TCS-NET MODBUS
Specifications Manual
TCS-NET Modbus Protocol Conversion Interface
Model name:
TCB-IFMB640TLE
Contents
1 System Overview....................................................................................................................... 2
2 RS 485 Communication Parameters ......................................................................................... 3
3 Applied Function Codes............................................................................................................. 3
4 Exception Response.................................................................................................................. 4
5 Counters and Registers ............................................................................................................. 4
6 Sequence................................................................................................................................... 5
7 Address Assignment Table........................................................................................................ 6
8 Appendix.................................................................................................................................. 15
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
+00DHxxxxxxxx_01EN_IFMB640TLE_Spec.book Page 2 Friday, June 20, 2008 9:17 AM
Heronhill - for all your Toshiba requirements
Specifications Manual
TCS-NET Modbus Protocol Conversion Interface
1
System Overview
This manual describes Modbus* protocol implementation specifications of TCB-IFMB640TLE. TCB-IFMB640TLE
is equipped with the Modbus Slave function. Specifications that are not detailed in this manual conform to the
following MODBUS specifications.
• MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1b
• MODBUS over Serial Line Specification and Implementation Guide V1.01
http://www.modbus-ida.org/
This implementation specification specifies the operation of Modbus that works on the RS485 serial line, where a
slave device sends a response to a request from the master device. Multiple slave devices are connected to the
RS485 bus. Modbus uses the Modbus RTU mode with the frame format shown below.
START
SLAVE ADDRESS
FUNCTION
DATA
CRC
>=3.5 characters
8 bits
8 bits
N*8 bits (N = 252 max.) 16 bits
END
>= 3.5 characters
Each slave device is connected to the TCC-LINK main bus. The internal data and operation of indoor units and
TCB-IFCG1TLE units (general purpose interface) to which central addresses 1 to 64 are assigned are controlled
by the master device. Up to 15 slave devices may be connected to the master device.
A broadcast message will be sent when the slave address 0x00 is specified in a request, and all slave devices will
receive the request but send no response including exception response. The figure below shows an example of
the connection of the master device, slave devices, and air conditioners.
Terminator
A
TCB-IFMB640TLE
Terminator
A
Modbus-Master
Modbus-I/F Slave 1
B
B
U1 U2
TCC-LINK Bus
……
INDOOR/OUTDOOR
TCB-IFCG1TLE
TCB-IFMB640TLE
RS-485 Bus
A
Modbus-I/F Slave 2
B
U1 U2
TCC-LINK Bus
……
INDOOR/OUTDOOR
TCB-IFCG1TLE
TCB-IFMB640TLE
A
Modbus-I/F Slave N
B
U1 U2
TCC-LINK Bus
……
INDOOR/OUTDOOR
TCB-IFCG1TLE
N = Max. 15
* “Modbus” is a registered trademark of Schneider Electric SA.
2 (EN)
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
+00DHxxxxxxxx_01EN_IFMB640TLE_Spec.book Page 3 Friday, June 20, 2008 9:17 AM
Heronhill - for all your Toshiba requirements
Specifications Manual
TCS-NET Modbus Protocol Conversion Interface
2
RS 485 Communication Parameters
RS 485 communication parameters are shown below.
• Character length = 11 bits, Data = 8 bits, Parity Check = even, Start bit =1 bit low, Stop bit = 1bit high
• Communication: 9600/19200/38400 bps (default: 19200 bps) Selected manually.
• Bit transmission order: LSB first (b0, b1….). Bit data is transmitted sequentially from the LSB.
• Byte transmission order: Big Endian. 0x1234 -> 0x12 then 0x34. Byte data is transmitted in the big endian order.
• Half duplex, 2 wires. 120 Ω termination. A: Non-inverted input, B: Inverted input
• After receiving a packet, a response is permitted after at least 3.5 characters.
• Connecter: 2 terminals
3
Applied Function Codes
The following function codes are implemented.
Function code
Sub function code
Function name
0x01
None
Read coils
0x02
None
Read Discrete input
0x03
None
Read holding register
0x04
None
Read Input register
0x05
None
Write single coil
0x06
None
Write single holding register
0x08
0x00, 01, 02, 04, 0A, 0B, 0C, 0D, 0E, 0F, 11, 12, 14
Diagnostics
0x0B
None
Get Comm Event Counter
0x0C
None
Get Comm Event Log
0x0F
None
Write multiple coils
0x10
None
Write multiple holding registers
Exception
The relationship between the start address specified in a request from the master device and the value shown by
“Modbus-address for registers” in the address assignment table is as follows:
• For Coil
Start address = (Value of Modbus-address for registers) - 1
• For Discrete input
Start address = (Value of Modbus-address for registers) - 10001
• For Input register
Start address = (Value of Modbus-address for registers) - 30001
• For Holding register
Start address = (Value of Modbus-address for registers) - 40001
3 (EN)
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
+00DHxxxxxxxx_01EN_IFMB640TLE_Spec.book Page 4 Friday, June 20, 2008 9:17 AM
Heronhill - for all your Toshiba requirements
TCS-NET Modbus Protocol Conversion Interface
4
Specifications Manual
Exception Response
Except for Broadcast, the master device issues a request expecting a normal response from a slave device. Slave
units return a normal response when no error is detected, but return no response when an error occurs during the
parity check or CRC check. Slave units must return an exception response when they receive a request which has
been sent correctly but contains an error that applies to any of the following exception codes.
Exception code Name
0x01
Illegal function
A request of illegal function that is not supported by this specification is received
0x02
Illegal data address
An illegal address that does not exist in section 7 of this manual. Address Assignment table or a data
request size larger than 249 octets is specified.
0x03
Illegal data value
Illegal data in any of the following cases:
1) When data other than that defined in section 7 of this manual Address Assignment table is specified.
2) When Broadcast (slave address = 0) is specified with a function code other than 0x05, 0x06, 0x0F, 0x10
3) When an address is specified for two or more devices
0x04
Slave device failure
Slave device internal processing is not correct (When any error occurs during booting or reading the RAM).
0x05
ACK
A slave device returns response ACK when it received a request while it is acquiring response data during
the slave device initial data acquisition process.
0x06
Slave device busy
When a slave device is busy and cannot return response data, this code is returned.
0x07
When a master’s request is about an indoor unit which does not respond to the request. (However, the
master’s request is sent to the indoor unit.)
5
Counters and Registers
TCB-IFMB640TLE is equipped with the following counters and registers that are cleared by a power-on reset,
restart process, or a counter reset command.
Register/Counter
Description
Coils (R/W)
For air-conditioner database
Discrete input (R)
For air-conditioner database
Input register (R)
For air-conditioner database
Holding register (R/W)
For air-conditioner database
Event counter
Counted when a slave device has processed a received message correctly. This counter is
not incremented when the exception command or 0B command is received.
Message counter
Retains the number of messages sent by the slave device.
Diagnostics register
A 16-bit register that retains the content of diagnosis.
0x0000: Normal
0x0001: CRC error
0x0002: EEPROM checksum error
Other: Reserved
Bus Communication Error
Count
Total number of CRC errors detected by slave devices
Exception Error Count
Total number of exception errors detected by slave devices
Slave Message Count
Total number of messages received by the corresponding slave device
No Response Count
Total number of messages received by the corresponding slave device, which are not
accompanied by response
Busy Count
Total of Busy Count (exception error) detected by the corresponding slave device
Bus Character Overrun Count
Number of character overrun errors (failure in receiving part of the data) detected in
messages to the corresponding slave device
4 (EN)
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
+00DHxxxxxxxx_01EN_IFMB640TLE_Spec.book Page 5 Friday, June 20, 2008 9:17 AM
Heronhill - for all your Toshiba requirements
Specifications Manual
TCS-NET Modbus Protocol Conversion Interface
6
Sequence
The master device sends a request sequentially to each slave device, and gets response data from each slave
device. A slave device returns a response to a request from the master device within one second (see the diagram
below). When a slave device receives a data read request, the slave device returns the data stored in the register.
It is recommended that the master device collects specific information such as air conditioner models, addresses,
unique numbers, and operation setting range when the master device accesses the air conditioning system for the
first time.
When writing to air conditioners, the master device must read the operation range for, operation mode, fan speed
and setting temperature from each air conditioner and write values within the operation range. Pay attention to the
sequence of simultaneous setting for writing to air conditioners because it requires time for processing on the slave
device side. Furthermore, because no response or exception response with respect to the writing for broadcast
message is sent from slave devices, it is recommended that data written to slave devices be checked on the master
device side as required. It is recommended to confirm whether a master’s request is reflected by reading the read
register after appropriate time once a communication is completed, because indoor units may not be able to receive
a normal request from the mater due to TCC-LINK communication condition.
In addition, it is also recommended that data be requested at appropriate intervals so that the alarm data that is
output from air conditioners is properly reflected in the discrete input register.
Master
Slave 1
Slave 2
Slave 3
Slave N
Indoor #1 request
Indoor #1 response
Indoor #2 request
Indoor #2 response
………………………..
Indoor #64 request
Indoor #64 response
Indoor #1 request
Indoor #1 response
5 (EN)
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
+00DHxxxxxxxx_01EN_IFMB640TLE_Spec.book Page 6 Friday, June 20, 2008 9:17 AM
Heronhill - for all your Toshiba requirements
Specifications Manual
TCS-NET Modbus Protocol Conversion Interface
7
Address Assignment Table
Total 42368 octets (9728*2/8 + 9984*2*2). The data of the address assignment table is cleared during initialization.
Modbusdescription
ModbusIndoornumber address for
registers
Data name
Octet
Length Order
Explanation
Coills (R/W)
1
On/Off setting
1 octet
1= On,0 =Off (address=1)
1-8
1
Filter sign reset setting
1= reset,others=no action (address=2)
Reserved
9-16
Operation mode
setting
1 octet
2
0x00=unfix,0x 01= heat,0x 02= cool,0x 03= dry 0x
04= fan,0x05 auto (address=9LSB ,address=
16MSB)
17-24
Fan speed setting
1 octet
3
0x00=Invalid,0x01=Fan
Stop,0x02=Auto,0x03=High,0x04=Medium,0x05=
Low,0x06=Ultra Low,0x07=unfix (address=17
LSB,address=24MSB)
25-32
Louver setting
1 octet
4
0x00= invalid ,0x 1 =swing, 0x 2= f1,0x 3 =f2,0x 4= f3,
0x 5= f4 ,0x 6 =f5,0x7=stop (address=25
LSB,address=32MSB)
33-40
Remote controller on/
off prohibit setting
1 octet
5
Remote controller on/off prohibit setting (address=33)
Remote controller mode prohibit setting (address=34)
Remote controller setpoint prohibit setting
(address=35)
Remote controller louver prohibit setting
(address=36)
Remote controller fan speed prohibit setting
(address=37)
1=prohibit 0=permit
41-48
Relay 1ch output for
TCB-IFCG1TLE
1 octet
6
TCB-IFCG1TLE bit output
see manual of TCB-IFCG1TLE
Relay 2ch output for
TCB-IFCG1TLE
Relay 3ch output for
TCB-IFCG1TLE
Relay 4ch output for
TCB-IFCG1TLE
Reserved
2
49-152
Reserved
104bit
7-19
153-160
On/Off setting
1 octet
20
Filter sign reset setting
1= On,0 =Off (address=153)
1= reset,others=no action (address=154)
Reserved
161-168
Operation mode
setting
1 octet
21
0x00= unfix,0x 01= heat,0x 02= cool,0x 03= dry 0x
04= fan ,0x05 auto (address=161 LSB ,address=
168MSB)
169-176
Fan speed setting
1 octet
22
0x00=Invalid,0x01=Fan
Sop,0x02=Auto,0x03=High,0x04=Medium,0x05=
Low,0x06=Ultra Low,0x07=unfix (address=169
LSB,address=176MSB)
177-184
Louver setting
1 octet
23
0x00= invalid ,0x 1 =swing, 0x 2= f1,0x 3 =f2,0x 4= f3,
0x 5= f4 ,0x 6 =f5,0x7=stop (address=177
lsb,address=184MSB)
185-192
Remote controller on/
off prohibit setting
1 octet
24
Remote controller on/off prohibit setting
(address=185)
193-200
Relay output for TCB- 1 octet
IFCG1TLE
25
TCB-IFCG1TLE bit output
(See manual of TCB-IFCG1TLE)
201-304
Reserved
26-38
104bit
6 (EN)
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
+00DHxxxxxxxx_01EN_IFMB640TLE_Spec.book Page 7 Friday, June 20, 2008 9:17 AM
Heronhill - for all your Toshiba requirements
Specifications Manual
TCS-NET Modbus Protocol Conversion Interface
Modbusdescription
ModbusIndooraddress for
number
registers
Data name
Length
Octet
Order
n
On/Off setting
1 octet
19*n –18
(152*n -151)(152*n -144)
Explanation
Filter sign reset setting
Reserved
64
(152*n –143)(152*n –136)
Operation mode
setting
1 octet
19*n –17
(152*n –135)(152*n –128)
Fan speed setting
1 octet
19*n –16
(152*n –127)(152*n –120)
Louver setting
1 octet
19*n –15
(152*n –119)(152*n –112)
Remote controller on/
off prohibit setting
1 octet
19*n –14
(152*n –111)(152*n –104)
Relay output for TCB- 1 octet
IFCG1TLE
(152*n –103)152*n
Reserved
104 bits 19*n –
12—19*n
9577-9584
On/Off setting
1 octet
19*n –13 TCB-IFCG1TLE bit output See manual of TCBIFCG1TLE
1198
Filter sign reset setting
1= On,0 =Off1 (address=9577)
1= reset,others=no action (address=9578)
Reserved
9585-9592
Operation mode
setting
1 octet
1199
0x00=unfix,0x 01= heat,0x 02= cool,0x 03= dry 0x
04= fan,0x05 auto (address=9585 LSB,address=
9592MSB)
9593-9600
Fan speed setting
1 octet
1200
0x00=Invalid,0x01=Fan
Sop,0x02=Auto,0x03=High,0x04=Medium,0x05=
Low,0x06=Ultra Low,0x07=unfix (address=9593
LSB,address=9600MSB)
9601-9608
Louver setting
1 octet
1201
0x00= invalid ,0x 1 =swing, 0x 2= f1,0x 3 =f2,0x 4= f3,
0x 5= f4 ,0x 6 =f5,0x7=stop (address=9601
LSB,address=9608MSB)
9609-9616
Remote controller on/
off prohibit setting
1 octet
1202
Remote controller on/off prohibit setting
(address=9609)
Remote controller mode prohibit setting
(address=9610)
Remote controller setpoint prohibit setting
(address=9611)
Remote controller louver prohibit setting
(address=9612)
Remote controller fan speed prohibit setting
(address=9613)
1=prohibit 0=permit
9617-9624
Relay output for TCB- 1 octet
IFCG1TLE
1203
TCB-IFCG1TLE bit output (See manual of TCBIFCG1TLE)
9625-9728
Reserved
104 bits 12041216
7 (EN)
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
+00DHxxxxxxxx_01EN_IFMB640TLE_Spec.book Page 8 Friday, June 20, 2008 9:17 AM
Heronhill - for all your Toshiba requirements
Specifications Manual
TCS-NET Modbus Protocol Conversion Interface
Modbusdescription
Discrete
input (R)
ModbusIndoornumber address for
registers
1
Octet
Length Order
Data name
10001-10004 On/Off setting status
1 octet
1
Explanation
1= On,0 =Off
(address=10001)
Filter sign status
1= abnormal, 0 =normal) (address =10002)
Alarm Status
1= abnormal, 0 =normal) ( address =10003)
Reserved
10005-10008 Reserved
10009-10016 Operation mode status 1 octet
2
0x00= invalid,0x 01= heat,0x 02= cool,0x 03= dry 0x
04= fan,0x05 auto heat ,0x06=auto cool,0x07=unfix
(address=9 LSB,address 16=MSB)
10017-10024 Fan speed set status
1 octet
3
0x00=Invalid,0x01=Fan
Sop,0x02=Auto,0x03=High,0x04=Medium,0x05=
Low,0x06=Ultra Low,0x07=unfix (address=10017
LSB,address=10024MSB)
10025-10032 Louver setting status
1 octet
4
0x00= invalid ,0x 1 =swing, 0x 2= f1,0x 3 =f2,0x 4= f3,
0x 5= f4 ,0x 6 =f5,0x7=stop (address=10025
LSB,address=10032MSB)
10033-10040 Remote controller on/
off prohibit setting
status
1 octet
5
Remote controller on/off prohibit setting
(address=10033)
Remote controller mode prohibit setting
(address=10034)
Remote controller setpoint prohibit setting
(address=10035)
Remote controller louver prohibit setting
(address=10036)
Remote controller fan speed prohibit setting
(address=10037)
1=prohibit 0=permit
10041-10048 Reserved
1 octet
6
10049-10056 Reserved
1 octet
7
10057-10064 On/Off input for TCBIFCG1TLE
1 octet
8
88 bits
9-19
TCB-IFCG1TLE bit input See manual of TCBIFCG1TLE
Alarm input for TCBIFCG1TLE
Din2 input for TCBIFCG1TLE
Din3 input for TCBIFCG1TLE
Local Prohi. input for
TCB-IFCG1TLE
Din1 input for TCBIFCG1TLE
Reserved
10065-10152 Reserved
8 (EN)
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
+00DHxxxxxxxx_01EN_IFMB640TLE_Spec.book Page 9 Friday, June 20, 2008 9:17 AM
Heronhill - for all your Toshiba requirements
Specifications Manual
TCS-NET Modbus Protocol Conversion Interface
Modbusdescription
ModbusIndoor- address for
number
registers
2
Length Octet
Order
Data name
10153-10156 On/Off setting status
1 octet
20
Explanation
1= On,0 =Off
(address=10153)
Filter sign status
1= abnormal, 0 =normal) (address =10154)
Alarm Status
1= abnormal, 0 =normal) ( address =10155)
Reserved
10157-10160 Reserved
n
10161-10168 Operation mode status 1 octet
21
0x00= invalid,0x 01= heat,0x 02= cool,0x 03= dry 0x
04= fan,0x05 auto heat ,0x06=auto cool,0x07=unfix
(address=10161 LSB ,address=10168MSB)
10169-10176 Fan speed set status
1 octet
22
0x00=Invalid,0x01=Fan
Sop,0x02=Auto,0x03=High,0x04=Medium,0x05=
Low,0x06=Ultra Low,0x07=unfix (address=10169
LSB,address=10176MSB)
10177-10184 Louver setting status
1 octet
23
0x00= invalid ,0x 1 =swing, 0x 2= f1,0x 3 =f2,0x 4= f3,
0x 5= f4 ,0x 6 =f5,0x7=stop
(address=10177LSB,address=10184MSB)
10185-10192 Remote controller on/
off prohibit setting
status
1 octet
24
Remote controller on/off prohibit setting
(address=10185)
Remote controller mode prohibit setting
(address=10186)
Remote controller setpoint prohibit setting
(address=10187)
Remote controller louver prohibit setting
(address=10188)
Remote controller fan speed prohibit setting
(address=10189)
1=prohibit 0=permit
10193-10200 Reserved
1 octet
25
10201-10208 Reserved
1 octet
26
10209-10216 On/Off input for TCBIFCG1TLE
1 octet
27
10217-10304 Reserved
88 bits
28-38
152*n+9849 On/Off setting status/
-152*n+9856 etc
1 octet
19*n –18
152*n+9857 Operation mode status 1 octet
-152*n+9864
19*n –17
152*n+9865 Fan speed set status
-152*n+9872
1 octet
19*n –16
152*n+9873 Louver setting status
-152*n+9880
1 octet
19*n –15
152*n+9881 Remote controller on/
-152*n+9888 off prohibit setting
status
1 octet
19*n –14
152*n+9889 Reserved
-152*n+9896
1 octet
19*n –13
152*n+9897 Reserved
-152*n+9904
1 octet
19*n –12
152*n+9905 On/Off input for TCB-152*n+9912 IFCG1TLE/ETC
1 octet
19*n –11 TCB-IFCG1TLE bit input See manual of TCBIFCG1TLE
152*n+9913 Reserved
152*n+10000
88 bits
19*n –
10-19*n
TCB-IFCG1TLE bit input See manual of TCBIFCG1TLE
9 (EN)
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
+00DHxxxxxxxx_01EN_IFMB640TLE_Spec.book Page 10 Friday, June 20, 2008 9:17 AM
Heronhill - for all your Toshiba requirements
Specifications Manual
TCS-NET Modbus Protocol Conversion Interface
Modbusdescription
ModbusIndoornumber address for
registers
64
Octet
Length Order
Data name
19577-19580 On/Off setting status
1 octet
1198
Explanation
1= On,0 =Off
(address=19577)
Filter sign status
1= abnormal, 0 =normal) (address =19578)
Alarm Status
1= abnormal, 0 =normal) ( address =19579)
Reserved
19581-19584 Reserved
19585-19592 Operation mode status 1 octet
1199
0x00= invalid,0x 01= heat,0x 02= cool,0x 03= dry 0x
04= fan,0x05 auto heat ,0x06=auto cool,0x07=unfix
(address=19585 LSB ,address=19592MSB)
19593-19600 Fan speed set status
1 octet
1200
0x00=Invalid,0x01=Fan
Sop,0x02=Auto,0x03=High,0x04=Medium,0x05=
Low,0x06=Ultra Low,0x07=unfix (address=19593
LSB,address=19600MSB)
19601-19608 Louver setting status
1 octet
1201
0x00= invalid ,0x 1 =swing, 0x 2= f1,0x 3 =f2,0x 4= f3,
0x 5= f4 ,0x 6 =f5,0x7=stop
(address=19601LSB,address=19608MSB)
19609-19616 Remote controller on/
off prohibit setting
status
1 octet
1202
Remote controller on/off prohibit setting
(address=19609)
Remote controller mode prohibit setting
(address=19610)
Remote controller setpoint prohibit setting
(address=19611)
Remote controller louver prohibit setting
(address=19612)
Remote controller fan speed prohibit setting
(address=19613)
1=prohibit 0=permit
19617-19624 Reserved
1 octet
1203
19625-19632 S-code Status
1 octet
1204
19633-19640 On/Off input for TCBIFCG1TLE/ETC
1 octet
1205
19641-19728 Reserved
88 bits
12061216
TCB-IFCG1TLE bit input (See manual of TCBIFCG1TLE)
10 (EN)
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
+00DHxxxxxxxx_01EN_IFMB640TLE_Spec.book Page 11 Friday, June 20, 2008 9:17 AM
Heronhill - for all your Toshiba requirements
Specifications Manual
TCS-NET Modbus Protocol Conversion Interface
Modbusdescription
Indoor- Modbusnumber address for
registers
Input register 1
(R)
n
Data name
Length
Explanation
30001
Room temperature
2 octets
unit:°C SEEEEMMM MMMMMMMM
Temperature = (-1)S × (0.01 × M) × 2(E)
s: sign (s = 1: -, s = 0: +), M: -2048 to +2047
Range:-671088.64-----670760.96 unit: °C
30002
Setting temperature 2 octets
status
Same as Room temperature
30003-30006
Alarm code
8 octets
30003 upper header indoor unit: 00 when no alarm occurs
30003 lower follower indoor unit 1: 00 when no alarm occurs
……………………………
30006 upper follower indoor unit 6: 00 when no alarm occurs
30006 lower follower indoor unit 7: 00 when no alarm occurs
30007-30014
Model name
16 octets
16 characters in 16 ASCII codes
30015-30022
Peculiar number
16 octets
16 characters in 16 ASCII codes
30023
Ability
2 octets
Unit ability Octet expression
30024
Indoor Type
2 octets
Octet expression 0x00**
30025-30030
Analog input for
TCB-IFCG1TLE
2 octets*6CH
6-channel analog input for TCB-IFCG1TLE (See manual of
TCB-IFCG1TLE) address=30025 CH1, address=30026 CH2
etc. see Note
30031
OperationMode/
Fan
2 octets
RS FM Operation mode and air volume can be set
30032
Cool temp range
2 octets
CT CB Temperature setting upper and lower limits in cool
mode
30033
Heat temp range
2 octets
HT HB Temperature setting upper and lower limits in heat
mode
30034
Dry temp range
2 octets
DT DB Temperature setting upper and lower limits in dry
mode
30035
Auto temp range
2 octets
FT FB Temperature setting upper and lower limits in auto
mode
30036-30156
Reserved
126*2 octets
29845+156*n
Room temperature
2 octets
29846+156*n
Setting temperature 2 octets
status
29847+156*n Alarm code
-29850+156*n
8 octets
29851+156*n Model name
-29858+156*n
16 octets
29859+156*n Peculiar number
-29864+156*n
16 octets
29865+156*n
Ability
2 octets
29868+156*n
Indoor Type
2 octets
29869+156*n- Analog input for
29874+156*n TCB-IFCG1TLE
2 octets*6CH
6-channel analog input for TCB-IFCG1TLE (See manual of
TCB-IFCG1TLE)
29875+156*n
OperationMode/
Fan
2 octets
RS FM Operation mode and air volume can be set
29876+156*n
Cool temp range
2 octets
CT CB Temperature setting upper and lower limits in cool
mode
29877+156*n
Heat temp range
2 octets
HT HB Temperature setting upper and lower limits in heat
mode
29878+156*n
Dry temp range
2 octets
DT DB Temperature setting upper and lower limits in dry
mode
29879+156*n
Auto temp range
2 octets
FT FB Temperature setting upper and lower limits in auto
mode
29880+156*n- Reserved
30000+156*n
126*2 octets
11 (EN)
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
+00DHxxxxxxxx_01EN_IFMB640TLE_Spec.book Page 12 Friday, June 20, 2008 9:17 AM
Heronhill - for all your Toshiba requirements
Specifications Manual
TCS-NET Modbus Protocol Conversion Interface
Modbusdescription
Holding
register
(R/W)
Indoor- Modbusnumber address for
registers
Data name
Length
Explanation
64
39829
Room temperature
2 octets
See Modbus address 30001-30024
39830
Setting temperature 2 octets
status
See Modbus address 30001-30024
39831-39834
Alarm code
8 octets
See Modbus address 30001-30024
39835-39842
Model name
16 octets
See Modbus address 30001-30024
39843-39850
Peculiar number
16 octets
See Modbus address 30001-30024
39851
Ability
2 octets
See Modbus address 30001-30024
39852
Indoor Type
2 octets
See Modbus address 30001-30024
39853-39858
Analog input for
TCB-IFCG1TLE
2 octets*6CH
6-channel analog input for TCB-IFCG1TLE See manual of
TCB-IFCG1TLE
39859
OperationMode/
Fan
2 octets
RS FM Operation mode and air volume can be set
39860
Cool temp range
2 octets
CT CB Temperature setting upper and lower limits in cool
mode
39861
Heat temp range
2 octets
HT HB Temperature setting upper and lower limits in heat
mode
39862
Dry temp range
2 octets
DT DB Temperature setting upper and lower limits in dry
mode
39863
Auto temp range
2 octets
FT FB Temperature setting upper and lower limits in auto
mode
39864-39984
Reserved
126*2 octets
39985-39992
Software version
16 octets
TCB-IFCG1TLE is expressed in ASCII codes followed by the
version number.
40001
Temperature
setting value
2 octets
Same as Room temperature
Valid range: 0 to 92, unit: 1, fractions rounded off
40002
Accumulated
operation time
2 octets
Octet expression unit: hour
ex) 255hours=0xFF
Unit: hour. Monitor on/off of the discrete input register to
check the on/off state of all air conditioners every 15 minutes.
When the register state is on, add 15 minutes. The register
data is retained even during power-off.
40003-40006
Analog output for
TCB-IFCG1TLE
2 octets*4CH
4-channel analog output for TCB-IFCG1TLE (See manual of
TCB-IFCG1TLE) see Note 2
1
2
n
64
40007-40156
Reserved
150*2 octets
See Modbus address 40001-40156
40157
Temperature
setting value
2 octets
See Modbus address 40001-40156
40158
Accumulated
operation time
2 octets
See Modbus address 40001-40156
40159-40162
Analog output for
TCB-IFCG1TLE
2 octets*4CH
See Modbus address 40001-40156
40163-40312
Reserved
150*2 octets
See Modbus address 40001-40156
39845+156*n
Temperature
setting value
2 octets
See Modbus address 40001-40156
39846+156*n
Accumulated
operation time
2 octets
See Modbus address 40001-40156
39847+156*n- Analog output for
39850+156*n TCB-IFCG1TLE
2 octets*4CH
See Modbus address 40001-40156
39851+156*n- Reserved
40000+156*n
150*2 octets
See Modbus address 40001-40156
49829
Temperature
setting value
2 octets
See Modbus address 40001-40156
49830
Accumulated
operation time
2 octets
See Modbus address 40001-40156
49831-49834
Analog output for
TCB-IFCG1TLE
2 octets*4CH
See Modbus address 40001-40156
49835-49984
Reserved
150*2 octets
See Modbus address 40001-40156
12 (EN)
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
+00DHxxxxxxxx_01EN_IFMB640TLE_Spec.book Page 13 Friday, June 20, 2008 9:17 AM
Heronhill - for all your Toshiba requirements
Specifications Manual
TCS-NET Modbus Protocol Conversion Interface
Note 1
• Analog In (2 channels, thermistor) reading
Received TCC-LINK value is retained in this register with two bytes.
The received 2-byte data is a two’s complement and is converted to as an absolute measurement temperature
by dividing it by 100.
• Example) Received value 0xFE90 -> x0169 (converted to two’s complement) -> 361 -> converted to 3.61 (K)
(divided by 100) The Celsius temperature is obtained by subtracting 273.15 from 3.61.
• Analog In (4CH 0-10VDC)
Received TCC-LINK value is retained in this register with two bytes. The true value is a two’s complement, and
the value obtained by dividing the true value by 1000 becomes the board input value.
Example) Received value 0xD8F1 -> converted to 0x270F (two’s complement) -> 9999 -> converted to 9.999V
(divided by 1000)
Note 2
• TCB-IFCG1TLE Analog Out 4-channel writing
The master device writes a 2-byte two’s complement that is 1000 times of the transmit value.
The TCB-IFCG1TLE board value is obtained by dividing a two’s complement of 2-byte received value by 3000.
A level in accordance with the value is output from the MPU treating 3.333 as 256 levels. The MPU output value
is multiplied by 3 in the external circuit, and the TCB-IFCG1TLE board output value equals the transmit value.
Example 1) A value 9.999V calculated by the master device is sent -> -> 9999 (1000 times) -> 0x270F---> 0x D8F1
(two’s complement) This value is written.
Calculation at the receiver (TCB-IFCG1TLE board) 0xD8F1- -> 0x270F (two’s complement) -> 9999 ->
3.333V (divided by 3000)- -> 256 levels = 0xFF (3.333V) is DA output. A value 3.333*3 = 9.999V is output
from “Analog Out” on the TCB-IFCG1TLE board.
Example 2) A value 3.000V calculated by the master device is sent -> 3000 (1000 times) -> 0x0BB8-- -> 0xF448
(two’s complement) This value is written to the register.
Calculation at the receiver (TCB-IFCG1TLE board) 0xF448 -> 0x0BB8 (two’s complement) -> 3000 -> 1V
(divided by 3000) - -> 77 levels = 0x4D (1.00V) is DA output. A value 1.00*3 = 3.00V is output from “Analog
Out” on the TCB-IFCG1TLE board.
Note 3
• Unused bits can be read and written. No data can be written to reserved areas. If a reserved area is read, 00 is
always returned.
Note 4
• The meaning of RS/FM (operation mode, fan speed), CT/CB (temperature setting upper and lower limits in cool
mode), HT/HB (temperature setting upper and lower limits in heat mode), DT/DB (temperature setting upper and
lower limits in dry mode), and FT/FB (temperature setting upper and lower limits in auto mode) in the Input
register (R) is shown below. The master device must read the following values from each air conditioner in
advance, and must set values within this range when specifying operation data.
Bits of RS
Meaning
b7, b6
00 All operation modes enabled
01 Cooling/drying disabled
10 Heating disabled
11 Fan only enabled
b5
1: Auto mode enabled, 0: Auto mode disabled
b4
1: Ventilation enabled, 0: Ventilation disabled
b3
1: Heating mode enabled, 0: Heating mode disabled
b2
1: Drying mode enabled, 0: Drying mode disabled
b1
1: Cooling mode enabled, 0: Cooling mode disabled
LSB
1: Fan mode enabled, 0: Fan mode disabled
13 (EN)
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
+00DHxxxxxxxx_01EN_IFMB640TLE_Spec.book Page 14 Friday, June 20, 2008 9:17 AM
Heronhill - for all your Toshiba requirements
TCS-NET Modbus Protocol Conversion Interface
Bits of FM
Meaning (fan speed)
b3
1: High fan speed enabled, 0: Rapid fan speed disabled
b2
1: Medium fan speed enabled, 0: High fan speed disabled
b1
1: Low fan speed enabled, 0: Low fan speed disabled
b0
1: Ultra-low fan speed enabled, 0: Weak fan speed disabled
Upper-limit / lower-limit
temperature
Meaning
CT
CB
Temperature setting upper-limit value in cool mode
Temperature setting lower-limit value in cool mode
HT
HB
Temperature setting upper-limit value in heat mode
Temperature setting lower-limit value in heat mode
DT
DB
Temperature setting upper-limit value in dry mode
Temperature setting lower-limit value in dry mode
FT
FB
Temperature setting upper-limit value in auto mode
Temperature setting lower-limit value in auto mode
Specifications Manual
The upper-limit and lower-limit values in the table above are converted to Celsius temperatures using the following
formula.
Celsius temperature (°C) = -35 + (decimal read value / 2)
14 (EN)
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
+00DHxxxxxxxx_01EN_IFMB640TLE_Spec.book Page 15 Friday, June 20, 2008 9:17 AM
Heronhill - for all your Toshiba requirements
Specifications Manual
TCS-NET Modbus Protocol Conversion Interface
8
Appendix
Alarm Codes
Code
Description
Note
0x25, 0x26
TCC-LINK central control device transmit error
Ox41
Indoor-remote controller communication error
0x42
Remote controller transmit error
0x43
Indoor-remote controller communication error
Detected by indoor unit
0x44
Indoor-outdoor communication error
Detected by indoor unit
0x46
Decrease in the number of indoor units
0x47
Indoor-outdoor communication circuit error
0x48
Indoor address duplication
0x49
Master remote controller duplication
0x4a
Communication error in indoor PCB
0x4c
Automatic address start error
Detected by remote controller
Detected by outdoor unit
0x4f
No indoor unit during automatic addressing
0x50
Too many indoor units connected or over capacity
0x52
Header-follower indoor units communication error
0x53
Error in the number of header outdoor units
0x54
Connection to other system refrigerant line during automatic addressing
0x57
Outdoor-outdoor communication error
0x59
Follower outdoor setup address duplication
0x5a
Decrease in the number of outdoor units
0x5c
Follower outdoor error
0x5f
IPDU communication error
0x61
Indoor coil TC1 sensor error
0x62
Indoor coil TC2 sensor error
0x63
Indoor coil TC1 sensor error
0x64
TD1 sensor error
0x65
TD2 sensor error
0x66
TE1 sensor error
0x67
TL sensor error
0x68
TO sensor error
0x6a
Indoor suction temperature TA sensor error
0x6c
TS1 sensor error
0x6d
TH sensor error
0x6F
Outdoor temperature sensor incorrect wiring (TE, TL)
0x70
Outdoor pressure sensor incorrect wiring (Pd, Ps)
0x77
Ps sensor error
0x78
Pd sensor error
0x7d
Other indoor errors
0x7f
Outdoor EEPROM error
0x81
Compressor breakdown
0x82
Compressor error (lock)
0x83
Current detector circuit error
0x84
Compressor 1 case thermostat operation
0x86
Low-pressure protective operation
0x87
Low oil level detection protection
0x88
Oil level detection temperature sensor error
0x8e
Compressor 2 case thermostat operation
15 (EN)
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
+00DHxxxxxxxx_01EN_IFMB640TLE_Spec.book Page 16 Friday, June 20, 2008 9:17 AM
Heronhill - for all your Toshiba requirements
Specifications Manual
TCS-NET Modbus Protocol Conversion Interface
Code
Description
0x90
Oil level detection circuit error
0xc3
Indoor header address duplication
0xc4
Outdoor line address duplication
0xc5
Priority indoor unit duplication (displayed on unit with priority)
0xc6
Priority indoor unit duplication (displayed on unit with priority)
0xc7
Group wire on individual indoor
0xc8
No address setting of indoor group
0xc9
No setting of indoor capacity
0xca
No setting of outdoor capacity
0xd4
Central control address duplication
0xdc
Too many outdoor units connected
Note
0xdd
IPDU error
0xde
External interlock error in indoor unit
0xdf
IC error
0xe1
Indoor fan moter error
0xe3
Discharge temperature TD1 error
0xe4
High-pressure switch operation error
0xe5
Missing phase detected, phase sequence error
0xe7
Heatsink TH overhead error
0xea
Indoor water overflow error
0xec
Indoor DC fan motor error
0xed
Outdoor liquid back detection error
0xef
Gas leak detected
0xf1
Discharge temperature TD2 error
0xf3
4-way valve error
0xf4
High-pressure protective operation
0xf6
Outdoor fan IPDU error
0xfa
G-TR short-circuit protection error
0xfd
Compressor position detector circuit error
0xff
Other indoor unit errors
0x100
Intelligent Server communication error
0x103
Group follower indoor unit error
0x104
BMS-IFWH communication error
0x105
BMS-IOKIT communication error
0x106
BMS-IFWH communication error
0x107
BMS-IFDD communication error
0x108
Communication error
0x109
Communication error
16 (EN)
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
+00DHxxxxxxxx_01EN_IFMB640TLE_Spec.book Page 17 Friday, June 20, 2008 9:17 AM
Heronhill - for all your Toshiba requirements
Specifications Manual
TCS-NET Modbus Protocol Conversion Interface
Converted Capacity Values
Hexadecimal converted capacity values corresponding to TCC-LINK return values are used as response data.
Example) A value acquired as 0x03 (decimal 3) is converted to 28 as capacity.
Return value (decimal) Converted capacity value
(decimal)
Return value (decimal) Converted capacity value
(decimal)
0
Invalid
21
224
1
22
22
250
2
25
23
280
3
28
24
340
4
32
25
355
5
36
26
450
6
40
27
500
7
45
28
560
8
50
29
600
9
56
30
630
10
63
31
670
11
71
32
710
12
80
33
800
13
90
34
840
14
100
15
112
16
125
17
140
18
160
19
180
20
200
17 (EN)
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
+00DHxxxxxxxx_01EN_IFMB640TLE_Spec.book Page 18 Friday, June 20, 2008 9:17 AM
Heronhill - for all your Toshiba requirements
DE88909601
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising