the information on the control page will be
outdated unless the page is re-loaded. Whenever a user changes the state of the relay via the web browser,
the web page will automatically reload the control page to display current information. If, however, the
relay state changes due to a change due to a command sent from another machine, the relay state will not be
updated and the control page information will be obsolete. The ‘Auto Refresh Page’ option will cause the
control page to continually update its contents by setting a timer in the web page that causes it to be reloaded
at a specified time interval.
3. Duration:
If the ‘Auto Refresh Page’ option is set to Yes, this field specifies the time interval in seconds that the page
will be refreshed. It can be set from 1 to 32 seconds.
The following settings (4-15) are included on all four relay setup pages. The settings correspond only to the
relay associated with that page.
Xytronix Research & Design, Inc.
page 22
Revision 2.2b
WebRelay-QuadTM Users Manual
4. Relay Description:
This text is used to describe the function of the relay on the control page. This text will not appear if the
‘Display Relay Status’ is set to No, the ‘On/Off Buttons’ is set to 0, and the ‘Pulse Button’ is set to No.
This field can be up to 20 characters in length.
5. Display Relay Status:
When this option is set to Yes, the relay status will be displayed on the control page. If it is set to No, the
relay status will not be displayed.
6. Status ON Color:
When the ‘Display Relay Status’ option is set to Yes, this field specifies the color that will be displayed
when the relay is on (coil energized).
7. Status ON Text:
When the ‘Display Relay Status’ option is set to Yes, this field specifies the text that will be displayed when
the relay is on (coil energized).
8. Status OFF Color:
When the ‘Display Relay Status’ option is set to Yes, this field specifies the color that will be displayed
when the relay is off (coil not energized).
9. Status OFF Text:
When the ‘Display Relay Status’ option is set to Yes, this field specifies the text that will be displayed when
the relay is off (coil not energized).
10. ON/OFF Buttons:
This option allows the user to specify 0, 1, or 2 buttons to turn the relay on or off. Zero buttons disables the
users ability to turn the relay on and off (a pulse button may still be included... see below). One button may
be used to toggle the relay on and off. Two buttons gives the user one button to turn the relay on and another
button to turn the relay off.
11. Button 1 Label:
When 1 or 2 buttons is selected in the ‘ON/OFF Buttons’ option, this field specifies the text that will be
displayed in pushbutton number 1.
12. Button 2 Label:
When 2 buttons is selected in the ‘ON/OFF Buttons’ option, this field specifies the text that will be
displayed in pushbutton number 2.
13. Pulse Button:
This option allows the user to include a pulse button to control the relay. If the pulse button is included, the
relay will pulse for the time specified in the ‘Pulse Duration’ field in the ‘Relay/Input’ page each time the
button is pressed.
14. Pulse Button Label:
When the ‘Pulse Button’ option is set to Yes, the text entered here will appear in the pulse button on the
control page.
15. Pulse Duration:
When WebRelay-QuadTM receives a command (from over the network or through an input change) to pulse
the relay, this is the time in seconds that the relay will pulse on. This time can be set from 0.1 seconds to
86,400 seconds (1 day). Note that each time WebRelay-QuadTM receives a pulse command, the relay will be
turned on (if not on already) and the pulse timer will be reset. If WebRelay-QuadTM receives a pulse
command and and a second pulse command comes in before the pulse timer has expired, the relay will
Xytronix Research & Design, Inc.
page 23
Revision 2.2b
WebRelay-QuadTM Users Manual
remain on and the pulse timer will be reset so the duration of the pulse will be extended. If pulse commands
are issued continuously so that the pulse timer is not allowed to expire, the relay will remain on until after
the last pulse command was sent (to be precise, the relay will go off at the time of the last command plus the
Pulse Duration time). The pulse command can be canceled before the pulse duration time has expired by
issuing any other command. The factory default setting for this is 1.5 seconds.
Xytronix Research & Design, Inc.
page 24
Revision 2.2b
WebRelay-QuadTM Users Manual
Section 3: Operation
WebRelay-QuadTM can be operated by using a web browser, by sending text commands to an XML status/control
page, or by sending Modbus/TCP requests.
3.1 Browser Operation
Once the unit is set up, the control page may be accessed by typing the following URL into the web browser:
http://192.168.1.2 (Note that if the IP address was changed, replace the default IP address shown with the new
address that was assigned. Note also that if any port is used other than port 80, the port must also be included in the
request: http://192.168.1.2:8000 ) The new control page will appear. A control page with default settings is shown
below.
3.2 XML Operation
Custom computer applications may be created to monitor and control WebRelay-QuadTM without using a web
browser. Monitoring the state of the relays is done by sending a GET request to port 80 (or port specified in setup)
for the XML page. Control of the relay is done by sending GET requests to the same page. This can be demonstrated
by entering commands into the URL line of a web browser.
Request the current state: http://192.168.1.2/state.xml
This will return the following XML page.:
<?xml version="1.0" encoding="utf-8" ?>
- <datavalues>
<relay1state>0</relay1state>
<relay2state>1</relay2state>
<relay3state>1</relay3state>
<relay4state>1</relay4state>
</datavalues>
The tags <relay1state>... <relay4state> indicate the current state of each of the four relays. Values for
the tags are described below.
Xytronix Research & Design, Inc.
page 25
Revision 2.2b
<relayXstate>
WebRelay-QuadTM Users Manual
0=off(coil off)
1=on (coil energized)
Commands can be sent to WebRelay-QuadTM to control the relays. Commands are sent using variables called
relay1State, relay2State, relay3State and relay4State. Examples of using relayXState (X represents the appropriate
relay) are given here.
Turn relay 1 ‘off’: http://192.168.1.2/state.xml?relay1State=0
Turn relay 1 ‘on’: http://192.168.1.2/state.xml?relay1State=1
Turn relay 1 'on' and turn relay3 'off': http://192.168.1.2/state.xml?relay1State=1&relay3State=0
Commands can be issued to pulse the relays instead of simply turning them on or off by setting the relayXState to 2.
Pulse relay 1: http://192.168.1.2/state.xml?relay1State=2
The example above will cause relay 1 to pulse. The pulse time is specified in the setup page for each relay.
Commands can also specify pulse times so that the relay can be pulsed for times other than the times specified in the
relay setup pages. This is done by sending an additional variable called pulseTimeX (once again, X represents the
appropriate relay).
Pulse relay1: http://192.168.1.2/state.xml?relay1State=2&pulseTime1=5.5
The example above will cause relay 1 to pulse for 5.5 seconds.
Note that the pulseTimeX variable does not change the pulse time specified in the setup page and it is not stored or
recorded. The pulseTimeX variable only changes the pulse duration for the single pulse initiated by that command.
In other words, you must issue the pulseTimeX for each pulse command that differs from the preset pulse time. For
example, suppose the pulse time is set to 1.5 seconds in the configuration pages. To issue one 1.5 second pulse, three
five second pulses, and a 1.5 second pulse once again, you would issue the following commands...
state.xml?relay1State=2
This will pulse the relay for the preset time (1.5 seconds)
state.xml?relay1State=2&pulseTime1=5
This will pulse the relay for 5 seconds.
state.xml?relay1State=2&pulseTime1=5
This will pulse the relay for 5 seconds
state.xml?relay1State=2&pulseTime1=5
This will pulse the relay for 5 seconds
state.xml?relay1State=2
This will pulse the relay for the preset time (1.5 seconds)
(Note that http://192.168.1.2/ would be included on all commands above)
Multiple relays can be changed with a single command by submitting multiple relayXState variables separated by an
ampersand symbol (&). All four relayXState variables or a subset of the relayXState variables can be included. The
relayXState variables can be in any order. Relays that are already in the desired state will not be affected by on/off
commands. Note that pulse commands will reset the pulse timer each time a command is received.
The following line illustrates how to turn ‘on’ relay 1, turn ‘on’ relay 2, and turn ‘off’ relay 4.
http://192.168.1.2/state.xml?relay1State=1&relay4State=0&relay2State=1
When the above commands are sent to WebRelay-QuadTM, its current state is returned in the form of an XML page.
The commands can also be sent without having WebRelay-QuadTM return the XML page. This is accomplished by
adding the noReply field as follows.
Turn relay3 ‘on’ without returning state: http://192.168.1.2/state.xml?relay3State=1&noReply=1
Turn relay3 ‘off’ without returning state: http://192.168.1.2/state.xml?relay3State=0&noReply=1
Password :
If the control password is enabled in the WebRelay-QuadTM unit and the XML page is requested through a browser,
Xytronix Research & Design, Inc.
page 26
Revision 2.2b
WebRelay-QuadTM Users Manual
the browser will prompt the user for the password. If the XML request is sent from another application and not a
browser, the html request will need to contain the password encoded using the base 64 encoding scheme. The html
request header without the password looks like this:
GET /state.xml?noReply=1 HTTP/1.1 (Ends with two \r\n)
The html request header with the password looks like this:
GET /state.xml?relay2State=1&noReply=1 HTTP/1.1 (Ends with two \r\n)
Authorization: Basic bm9uZTp3ZWJyZWxheQ== (Ends with two \r\n)
where bm9uZTp3ZWJyZWxheQ== is the base 64 encoded version of the username and password
none:webrelay
A utility is provided at http://www.ControlByWeb.com/encoder that can be used to encode the password. The utility
is used by simply typing the string username:password into the website and pressing encode.
3.3 Modbus Operation
WebRelay-QuadTM can be controlled (and read) using Modbus/TCP protocol. This provides a standard means of
using WebRelay-QuadTM in conjunction with devices and software from other manufacturers. This section contains
the information necessary to communicate with WebRelay-QuadTM using Modbus/TCP. This is not a tutorial on
Modbus and it is assumed that reader is already familiar with Modbus. Detailed Modbus information can be found at
http://www.modbus.org.
It is important to note that when the control password in WebRelay-QuadTM is enabled, Modbus/TCP communications
are disabled. This is because Modbus/TCP does not provide a mechanism for password protection. Make sure the
control password is disabled (default) before using Modbus with WebRelay-QuadTM.
WebRelay-QuadTM functions as a Modbus server. Client devices open a connection with WebRelay-QuadTM on port
502 (unless another modbus port is selected) and sends commands or requests to to read the state of a relay, or
change a relay. When WebRelay-QuadTM receives a command, it will perform the desired function and return a
response. The following commands are available:
Read Coils (Modbus function 01) - read the status of the relay (and/or the input).
Write Single Coil (Modbus function 05) - change the relay state
Write Multiple Coils (Modbus Function Code 15) – change multiple relays at the same time
Write Multiple Registers (Modbus function 16) - pulse the relay or multiple relays.
Multiple commands may be sent without closing and re-opening the connection but if no data is transferred for about
50 seconds the connection will time out. To keep the connection open, a read request can be sent periodically.
3.3.1 Read Coils (Modbus Function Code 01 (0x01))
This function returns the state of the relay coil(s).
Relay 1 is at address 0x0000, relay 2 is at address 0x0001, relay 3 is at address 0x0002, and relay 4
is at address 0x0003. Multiple relays may be read at the same time by specifying the correct
starting address and quantity of coils. When address 0x0000 is used, the quantities of coils can be
0x0001, 0x0002, 0x0003 or 0x0004. When address 0x0003 is used, the only valid quantity of coils
is 0x0001. This means that relays 1 and 4 cannot be read without reading relays 2 & 3.
Request
Modbus/TCP:
Transaction identifier (2 Bytes): 0x0001
Xytronix Research & Design, Inc.
page 27
Revision 2.2b
WebRelay-QuadTM Users Manual
Protocol identifier (2 Bytes): 0x0000
Length (2 Bytes): 0x0006
Unit identifier (1 Byte): 0xff
Modbus:
Function code (1 Byte): 0x01 (read coils)
Starting address (2 Bytes): 0x0000 (0x0000 ~ 0x0003)
Quantity of coils (2 Bytes): 0x0002 (0x0001 ~ 0x0004)
Character String Example:
char read_coils_mb_request[] ={0x00, 0x01, 0x00, 0x00, 0x00, 0x06, 0xff, 0x01, 0x00, 0x00,
0x00, 0x02 };
Response
Modbus/TCP:
Transaction identifier (2 Bytes): 0x0001
Protocol identifier (2 Bytes): 0x0000
Length (2 Bytes): 0x0004
Unit identifier (1 Byte): 0xff
Modbus:
Function code (1 Byte): 0x01 (Read coils)
Byte count (1 Byte): 0x01
Coil status (1 Byte): 0x00 to 0x0F (see chart below)
Data Byte (hex)
LS Data Bits (binary)
Relay 4 State
Relay 3 State
Relay 2 State
Relay1 State
0x00
0000
off
off
off
off
0x01
0001
off
off
off
on
0x02
0010
off
off
on
off
0x03
0011
off
off
on
on
0x04
0100
off
on
off
off
0x05
0101
off
on
off
on
0x06
0110
off
on
on
off
0x07
0111
off
on
on
on
0x08
1000
on
off
off
off
0x009
1001
on
off
off
on
0x0A
1010
on
off
on
off
0x0B
1011
on
off
on
on
0x0C
1100
on
on
off
off
0x0D
1101
on
on
off
on
0x0E
1110
on
on
on
off
0x0F
1111
on
on
on
on
Modbus Error:
Function code (1 Byte): 0x81
Exception code (1 Byte): 0x01 or 0x02
Exception codes:
0x01 - Function code not supported
Xytronix Research & Design, Inc.
page 28
Revision 2.2b
WebRelay-QuadTM Users Manual
0x02 - Incorrect starting address / quantity of outputs combination
Character String Example:
char read_coils_mb_response[] = {0x00, 0x01, 0x00, 0x00, 0x00, 0x04, 0xff, 0x01, 0x01, 0x01};
3.3.2 Write Single Coil (Modbus Function Code 05 (0x05))
Request
Modbus/TCP:
Transaction identifier (2 Bytes): 0x0001
Protocol identifier (2 Bytes): 0x0000
Length (2 Bytes): 0x0006
Unit identifier (1 Byte): 0xff
Modbus:
Function code (1 Byte): 0x05 (write coil)
Output address (2 Bytes): 0x0000 – 0x0003 (specifies relay)
Output value (1 Byte): 0xff - turn relay on, 0x00 - turn relay off
Padding (1 Byte): 0x00
char write_coil_mb_request[] = {0x00, 0x01, 0x00, 0x00, 0x00, 0x06, 0xff, 0x05, 0x00, 0x00, 0xff,
0x00 };
Response
Modbus/TCP:
Transaction identifier (2 Bytes): 0x0001
Protocol identifier (2 Bytes): 0x0000
Length(2 Bytes): 0x0006
Unit identifier (1 Byte): 0xff
Modbus:
Function code (1 Byte): 0x05 (write coil)
Reference number (2 Bytes): 0x0000
Data (1 Byte): 0xff - relay on, 0x00 - relay off
Padding (1 Byte): 0x00
Modbus Error:
Function code (1 Byte): 0x85
Exception code (1 Byte): 0x01 or 0x02
Exception codes:
0x01 - Function code not supported
0x02 - Incorrect starting address / quantity of outputs combination
char write_coil_mb_response[] = {0x00, 0x05, 0x00, 0x00, 0x00, 0x06, 0xff, 0x05, 0x00, 0x00,
0xff, 0x00 };
Xytronix Research & Design, Inc.
page 29
Revision 2.2b
WebRelay-QuadTM Users Manual
3.3.3 Write Multiple Coils (Modbus Function Code 15 (0x0F))
A single byte can be written to set the state of all four relays. To do this, set the starting address to 0, set the
quantity of outputs to 4, and write a single byte with the appropriate value according to the table below.
Data Byte (hex)
LS Data Bits (binary)
Relay 4 State
Relay 3 State
Relay 2 State
Relay1 State
0x00
0000
off
off
off
off
0x01
0001
off
off
off
on
0x02
0010
off
off
on
off
0x03
0011
off
off
on
on
0x04
0100
off
on
off
off
0x05
0101
off
on
off
on
0x06
0110
off
on
on
off
0x07
0111
off
on
on
on
0x08
1000
on
off
off
off
0x009
1001
on
off
off
on
0x0A
1010
on
off
on
off
0x0B
1011
on
off
on
on
0x0C
1100
on
on
off
off
0x0D
1101
on
on
off
on
0x0E
1110
on
on
on
off
0x0F
1111
on
on
on
on
Alternatively, to modify the state of one, two, or three relays only, the starting address and quantity of outputs can be
set to values other than 0, and 4 respectively.
Request
Modbus/TCP:
Transaction identifier (2 Bytes): 0x0001
Protocol identifier (2 Bytes): 0x0000
Length (2 Bytes): 0x0008
Unit identifier (1 Byte): 0xff
Modbus:
Function code (1 Byte): 0x0f (write coil)
Starting address (2 Bytes): 0x0000 ~ 0x0003
Quantity of outputs (2 Bytes): 0x0001 ~ 0x0004
Byte count (1 Byte): 0x01
Output value (1 Byte): 0x00 ~ 0x0f (see table above)
char write_mult_coil_mb_request[] = {0x00, 0x01, 0x00, 0x00, 0x00, 0x08, 0xff, 0x0f, 0x00, 0x00,
0x00, 0x01, 0x01, 0x0F };
Response
Modbus/TCP:
Transaction identifier (2 Bytes): 0x0001
Protocol identifier (2 Bytes): 0x0000
Length(2 Bytes): 0x0006
Unit identifier (1 Byte): 0xff
Xytronix Research & Design, Inc.
page 30
Revision 2.2b
WebRelay-QuadTM Users Manual
Modbus:
Function code (1 Byte): 0x05 (write coil)
Starting address (2 Bytes): 0x0000
Quantity of outputs (1 Byte): 0xff - relay on, 0x00 - relay off
Modbus Error:
Function code (1 Byte): 0x8f
Exception code (1 Byte): 0x01 or 0x02
Exception codes:
0x01 - Function code not supported
0x02 - Incorrect starting address / quantity of outputs combination
char write_coil_mb_response[] = { 0x00, 0x05, 0x00, 0x00, 0x00, 0x06, 0xff, 0x05, 0x00, 0x00,
0xff, 0x00 };
3.3.4 Write Multiple Registers (Modbus Function Code 16 (0x10))
This is used to pulse the relay(s) for a specified time. When WebRelay-QuadTM receives this command, it
immediately turns the appropriate relay coil(s) on (if not on already on) and starts the pulse timer. The
relay(s) are selected by writing the pulse time to the register(s) associated with the appropriate relay(s). The
pulse time is specified in the register value field and can range from 0.1 seconds to 86400 seconds (1 day).
When the pulse time expires, the relay coil will be turned off. If a pulse time command is sent with a value
greater than 86400, the pulse timer will be set to 86400. If a pulse time command is sent with a value less
than 0.1, the pulse timer will be set to 0.1. If any commands are sent to WebRelay-QuadTM (commands may
be modbus, xml or html) before the pulse timer has expired, the pulse timer will be canceled immediately
and the new command will be executed.
The pulse time is provided in IEEE 754 floating point format. The four data bytes are treated as two
individual big endian 16-bit words but the least significant word is sent first. In other words, the 32-byte
floating point number represented as ABCD is sent as CDAB. In the example shown below, the relay will
pulse for 10 seconds. Ten seconds is represented using a floating point number of 41200000. It is
transferred as 00004120.
Request
Modbus/TCP:
Transaction identifier (2 bytes): 0x0001
Protocol identifier (2 bytes): 0x0000
Length (2 bytes): 0x000b
Unit identifier (1 byte): 0xff
Modbus:
Function code (1 Byte): 0x10 (Write Multiple Registers)
Starting address (2 Bytes): 0x0010 (0x0010 relay1, 0x0012 relay 2, 0x0014 relay 3, 0x0016 relay
4)
Number of registers (2 Bytes): 0x0002 (2 registers for each relay to be pulsed)
Byte count (1 Byte): 0x04 (2 times the number of registers)
Register value (4 Bytes for each relay to be pulsed): 00 00 41 20 (10 second pulse time)
char write_registers_mb_request = {0x00, 0x01, 0x00, 0x00, 0x00, 0x0b, 0xff, 0x10, 0x00, 0x10,
0x00, 0x02, 0x04, 0x00, 0x00, 0x41, 0x20 };
Response
Modbus/TCP:
Transaction identifier (2 Bytes): 0x0001
Protocol identifier (2 Bytes): 0x0000
Xytronix Research & Design, Inc.
page 31
Revision 2.2b
WebRelay-QuadTM Users Manual
Length (2 Bytes): 0x0006
Unit identifier: 0xff
Modbus:
Function (1 Byte): 0x10 (Write Multiple Registers)
Reference number (2 Bytes): 0x0010
Word count (2 Bytes): 0x0002
Modbus Error:
Function code (1 Byte): 0x90
Exception code (1 Byte): 0x01, 0x02, 0x03, or 0x04
Exception codes:
0x01 - Function code not supported
0x02 - Incorrect starting address / quantity of outputs combination
char write_registers_mb_response[] = {0x00, 0x05, 0x00, 0x00, 0x00, 0x06, 0xff, 0x10, 0x00,
0x10, 0x00, 0x02 };
Xytronix Research & Design, Inc.
page 32
Revision 2.2b
WebRelay-QuadTM Users Manual
Appendix A: Restoring Factory Default Settings
In the event that the IP address or passwords are forgotten, WebRelay-QuadTM may be restored to its original factory
default settings. To do this, first remove the power from the unit. Next, insert a thin object (such as a toothpick)
through the small hole in the bottom of the unit to press the small button that is located inside the unit. When the
object is inserted, a tactile feel can be detected as the button is depressed. While holding the button down, apply
power and wait for about 10 seconds. After about 10 seconds, release the button. Now all settings will be back to
the original factory defaults. CAUTION: DO NOT USE METAL OBJECTS FOR THIS FUNCTION.
Small hole
to access
Reset Button
Xytronix Research & Design, Inc.
page 33
Revision 2.2b
WebRelay-QuadTM Users Manual
Appendix B: Specifications
Power Requirements:
Model X-WR-4R1-5
Voltage: 5VDC ± 5%
Current: See table below for typical values
10Mbps Network
100Mbps Network
No Relays On
130mA
255mA
All 4 Relays On
335mA
477mA
Model X-WR-4R1-I
Voltage: 9~28VDC
Current: See table below for typical values
10Mbps Network
100Mbps Network
9V No Relays On
98mA
186mA
9V All 4 Relays On
225mA
320mA
12V No Relays On
75mA
140mA
12V All 4 Relays On
170mA
240mA
24V No Relays On
40mA
73mA
24V All 4 Relays On
88mA
123mA
Model X-WR-4R1-E
POE Class 1 (0.44 to 3.84 Watt). Optionally can be powered with external 5VDC power supply.
I/O: 4 Relays
Relay Contacts:
Contact Form: SPDT (Form C) (Direct access to dry contacts)
Contact Material: Ag (Au clad)
Max Voltage: 28V
Max Current: 1A
Min Load: 1mA @ 5VDC
Relay Control Options: ON/OFF or Pulsed
Pulse Timer Duration: 100ms to 86400 Seconds (1 day)
Accuracy of pulse timer: 99.99%
Network: 10/100Base-T Ethernet
Network Setup: static IP address assignment, TCP port selectable
Connectors:
Power/Relay Contacts: 14-position, removable terminal strip, 3.81mm terminal spacing
(Replacement part number, Phoenix Contact 1803691 )
Network: 8-pin RJ-45 socket
Xytronix Research & Design, Inc.
page 34
Revision 2.2b
WebRelay-QuadTM Users Manual
LED Indicators: 7
-Power on
-Relay coils (1-4) engaged
-Network linked
-Network activity
Physical:
Operating Temperature: -20° to 70°C ( -4°-158°F)
Size: 1.41in (35.7mm) wide X 3.88in (98.5mm) tall X 3.1 in(78.0mm) deep
Weight: 4.5oz (128 grams)
Enclosure Material: Lexan 940 (UL94 V0 flame rated)
Password Settings:
Password protection on setup page: Yes
Password protection on control page: Optional
Password Encoding: Base 64
Max password length: 10 characters
Regulatory Compliance:
Electromagnetic Compliance:
IEC CISPR 22, CISPR 24
FCC 47CFR15 (-I and -5 Models class B, POE Model Class A)
EU EN55024, EN55022
Product Safety:
IEC 60950-1 / EN 60950-1
Xytronix Research & Design, Inc.
page 35
Revision 2.2b
WebRelay-QuadTM Users Manual
Appendix C: Mechanical Information
Xytronix Research & Design, Inc.
page 36
Revision 2.2b
WebRelay-QuadTM Users Manual
Appendix D: Open TCP Legal Notice
Portions of the software used in WebRelay-QuadTM are open source. The appropriate notices are listed below. All
other parts of the software are property of Xytronix Research & Design, Inc. ©2005-2006.
Copyright (c) 2000-2002 Viola Systems Ltd.
All rights reserved.
Redistribution and use in source and binary forms, with or without
modification, are permitted provided that the following conditions
are met:
1. Redistributions of source code must retain the above copyright
notice, this list of conditions and the following disclaimer.
2. Redistributions in binary form must reproduce the above copyright
notice, this list of conditions and the following disclaimer in the
documentation and/or other materials provided with the distribution.
3. The end-user documentation included with the redistribution, if
any, must include the following acknowledgment:
"This product includes software developed by Viola
Systems (http://www.violasystems.com/)."
Alternately, this acknowledgment may appear in the software itself,
if and wherever such third-party acknowledgments normally appear.
4. The names "OpenTCP" and "Viola Systems" must not be used to
endorse or promote products derived from this software without prior
written permission. For written permission, please contact
opentcp@opentcp.org.
5. Products derived from this software may not be called "OpenTCP",
nor may "OpenTCP" appear in their name, without prior written
permission of the Viola Systems Ltd.
THIS SOFTWARE IS PROVIDED "AS IS" AND ANY EXPRESSED OR IMPLIED
WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED.
IN NO EVENT SHALL VIOLA SYSTEMS LTD. OR ITS CONTRIBUTORS BE LIABLE
FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR
CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF
SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR
BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY,
WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE
OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE,
EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.
====================================================================
OpenTCP is the unified open source TCP/IP stack available on a series
of 8/16-bit microcontrollers, please see <http://www.opentcp.org>.
For more information on how to network-enable your devices, or how to
obtain commercial technical support for OpenTCP, please see
<http://www.violasystems.com/>.
Xytronix Research & Design, Inc.
page 37
Was this manual useful for you? yes no
Thank you for your participation!