DRP-480S
D R P - 4 8 0 S series
480W Single Output DIN RAIL with PFC Function
Features :
AC input range selectable by switch
Built-in passive PFC function compliance to EN61000-3-2
High efficiency 89% and low dissipation
Protections:Short circuit/Over load/Over voltage/Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
3 years warranty
R
SPECIFICATION
MODEL
OUTPUT
DRP-480S-24
DRP-480S-48
DC VOLTAGE
24V
48V
RATED CURRENT
20A
10A
CURRENT RANGE
0 ~ 20A
0 ~ 10A
RATED POWER
480W
480W
RIPPLE & NOISE (max.) Note.2 120mVp-p
120mVp-p
VOLTAGE ADJ. RANGE
48 ~ 55V
1.0%
24 ~ 28V
VOLTAGE TOLERANCE Note.3 1.0%
LINE REGULATION
0.5%
0.5%
LOAD REGULATION
1.0%
1.0%
SETUP, RISE, HOLD TIME
1200ms, 40ms, 20ms/230VAC,115VAC at full load
VOLTAGE RANGE
90 ~ 132VAC/180 ~ 264VAC by switch
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR
INPUT
0.7/230VAC only
EFFICIENCY (Typ.)
89%
AC CURRENT
INRUSH CURRENT (max.)
11A/115VAC
4A/230VAC
COLD START 30A/115VAC
LEAKAGE CURRENT
<3.5mA / 240VAC
OVER LOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
254 ~ 370VDC
50A/230VAC
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
59 ~66V
30 ~ 36V
Protection type : Shut down o/p voltage, re-power on to recover
100
5 (TSW : Detect on heatsink of power switch)
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-20 ~ +70 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-40 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL508, TUV EN60950 Approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
SAFETY & ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B
EMC
(Note 4)
HARMONIC CURRENT
EMS IMMUNITY
MTBF
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61204-3, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A
187.9Khrs min. MIL-HDBK-217F (25 )
OTHERS
DIMENSION
PACKING
227*125.2*100mm (W*H*D)
2.6Kg; 6pcs / 16.6Kg / 1.75CUFT
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
File Name:DRP-480S-SPEC 2004-06-02
D R P - 4 8 0 S series
480W Single Output DIN RAIL with PFC Function
Mechanical Specification
Case No.930
100
Unit:mm
56.6
227
10 6
125.2
12
230VAC
115VAC
TB1
3 2 1
LED
TB2
4 3 2 1
+V ADJ.
35
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
TB1 Terminal Pin. No Assignment
Pin No.
1
2
3
TB2 Terminal Pin. No Assignment
Pin No.
1,2
3,4
Assignment
AC/L
AC/N
FG
Derating Curve
Output Derating VS Input Voltage
100
100
180 ~ 264VAC
90 ~ 132VAC
90
80
80
70
LOAD (%)
LOAD (%)
60
40
20
-20
Assignment
DC OUTPUT +V
DC OUTPUT -V
0
10
20
30
40
AMBIENT TEMPERATURE (
50
)
60
70 (VERTICAL)
60
50
40
90
180
100
190
115
230
132
264
INPUT VOLTAGE (V) 60Hz
File Name:DRP-480S-SPEC 2004-06-02
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising