Well-Guard Control Pumping Plant Panels Catalog
Well-Guard Control™
Pumping Plant Panels
Catalog
8940CT9701R7/08
2008
Class 8940
IRRIGATION
OIL PRODUCTION
CONTENTS
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page
Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3
Factory Modifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 12
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
2
09/2008
© 1997-2008 Schneider Electric
All Rights Reserved
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
Well-Guard Control™ Pump Panels, Full Voltage–Class 8940
Irrigation Style Selection Guide
Class 8940 Type NP IEC Style Pump Panels, in NEMA Type 3R enclosures, are specifically designed
for irrigation applications. All panels are supplied with a visible-blade fused disconnect switch (unless
noted). Extra panel space is provided for field installation of auxiliary equipment (refer to page 12 for
approximate dimensions).
•
•
•
•
•
•
•
•
Approved for submersible pump applications
Class 10 bimetallic overload relay through 100 hp-480 V, 50 hp–240 V
Adjustable trip current
Includes a Start push button and a Hand-Off-Auto selector switch
Ambient temperture compensated
TeSys™ D and TeSys™ F contactors are used as standard
Sizes closely matched to common motor sizes
All devices are UL Listed and marked “SUITABLE ONLY FOR USE AS SERVICE EQUIPMENT”
Fusible Disconnect Switch Type
600 Volts Max. – 3-Pole – 50-60 Hertz
Volts
Max. hp Polyphase
Fuse Clip Amperes q
Class 8990 Type c
30
NPD2003V03
5
30
NPE2005V03
7.5
30
NPE2007V03
10
60
NPF2010V03
15
240
Listed File
E152395
Coil Voltage k
3
20
240-60
220-50
60
NPF2015V03
100
NPG2020V03
25
100
NPG2025V03
30
100
NPJ2030V03
40
200
NPJ2040V03
50
200
NPJ2050V03
30
NPD4003V06
Above 50 hp, see page 4
Listed File
E152395
3
Coil Voltage Codes
Voltage
60 Hz
50 Hz
Code
480
24 jp . . .
V01
120 j
110
V02
208 j
...
V08
240
220
V03
...
380
V05
480
440
V06
600 j
550
V07
For hp higher than 100, see
page 4.
p Must be specially
wound for NPJ devices.
j Form S (separate
control) required for
24 V, 120 V, 208 V, and
600 V coils.
480-60
440-50
5
30
NPD4005V06
7.5
30
NPD4007V06
10
30
NPE4010V06
15
30
NPE4015V06
20
60
NPF4020V06
25
60
NPF4025V06
30
60
NPF4030V06
40
100
NPG4040V06
50
100
NPG4050V06
60
100
NPJ4060V06
75
200
NPJ4075V06
100
200
NPJ4100V06
Above 100 hp, see page 4.
k Coil voltage code must be specified to order this product. Refer to standard voltage codes listed at left.
q Fuse clips are sized for use with dual-element time-delay fuses.
3
© 1997-2008 Schneider Electric
All Rights Reserved
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
09/2008
www.barr-thorp.com
Well-Guard Control™ Pump Panels, Full Voltage–Class 8940
Irrigation and Oil Field Style Selection Guide
Class 8940 Type NS, SS and XS Pump Panels, in NEMA Type 3R enclosures, are specifically
designed for irrigation and oil field applications. All panels are supplied with a visible-blade fused
disconnect switch (unless noted). Extra panel space is provided for field installation of auxiliary
equipment (refer to page 12 for approximate dimensions).
•
•
•
•
•
•
•
Type S contactor provided as standard
Approved for submersible pump applications
Class 10 Motor Logic® SSOLR through 200 hp-480 V, 100 hp-240V —Type SS*
Includes a Start push button and a Hand-Off-Auto selector switch
Adjustable trip current
Ambient temperature compensated
All devices are UL Listed and marked “SUITABLE ONLY FOR USE AS SERVICE EQUIPMENT”
NOTE: The Class 10 Motor Logic SSOLR (solid-state overload relay) does not protect for phase imbalance;
however, it does include a rubber boot dust cover.
3-Pole Polyphase – 600Vac Maximum (50-60 Hz) – Fusible Disconnect Switch Type
Volts
240
Max. hp Polyphase
Coil Voltage j
SSC2007 f
10, 15
60
SSD2015 f
20, 25, 30
100
SSE2030 f
40, 50
200
SSF2050 f
LAL36250 t
XSG2075V03 c
75
100
240-60
220-50
400
SSG2100
100
LAL36350 t
XSG2100V03 c
200
MAL36700 t
XSH2200V03 c
250
MAL36800 t
XSJ2250V03 c
300
MAL361000 t
XSJ2300V03 c
3, 5, 7.5, 10
30
SSC4010 f
15, 20, 25
60
SSD4025 f
60
SSD4030 f
40, 50
100
SSE4050 f
60, 75, 100
200
SSF4100 f
LAL36250 t
XSG4150V06 c
150
200
480-60
440-50
400
SSG4200
LAL36350 t
XSG4200V06 c
300
MAL36500 t
XSH4300V06 c
350
MAL36600 t
XSH4350V06 c
400
MAL36700 t
XSH4400V06 c
500
MAL36800 t
XSJ4500V06 c
600
MAL361000 t
XSJ4600V06 c
200
t
q
f
c
Class 8940 Type c
30
30
480
Fuse Clip Amperes q
3, 5, 7.5
MAG-GARD circuit breaker disconnect supplied.
Fuse clips are sized for use with dual-element time-delay fuses.
Voltage code not required for 240 V or 480 V with 8940SS___ controllers.
Type SSC, SSD, SSE, SSF, SSG, and XSJ panels include the Motor Logic SSOLR and do not require thermal units. Types
XSG and XSH panels include a three-unit overload relay. Thermal units must be ordered separately. See Pages 8-9 for
selection information.
NOTE: To substitute an ambient compensated bimetallic overload relay (up to size 4) for the Motor Logic SSOLR,
request Form B12 and state motor hp (no charge).
3-Pole Polyphase – 600 Volts AC Maximum (50-60 Hz) – Circuit Breaker
Volts
Listed File
E152395
Listed File
E152395
Max. hp Polyphase
25
30
240
40
50
40
50
60
480
75
100
j See Page 3 for coil voltage codes.
Coil Voltage j
240-60
220-50
Circuit Breaker
Class 8940 Type
XSE2025V03
XSE2030V03
XSE2040V03
XSE2050V03
XSE4040V06
XSE4050V06
XSE4060V06
XSE4075V06
XSE4100V06
FAL36100-18M
KAL36250-26M
KAL36250-29M
FAL36100-18M
480-60
440-50
KAL36250-25M
KAL36250-29M
4
09/2008
© 1997-2008 Schneider Electric
All Rights Reserved
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
Well-Guard Control™ Pump Panels, Full Voltage–Class 8940
Oil Field Style Selection Guide
Class 8940 Type S2 Pump Panels, in NEMA Type 3R enclosures, are specifically designed for Oil
Field applications. All panels are supplied with a visible-blade fused disconnect switch or a Mag-Gard®
circuit breaker, depending on the Type number. Extra panel space is provided for field installation of
auxiliary equipment (refer to page 12 for approximate dimensions).
•
•
•
•
•
•
•
Rugged spring latches for easy access without a tool
Side mounted control units for convenient operation
Door retainer available for windy areas (Form G45)
Hand-Off-Auto selector switch
UL Listed for use as Service Equipment for Motors
Extra panel space for additional electrical controls
All devices UL Listed and marked “SUITABLE ONLY FOR USE AS SERVICE EQUIPMENT”
NOTE: Overload relays are ambient temperature compensated.
600 Volts Max. – 3-Pole – 50-60 Hertz
Volts
240
Coil
Voltage t
240 @
60 Hz
220 @
50 Hz
Max. hp
Polyphase
NEMA
Size
7.5
1
10
15
30
40
50
7.5
10
480
480 @
60 Hz
440 @
50 Hz
15
25
50
75
100
Fusible Disconnect Type
Circuit Breaker Type
Fuse Clip
Amperes a
Class 8940
Type
Frame Size
30
WC1S2V03
2
60
WD1S2V03
3
100
WE1S2V03
4
1
200
30
WF1S2V03
WC3S2V06
2
60
WD3S2V06
3
100
WE3S2V06
4
200
WF3S2V06
Class 8940
Type
GJL36030M04
XC1S2V03
GJL36050M05
XD1S2V03
FAL3610018M
XD2S2V03
FAL3610018M
XE1S2V03
KAL3625026M
XF1S2V03
KAL3625029M
XF2S2V03
GJL36015M03
XC3S2V06
GJL36030M04
XC4S2V06
GJL36030M04
XD3S2V06
GJL36050M05
XD4S2V06
FAL3610018M
XE3S2V06
KAL3625025M
XF3S2V06
KAL3625029M
XF4S2V06
a Fuse clips are sized for use with dual-element time-delay fuses.
k Thermal units must be ordered separately.
t Coil voltages must be specified to order this product. See coil voltage codes below.
Coil Voltage Codes
Voltage
Code
60 Hz
50 Hz
24 jq
—
120 j
110
V02
208 j
—
V08
240
220
V03
—
380
V05
480
440
V06
600 j
550
V07
Listed File E152395
CCN NKJH
V01
Listed File E152395
CCN NKJH7
q 24V coils are not available on Size 4 starters.
On Size 1-3, 24V coils are available. Form S must be used.
j Form S (separate control) required for 24 V, 120 V, 208 V, and
600 V coils.
5
© 1997-2008 Schneider Electric
All Rights Reserved
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
09/2008
www.barr-thorp.com
Well-Guard Control™ Pump Panels, Full Voltage–Class 8940
Factory Modifications
Factory Modifications
Description
Form
Start push button in oil field panel (S2) only
A28
Substitute Class 10 IEC overload relay – state motor hp
B12
Control Transformer with Fused Primary:
Types:
NPD, NPE, NPF, WC, XC, NSC, SSC (50 VA)
NPG, NSG, XD, WD, SSD (100 VA)
NPJ, NSE, XE, WE, SSE (150 VA)
NSF, XF, WF, SSF (300 VA)
NSG, XSG, (50 VA and an interposing control relay)
F4T
Door wind latch assembly, factory installed in a standard 8940NPD, NPE, NPF, NPG, NPJ, SSC, SSO, SSE, or
SSF panel.
G45
Elapsed time meter
G97
Substitute Class 10 Motor Logic® SSOLR (without phase imbalance protection)
H10
On delay timer, 0.1 seconds to 1 minute
K25
Off delay timer, 0.1 seconds to 1 minute
K26
On delay timer, 1 minute to 3 minute
K37
Off delay timer, 1 minute to 3 minute
K38
Backspin timer (time delay on energization)
K15
Slim panel (Types WC, WD, WF, XC, XD, XF only)
L8
Short Panel (Types SSE, SSF only)
L9
Pilot light, red (does not include auxiliary contact)
P1
Pilot light, green (does not include auxiliary contact)
P2
Separate Control
S
Auxiliary Contacts (Specify N.O. or N.C.)
Xq
Special UL panel label for modified UL Listed devices on non-standard panels. Requires approval by
manufacturing plant.
Y1
Lightning Arrester
Y1532
Phase failure, phase reversal relay with time delay, including undervoltage and overvoltage protection
R44 j
Substitute Standard-Trip Melting Alloy Overload Relays (Type S2 only)
Y61
Substitute Quick-Trip Melting Alloy Overload Relay (Type S2 only)
Y611
j Requires the use of 120 volt control (Form S or FF4T).
q To determine the maximum number of auxiliary contacts which can be added to each Type S device, and for the appropriate X
Form, refer to tables in the Class 8536 section of the current Digest.
6
09/2008
© 1997-2008 Schneider Electric
All Rights Reserved
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
Well-Guard Control™ Pump Panels, Full Voltage–Class 8940
Reduced Voltage Type
Class 8940 Reduced Voltage panels in NEMA Type 3R enclosures are specifically designed for
pumping applications. Extra space is provided for field installation of auxiliary equipment.
•
•
•
Type S contactors/starters provided as standard.
All devices are UL Listed and marked “SUITABLE ONLY FOR USE AS SERVICE EQUIPMENT.”
Includes Hand-Off-Auto selector switch and Start push button.
Closed Transition Autotransformer Type
3-Pole Polyphase – 600 Volts AC Maximum – 50-60 Hertz
Motor
(Starter)
Volts
Max. hp
Polyphase
Coil
Voltage
15
25
230
(240)
30
50
2
3
240 @ 60 Hz
220 @ 50 Hz 4
75
5
100
25
2
30
3
50
75
460
(480)
100
150
NEMA
Size
480 @ 60 Hz
440 @ 50 Hz
200
300
4
5
6
400
600
7
Fusible Disconnect Type
Fuse Clip
Amperes a
Class 8940
Type k
Circuit Breaker Type
Circuit
Breaker
Class 8940
Type k
60
RD4DV03
FAL36080
VD1DV03
100
RE4FV03
FAL36100
VE1FV03
200
RE1GV03
KAL36100
VE2GV03
200
RF4JV03
KAL36200
VF1JV03
400
RG1LV03
LAL36250
VG2LV03
400
RG1MV03
LAL36350
VG2MV03
60
RD2FV06
FAL36070
VD1FV06
100
RE2GV06
FAL36080
VE1GV06
100
RE2JV06
FAL36100
VE1JV06
200
RF2LV06
KAL36125
VF1LV06
200
RF2MV06
KAL36200
VF1MV06
400
RG3PV06
LAL36250
VG4PV06
400
RG3QV06
LAL36350
VG4QV06
—
—
MAL36600
VH1SV06
—
—
MAL36900
VH2TV06
—
—
MAL36100
VJ1WV06
a Fuse clips are sized for use with dual-element time-delay fuses.
k Thermal units must be ordered separately.
Part Winding Type
3-Pole Polyphase – 600 Volts AC Maximum – 50-60 Hertz
Motor
(Starter)
Volts
Max. hp
Polyphase
25
30
230
(240)
50
75
100
125
Coil
Voltage
NEMA
Size
2PW
3PW
240 @ 60 Hz
4PW
220 @ 50 Hz
5PW
150
30
40
60
460
(480)
Listed File E152395
CCN NKJH
75
100
150
3PW
480 @ 60 Hz
440 @ 50 Hz 4PW
200
250
Listed File E152395
CCN NKJH7
2PW
400
5PW
Combination Fusible
Disconnect Type
Combination Circuit Breaker
Type
Fuse Clip
(2 sets)
Amperes a
Class 8940
Type k
Circuit
Breaker (2
Bkrs.)
Frame Size
Class 8940
Type k
60
MD4FV03
FAL36070
PD1FV03
60
ME5GV03
FAL36080
PE3GV03
100
ME6JV03
FAL36100
PE3JV03
200
MF1LV03
KAL36150
PF3LV03
200
MG3MV03
KAL36175
PG2MV03
400
MG1NV03
LAL36250
PG3NV03
400
MG1PV03
LAL36250
PG3PV03
30
MD5GV06
FAL36040
PD1GV06
60
MD2HV06
FAL36050
PD1HV06
60
ME7KV06
FAL36070
PE3KV06
100
ME3LV06
FAL36090
PE3LV06
200
MF3MV06
FAL36100
PF2MV06
200
MF3PV06
KAL36125
PF3PV06
200
MG4QV06
KAL36175
PG2QV06
200
MG4RV06
LAL36225
PG3RV06
400
MG2TV06
LAL36300
PG3TV06
a Fuse clips are sized for use with dual-element time-delay fuses.
k Thermal units required. Order separately. Refer to pages 10–11.
7
© 1997-2008 Schneider Electric
All Rights Reserved
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
09/2008
www.barr-thorp.com
Well-Guard Control™ Pump Panels, Full Voltage–Class 8940
Replacement Part Application Data
Application Data
Disconnect
Switch
Fuse Base
Contactor
Overload Relay
Overload Relay
Mounting Bracket
NPD2003
40567-200-51t
40566-143-51
LC1D12
LRD16
LAD7B10
NPE2005
40567-200-51t
40566-143-51
LC1D18
LRD21
LAD7B10
NPE2007
40567-200-51t
40566-143-51
LC1D25
LRD22
LAD7B10
NPF2010
40567-200-51t
40566-143-51
(60 A 250 V)
40566-144-51
(60 A 600 V)
LC1D32
LRD32
LAD7B10
NPF2015
40567-200-51t
40566-143-51
(60 A 250 V)
40566-144-51
(60 A 600 V)
LC1D50
LRD3357
LA7D3064
NPG2020
31301-056-65
31301-059-50
LC1D65
9065TJF40
NA
NPG2025
31301-056-65
31301-059-50
LC1D80
9065TJF40
NA
NPJ2030
31301-056-65
31301-059-50
LC1F115
9065TJF63
NA
NPJ2040
31055-366-51
Included with switch
LC1F115
9065TJF63
NA
NPJ2050
31055-366-51
Included with switch
LC1F150
9065TJF100
NA
Class 8940 Type
NPD4003
40567-200-51t
40566-143-51
LC1D09
LRD10
LAD7B10
NPD4005
40567-200-51t
40566-143-51
LC1D09
LRD12
LAD7B10
NPD4007
40567-200-51t
40566-143-51
LC1D12
LRD16
LAD7B10
NPE4010
40567-200-51t
40566-143-51
LC1D18
LRD21
LAD7B10
NPE4015
40567-200-51t
40566-143-51
LC1D25
LRD22
LAD7B10
NPF4020
40567-200-51t
40566-143-51
(60 A 250 V)
40566-144-51
(60 A 600 V)
LC1D32
LRD32
LAD7810
NPF4025
40567-200-51t
40566-143-51
(60 A 250 V)
40566-144-51
(60 A 600 V)
LC1D40
LRD3355
LA7D3064
NPF4030
40567-200-51t
40566-144-51
(60 A 250 V)
LC1D50
LRD3357
LA7D3064
NPG4040
31301-056-65
31301-059-50
LC1D65
9065TJF40
NA
NPG4050
31301-056-65
31301-059-50
LC1D80
9065TJF40
NA
NPJ4060
31301-056-65
31301-054-50
LC1F115
9065TJF63
NA
NPJ4075
31055-366-51
Included with switch
LC1F115
9065TJF63
NA
NPJ4100
31055-366-51
Included with switch
LC1F150
9065TJF100
NA
t Includes switch base and operating mechanism. To ensure handle compatibility, part number HM0610F must also be
purchased.
NOTE: Two operating mechanisms will be shipped; keep one mechanism as a spare.
8
09/2008
© 1997-2008 Schneider Electric
All Rights Reserved
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
Well-Guard Control™ Pump Panels, Full Voltage–Class 8940
Replacement Part Application Data
Application Data
Class 8940 Type
Disconnect Switch
Fuse Base
Contactor
Overload Relay
SSC2007
40567-200-51t
40566-143-51
8502SCO2
31161-547-64
SSD2015
40567-200-51t
40566-143-51
(60 A 250 V)
40566-144-51
(60 A 600 V)
8502SDO2
31161-548-83
SSE2030
31301-056-65
31301-059-50
8052SEO2
31161-551-58
SSF2050
31055-366-51
Included with switch
8502SFO2
31161-551-58
SSC4010
40567-200-51t
40566-143-51
8052SCO2
31161-547-64
SSD4025
40567-200-51t
40566-143-51
(60 A 250 V)
40566-144-51
(60 A 600 V)
8502SDO2
31161-548-83
SSD4030
40567-200-51t
40566-143-51
(60 A 250 V)
40566-144-51
(60 A 600 V)
8502REQ2617G
31161-548-83
SSE4050
31301-056-65
31301-059-50
8502SEO2
31161-551-58
SSF4100
31055-366-51
Included with switch
8502SFO2
31161-553-68
9065SE06B
XSG2075
LAL36250
NA
8502SGO2
SSG2100
9422TG2
NA
31102-668-50
31161-184-74
XSG2100
LAL36350
NA
8502SGO2
9065SE06B
9065SE06B
XSH2200
MAL36700
NA
8536SHO2
XSJ2250
MAL36800
NA
8536JO2
9065SE06B
XSJ2300
MAL361000
NA
8536JO2
9065SE06B
9065SE06B
XSG4150
LAL36250
NA
8502SGO2
SSG4200
9422TG2
NA
31102-668-00
31161-184-74
XSG4200
LAL36350
NA
8502SGO2
9065SE06B
XSH4300
MAL36500
NA
8536SHO2
9065SE06B
XSH4300
MAL36600
NA
8536SHO2
9065SE06B
9065SE06B
XSH4400
MAL36700
NA
8536SHO2
XSJ4500
MAL36800
NA
8536JO2
31161-184-77
XSJ4600
MAL361000
NA
8536JO2
31161-184-77
t Incluses switch base and operating mechanism. To ensure handle compatibility, part number HM0610F must also be
purchased.
NOTE: Two operating mechanisms will be shipped; keep one as a spare.
Class 8940 Electrical Interlocks
Disconnect Switches
Circuit Breakers
Rating
Style
SPDT
DPDT
SPDT
DPDT
30A
EIK1t
EIK2t
GJL
NA
NA
60A
EIK1t
EIK2t
FAL
9999R26
9999R27
100A
9999TC10
9999TC20
KAL
9999R26
9999R27
200A
9999R39
9999R40
LAL
9999R26
9999R27
400A
9999R35
9999R36
MAL
9999R26
9999R27
t No class number required.
9
© 1997-2008 Schneider Electric
All Rights Reserved
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
09/2008
www.barr-thorp.com
Well-Guard Control™ Pump Panels, Full Voltage–Class 8940
Thermal Units
Bimetallic Thermal Unit Selection Tables Based on Motor Full Load Current
Table A - NEMA Size 1 (Table 33)
Types WC, XC
Table D - NEMA Size 4 k (Table 29)
Types MF, PF, RF, VF, WF, XF
Motor Amperes
Thermal Unit
Motor Amperes
Thermal Unit
6.28-6.97
6.98-7.59
7.60-7.89
7.90-8.95
8.96-10.3
AR 10.2
AR 11.2
AR 12.4
AR 13.6
AR 15.4
50.0-55.9
56.0-60.9
61.0-65.9
66.0-69.9
70.0-75.9
E 88
E 89
E 91
E 92
E 93
10.4-11.7
11.8-13.3
13.4-15.2
15.3-17.2
17.3-19.7
AR 17.6
AR 20.5
AR 23
AR 27
AR 30
76.0-81.9
82.0-86.9
87.0-92.9
93.0-97.9
98.0-107.9
E 94
E 96
E 97
E 98
E 99
19.8-22.4
22.5-26.0
AR 35
AR 40
108.0-113.9
114.0-125.9
E 101
E 102
Table B - NEMA Size 2k (Table 70)
Types MD, PD, RD, VD,WD, XD
Motor Amperes
Thermal Unit
8.56-9.74
9.75-11.1
11.2-12.7
12.8-14.4
14.5-16.4
AR 17.6
AR 20.5
AR 23
AR 27
AR 30
16.5-18.9
19.0-21.6
21.7-23.3
23.4-24.9
25.0-26.9
AR 35
AR 40
AR 44
AR 47
AR 51
27.0-29.1
29.2-31.3
31.4-33.5
33.6-36.9
37.0-39.1
AR 55
AR 60
AR 66
AR 72
AR 79
39.2-40.9
41.0-45.0
AR 86
AR 94
Table C - NEMA Size 3k (Table 37)
Types ME, PE, RE, VE, WE, XE
Motor Amperes
Thermal Unit
27.1-30.0
30.1-33.2
33.3-35.7
35.8-39.4
39.5-43.4
E 67
E 69
E 70
E 71
E 72
43.5-46.9
47.0-51.5
51.6-57.0
57.1-62.8
62.9-69.1
E 73
E 74
E 76
E 77
E 78
69.2-75.0
75.1-83.3
E 79
E 80
t These thermal unit selections are for controllers protected from
solar radiation and located in an ambient temperature of 40 oC
(104 oF) or less. For overload relays which are not ambient
temperature compensated (NEMA Size 3 and 4), thermal units
larger than normal can be required under conditions of high
ambient temperature and/or solar radiation. Consult your local
Square D field office.
k To select thermal units for Type M part winding devices, first
divide total motor full load current by 2. Use tables above.
u Order Type E thermal units by number from Square D
Company, Furnas Electric Company, Batavia, IL or a
Furnas Distributor.
Table E- NEMA Size 5qk (Table 46)
Types MG, PG, RG, VG, WG, XG
Motor Amperes
Thermal Unit
105-116
117-132
133-148
149-165
166-184
AR 3.28
AR 3.62
AR 3.98
AR 4.37
AR 4.80
185-207
208-229
230-266
AR 5.30
AR 5.8
AR 6.4
q With 300:5 Current Transformer Ratio. Across-the-line and
auto-transformer type reduced voltage.
Table F- NEMA Size 6q (Table 47)
Type VH, XH
Motor Amperes
Thermal Unit
146-169
170-185
186-201
202-217
218-236
AR 1.68
AR 1.85
AR 2.04
AR 2.24
AR 2.46
237-253
254-279
280-311
312-353
354-396
AR 2.71
AR 2.98
AR 3.28
AR 3.62
AR 3.98
397-442
443-492
493-520
AR 4.37
AR 4.80
AR 5.30
q With 800:5 Current Transformer Ratio. Auto-transformer
type reduced voltage.
Table G- NEMA Size 7
Type
Motor Amperes
Thermal Unit
Motor Logic SSOLR
Adjustable 270-810 Full Load Current (Ambient Insensitive)
NOTE: This is a partial Thermal Unit Selection Table
listing. The complete list can be found in the current
Digest.
10
09/2008
© 1997-2008 Schneider Electric
All Rights Reserved
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
Well-Guard Control™ Pump Panels, Full Voltage–Class 8940
Thermal Units
Melting Alloy Quick Trip Thermal Unit Selection Tables (Form Y611)
Based on Motor Full Load Currentt
Table H- NEMA Size 1 (Table 78)
Types WC, XC
Table I - NEMA SIZE 2 (Table 79)
Types WD, XD
Motor Amperes
Thermal Unit
Motor Amperes
Thermal Unit
2.26-2.51
2.52-2.81
2.82-3.09
3.10-3.30
3.31-3.69
FB 3.33
FB 3.71
FB 4.1
FB 4.5
FB 4.75
4.24-4.69
4.70-5.21
5.22-5.49
5.50-5.74
5.75-6.07
FB 6.1
FB 6.75
FB 7.45
FB 7.8
FB 8.21
3.70-4.27
4.28-4.72
4.73-5.25
5.26-5.53
5.54-5.81
FB 5.3
FB 6.1
FB 6.75
FB 7.45
FB 7.8
6.08-6.35
6.36-6.71
6.72-7.03
7.04-7.53
7.54-7.91
FB 8.6
FB 9.0
FB 9.5
FB 10
FB 10.6
5.82-6.14
6.15-6.44
6.45-6.81
6.82-7.19
7.20-7.59
FB 8.2
FB 8.6
FB 9.0
FB 9.5
FB 10
7.92-8.53
8.54-9.14
9.15-9.71
9.72-10.2
10.3-10.8
FB 11.2
FB 12.1
FB 13.1
FB 13.9
FB 14.8
7.60-7.99
8.00-8.17
8.18-8.74
8.75-9.31
9.32-9.94
FB 10.6
FB 11.2
FB 12.1
FB 13.1
FB 13.9
9.95-10.5
10.6-11.1
11.2-12.0
12.0-12.4
12.5-13.1
FB 14.8
FB 15.6
FB 16.4
FB 17.6
FB 18.4
10.9-11.5
11.6-12.3
12.4-13.0
13.1-13.9
14.0-15.1
15.2-16.1
16.2-16.9
17.0-17.9
18.0-19.4
19.5-20.7
FB 15.6
FB 16.4
FB 17.6
FB 18.4
FB 19.4
FB 21.1
FB 22.6
FB 23.6
FB 24.8
FB 26.7
13.2-14.3
14.4-15.3
15.4-15.9
16.0-16.9
17.0-18.3
FB 19.4
FB 21.1
FB 22.6
FB 23.6
FB 24.8
20.8-21.7
21.8-22.3
22.4-23.9
24.0-25.1
25.2-25.9
FB 28.3
FB 29.6
FB 30.5
FB 32.6
FB 34.1
18.4-19.5
19.6-20.5
20.6-21.1
21.2-22.6
22.7-23.7
FB 26.7
FB 28.3
FB 29.6
FB 30.5
FB 32.6
26.0-27.1
27.2-28.6
28.7-30.1
30.2-31.7
31.8-33.3
FB 35
FB 36.6
FB 38.3
FB 40.2
FB 42
23.8-24.3
24.4-26.0
FB 34.1
FB 35
33.4-34.5
34.6-36.5
36.8-38.5
38.6-39.9
40.0-45.0
FB 44
FB 46
FB 48
FB 50.5
FB 52.5
Table J - NEMA SIZE 3 (Table 80)
Types WE, XE
Motor Amperes
Thermal Unit
20.5-21.7
21.8-23.1
23.2-24.8
24.9-26.5
26.6-28.4
FB 26.7
FB 28.3
FB 29.6
FB 30.5
FB 32.6
28.5-30.4
30.5-32.8
32.9-34.9
35.0-37.3
37.4-39.8
FB 34.1
FB 38.3
FB 40.2
FB 42
FB 44
39.9-42.5
42.6-45.8
45.9-48.2
48.3-50.6
50.7-53.1
FB 46
FB 48
FB 50.5
FB 52.5
FB 55.5
53.2-56.5
56.6-59.4
59.5-63.4
63.5-71.0
71.1-78.8
FB 58
FB 60
FB 63.5
FB 69
FB 77
78.9-86.0
FB 84
Table K - NEMA SIZE 4 (Table 81)
Types WF, XF
Motor Amperes
Thermal Unit
52.2-55.6
55.7-58.8
58.9-62.5
62.6-66.0
66.1-70.1
FB 50.5
FB 52.5
FB 55.5
FB 58
FB 60
70.2-78.6
78.7-92.0
92.1-102
103-114
115-123
FB 63.5
FB 69
FB 77
FB 84
FB 92
124-133
FB 105
t These thermal unit selections are for controllers protected
from solar radiation and located in an ambient temperature
of 40oC (104oF) or less. For overload relays which are not
ambient temperature compensated (NEMA Size 3 and 4),
thermal units larger than normal can be required under
conditions of high ambient temperature and/or solar
radiation. Consult your local Square D field office.
NOTE: This is a partial Thermal Unit Selection
Table listing. The complete list can be found in
the current Digest.
11
© 1997-2008 Schneider Electric
All Rights Reserved
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
09/2008
www.barr-thorp.com
Well-Guard Control™ Pump Panels, Full Voltage–Class 8940
Replacement Part Application Data
Approximate Dimensions
Type
NPD
NPE
NPF
SSC
NPG
NPJ
SSE
SSF
XSE
Fig.
Dim.
in.
A
B
39.05
13.73
C
6.67
D
9.70
E
33.05
F
37.93
G
7.00
H
2.41
J
3.00
K
Conduit
L
3.00
1
Knockout
M
mm
992
349
169
246
839
963
178
61
76
76
in.
49
19.15
8.81
10.37
44.07
47.88
7.00
2.17
2.69
3.44
S
T
1/2, 3/4
1-1/4,
1-1/2
1/2,3/4
1-1/4
1,2-1/2
1,1-1/4
1-1/2,2
2.41
1-1/2
61
2-1/2
2.57
2
1/2, 3/4
mm
1245
486
249
263
1119
1216
178
55
68
87
V
R
65
1.41
36
1.41
36
Handle
Swing
Figure 1
Figure 2
Dual Dimensions:
in.
mm
12
09/2008
© 1997-2008 Schneider Electric
All Rights Reserved
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
Well-Guard Control™ Pump Panels, Full Voltage–Class 8940
Replacement Part Application Data
Approximate Dimensions
Type
Fig. Dimensions A
WC-S2
WD-S2
XC-S2
1
WE-S2
WF-S2
XE-S2
1
in.
NSG
XSG
2
XSH
3
XSJ
3
38.50
B
19.00
C
7.29
D
9.39
E
34.00
F
37.38
G
7.00
H
2.18
J
2.13
K
Conduit
L
2.13
978
483
185
539
864
949
178
55
54
54
in.
56.50
23.00
8.23
10.33
52.00
55.38
7.00
2.18
2.69
3.44
R
S
1/2-3/4
1, 1-1/4,
1/2, 3/4
1-1/2
2.12
1-1/2
mm
Knockout
M
54
2.68
1/2
1/2-3/4
1, 1-1/4, 1, 1-1/4
2, 2-1/2 1-1/2, 2
—
—
1.50
mm
1435
584
209
262
1321
1407
178
55
68
87
in.
74.50
22.00
13.80
17.55
73.00
0.50
14.00
—
0.56
—
—
—
—
—
—
1.50
mm
1892
559
351
446
1854
13
356
—
14
—
—
—
—
—
—
38
in.
82.50
36.00
20.00
23.25
80.00
33.75
16.50
—
—
—
—
—
—
—
—
—
mm
2096
914
508
591
2032
857
419
—
—
—
—
—
—
—
—
—
in.
92.50
34.00
20.00
23.25
90.00
31.75
16.50
—
—
—
—
—
—
—
—
—
mm
2350
864
508
591
2286
806
419
—
—
—
—
—
—
—
—
—
Dia. Mtg. Holes
68
V
T
38
Dia. Mtg. Holes
Dia. Mtg. Holes
Figure 1
Figure 2
Figure 3
Dual Dimensions:
13
© 1997-2008 Schneider Electric
All Rights Reserved
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
in.
mm
09/2008
www.barr-thorp.com
Well-Guard Control™ Pump Panels, Full Voltage–Class 8940
Replacement Part Application Data
Part Winding - Reduced Voltage Type
Type
PD
MD
PE
PF
ME
MF
PG
MG
PH
Dimensions t
A
B
C
D
E
F
in.
19.00
34.50
12.25
13.00
33.50
0.44
Figure
mm
483
876
311
330
851
11
in.
23.00
25.50
10.60
17.00
24.50
0.44
mm
584
648
269
432
622
11
in.
30.00
47.00
13.25
22.00
46.00
0.56
mm
762
1194
337
559
1168
14
in.
25.00
52.50
12.13
19.00
51.50
0.44
mm
635
1334
308
483
1308
11
in.
36.00
93.00
19.25
33.75
12.50
0.69
mm
914
2362
489
857
318
18
in.
36.00
73.00
19.25
33.75
12.50
0.69
mm
914
1854
489
857
318
18
in.
38.00
93.00
19.25
35.75
12.50
0.69
mm
965
2362
489
908
318
18
2
1
2
2
3
3
3
Auto-transformer - Reduced Voltage Type
Type
Dimensions t
A
B
C
D
E
F
RD
VD
in.
25.00
52.50
11.13
19.00
51.50
0.44
mm
635
1334
283
483
1308
11
RE, VE
RF, VF
in.
32.00
72.50
19.25
29.75
12.50
0.68
mm
813
1842
489
756
318
17
RG
VG
VH
VJ j
Figure
in.
36.00
93.00
19.25
33.75
12.50
0.69
mm
914
2362
489
857
318
17
in.
32.00
72.50
19.25
29.75
12.50
0.68
mm
813
1842
489
756
318
17
in.
34.00
93.00
23.25
3133.75
16.50
0.69
mm
864
2362
591
806
419
17
in.
64.00
93.00
27.25
61.75
17.25
0.81
mm
1626
2362
692
1568
438
21
2
3
3
3
3
3✝
j Cabinet has double doors
Figure 1
Figure 2
Figure 3
t
Dual Dimensions:
in.
mm
14
09/2008
© 1997-2008 Schneider Electric
All Rights Reserved
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
www.barr-thorp.com
Well-Guard Control™
Replacement Part Application Data
15
© 1997-2008 Schneider Electric
All Rights Reserved
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123
09/2008
www.barr-thorp.com
Schneider Electric USA
8001 Knightdale Blvd.
Knightdale, NC 27545
1-888-Square D
1-888-778-2733
www.schneider-electric.us
8940CT9701R7/08 © 1997-2008 Schneider Electric All Rights Reserved
Replaces 8940CT9701, December 1997
09/2008
This document provided by Barr-Thorp Electric Co., Inc. 800-473-9123