S4090-0006-6 7/11 4090-9117 4090-9117 Addressable Power Isolator for 4100ES, 4100U and 4010ES Series Fire Alarm Controls

S4090-0006-6 7/11 4090-9117 4090-9117 Addressable Power Isolator for 4100ES, 4100U and 4010ES Series Fire Alarm Controls
Addressable Peripherals
UL, ULC, CSFM Listed; FM Approved;
MEA (NYC) Acceptance*
4090-9117 Addressable Power Isolator for
4100ES, 4100U and 4010ES Series Fire Alarm Controls
Features
24VB-
24VA-
ADDRESSABLE PWR ISOLATOR
IDNet+
IDNetON
1
2
3
4
5
6
7
8
1 2 34 5 6 78
ADDRESS CODE
4090-9117 Addressable Power Isolator for
4100ES/4100U/4010ES IDNet Communications
(shown approximately 1/2 size)
Product Selection
Model
4090-9117
4090-9801
4090-9802
Description
Addressable Power Isolator
For semi-flush
mounted box
For surface
mounted box
Optional trim plate with LED viewing
window, includes mounting screws;
galvanized steel
Specifications
Electrical
Current Rating
2 A maximum @ 32 VDC maximum
Input Power
10 mA maximum @ 24 VDC, system power
Communications
Description
Short Circuit Isolation. Under normal conditions, the
4090-9117 Addressable Power Isolator provides continuity
between ports. In the event of a short circuit, or if requested
from the control panel, the isolator opens a two-pole
electronic switch, isolating both power circuit conductors.
Operation. Isolators power-up in isolation mode and are
directed to connect by the control panel. If the output
wiring is acceptable, the isolator will connect to the rest
of the circuit. If the output wiring is shorted, the isolator
remains isolated.
Status Tracking. The isolator reports to the panel when it
is in isolation mode and the extent of shorted wiring is
available at the panel by identifying non-communicating
device addresses. [Isolators are assigned sequentially to low
number addresses to expedite Signaling Line Circuit (SLC)
power-up. Refer to Installation Instructions 574-873 for
additional information.]
Earth Faults. During system installation, earth faults
frequently occur. Finding these faults normally requires
extensive wiring disconnection. With the Addressable
Power Isolator, earth faults on fire alarm system power
wiring can be more quickly located to expedite repair.
24VB+
24VA+
Dual port, bi-directional power isolator for use with
®
Simplex 4100ES, 4100U and 4010ES Series fire
alarm control panels:
Either port can serve as an input or output, ports are
automatically separated when a power wiring short
circuit occurs
Isolation can also be activated from the 4100ES, 4100U,
or 4010ES control panel for system diagnostics
For use with fire alarm control panel system power,
rated for up to 2 A @ 32 VDC
Isolators communicate their location specific address
and status, and accept control via 4100ES, 4100U, or
4010ES IDNet™ communications
Small size fits into 4” square electrical box and allows
convenient mounting where protection is required
Visible LED flashes to indicate communications; optional
covers are available to view LED after installation
Earth fault isolation reduces time to fix wiring
problems:
Built-in control panel diagnostics can activate the
addressable power isolator, assisting in locating earth
fault conditions – the most common installation wiring
problem
For Class B or Class A power wiring:
Power is monitored from either port
Two Isolators can be connected to produce Class A
power wiring that can optimize operation by
maintaining connection with devices outside of the
isolated wiring section
UL listed to Standard 864
Wire Connections
4100ES/4100U/4010ES IDNet, 1 address, one
unit load
Screw terminals for input and output wiring,
18 to 14 AWG (0.82 mm2 to 2.08 mm2), two
wires/terminal; up to 12 AWG (3.31 mm2), one
wire/terminal
Wiring Reference
Power Wiring
IDNet
Communications
Wiring Reference
Refer to individual devices for wiring distances
Compatible with 2081-9028 Circuit Protector
Up to 2500 ft ( 762 m) from fire alarm control
Up to 10,000 ft ( 3048 m) total wiring distance
(including T-Taps)
Compatible with Simplex 2081-9044
Overvoltage Protectors
Mechanical
Dimensions
4-1/8” H x 4-1/8” W x 1-3/8” D
(105 mm x 105 mm x 35 mm)
Temperature
Humidity Range
32° to 120° F (0° to 49° C) indoor operation only
10 to 90% RH at 90° F (32° C)
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7300-0026:252 for allowable values and/or conditions concerning material presented in
this document. It is subject to re-examination, revision, and possible cancellation.
Additional listings may be applicable; contact your local Simplex product supplier for the
latest status.
S4090-0006-6
Power Isolator Multi-Floor Example 1
Earth Fault Isolation. In the event of an earth wiring
fault, each floor’s power wiring can be individually
isolated using 4100ES/4100U/4010ES control panel
diagnostics. This narrows the search area by
disconnecting the isolated wiring section and can result in
decreasing the time required to locate and correct the
earth fault.
Short Circuit Isolation. The one-line diagram on this
page shows a multiple floor example with Class B IDNet
communications and conventional Class B power wiring.
Each floor’s wiring starts at an isolator. If any floor
wiring beyond the isolator experiences a short circuit,
each floor will be individually separated from the next,
preventing the short circuit from disabling the entire
wiring run.
Duct sensor housing
with relay output
I
air handling syste m in which it is installed,
smoke variab
dilution
lesaatification
such
over
aswhich
which this device is attached as a secondary detection device.
DO NOT REMO VE THI S NOTICE!
24VA+
24VB+
24VA-
24VB-
ADDRESSABLE PWR ISOLAT OR
IDNet+
IDNetON
1 2
3
4
5
6
7
8
1 2 3 4 5 6 78
ADDRESS C ODE
Third floor
I
1
+0V
24V
ZONE
PWR
5
+
2
ZONE
PWR
6
3
IDC
+
4+IDNET
- IDNET
IDC
- 7
8
To local
zone
1
5
2
6
3
Zone Adapter
Module
7 CO.
SIMPLEX TI ME R ECORDER
4090-9101
MONITOR Z AM, CLASS B
INSTAL. INSTR. 574-183 8
DATE COD E:
1
4
24VA+
24VB+
24VA-
24VB-
ADDRESSABLE PWR ISOLAT OR
IDNet+
IDNetON
1 2
3
4
5
6
7
8
1 2 3 4 5 6 78
ADDRESS C ODE
Second floor
I
24VA+
24VB+
24VA-
24VB-
System power ,
24 VDC nominal
ADDRESSABLE PWR ISOLAT OR
First floor
IDNet+
IDNetON
1 2
3
4
5
6
7
8
1 2 3 4 5 6 78
ADDRESS C ODE
In-duct sensor
with relay output
4100ES/4100U/4010ESIDNet
communications ,
2 wire (see wiring notes )
Class B risers
24VA+
24VB+
24VA-
24VB-
4090 -9117 IDNet
Addressable Power Isolator
ADDRESSABLE PWR ISOLAT OR
IDNet+
IDNetON
1 2
3
4
5
6
7
8
1 2 3 4 5 6 78
ADDRESS C ODE
TrueAlarm sensor with relay base
I
IDNet Addressable Isolator
4090 -9116 (see note 3)
Wiring Notes :
1. This is a one -line drawing showing only IDNet communications
and power wiring .
2. Operation of the 4090 -9117 Addressable IDNet Power Isolator
requires connection to a 4100ES, 4100U or 4010ES IDNet
communications channel .
Simplex 4100 ES Series
Fire Control Panel
(shown for reference)
3. IDNet isolators are shown for typical reference but are not
required .
2
S4090-0006-6
Power Isolator Multi-Floor Example 2
Class A Wiring. The illustration below is a modification
of Example 1. Each floor wiring loop connects to the next
floor in a Class A connection. From the last device, the
wiring returns to the panel providing a secondary path
that is monitored for loop integrity. Class A power wiring
is available from a 4100ES/4100U/4010ES Fire Control
Panel programmed for this application using two 40909117 Power Isolators mounted close-nippled at the panel.
Diagnostic Assistance. It is recommended that for
Class A wiring, isolators be located as the first and last
devices in the loop (as shown below). With the resulting
wiring isolation flexibility, locating earth wiring faults
can be made easier
Last Remote
Powered Device
24VA+
Last IDNet Device
(see note 3)
24VB+
24VA-
Alternate Wiring Example
Class A riser with Class B
taps using Isolators
24VB-
IDNet+
IDNetON
1 2
3
4
5
6
7
8
1 2 3 4 5 6 78
ADDRESS C ODE
I
Duct sensor housing
with relay output
I
air handling syste m in which it is installed, variab les such
over as
which
which this device is attached as a secondary detection device.
DO NOT REMO VE THI S NOTICE!
24VA+
24VB+
24VA-
24VB-
IDNet+
IDNetON
1 2 3 4 5
1 2 3 4 5 6 78
6
7
8
ADDRESS C ODE
Third floor
I
1
+0V
24V
ZONE
PWR
5
+
2
ZONE
PWR
6
3
IDC
+
4+IDNET
- IDNET
IDC
- 7
8
To local
zone
1
5
2
6
3
4
24VA+
7 CO.
SIMPLEX TI ME R ECORDER
4090-9101
MONITOR Z AM, CLASS B
INSTAL. INSTR. 574-183 8
DATE COD E:
1
24VA+
24VB+
24VA-
24VB-
24VA-
24VB+
24VA+
24VB-
24VA-
IDNet+
IDNet-
24VB+
24VB-
IDNet+
ON
1 2 3 4 5 6 78
ADDRESS C ODE
IDNet-
ON
1 2 3 4 5 6 78
ADDRESS C ODE
IDNet+
IDNetON
1 2
3
4
5
6
7
8
1 2 3 4 5 6 78
ADDRESS C ODE
Zone Adapter
Module
Second floor
I
24VA+
24VB+
24VA-
24VB-
IDNet+
IDNetON
1 2
First floor
3
4
5
6
7
8
1 2 3 4 5 6 78
ADDRESS C ODE
First Remote
Powered Device
First IDNet
device
(see note 3)
In-duct sensor
with relay output
Class A system power
24 VDC nominal
4100ES/4100U/4010ES IDNet communications ,
2 wire (see wiring notes )
Primary
Return
24VA+
24VB+
24VA-
24VB-
4090-9117 IDNet
Addressable Power Isolator
Two, 4090-9117 IDNet
Addressable Power Isolators,
close-nippled in conduit
ADDRESSABLE PWR ISOLAT OR
IDNet+
IDNetON
1 2
3
4
5
6
7
8
1 2 3 4 5 6 78
24VA+
24VB+
24VA+
24VB+
24VA-
24VB-
24VA-
24VB-
ADDRESS C ODE
ADDRESSABLE PWR ISOLAT OR
IDNet+
IDNet+
IDNet-
IDNetON
1 2 3 4 5
1 2 3 4 5 6 78
ADDRESS C ODE
6
7
8
ON
1 2 3 4 5
1 2 3 4 5 6 78
6
7
8
ADDRESS C ODE
TrueAlarm sensor with relay base
I
Class B System
power, 24 VDC
nominal
IDNet Addressable Isolator
4090-9116 (see note 3)
Wiring Notes:
1. This is a one-line drawing showing power wiring and IDNet
communications only . Class A power requires using two 4090-9117
Power Isolators located close-nippled at the panel with Class A
operation performed by panel control of the Isolators.
2. Operation of the 4090-9117 Addressable IDNet Power Isolator
requires connection to a 4100ES, 4100U or 4010ES IDNet
Communications
.
Channel
3. IDNet isolators are shown for typical reference but are not
required. For Class A IDNet SLCs, locate isolators as first and
last device on the SLC for service convenience.
Simplex 4100ES Control Panel
(shown for reference)
3
S4090-0006-6
Mounting Information
Status indicating LED
4" (102 mm) square box, 2-1/8"
(54 mm) minimum depth, RACO 232
or equal (supplied by others)
4090-9117 Addressable
Power Isolator
Double gang blank cover plate and mounting screws, for
use when LED is not required to be externally viewed
(supplied by others)
Mounting Reference, Double Gang Blank Cover Plate
Light pipe for LED viewing
4-5/16"
(109 mm)
4-9/16"
(116 mm)
4-9/16" (116 mm)
4-5/16" (109 mm)
4090-9801, Trim plate for
semi-flush mounted box
4090-9802, Trim plate for
surface mounted box
Optional Trim Plates for Visible LED
Tyco is a registered trademark of Tyco International Services GmbH and is used under license. Simplex, the Simplex logo, TrueAlarm, and IDNet are trademarks of Tyco
International Ltd. and its affiliates and are used under license.
SimplexGrinnell LP Westminster • Westminster, MA • 01441-0001 • USA
www.simplexgrinnell.com
S4090-0006-6
© 2011 Tyco. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.