Data Report: ASME Gas Heater Form 002863

Data Report: ASME Gas Heater Form 002863
FORM HLW-6 MANUFACTURER'S DATA REPORT FOR
WATER HEATERS OR STORAGE TANKS
As Required by the Provisions of the ASME Code Rules
2606350
Work Order #
1. Manufactured and certified by Hayward Industries, Inc., 2935 Sidco Drive, Nashville, Tennessee, 37204
(name and address of manufacturer)
2. Manufactured for Stock
(name and address of purchaser)
3. Location of Installation Stock
4. Identification
(name and address)
21131504106786001 to
21131504106799001
N/A
2902586801 Rev M
2863-2876
2015
(manufacturer's serial no.)
(CRN)
(drawing no.)
(National Board no.)
(year built)
5. The chemical and physical properties of all parts meet the requirements of material specifications of the ASME BOILER AND PRESSURE VESSEL
CODE. The design, construction, and workmanship conform to Part HLW, Section IV
2013
N/A
2768
(year)
6. Shell
[addenda (as applicable) (date)]
(Code Case no.)
1
SB-584 (C90300)
.300
None
2.88" ID
0' 14.96"
(no.)
(material spec., gr.)
(thickness)
(lining)
(diameter)
[length(overall)]
7. Joints
Seamless "Casting"
80%
[long. (seamless, welded)]
8. Heads
Seamless "Casting"
[eff. (compared to seamless)]
Flat
Location
Material Spec., Gr., Thickness
Crown Radius
END
SB-584 (C90300) .250"
N/A
9. Tubesheet
SA-240 T304
Tubes
(material spec., gr.)
Handhole
Inlet/Outlet Port
Drain Valve Port
Pressure Relief Valve
Temp Sensor Ports
Pressure Sensor Port
Thermistor Temp Sensor Port
11. MAWP
125 psi
2
1
1
2
1
1
Diameter or
Size
2.40
3/4"NPT
3/4"NPT
1/4"NPT
1/8"NPT
3/8"NPT
Max. input
Knuckle Radius
Elliptical Ratio
(no. of shell courses)
Flat Diameter
Side Pressure
(concave, convex)
4.75"
4
.750 in
5' 8.717"
SB-543 (C70600)
.049 in
Both
(no. )
(size)
[length(overall)]
(mat'l spec., gr.)
(thickness)
(rolled or welded)
10. Nozzles, inspection, and safety valve openings:
Purpose (inlet, outlet, drain, etc.) No.
1
[girth (seamless, welded)]
Type
N/A
Flanged
Female Thrd
Female Thrd
Female Thrd
Female Thrd
Female Thrd
500,000 BTU
How Attached
Cast
Machined
Machined
Machined
Machined
Machined
Material
Nominal
Thickness
Reinforcement Material
N/A
N/A
SB584/C90300 .300
Thrd Opening
Thrd Opening
Thrd Opening
Thrd Opening
Thrd Opening
Max. temp.
140 °F
Location
Shell
Shell
Shell
Shell
Shell
Shell
Hydrostatic test
188 psi
12. Manufacturer's Partial Data Reports properly identified and signed by Commissioned Inspectors have been furnished for the following items for this report
N/A
(name of part, item no., manufacturer's name, identification stamps)
13. Remarks
Cast header is also called the shell as refered to in section 6,7, and 10 above.
3/4" and below ports are drilled and tapped openings in shell casting.
PKEY 2275674
exe: v6.2.47
HLW6-7
NB-30 Rev 7
NB Number 2863-2876
HLW-6 (BACK)
CERTIFICATE OF SHOP COMPLIANCE
We certify that the statements made in this data report are correct and that all details of design, material, construction, and workmanship of this
water heater or storage tank conform to Section IV of the ASME BOILER AND PRESSURE VESSEL CODE.
"HLW" Certificate of Authorization no.
Date 5/8/2015
Name
40380
expiration date
2/16/2017
Hayward Industries, Inc.
(manufacturer that constructed and certified water heater or storage tank)
.
Signed
(by representative)
CERTIFICATE OF SHOP INSPECTION
Constructed by
Hayward Industries, Inc.
at 2935 Sidco Drive, Nashville, Tennessee, 37204
I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and employed by
HSB Global Standards
have inspected parts referred to as data items
6 thru 11
and have examined Manufacturer's Partial Data Report for items
and state that, to the best of my knowledge and belief, the manufacturer has constructed the water heater or storage tank in accordance with
Section IV of the ASME BOILER AND PRESSURE VESSEL CODE.
By signing this certificate, neither this Inspector, nor his employer makes any warranty, expressed or implied, concerning the water heater or
storage tank described in this Manufacturer's Data Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for
any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Date
5/14/2015
Commission
Signed
(Authorized Inspector)
PKEY 2275674
exe: v6.2.47
15227A
(National Board commission number and endorsement)
HLW6-7
NB-30 Rev 7