Product Information
PEAD-RP100EA2
Power Inverter Heat Pump
R410A Ceiling Concealed Ducted System
Advanced inverter technology makes the Mr Slim Power Inverter the number one
choice for improving comfort. They provide energy savings of up to 70% annually
when compared to a previous non-inverter model. Operating noise has also been
reduced thanks to improvements in fan design, while existing pipe work is reusable
for easier maintenance and installation.
Pictures not to scale
Product Details
Dimensions
PEAD-RP100EA2 Indoor Unit
Capacity (kW):
PEAD-RP100EA2
Heating (Nominal) (Low - High)
11.20 (4.50 - 14.00)
Cooling (Nominal) (Low - High)
10.00 (4.90 - 11.40)
Heating (UK) (Low - High)
9.50 (3.85 - 11.90)
Cooling (UK) (Low - High)
9.00 (4.40 - 10.25)
SHF R410A (Nominal)
0.86
COP / EER (Nominal)
3.51 / 3.27
Energy Label Heating / Cooling
B/A
Width - mm
1415
Depth - mm
740
Height - mm
325
Weight - kg
65
Airflow (m3/min) - Lo-Hi
33.5-42
External Static Pressure Pa - Lo-Hi
70-130
Noise (dBA) - Lo-Hi
Pipe Size Gas mm (in)
Pipe Size Liquid mm (in)
Electrical Supply
Phase
Fuse Rating (BS88) - HRC (A)
Interconnecting Cable No. Cores
Remote Controller Ref
44-50
15.88 (5/8)
9.52 (3/8)
Fed by Outdoor Unit
Single
6
4
PAR-21MAA
PUHZ-RP100VHA2
PUHZ-RP100VHA2 Outdoor Unit
Width - mm
950
Depth - mm
330 + 30
Height - mm
1350
Weight - kg
Noise (dBA) (Heating / Cooling)
Electrical Supply
Phase
Fuse Rating (BS88) - HRC (A)
121
51 / 49
220-240v, 50Hz
Single
32
System Power Input (kW) - Heating (Nominal)
3.19
System Power Input (kW) - Cooling (Nominal)
3.06
System Power Input (kW) - Heating (UK)
2.84
System Power Input (kW) - Cooling (UK)
2.6
Starting Current (A)
System Running Current (A) - Heating /
Cooling
Mains Cable No. Cores
5
15.01 / 15.15
3
Max Pipe Length (m)
75
Max Height Difference (m)
30
Charge (kg) - 30m
5
Telephone: 01707 282880
Email: air.conditioning@meuk.mee.com Website: http://www.mitsubishielectric.co.uk/aircon
Tel:
Fax:
Mitsubishi Electric reserves the right to make any variation in technical specification to the
equipment described, or to withdraw or replace products without prior notification or public
announcement.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising