Pipe Collars - 2 Hour & 4 Hour Fire Rated

Pipe Collars - 2 Hour & 4 Hour Fire Rated
QUICK VIEW
Pipe Collars - 2 Hour & 4 Hour Fire Rated
Application:
Fire Resistance Period:
Insulation/Integrity:
Test Standard:
Page No:
Service Penetrations - Plastic SWD Systems
120 minutes and 240 minutes
Insulation and Integrity
BS476 Part 20: 1987
1 of 2
Product Data Sheet
Pyroplex® pipe collars have been specifically designed to
re-instate the fire resistance of a wall or floor which has
been penetrated by services such as plastic flammable
pipes used in soil, waste and drainage services.
Pyroplex® pipe collars will seal closed flammable pipes
from 25mm to 400mm diameter and can be face fixed or
set-in to a wall or ceiling structure. They are suitable for
use on concrete, masonry and plasterboard partitions.
Pyroplex® pipe collars are available in two fire ratings;
2 hour and 4 hour. Each version features a tab closing
device which ensures the pipe collars are quick and easy
to fix in place.
Pyroplex® pipe collars are tested to BS476 Part 20:1987
and many other International Standards.
Typical Installation - Wall Application
1
2
3
4
5
Field of Application
Product Range
Pyroplex® pipe collars have been specifically designed to
prevent the passage of fire and hot gases through:
2 Hour FR Pipe Collar with Zintec Mild Steel Galvanised Casing
Part Number
Pipe Diameter
Collar Depth
No. of Fixing Lugs
• Concrete, masonry and plasterboard partitions.
PPC55-2
55
60
3
• Concrete floor constructions.
PPC82-2
82
60
3
• Soil, waste and drainage ‘above ground’ applications.
PPC110-2
110
60
4
PPC160-2
160
60
6
Product Features
• Collars have achieved a fire rating of either 2 hour or 4 hour.
4 Hour FR Pipe Collar with Stainless Steel Casing
Part Number
Pipe Diameter
Collar Depth
No. of Fixing Lugs
• 2 hour collar has a galvanised steel outer casing.
PPC25-4
25
60
2
• 4 hour collar has a stainless steel outer casing.
PPC32-4
32
60
2
• Tab closing device means collars are easy to fix in place around
pipe and rotate or slide into position.
PPC40-4
40
60
2
PPC48-4
48
60
2
• Intumescent material is totally unaffected by water, is robust,
‘non-flaking’ and difficult to tear.
PPC55-4
55
60
3
PPC68-4
68
60
3
PPC82-4
82
60
3
PPC110-4
110
60
4
PPC125-4
125
60
4
PPC135-4
135
60
4
PPC160-4
160
60
6
PPC200-4
200
190
7
PPC225-4
225
190
7
PPC250-4
250
190
8
PPC275-4
275
190
9
PPC315-4
315
190
11
PPC350-4
350
190
12
PPC400-4
400
190
14
Product Testing
Pyroplex® have carried out numerous independent fire
resistance tests to confirm the suitability of the product and to
demonstrate product compliance by utilising BS476: Part 20:1987
and other international standards.
The reports have been consolidated in Assessment Report No.
FEA/F98105 and this is available on request from Pyroplex®
Limited.
All measurements are shown in millimetres (mm).
Pyroplex Limited, The Furlong, Droitwich, Worcestershire WR9 9BG, UK
Tel: +44 (0)1905 795432 Fax: +44(0)1905 791878
Email: info@pyroplex.com Web: www.pyroplex.com
QUICK VIEW
Application:
Fire Resistance Period:
Insulation/Integrity:
Test Standard:
Page No:
Service Penetrations - Plastic SWD Systems
120 minutes and 240 minutes
Insulation and Integrity
BS476 Part 20: 1987
2 of 2
Pipe Collars - 2 Hour & 4 Hour Fire Rated
Product Data Sheet
Installation Instructions
Health and Safety Information
Wall Applications
Floor Applications
For detailed information on this product please refer to the
relevant Material Safety Data Sheet which is available on
request or downloadable at www.pyroplex.com.
Transportation & Storage
Transport Hazards:
No regulations apply for the transport of this material. Not
classified as hazardous for road, rail, sea or air transport.
Face fixed
Face fixed
Face fixed
Storage:
Store dry and in a cool place (not above 35°C) and ensure
sufficient ventilation.
Product Guarantee
Cast-in
Cast-in
Cast-in
Check the likely direction of the fire. In some cases, two collars
may need to be fitted to prevent the fire spread.
1. Ensure that the substrate around the penetration is flat and
free from any obstructions, which may prevent the correct
installation of the collar. Beware of any obstructions, which
may interfere with the fixing tags. If the substrate is uneven it
may be necessary to first render the substrate with mortar or
some form of rendering material.
2. Any residual gaps, which are smaller than 3mm around the
service penetration will need to be filled, this can done by
using Pyroplex® Intumescent Acrylic, ensure that the gap is
completely back filled. For any gaps which are greater than
3mm the penetration should be back filled using mortar or
some other form of rendering material.
3. Remove the Pyroplex® pipe collar from its packaging, and
remove the retaining pin.
4. Using both hands open the collar by sliding the tab through
the slot, this will release the collar ‘open’ to allow installation.
5. Using both hands fit the collar around the pipe by sliding the
tag through the slot. Once through, ensure that the collar is
firmly fitted around the pipe and that the two sections of the
collar meet.
6. The tag can now be folded back through 180° and once
completed the collar can be moved towards the substrate.
Correct fitting can be achieved by rotating and pushing the
collar, in some instances the collar can be slid into place.
7. Once the collar has been presented to the substrate it can be
securely fitted. Using a drill, fitted with a masonry bit, place
the drill in the circular-fixing hole of the fixing tag and
commence drilling to the required depth. This usually is
65mm deep into the substrate and remove any debris from
the hole. Using M8 x 65mm sleeve anchors (not plastic), place
the anchor in the hole and using a hammer lightly tap the
anchor into position. Tighten the sleeve anchor firmly to fix
into position. Repeat this procedure, until all fixings tags have
been fitted.
8. When the collar has been securely fitted into place any
residual gaps between the collar and the substrate can be
filled using Pyroplex® Intumescent Acrylic.
9. Ensure that any obstructions, which may have been
temporarily moved, are refitted into place.
Pyroplex Limited, The Furlong, Droitwich, Worcestershire WR9 9BG, UK
Tel: +44 (0)1905 795432 Fax: +44(0)1905 791878
Email: info@pyroplex.com Web: www.pyroplex.com
Providing the product is installed in accordance with the
requirements of the guidance document the product is
guaranteed for a period of 10 years.
Quality Approval
Pyroplex® Limited has a Quality Management System that
meets the requirements of BS EN ISO 9001:2000, and is
independently verified by BSI Quality Assurance under
Certificate FM10371.
Related Product
We recommend the use of Pyroplex® Intumescent Acrylic for
residual gaps, face finishing and air tightness.
Technical Support and Guidance
Should you require any further information regarding this
product please contact Pyroplex® Limited or visit our website,
www.pyroplex.com.
Additional Information
The information contained herein is based upon the present
state of our knowledge. Recipients of our Pyroplex® products
must take responsibility for observing existing laws and
regulations.
Due to our policy of continuous improvement Pyroplex®
Limited reserves the right to amend specifications without prior
notice.
Pyroplex® Jargon Buster
At Pyroplex we understand that some of the terms used in
our literature may need explaining in more detail.
What are BS references, in particular BS476?
BSI British Standards is a component of the UK’s National
Standards Body (NSB). Standards help to make life simpler
and to increase the reliability and the effectiveness of many
goods and services we use. Although the standards are
designed as voluntary, laws and regulations may refer to
certain standards and make compliance with them
compulsory.
One area of fire safety is BS476 which is concerned with fire
testing on building materials and structures.
When the tests are undertaken the results of the tests are
expressed as a number of minutes for each of the following
characteristics; Stability, Integrity and Insulation.
QUICK VIEW
Pipe Collars - 2 & 4 Hour Fire Rated
Issue Date:
1st October 2007
Application:
Fire Resistance Period:
Insulation/Integrity:
Test Standard:
Service Penetrations - Plastic SWD Systems
120 minutes and 240 minutes
Insulation and Integrity
BS476 Part 20: 1987
Technical Data Sheet
Issue No.
No. of Pages
1
2
Revision No. 1
1 of 2
Page No.
1. Field of Application
6. Specifications of Metal Work
Pyroplex® pipe collars have been specifically designed to reinstate the fire resistance of a wall or floor which has been
penetrated by services such as plastic flammable pipes used in
soil, waste and drainage services.
2 Hour Pipe Collar:
Zintec Mild Steel, compliant with BS EN10152:2003.
Pyroplex® pipe collars seal closed flammable pipes from 25mm
to 400mm diameter and can be face fixed or set-in to a wall or
ceiling structure. They are suitable for use on concrete, masonry
and plasterboard partitions.
4 Hour Pipe Collar:
Stainless Steel Type 430 BA, compliant with BS EN10152:2003.
7. Installation Guidance Notes
Equipment Required:
Pipe collars are available in two fire ratings; 4 hours and 2 hours.
Each version features a tab closing device which ensure the
pipe collars are quick and easy to fix in place.
Pyroplex® pipe collars
Pipe collars are tested to BS476 Part 20:1987 and many other
International Standards.
Mastic gun
Sleeve anchors, M8 x 65mm (not plastic based)
Pyroplex® Intumescent Acrylic
Drill, with masonry facility
Personal protective equipment - Gloves, eye protection and face mask
2. Service Penetrations
Suitable for use on plastic flammable pipes. Typical Installations
include soil, waste and other service applications. Piping
materials include UPVC, CPVC (unplasticised and chlorinated),
Polyethylene (PP) Polypropylene. Not suitable for use on
metallic services.
3. Structural Constructions
Pyroplex® pipe collars can be used in wall and floors, with a
solid construction of a density not less than 650kg/m3. Can be
used in stud wall partitions with a fire resistance up to 2 hours.
Collars can be installed directly, face fixed or semi-cast into the
penetration.
4. Pyroplex Test Reports
Pyroplex® have carried out numerous independent fire
resistance tests to confirm the suitability of the product and to
demonstrate product compliance by utilising BS476: Part 22,
EN1366-4 and other international standards.
Test Reports
Warrington Fire Research Warres No. 101758
Warrington Fire Research Warres No. 102754
Chiltern International Fire Report No. IF98040
Chiltern International Fire Report No. IF98041
SP, Sweden Test Report No. 98R1 3166B
Afiti-Licof Test Report No. 3971/99
Chiltern International Fire Report No. IF00028
Chiltern International Assessment Report FEA/F98105
The reports have been consolidated in Assessment Report No.
FEA/F98105 and this is available on request from Pyroplex®.
5. Intumescent Material
The Intumescent material is based upon an expandable
graphite, which when heated expands multi-directionally
generating high pressure to fill the cavity of the plastic pipe
which has been consumed in the fire. The expanded graphite
exhibits sufficient char to restrict the passage of fire through the
penetration for 2 hours and 4 hour fire resistance.
Pyroplex® Limited, The Furlong, Droitwich, Worcestershire WR9 9BG, UK
Tel: +44 (0)1905 795432 Fax: +44(0)1905 791878
Email: info@pyroplex.com Web: www.pyroplex.com
Check the likely direction of the fire, in some cases, two collars
may need to be fitted to prevent the fire spread within a
compartment. This information can be obtained from the
Architect or specifier or by reference to the Building Control
Officer or local Building regulations.
1. Ensure that the substrate around the penetration is flat and
free from any obstructions, which may prevent the correct
installation of the collar. Beware of any obstructions, which
may interfere with the fixing tags. If the substrate is uneven it
may be necessary to first render the substrate with mortar or
some form of rendering material.
2. Any residual gaps, which are smaller than 3mm around the
service penetration will need to be filled, this can done by
using Pyroplex® Intumescent Acrylic, ensure that the gap is
completely back filled. For any gaps which are greater than
3mm the penetration should be back filled using mortar or
some other form of rendering material.
3. Remove the Pyroplex® pipe collar from its packaging, and
remove the retaining pin.
4. Using both hands open the collar by sliding the tab through
the slot, this will release the collar ‘open’ to allow installation.
5. Using both hands fit the collar around the pipe by sliding the
tag through the slot. Once through, ensure that the collar is
firmly fitted around the pipe and that the two sections of the
collar meet.
6. The tag can now be folded back through 180° and once
completed the collar can be moved towards the substrate.
Correct fitting can be achieved by rotating and pushing the
collar, in some instances the collar can be slid into place.
7. Once the collar has been presented to the substrate it can be
securely fitted. Using a drill, fitted with a masonry bit, place
the drill in the circular-fixing hole of the fixing tag and
commence drilling to the required depth. This usually is
65mm deep into the substrate and remove any debris from
the hole. Using M8 x 65mm sleeve anchors (not plastic), place
the anchor in the hole and using a hammer lightly tap the
anchor into position. Tighten the sleeve anchor firmly to fix
into position. Repeat this procedure, until all fixings tags
have been fitted.
QUICK VIEW
Pipe Collars - 2 & 4 Hour Fire Rated
Issue Date:
1st October 2007
7. Installation Guidance Notes (cont’d.)
8. When the collar has been securely fitted into place any
residual gaps between the collar and the substrate can be
filled using Pyroplex® Intumescent Mastic.
9. Ensure that any obstructions, which may have been
temporarily moved, are refitted into place.
8. Fixing Details
All fixing tags are elongated for aid alignment and
positioning. Pyroplex® collars also can be supplied with loose
fixing tags for use in restricted areas, or limited fixings can be
installed.
Dependent upon the density and type of wall or floor, will
determine the types of fixings that can be used. Pyroplex®
recommend M8 x 65mm sleeve anchors or 70mm Tapcon
anchors, all tags provided shall be fixed and secured firmly
into position.
Do not rely upon anchors that rely upon plastic fixings or
chemical ‘cement’ bonding.
9. Supporting Constructions
Any supporting constructions shall be replaced after installation
of the collar. Once the collar has been installed no other
supporting system is necessary unless otherwise specified.
10. Maintenance and Installation Records
Since the product is not subject to routine and replacement
programmes, Pyroplex® recommend that all firestopping
materials are checked on a regular basis to ensure that the
product remains integral. Replace and fit any damaged
components to reinstate the fire resistance of the wall or floor.
11. Product Guarantee
Providing the product is installed in accordance with the
requirements of the guidance document the product is
guaranteed for a period of 10 years.
12. Quality Approval
Pyroplex® Limited has a Quality Management System that
meets the requirements of BS EN ISO 9001:2000, and is
independently verified by BSI Quality Assurance under
Certificate Number FM10371. Copies of this approval are
available on request.
13. Technical Support and Guidance
Should you require any further information regarding this
product please contact Pyroplex® or visit our website,
www.pyroplex.com.
Pyroplex® Limited, The Furlong, Droitwich, Worcestershire WR9 9BG, UK
Tel: +44 (0)1905 795432 Fax: +44(0)1905 791878
Email: info@pyroplex.com Web: www.pyroplex.com
Application:
Fire Resistance Period:
Insulation/Integrity:
Test Standard:
Service Penetrations - Plastic SWD Systems
120 minutes and 240 minutes
Insulation and Integrity
BS476 Part 20: 1987
Technical Data Sheet
Issue No.
No. of Pages
1
2
Revision No. 1
2 of 2
Page No.
QUICK VIEW
Pipe Collars - 2 & 4 Hour Fire Rated
Issue Date:
1st October 2007
In accordance with 91/155/EEC directive
1. Field of Application
For sealing flammable pipes - 2 and 4 hour fire resistance
2. Composition/Information on Ingredients
Application:
Fire Resistance Period:
Insulation/Integrity:
Test Standard:
Service Penetrations - Plastic SWD Systems
120 minutes and 240 minutes
Insulation and Integrity
BS476 Part 20: 1987
Material Safety Data Sheet
Issue No.
No. of Pages
Revision No. 1
1 of 1
Page No.
1
1
9. Physical and Chemical Properties
Form:
Solid
Colour:
Black
Odour:
Acidic
Explosion limits:
None
Density:
1.3 kg/m3
Chemical Nature: Thermoplastic element composition
containing intercalated graphite in a synthetic compound with
the addition of fillers and process oils. Presented in a ‘steel’
outercasing to form the final product.
10. Stability and Reactivity
3. Possible Hazards
Conditions to be avoided: Thermal decomposition above 300°C
Principle Hazards: Not subject to decree of hazardous
substances.
Hazardous Decomposition Products: Thermal decomposition,
fumes contain hydrogen chloride. However, the activated
graphite is effective at removing aromatic particles from smoke
emissions.
Critical Hazard to Man and Environment: Not applicable
4. First Aid Measures
On Skin Contact: Wash thoroughly with soap and water
On Contact with Eyes: Wash for at least 15 minutes under
running water with eyelids held open, consult an eye specialist.
On Ingestion: Rinse mouth immediately, do not induce
vomiting, and seek immediate medical attention.
If inhaled: Not applicable in solid state.
5. Fire Fighting Measures
Pyroplex® intumescent material is self-extinguishing.
Suitable Extinguishing Media: Water, foam, powders and dry
extinguishing media.
Special Protective Equipment: Suitable forms of PPE (personal
protective equipment.)
In the event of fire, contact the appropriate emergency services
for assistance.
6. Accidental Release Measures
Personal Precaution: In the event of fire ensure sufficient
ventilation.
Environmental Precaution: Do not discharge the product into
drains or water courses, ensure materials are disposed of in
accordance with Local Authority regulations and/or
Government legislation.
Methods for Cleaning Up: No special measures necessary.
7. Handling and Storage
Handling: No special requirements. Keep away from food and
drink.
Storage: Store dry and in a cool place (not above 35°C). Keep
out of reach of children. Take care for sufficient ventilation.
8. Exposure Controls and Personal Protection
Respiratory protection: None normally required, when supplied
in solid form. Drilling create a dust hazard.
Hand protection: Appropriate protective gloves.
Eye protection: Appropriate protective goggles.
Skin protection: None normally required.
Pyroplex Limited, The Furlong, Droitwich, Worcestershire WR9 9BG, UK
Tel: +44 (0)1905 795432 Fax: +44(0)1905 791878
Email: info@pyroplex.com Web: www.pyroplex.com
11. Toxiological Information
Acute Toxicity: Not applicable in solid state.
12. Ecological Information
General Advice: Observe the legal provisions regarding the
prevention of ground water and surface water as well as air. Do
not discharge product into natural waters without pretreatment.
13. Disposal Considerations
Product Packaging: Refer to local authority regulations
Recommendations: Disposal of by special means in accordance
with local regulations e.g. suitable deposition
Contaminated Packaging Recommendation: Not applicable
14. Transport Information
Transport Hazards: No regulations apply for the transport of this
material. Not classified as hazardous for road, rail, sea or air
transport.
15. Regulatory Information
Labelling according to EEC directives:
National legislation/ regulations
Not applicable
VbF Classifications
None
Water hazard class
Not applicable
16. Additional Information
The information contained herein is based upon the present
state of our knowledge. Recipients of our Pyroplex® products
must take responsibility for observing existing laws and
regulations.
Due to our policy of continuous improvement Pyroplex Limited
reserves the right to amend specifications without prior notice.