VFD Function Form

VFD Function Form
PRE-FUNCTIONAL CHECKLIST
VARIABLE FREQUENCY DRIVE (VFD)
University of Scranton
Serving: ____________________
Location: ____________________
1.
Upper Class Residence Hall
Fed From Panel: _________
Page 1 of 3
Requested documentation submitted
Check if Okay. Enter comment or note number if deficient.
Equip Tag->
Contr.
Check
Manufacturer’s cut sheets
Performance data (fan curves, coil data, etc.)
Installation and startup manual and plan
Sequences and control strategies
O&M manuals
Documentation complete as per contract documents for given trade........ ___ YES ___ NO
2.
Model verification
[Contr = ________]
1 = as specified, 2 = as submitted, 3 = as installed. Check if Okay. Enter note number if deficient.
Equip Tag--->
Manuf.
Model
Serial #
Capacity
1
2
3
1
2
3
3
1
2
3
The equipment installed matches the specifications for given trade ......... ___ YES ___ NO
4.
Installation Checks
Check if Okay. Enter comment or note number if deficient.
Equip Tag->
Contr.
Check
General Installation
Permanent label affixed
Securely mounted
Drive location not subject to excessive temperatures
Drive location not subject to excessive moisture or dirt
Drive size matches motor size
Pilot lights functioning
VFD wired to controlled equipment
VFD Function Form.doc
5/12/2011
1
PRE-FUNCTIONAL CHECKLIST
VARIABLE FREQUENCY DRIVE (VFD)
University of Scranton
Serving: ____________________
Location: ____________________
Upper Class Residence Hall
Fed From Panel: _________
Page 2 of 3
Check if Okay. Enter comment or note number if deficient.
Equip Tag->
Contr.
Check
Programming and Controls
Internal setting designating the model is correct
Input of motor FLA represents 100% to 105% of motor FLA rating
Overload Settings are set in accordance with the NEC
Accel and decel times are around 10-50 seconds, except for
special applications. Record actual for each unit.
Lower frequency limit at 0 for VAV fans and around 10-30% for
chilled water pumps. Record actual for each unit.
Upper frequency limit set at 100%, unless explained otherwise
VFD interlocked to control system
Static or differential pressure sensor or other controlling sensor
properly located and per drawings
Controlling sensor calibrated
Unit is programmed with full written programming record submitted
RPM readout in BAS verified with VFD readout
All control devices, pneumatic tubing and wiring complete
Specified sequences of operation and operating schedules have
been implemented with all variations documented
Specified point-to-point checks have been completed and
documentation record submitted for this system
Monitor reports proper Voltage and is calibrated within 1%
Monitor reports proper Amperage and is calibrated within 1%
Final
Startup report completed with this checklist attached
Safeties installed and safe operating ranges for this equipment
provided to the commissioning agent
The checklist items of Part 4 are all successfully completed for given trade.___ YES ___ NO
VFD Function Form.doc
5/12/2011
2
PRE-FUNCTIONAL CHECKLIST
VARIABLE FREQUENCY DRIVE (VFD)
University of Scranton
Serving: ____________________
Location: ____________________
ISSUE #
Upper Class Residence Hall
Fed From Panel: _________
Page 3 of 3
ISSUE – PLEASE BE DETAILED AND SPECIFIC
DATE
RECORDED
BY
-- END OF CHECKLIST --
VFD Function Form.doc