LE offers four different models of SeaHawk Spot Detectors (“SD
Series”) that can integrate with various RLE controllers or other
equipment and alarm monitoring systems. Spot detectors are
ideal for small spaces, and are the most economical way to detect fluids
in confined areas, such as condensation drip pans.
Product
Integration Capability
Leader Cable Length
Power
SD
Falcon FMS & RA1x2
14 feet (4.27m)
N/A
(powered by panel)
SD-Z
Any SeaHawk zone or
distance-read controller
Two, 10 inch (0.25m) w/
male & female connectors
N/A
(powered by panel)
SD-Z1
F200, LD310, LD1000 &
LDRA6 controllers
14 feet (4.27m)
N/A
(powered by panel)
SD-RO1
Any product that accepts a
digital dry contact input
14 feet (4.27m)
Isolated 24VAC/VDC
Supply
Features
•
•
•
•
No exposed metal sensing posts
Potted electronics
Adjustable probes
Can be screwed or ram set to floor or
baseboard
• Small footprint/enclosure
Benefits
• Nothing to rust or corrode
• Ensures functionality when submerged in
water
• Easily adjusted to desired height
• Simple installation
• Ideal for tight areas
The SD-Z and SD-Z1 each simulate 50 ft. (15.24m) of SeaHawk leak
detection cable. The SD-Z1 is for use with zone controllers only, and only
one of these spot detectors should be used per zone.
Spot detector example: use the SD-Z and SD-Z1 in conjunction with
an RLE SeaHawk leak detection controller.
Leak Detection
www.rletech.com
Spot Detectors Specifications
Power
SD-Z, SD-Z1
SD-RO1 requires an isolated power supply, as does the SD if it is powered by a power supply and not the FMS or RA1x2.
N/A (powered by controller)
SD
The SD is usually powered by the RLE FMS or RA1x2. In the event that it is not used in conjunction with one of these products:
24VDC (±10%) Isolated @ 0.1A max.; requires RLE power supply PSWA-DC-24-ST (not included)
NOTE: If a DC power supply is used the SD will be a latching device - once an alarm is detected, the spot detector will
remain in an alarm state until power is cycled to the SD.
24VAC (±10%) Isolated @ 0.1A max.; requires RLE power supply WA-AC-24-ST (not included)
SD-RO1
24VDC (±10%) Isolated @ 0.1A max.; requires RLE power supply PSWA-DC-24-ST (not included)
NOTE: If a DC power supply is used the SD-RO1 will be a latching device - once an alarm is detected, the spot detector
will remain in an alarm state until power is cycled to the SD-RO1.
24VAC (±10%) Isolated @ 0.1A max.; requires RLE power supply WA-AC-24-ST (not included)
Outputs
Solid State Output
Only available on SD
Relay Output
Only available on SD-RO1
12-36VAC @ 0.01A min., 0.1A max.; 18-36VDC @ 0.01A min., 0.1A max.
Dry Contact, Form C; 1A @ 24VDC, 0.5A resistive @ 120VAC
Leader Cable (Non-sensing)
Length
SD, SD-RO1, SD-Z1
SD-Z
Connector
SD, SD-RO1, SD-Z1
SD-Z
14 feet (4.27m)
10 inches (0.25m); male & female connector
N/A - spot detector leader cable wires directly into controller
1 male, 1 female; 4 pin, 0.96in (24.4mm) diameter; connects to SeaHawk sensing cable (SC) cable or non-sensing cable (NSC)
Operating Environment
Temperature
Humidity
Altitude
32° to 122°F (0° to 50°C)
5% to 95% RH, non-condensing
15,000ft (4,572m) max.
Storage Environment
-4° to 158°F (-20° to 70°C)
Dimensions
1.55"W x 2.0"H x 1.0"D (39.4mmW x 50.8mmH x 25.4mmD)
Sensor Probe Height
Distance from the sensor probe to floor is adjustable, from 0” to 0.19” (0mm - 4.8mm)
Spacers can be added under the spot detector if additional height is required.
Weight
SD
SD-Z
SD-Z1
SD-RO1
Certifications
4 oz. (105g)
3 oz. (93g)
5 oz. (136g)
7 oz. (192g)
CE; ETL listed: conforms to UL 61010-1, EN 61010-1; RoHS compliant
© Raymond & Lae Engineering, Inc. 2011. All rights reserved. RLE® is a registered trademark and Seahawk™, Falcon™, and Raptor™ are
trademarks of Raymond & Lae Engineering, Inc. The products sold by Raymond & Lae Engineering, Inc. are subject to the limited warranty,
limited liability, and other terms and conditions of sale set forth at http://rletech.com/RLE-Terms-and-Conditions.html.
v1.4
(08/2015)
104 Racquette Drive
Fort Collins, CO 80524
800.518.1519
rletech.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising