22.5 mm - 2 Relays 8A TK2R1 Part number 88865265
04/12/2014
www.crouzet.com
22.5 mm - 2 Relays 8A TK2R1 Part number 88865265
Relay output
Multi-function or mono-function
Multi-range
Multi-voltage
Screw terminals
LED status indicator
Part numbers
88 865 265
Type
Functions
Timing
Output
Nominal rating
Connections
Supply voltage
TK2R1
K
0,6s→160 s
2 change over relays
8A
Screw terminals
24 V DC / 24 →240 V AC
Specifications
Timing
Timing ranges (7 ranges)
Repetition accuracy with constant parameters
Drift Temperature
Drift Voltage
Display accuracy according to IEC/EN 61812-1
Immunity from micro power cuts : typical
1 s - 10 s - 1 min - 10 min - 1 h - 10 h - 100 h
± 0.5 % (IEC/EN 61812-1)
± 0,05 % / °C
± 0,2 % / V
± 10 % / 25 °C
< 10 ms
Supply
Multi-voltage power supply
Frequency (Hz)
Operating factor
Depending on version
50 / 60
100 %
Output specification
Rated power
Maximum breaking current
Minimum breaking current
Voltage breaking capacity
2000 VA/80 W
8 AAC 250 VAC resistive
8 ADC 30 VDC resistive
10 mA / 5 VDC
250 VAC / 8 AAC resistive
250 VDC / 0,3 A resistive
Electrical life (operations)
105
8 A 250 VAC resistive
Mechanical life (operations)
10 x 106
2,5 kV / 1 min / 1 mA / 50 Hz
5 kV
wave 1.2 / 50 μs
Breakdown voltage acc. to IEC/EN 61812-1
Impulse voltage acc. to IEC/EN 60664-1, IEC/EN 61812-1
General characteristics
Conformity to standards
IEC/EN 61812-1
IEC/EN 61000-6-1
IEC/EN 61000-6-2
IEC/EN 61000-6-3
IEC/EN 61000-6-4
CE, UL, cUL, CSA, GL
-20 →+60
-30 →+60
Certifications
Temperature limits use (°C)
Temperature limits stored (°C)
Installation category
Voltage surge category III
(acc. to IEC/EN 60664-1)
Creepage distance and clearance acc. to IEC/EN 60664-1 4 kV / 3 mm
Protection (IEC/EN 60529)
IP20
IP40
Degree of protection acc. to IEC/EN 60529 Front face
IP50
Vibration resistance
20 m/s2 10 Hz →150 Hz
acc. to IEC/EN 60068-2-6
Relative humidity no condensation acc. to IEC/EN 6006893 % non-condensing
2-30
Electromagnetic compatibility - Immunity to electrostatic
Level III (Air 8 kV / Contact 6 kV)
discharges acc to IEC/EN 61000-4-2
Immunity to radiated, radio-frequency, electromagnetic
Level I
field acc. IEC/EN 61000-4-3
(1 V/m : 2,0 G Hz →2,7 G Hz) Level II
(3 V/m : 1,4 G Hz →2,0 G Hz) Level III
(10 V/m : 80 M Hz →1 G Hz)
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
04/12/2014
Immunity to rapid transient bursts acc. to IEC/EN 61000-44
Immunity to shock waves on power supply acc. to IEC/EN
61000-4-5
Immunity to radio frequency in common mode acc. to
IEC/EN 61000-4-6
Immunity to voltage dips and breaks acc. to IEC/EN 610004-11
Mains-borne and radiated emissions acc. to EN 55022
(CISPR22), EN55011 (CISPR11)
Fixing : Symmetrical DIN rail
Terminal capacity Single-wire without ferrule
www.crouzet.com
Level III (direct 2 kV / Capacitive coupling clamp 1 kV)
Level III (2 kV / common mode 2 kV/residual current mode 1 kV)
Level III (10V rms : 0.15 M Hz to 80 M Hz)
0 % residual voltage, 1 cycle
70 % residual voltage, 25/30 cycles
Class B
35 mm
1 x 0,5 →3,3 mm2
(AWG 20 →AWG 12) 2 x 0,5 →2,5 mm2
(AWG 20 →AWG 14)
Terminal capacity Multi-wire with ferrule
1 x 0,5 →2,5 mm2
(AWG 20 →AWG 14) 2 x 0,5 →1,5 mm2
(AWG 20 →AWG 16)
Housing material
Self-extinguishing
Shock test IEC/EN 60068-2-27
15 g - 11 ms
Short interruption on power line acc to IEC/EN 61000-4-11 0 % residual voltage, 250/300 cycles
Timing
Minimum pulse duration typically
Minimum pulse duration typically (under load)
Maximum reset time by de-energisation typically
30 ms
100 ms
120 ms
Supply
Operating range
Max. absorbed power
85 →110 % Un
15 VA (400 VAC)
50 VA (240 VAC)
0,7 W (24 VDC)
1,2 VA (12 VAC)
0,5 W (12 VDC)
Output specification
2 changeover relays, AgNi (cadmium-free)
2 C/O
RQR1- RQR6 2 open contacts
General characteristics
Weight : casing 22,5 mm
Insulation resistance according to IEC/EN 60664-1
88 866 175 (RQR1) : 81 g
88 866 176 (RQR6) : 81 g
88 866 215 (RA2R1) : 87 g
88 866 300 (RU2R4) : 86 g
88 866 303 (RU2R3) : 90 g
88 866 305 (RU2R1) : 88 g
88 866 385 (RX2R1) : 88 g
> 500 MΩ (500 VDC)
Dimensions (mm)
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
04/12/2014
Curves
Function K- 2 relay outputs
Function K
Delay on de-energisation True delay OFF 2 relays
Connections
2 changeover relay outputs
Function
K
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
www.crouzet.com
Was this manual useful for you? yes no