K1 Series Catalog Page

K1 Series Catalog Page
NEW!
HAZARDOUS LOCATIONS
INTRINSICALLY SAFE PRESSURE TRANSMITTER
K1 SERIES
DESCRIPTION
The Ashcroft K1 Series intrinsically safe pressure
transmitter is exceptionally stable and is virtually unaffected
by shock, vibration, or orientation. Performance is directly
traceable to NIST standards, and a calibration certificate
is available for each unit upon request. These intrinsically
safe (IS) transmitters are ideal for monitoring pressures in
explosive atmospheres with barrier.
FEATURES
• Class I, Division 1, Groups C, D;
Class II, Division 1, Group G; Class III
• Nonincendive for Class I, Division 2, Groups A, B, C,
and D
• 0.5% accuracy, all ranges
• 4-20 mA, loop powered
• Ranges from 100-3000 psig (690-20,685 kPa)
C
FM
US
APPROVED
SPECIFICATIONS
HAZARDOUS LOCATIONS
8
Supply Voltage
10-36 VDC
Accuracy
±0.5% full scale
Thermal Effect
±0.03 full scale/°F zero and span
Output
4-20 mA
Maximum Output
Impedance
650Ω @ 24 VDC
Overpressure
Proof: 150%; Burst: 300%
Temperature
Compensation
-20° to 160°F (-29° to 71°C)
Operating Temperature-20° to 180°F (-29° to 82°C)
Response Time
5 ms
Materials Of
Construction
304 stainless steel case
WIRING
Hazardous Safe Area
Area
MTL7706
Intrinsically Safe Barrier
3
BR+
K1
1
Power
Bus
20-35 VDC
+
2
4
250Ω
1-5V
–
Process Connection
Diaphragm Material
Zero Span Adjust
Dimensions
Weight
Area
Approvals
Entity Parameters
Warranty
1'8" BNPT male 316 stainless steel
17-4 PH stainless steel
Field adjustable ±10%
4" L x 5/8" dia (10.2 x 1.6 cm)
0.65 lb (0.29 kg)
Intrinsically safe Class I, Division 1,
Groups C, D; Class II, Division 1,
Groups G; Class III
UL File #E152893, FM
Vmax=30V, Imax- 250 mA, Li = 0, Ci
= 0.1 µF
1 year
CAUTION: Intrinsically safe devices require the use of an
intrinsic safety barrier when applied in hazardous locations.
Provide wiring and grounding strictly in accordance with
manufacturer's instructions. When a K1 Series transmitter
is combined with the Model MTL7706 intrinsic safety barrier,
total cable capacitance between the two must be limited to
0.12 µF. Total cable inductance must be limited to 4.0 mH
(equivalent to 2700'/823m maximum Belden™ #8760 18/2
shielded twisted pair cable 0.18 µH/FT, 44 pF/FT).
Ground Here Only
ORDERING INFORMATION
456
MODEL
K15M0142F2100X
K15M0142F2200X
K15M0142F2500X
K15M0142F21KX
K15M0142F23KX
DESCRIPTION
4-20 mA intrinsically safe pressure transmitter 0-100 psig (690 kPa)
4-20 mA intrinsically safe pressure transmitter 0-200 psig (1379 kPa)
4-20 mA intrinsically safe pressure transmitter 0-500 psig (3448 kPa)
4-20 mA intrinsically safe pressure transmitter 0-1000 psig (6895 kPa)
4-20 mA intrinsically safe pressure transmitter 0-3000 psig (20,685 kPa)
250R-3-1
DCP-1.5-W
DCPA-1.2
MTL7706+
PT
RELATED PRODUCTS
250 OHM 3 WATT 1% Resistor Long Leads
Power supply, 24 VAC IN to 24 VDC OUT
Power supply, 120 VAC IN to 24 VAC/24 VDC OUT
Intrinsic safety barrier, 4-20 mA two-wire transmitters
1/4" pigtail syphon with fittings
888-397-5353 USA
kele.com
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
PAGE