PFB366 data sheet
W W W . M K S I N S T . C O M
Control & Information
Technology
Type PFB366
PROFIBUS™ SERIAL GATEWAY
The PFB366 is a compact RS232 to Profibus serial gateway. The unit is housed in a 2½ x 3¼ plastic housing with mounting tabs. A standard DB9-Female connector provides
the Profibus interface and a DB9-Male connector provides the RS232 interface. The Profibus channel is fully isolated from the supplied power. The power is conditioned by a
loss-of-ground protection circuit.
The PFB366 may be used to interface peripheral devices to a Profibus system. The RS232
serial stream is internally buffered, allowing a Master node to send and receive data using
standard Profibus messaging.
PFB366 provides a fully buffered serial interface between Profibus and peripheral devices.
Internal FIFO’s, buffer up to 255 bytes of receive and 255 bytes of transmit data, easing the
interface to slower RS232 based devices. Hardware or software flow control is supported.
Features & Benefits
•
•
•
•
•
•
Fully isolated Profibus channel
Powered from 11-28 VDC power
Rotary Hex ID switches
2 BI-color LED’s for module status
2 BI-color LED’s for serial channel status
Selectable serial baud rate (300-19200 baud)
Specifications
Profibus Interface
Power Requirements
Loss of Ground
Reverse Polarity
Signal Levels
RS232 Interface
Isolation
ESD Protection
Overload Protection
Short Circuit
Output Levels
Data Size
Parity
11-28 VDC @ 50mA
Yes
-30 VDC
RS485
500 Volts
±10kV
±30 Volt
Indefinite
±7.9 Volts (typical)
8/7 bits (software configuration)
Even/Odd/None (software configuration)
Stop Bits
Data Rate
Flow Control
Environmental
Temperature
Size
Mounting
Encapsulation
½ (software configuration)
300, 1220, 2400, 4800, 9600, 19.2k (software selected)
None, RTS/CTS, X-ON / X-OFF (software configuration)
0-70°C
3.25 X 2.37 X 1.08
1/2 inch tab, 3/16 diameter mounting hole
RTV Silicon Compound
Ordering Code Example: PFB366
Type PFB366
PFB366 Profibus Serial Gateway
Code
PFB366
ProfiBus Connector
(DB-9 pin female)
Pin
Function
RS232 Connector
(DB-9 pin male)
Pin
Function
1
1
N.C.
2
2
Receive Data
3
B-line
3
Transmit
4
RTS
4
DTR/DTS Loopback to Pin 6
5
GND (Iso.)
5
Ground
6
+5 (Iso.)
6
DTR/DTS Loopback to Pin 4
7
Request to send
7
8
A-line
9
PFB366 - 8/12
© 2005 MKS Instruments, Inc.
All rights reserved.
Configuration
PFB366
8
Clear to send
9
Power (+11 - 28 VDC)
Global Headquarters
Control & Information Technology
2 Tech Drive, Suite 201
Andover, MA 01810
134 W. Rio Robles Drive
San Jose, CA 95134
Tel: 978.645.5500
Tel: 800.227.8766 (in USA)
Web: www.mksinst.com
Tel:
408.750.0300
MKS products provided subject to the US and other country export regulations. Diversion or transfer contrary to U.S. or other
export laws is prohibited.
Specifications are subject to change without notice. Profibus™ is a trademark of Profibus Trade Organization.