FC BS R407 04
BS 15
BS 18
BS 24
BS 30
BS 36
BS 43
3.23
1.31
420/480/520
3.2/3.8/4.3
3.8
1.7
530/570/610
3.8/4.5/5
5.52
2.24
570/630/680
3/3.5/4
6.59
2.93
910/1035/1120
2.4/3.2/4
8.5
3.52
1040/1150/1300
2/3/4
10.26
3.84
1175/1380/1535
3.7/7
12.6
5.18
1430/1600/1765
5/9
dB(A)
dB(A)
37
53
40
54
41
47
41
47
43
62
54.5
62
64
64
A
mm2
8
Indoor unit
12
3x1.5
Indoor unit
16
3x1.5
In or outdoor unit
20
3x1.5
In or outdoor unit
25
3x2.5
Outdoor unit
-
-
Rotary
Rotary
8
Scroll
10
5x1.5
Outdoor unit
Scroll
R407C
- 10 °C / + 43 °C
12
5x1.5
Outdoor unit
Scroll
12
5x1.5
Outdoor unit
Scroll
16
5x1.5
Outdoor unit
Scroll
Linking specification between indoor and outdoor units
Linking pipes (not supplied)
m
20
Maximum pipe length
m
7
Maximum height difference
Inchs
1/4"
Liquid pipe diameter
Inchs
1/2"
Suction pipe diameter
20
15
1/4"
1/2"
15
10
3/8"
5/8"
30
10
3/8"
5/8"
30
10
3/8"
5/8"
50
25
3/8 "
3/4 "
50
25
3/8 "
3/4 "
Electrical connections (not supplied)
1 ~ 230 V version
3N ~ 400 V version
5x1.5
-
5x1.5
-
5x1.5
5x1.5
5x1.5
5x1.5
5x1.5
5x1.5
5x1.5
5x1.5
BS 11 RC
BS 15 RC
BS 18 RC
BS 24 RC
BS 30 RC
BS 36 RC
BS 43 RC
Power supply
- 1 ~ 230 V - 50 Hz
Motor fuse rating (1-230 V)
Power cable section (without heating)
Power supply side
- 3N ~ 380 V - 50 Hz
Motor fuse rating (3-400 V)
Power cable section (without heating)
Power supply side
Compressor type
Refrigerant
Operating limits - Winter / Summer
A
mm2
mm2
mm2
BS RC
Cooling capacity (1)
Power input
kW
kW
3.23
1.31
3.8
1.7
5.52
2.24
6.59
2.93
8.5
3.52
10.26
3.84
12.6
5.18
Heating capacity (2)
Power input
kW
kW
3.5
1.32
4.5
1.66
5.99
2.11
7.53
2.78
9.96
3.36
10.99
4.04
14
5.36
Linking specification between indoor and outdoor units
Linking pipes (not supplied)
m
20
Maximum pipe lenght
m
7
Maximum height difference
Inchs
1/4"
Liquid pipe diameter
Inchs
1/2"
Suction pipe diameter
20
15
1/4"
1/2"
15
10
3/8"
5/8"
30
10
3/8"
5/8"
30
10
3/8"
5/8"
50
25
3/8 "
3/4 "
50
25
3/8 "
3/4 "
Electrical connections (not supplied)
1 ~ 230 V version
3N ~ 400 V version
mm2
mm2
6x1.5
-
6x1.5
-
6x1.5
6x1.5
6x1.5
6x1.5
6x1.5
6x1.5
6x1.5
6x1.5
W
1600
o
o
1600
o
o
1900 (4)
o
o
4000 (5)
o
o
4000 (5)
o
o
-
-
Dimensions and weights
Indoor unit
Weight
Dimensions (LxDxH)
kg
mm
39
860x675x245
39
860x675x245
39
860x675x245
66
1190x675x270
66
1190x675x270
32
1100x475x300
40
1100x475x300
Outdoor unit
Weight
Dimensions (LxDxH)
kg
mm
38
795x290x610
41
795x290x610
56
850x370x690
58
850x370x690
82
900x340x860
93
900x340x970
95
900x350x970
Accessories for models
Single phase electric heating
N° 1 cassette air intake plenum kit
N° 2 cassette air intake plenum kit
NOTES: All values are specified for a 230 V ou 3N 400 V - 50 Hz supply voltage.
(1) Nominal cooling capacity: International conditions: 27° C / 19° C (wet bulb) - outdoor air temperature 35° C / 24° C (wet bulb) (Standards NF EN 255.2 - NF EN 814.2).
(2) Nominal heating capacity: International conditions: 20° C / 12° C (wet bulb) - outside air temperature 7° C / 6° C (wet bulb) (Standards NF EN 255.2 - NF EN 514.2).
(3) Acoustic levels: Global acoustic pressure in dBA (1m) under nominal conditions: outdoor unit in an open area against a reflective background - indoor unit: installations in an average sized
room (LS - 0.5 s reverberations).
(4) Accessories: Single heating fitted to three phase unit.
(5) Accessories: Identical model for single and three phase unit.
Your approved Airwell distributor
- Printed in the E.U.
BS 11
kW
kW
m3/h
daPa
Cooling capacity (1)
Power input
Airflows (LS/MS/HS)
Available static pressure (LS/MS/HS)
Acoustic pressure at 1 m (3)
Indoor unit (Fan/motor assy.)
Outdoor unit
ACE MARKETING RCS VERSAILLES B 421 305 996 - These specifications are provided for information purposes only and are subject to change without notice - Non contractual photos -
BS
BS DUCTED UNIT
REF : FC BSR407 04-798/AN
Split-System
customised
www.airwell.com
Split-System
BS Ducted units
Heat pump
R407C
flexible
D U C T E D
R A N G E
discreet
Cooling only
D U C T E D
T
R A N G E
he BS SPLIT-SYSTEM DUCTED range offers a
multitude of air distribution solutions. The design
freedom epitomised by this range enables truly
"customised" installations to be created,
being perfectly adapted
DESIGN FREEDOM
By offering air distribution by direct blowing or via a
duct network, the
BS SPLIT-SYSTEM DUCTED range offers
unequalled design freedom. You have complete
freedom to choose the location of both air intakes
and air outlets.
"Heat pump" versions
advantages
DISCREET SUSPENDED CEILING MOUNTING
The BS SPLIT-SYSTEM DUCTED range has
been designed to meet a multitude of dimensional
constraints.
Being ultra-slim, these units can be easily built in to
all types of suspended ceilings, even in the tightest
spaces.
INSTALLATION FLEXIBILITY
Thanks to the available static pressure
the rectangular or circular duct network can be
adapted precisely to the layout of all types of
premises, even the most complex.
With linking pipe lengths of up to 50 m, depending
on the models,
the BS SPLIT-SYSTEM range offers unrivalled
flexibility in terms of installation
of both outdoor and indoor units.
to the layout and the
configuration of the premises
Outdoor units
to be air conditioned.
Available in "Cooling only" or
compatible with water or air
condenser units, this range is
capable of meeting all
tertiary sector air
conditioning requirements.
VERTICAL MOUNTING POSSIBLE FOR
MODELS 11 TO 30.
HORIZONTAL MOUNTING ONLY FOR
MODELS 36 TO 43.
BS 11/15/18
Application domains
Restaurants
Hotels
Cafés
Shops
Infrared remote control
Range of up to 8 metres
Wall mounted remote control
Offices
Available as an accessory: hardwired control
Possibility of controlling up to indoor 32 units
(in 15 different zones).
Split-System
BS DUCTED UNITS
Evolution, innovation
High performance indoor units:
The indoor units offer a host of functions: multi-speed ventilation,
temperature regulation via adjustable thermostat, air filters...
Reliable outdoor consenser units:
Outdoor units are treated with anti-corrosion protection. Their low
fan speed guarantees discreet and economical operation.
Configuration possibilities:
Thanks to a vast range of standard and interchangeable
accessories, the BS indoor units provide numerous installation and
air distribution possibilities.
2
1
Indoor units
Direct blowing
Base unit + rectangular duct connection
on air blowing outlet and air return inlet.
Ducted blowing
Base unit + multi-zone duct blowing connection.
1
BS 24/30
+ cassette return plenum
under the unit
2
+ return duct network plenum connection
Grilles and duct not supplied
A choice of multi-function remote
controls with leading edge ergonomic
design
•
•
•
•
•
•
•
•
Automatic cooling / Heating regulation.
3 ventilation (fan) speeds.
Automatic ventilation.
"I Feel" function.
Night time slow running.
Dehumidification.
2 programming ranges: week and weekend.
Blacklit LCD screen.
Infrared receiver for remote control
COOL: Cooling mode light.
HEAT: Heating mode light.
OPER: Operating light. Lights up when the unit is
running. Flashes to confirm receipt of an infrared
signal.
STBY: Standby light. Lights up when the system is
connected and ready to receive instructions from the
remote control.
MODE: Emergency control. Pressing this key
enables the Heating and Cooling functions to be
selected in the event of the remote control not being
available.
Connection box
Connection board with terminals for connection the
infrared receiver.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising