S4602-0001-15
System Accessories, LED Annunciators
UL, ULC, CSFM Listed; FM Approved;
MEA (NYC) Acceptance*
4602 Series SCU (Status Command Units)
and RCU (Remote Command Units)
Features
Remote LED status annunciation with available
remote panel input switch control:
 Compatible with Simplex® 4005, 4007ES, 4010ES,
4100ES, and 4100U series fire alarm control panels
 Also compatible with Simplex legacy panel model series
4002, 4020, 4100, 4120, and Universal Transponders (UT)
 Supervised RUI (remote unit interface) communications
require a single, twisted, shielded wire pair to the fire
alarm control panel (power is supplied via a second wire
pair)
 Red zone status LEDs are provided with preprinted zone
numbers or can be individually labeled as desired
 LEDs are pluggable for color changing or replacement;
on-board internal pushbutton switch provides LED test
 Surface or flush-mount on standard electrical boxes
 UL listed to Standard 864
4602-9101 Status Command Unit (SCU)
4602-9102 Remote Command Unit (RCU)
Available as single units or can be ordered
modular for up to 4 units in a common cabinet:
 4602-9101, Status Command Unit (SCU) provides
16 red LED zone status indicators
 4602-9102, Remote Command Unit (RCU) provides
8 red LED zone status indicators; local power (green)
and trouble (yellow) LEDs; local tone-alert; and
switches for Trouble Silence, Alarm Silence, System
Reset, and Manual Evacuation (EVAC)
 4602-8001 Series panels provide selection of a remote
cabinet that can mount one RCU and up to three SCUs;
options include beige or stainless steel flush mount doors
 Graphic I/O Board Assemblies are available separately
for use with listed custom graphic annunciator panels;
available stand-alone (4602-9150), or plate mounted
(4602-7101); selectable as SCU or RCU; terminal blocks
are provided for LED, switch, and LED test feature
connections
Description
Status Command Units (SCU) provide 16 red zone
status LEDs. Multiples may be mounted together for
additional zone coverage.
Remote Command Units (RCU) provide 8 red zone
status LEDs, and control switches duplicating the switch
functions of the host Fire Alarm Control Panel. A
keyswitch enables the control switches. A green LED
indicates power is present and a yellow LED indicates
trouble.
Zone identification (i.e., Zone 1, Zone 2) is provided
on “slip-in” labels. Detailed local zone information may
be typed on the blank reverse side (i.e., East Wing, First
Floor, etc.) of the label. Pushbutton LED test switches are
located internally for “lamp test” feature. Terminations
are via convenient terminal block connections.
P
W
R
T
B
L
ZONE 1
ZONE 5
ZONE 2
ZONE 6
ZONE 3
ZONE 7
ZONE 4
ZONE 8
ZONE 1
ZONE 5
ZONE 9
ZONE 2
ZONE 6
ZONE 10
ZONE 14
ZONE 3
ZONE 7
ZONE 11
ZONE 15
ZONE 4
ZONE 8
ZONE 12
ZONE 16
ALAR
SILENC
M
E
TROUBL
SILENC
E
E
SYSTE
RESE
M
T
ENABL
E
MANUA
EVA
L
C
ZONE 13
CAUTION
DISCONNECT
ZONE 1
ZONE 5
ZONE 9
ZONE 13
ZONE 2
ZONE 6
ZONE 10
ZONE 14
ZONE 3
ZONE 7
ZONE 11
ZONE 15
ZONE 4
ZONE 8
ZONE 12
ZONE 16
ZONE 1
ZONE 5
ZONE 9
ZONE 13
ZONE 2
ZONE 6
ZONE 10
ZONE 14
ZONE 3
ZONE 7
ZONE 11
ZONE 15
ZONE 4
ZONE 8
ZONE 12
ZONE 16
POWER
BEFORE
SERVICING
4602
4602-8001 Annunciator Package with RCU on top and
three SCUs (shown as standard surface mount trim)
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7120-0026:0156 for allowable values and/or conditions concerning material presented in
this document. It is subject to re-examination, revision, and possible cancellation. Accepted
for use – City of New York Department of Buildings – MEA35-93E. Additional listings may
be applicable; contact your local Simplex product supplier for the latest status. Listings and
approvals under Simplex Time Recorder Co. are the property of Tyco Fire Protection
Products.
S4602-0001-15 11/2014
Product Selection
Individual LED/Switch Annunciators; Six-Gang box mounting (refer to mounting reference on page 3)
Description
Mounting Reference
4602-9101
Model
Status Command Unit (SCU) with beige trim plate
4602-9102
Remote Command Unit (RCU) with beige trim plate
4602-9111
Brushed stainless steel trim plate option for either 4602-9101 or
4602-9102, includes both slotted and tamper resistant screws
Trim dimensions = 11 13⁄16” W x
4 ½” H (114 mm x 300 mm)
Mounts on 6-gang box, 1 ½”
minimum depth (38 mm)
2975-9206
Surface mount box option for use with 4602-9101 or 4602-9102; painted steel, ivory finish;
dimensions = 11 31⁄32” W x 4 ⅝” H x 2 ¾” D (304 mm x 117 mm x 70 mm)
Individual Graphic I/O Module; for use with listed custom graphic annunciator panels
Model
4602-9150
Description
Graphic I/O RCU/SCU Board Assembly; operation is switch selectable as either RCU or SCU;
dimensions = 5 ⅛” x 7” (130 mm x 178 mm); see illustration reference below
Plate Mounted Graphic I/O Modules; for use with listed custom graphic annunciator panels
Model
Description
4602-8103
Graphic I/O Mounting Plate for up to four (4), 4602-7101 Graphic I/O RCU/SCU modules;
dimensions = 16 ⅛” W x 11 ⅛” H (409 mm x 282 mm)
4602-8902
Select when adding 4602-7101 modules in the field to an existing Graphic I/O annunciator mounting plate
4602-7101
Graphic I/O RCU/SCU module for mounting on 4602-8103 plate (up to four); operation is switch selectable as
either RCU or SCU; includes power and control wiring harnesses
Modular LED/Switch Annunciators; Cabinet Mounted (see mounting reference on page 4 for dimensions)
Model
Description
4602-8001
Basic annunciator panel; includes 2975-9197 beige box and beige surface mount door; has space for up to 4
RCU/SCU modules, ordered separately as listed below
4602-8901
Select when adding features in the field to an existing 4602 Modular LED/Switch annunciator cabinet
4602-7001
Remote Command Unit (RCU) module; typically one used per 4602-8001
4602-6001
Status Command Unit (SCU) module; up to 4 may be selected
4602-5001
Select when no 4602-7001 or 4602-6001 modules are to be selected; blank filler plates will be provided
4602-2201
Beige
4602-2202
Stainless Steel
Up to four modules may be
selected for one 4602-8001
Flush mount door and trim option; overall dimensions = 16” W x 20” H (406 mm x 508 mm)
SCU/RCU Options
Model
Description
4602-9110
Eight (8) pluggable Yellow LEDs; for field replacement of standard red LEDs
4602-9112
Zone labels numbered 1 through 64
4602-9150 Graphic I/O RCU/SCU Board Only Installation Reference
1.
Board size is 5 ⅛” x 7” (130 mm x 178 mm).
2.
Orientation may be vertical or horizontal.
3.
Mount within the listed custom graphic annunciator
enclosure or within a listed steel box close-nippled
to the annunciator.
4.
Required mounting hardware (not supplied):
6, 6-32 screws, ½” (12.7 mm) minimum length; 6
standoffs ⅜” (9.5 mm) minimum length.
5.
Refer to illustration for details.
6.
NOTE: For multiple custom annunciator Graphic
I/O applications, use model 4602-7101 for
mounting up to four on plate 4602-8103.
2
S4602-0001-15 11/2014
Specifications
Voltage
18.9 to 32 VDC from fire alarm control panel
4602-9101 SCU Supervisory = 36 mA; Alarm = 55 mA
4602-9102 RCU Supervisory = 40 mA; Alarm = 80 mA
Current
4602-7107 or Supervisory = 40 mA; Alarm = 65 mA minimum, up to 2.5 A maximum;
4602-9150
Graphic I/O Module LED/lamp driver outputs are rated 150 mA maximum each
Communications
RUI (Remote Unit Interface) external annunciator communications line SLC (signaling line circuit)
4100ES/4100U Capacity, Per
RUI Output
Up to 31 remote annunciators/MINIPLEX transponders per channel including the 4603-9101 LCD
Annunciator, the SCU, and the RCU; refer to data sheet S4100-0031 for additional 4100ES
information
4010ES Capacity
Up to 20 internal or external card addresses including 4603-9101 LCD Annunciators, the SCU, and
the RCU; refer to data sheets S4010-0004 for additional 4010ES information (refer to data sheet
S4100-0006 for International 4010ES applications)
4007ES Capacity
Up to 10 total RUI annunciators
4005 RUI Capacity
Up to 16 total SCUs and/or RCUs; refer to data sheet S4005-0001 for additional 4005 information
Data Single twisted, shielded pair, 18 AWG (0.82 mm2)
Wiring
Requirements
Power 18 to 12 AWG (0.82 mm2 to 3.31 mm2)
Earth
Wiring connections are via terminal blocks
A dedicated earth ground connection to the electrical box is required for proper ESD and EMI
protection; wire in accordance with NFPA 70 (National Electrical Code) Article 250
Operating Temperature
32° F to 120° F (0° C to 49° C)
Operating Humidity
Up to 93% RH, non-condensing @ 90° F (32° C) maximum
Additional Reference
All
Field Wiring Diagram 841-780
4602-9101 SCU and
4602-9102 RCU
Installation Instructions 574-015
4602-7107 or 4602-9150
Graphic I/O Module
Installation Instructions 574-024
RCU/SCU Mounting Reference
Flush Mount Ganged or
Masonry Boxes:
Use 6-gang box, 2-1/2"
(64 mm) min. depth
Surface Mount Box:
Simplex model 2975-9206
(ordered separately)
ZONE 1
ZONE 5
ZONE 2
ZONE 6
ZONE 3
ZONE 7
ZONE 4
ZONE 8
P
W
R
T
B
L
TROUBLE
SILENCE
Trim plate
SYSTEM
RESET
ALARM
SILENCE
ENABLE
MANUAL
EVAC
SCU or RCU
Assembly
3
S4602-0001-15 11/2014
4602-8001 Mounting Reference
Box width 14" (356 mm)
(Top and side views are shown
with surface mount door)
8 knockouts total: 2 on
top, bottom and back of
box, and 1 on each side
Box depth = 3-1/2" (89 mm)
8-1/2" (216 mm)
Surface mount
door thickness
= 1" (25.4 mm)
Box height
18" (457 mm)
15-3/4"
(400 mm)
Flush trim dimensions = 16" W x 20" H (406 mm x 508 mm)
Flush door dimensions = 13-1/2" W x 17-5/8" (343 mm x 448 mm)
Surface door dimensions
= 14-7/16" W" x 18-5/16" H
(367 mm x 465 mm)
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA
www.simplex-fire.com
S4602-0001-15 11/2014
© 2014 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.