Ordinys 3 fire protection application

Ordinys 3 fire protection application
fire protection
Ordinys® 3
➤ application
relay box for
smoke extraction fan
•P
ower control of a smoke extraction fan (insufflation
or extraction, all fans used in smoke extraction process).
• An Ordinys® only pilots one fan.
•O
rdinys® 3 is the interface between the TGBT and the smoke
extraction fan. It does the synthesis of defects that can take
place in satellites (proximity switch, pressostat)
of the smoke extraction installation.
➤ construction / composition
➤ advantages
• Detachable lid.
• Easy connection.
•E
asy control (24 and 48 Vcc, pulse or break with the same
Ordinys® 3).
• Simulation buttons.
•D
isplay and synthesis of defects on front and visible open
and close box.
• Calibers adapted to common fan intensities.
•P
roximity switch and pressostat assembled,
available as option.
➤ designation
Ordinys® 3 DS
CDAR
CIDAR
Type
1. P
lastic case (ABS) resistant to shocks, to water insertion,
IP 65 and to incandescent wire (650°), without halogen
(made respecting to nature).
1V400 I+P
1V230
2VBI
2VDA
Category
Supply
DS : Smoke extraction alone
CDAR : External smoke extraction comfort
CIDAR : Integrated smoke extraction comfort
Inter
+Pressostat
3A
3. Electronic card and display.
4. Removable lid by unscrewing the 4 angles.
Caliber
5. Proximity switch (assembled as an option)
6. Pressostat (under electronic card - assembled as an option).
7. C
omfort control accessory (circuit breaker or 2 speeds box
under the electronic card as the Ordinys® model).
➤ range
8. Simulation buttons.
• 3 versions of Ordinys® 3 :
- DS : Smoke extraction alone.
- CDAR : Comfort and no-return smoke extraction, external
comfort control accessory .
- CIDAR : Integrated comfort and smoke extraction, comfort and
control accessory (circuit breaker or box 2 speeds
integrated to the Ordinys® 3).
•C
alibers adapted to fan intensities and complies to the decision
of the 12 April 2002 of the CNMIS :
the nominal intensities of the Ordinys® 3 are equal to the
intensities AC3 of the contactors divided by 1.5.
(Example : nominal intensity motor 3A --> Ordinys® 3
with caliber 3A).
Available calibers : 3A, 8A, 12A, 18A, 25A, 43A, 100A.
Maxi 12 A in single-phase 230 V.
9. Protection Lexan.
10. Pressure balancer.
➤ packaging
•B
y individual box and anti-shock wedges with identification
marking.
➤ specifications
• T he relay box for smoke extraction fan will work with remote
control from the CMSI at 24 or 48 Vcc pulse or break.
ordinys® 3
•P
ossibility of piloting all types of motors in all versions :
- 1 single-phase speed 230 V.
- 1 three-phase speed 400 V.
- 2 independant winding speed three. 400 V.
- 2 speeds with Dahlander connection three-phase 400 V.
Guide created by France Air 2010 – All rights reserved.
2. Power contactors (under electronic cards).
• T he display of defects and the box status will be visible from
the front and inside of the box.
• The box will be certified NF.
• T he simulations of the functions can be done from the relay
box in the working period.
•A
lso foreseen the rearmament case, fireman control device,
the flow control as well as the proximity switch.
• Type Ordinys® 3, France Air brand.
www.france-air.com
779
fire protection
selection
➤ Selection principle
Fan
function
Only smoke
extraction
Smoke extraction
and comfort
Fan
number of speeds
1 speed
2 speeds
1 speed
LS and HS in
smoke extraction
Single
230 V
Three
400 V
Independant
winding
Three 400 V
2 speeds
Same speed
for comfort and
smoke extraction
Dalhander
coupling
Three 400 V
Single
230 V
Three
400 V
LS and HS
(comfort) and
smoke extraction
Independant
winding
Three 400 V
Dalhander
coupling
Three 400 V
The comfort
control accessory is
ordinys® 3
Outside
the relay box
Caliber choice
according to
the fan intensities
Caliber choice according to
the fan intensities
box
box
calibers
Inside
the relay box
Caliber choice
according to
min/max intensities
of the built-in comfort
accessory
Option : proximity switch and pressostat
family
supply
options
➤ Necessary equipment (to foresee outside) :
•R
earmament case with key (remote controlled with pulse).
• Differential pressostat or air flow controller with pallet.
Controls effective presence of an air flow required for smoke
extraction (can be assembled as option in the box Ordinys® 3).
780
•R
emote controlled case of fireman control device
(remote controlled with pulse current).
• Padlockable proximity switch (can be assembled as an option in
the box Ordinys® 3 for a maximum fitting of 2 m from the fan).
• Remote controlled security applying.
www.france-air.com
Guide created by France Air 2010. All rights reserved.
fire protection
technical description
➤ Reminders NF label
According to the norm NFS 61-932 relative to the installation rules of the Fire Security System, “the supply and the control of the smoke
extraction should be done with a relay box complying to the NF S 61-937 (card XIII of appendix A)”.
This is applicable to all types of fans, fire classified or not, insofar as it contributes to the smoke extraction (insufflation, extraction,
applying overpressure). According to the order of the 3 May 1999, the relay boxes have to be certified NF from the 01/01/2000.
Which means they must comply with the Specific Regulations NF RP 278. The quality system as well as the manufacturing process
is audited according to this RP.
IE :
• A relay box with fan contributing to smoke extraction.
• The nominal intensity of the relay box is equal to the characteristics of contactors AC3 divided by 1.5.
• The phase control is necessary. It checks the voltage presence as well as the phases inversion at the front of the box.
• In case of power cut, the box memorises the previous state, when the supply comes back, the box will display defect 6 “loss network
voltage” and will continue in its previous state that it will have memorised.
• The insulation control is integrated in the box.
➤ Compliance
• Label NF Relay box is n°1 holder.
➤ Compliance CE declaration
• The Ordinys® 3 complies to the low voltage directive.
➤ Dimensions, reservation and weight
If the proximity switch is in 1st position :
it's included in this rating
ordinys® 3
Size of box
A
B
C
Size of box
A
B
C
Box 1
280
225
180
Box 8
380
320
230
Box 2
430
225
180
Box 9
560
420
180
Box 3
330
225
180
Box 10
560
415
180
Box 4
380
315
180
Box 11
560
420
230
Box 5
280
235
180
Box 12
560
425
180
Box 6
380
320
180
Box 13
760
605
200
Box 7
430
315
180
Box 14
610
415
180
➤ Range of use
• The installation, to comply with the established law and it’s certification, has to follow the advice of the technical instructions
delivered with Ordinys® 3.
Guide created by France Air 2010 – All rights reserved.
www.france-air.com
781
fire protection
technical description
➤ Size of products (with or without pressostat and switch integrated)
1 V single-phase 230 V
Ordinys® 3
Option
I+P
Position
1 or 2
Caliber
Without
From 3 to 12 A
1 V three-phase 400 V
box
Option
I+P
Position
1 or 2
1
Without
Size
of
Smoke
extraction
alone
With 1
CDAR
external
smoke
extraction
comfort
Without
From 3 to 12 A
3A
3
4
12 A
6
From 3 to 12 A
7
Caliber
From 3 to 25 A
1
43 A
2
100 A
4
From 3 to 8 A
3
12 and 18 A
7
With 2
25 and 43 A
8
From 3 to 18 A
4
Without
From 25 to 43 A
6
100 A
12
from 3 to 18 A
7
25 A
8
43 A
11
From 0,63 to 18 A
(max. of circuit breaker)
4
24 A
(max. of circuit breaker)
6
40 to 65 A
(max. of circuit breaker)
9
From 0,63 to 18 A
(max. of circuit breaker)
7
24 A
(max. of circuit breaker)
8
From 40 to 65 A
(max. of circuit breaker)
11
With 1
With 1
With 1
Without
All
4
With 2
Without
CIDAR
Integrated
smoke
extraction
comfort
With 1
With 1
All
2 V BI 400 V
Size Option
I+P
of
box Position
1 or 2
7
With 2
Without
With 1
With 2
Without
With 1
With 2
Without
With 1
With 2
2V DA 400 V
Caliber
Size
of
box
From 3 to 18 A
4
25 and 43 A
6
100 A
12
From 3 to 18 A
7
25 A
8
43 A
11
From 3 to 18 A
4
25 and 43 A
6
100 A
12
From 3 to 18 A
7
25 A
8
43 A
11
From 1,7-0.63
to 18-10 A
4
From 24-10
to 40-10 A
6
From 40-10
to 65-24 A
9
From 1,7-0,63
to 18-10 A
7
From 24-10
to 40-18 A
8
From 40-18
to 65-24 A
11
Option
I+P
Position
1 or 2
Without
With 1
With 2
Caliber
size
of
box
From 3 to 18 A
4
25 and 43 A
6
100 A
12
From 3 to 18 A
7
25 A
6
43 A
11
From 3 to 18 A
10
25 and 43 A
9
100 A
13
With 1
From 3 to 18 A
14
With 2
From 25 to
43 A
11
From 1,7-0,63
to 18-6 A
4
24-10 A
6
From 40-10
to 65-24 A
9
From 1,7-0,63
to 18-6 A
7
24-10 A
8
From 40-10
to 65-24 A
11
Without
Without
With 1
With 2
ordinys® 3
Options
•P
ossibility of pre-connecting the fan and the adapted
Ordinys® 3 in factory :
- Time saving at the installation.
- Optimised pre-selection, reinforced security.
See chapter “Ventilation” : Défumair® XR, XTR, XTA
and Simoun® and Sygma XTR products.
• T he Ordinys® 3 have been tested, linked and/or assembled at
the time of the fan tests according to the norm NFEN 12101-3
in the settings of the marking CE.
• Assemblies valid in the compliance certificates CE.
• For an exterior installation, the protection hood in mandatory.
• T he fixing of the fan box at a distance can be done by fixation
terrace support.
782
www.france-air.com
Guide created by France Air 2010. All rights reserved.
fire protection
fitting and connection
➤ Principle
diagram of fan used only for smoke
extraction
➤ P
rinciple diagram of fan used for comfort and
smoke extraction, external comfort accessory
Power cables
(CR1 or C2 under cable protect way)
Control lines
(CR1 or C2 under protect way cable)
Remote control lines
(CR1 or C2 under cable protect way )
Comfort cables and lines
power or remote controlled (C2 )
CR1 : cable resistant to fire.
C2 : cable that doesn’t spread flames.
Connections according to the norm NF-S-61-932.
In the case of Ordinys® 3 Comfort Integrated smoke extraction (CIDAR), the comfort control accessory is integrated to the box Ordinys®
and it will be sufficient to connect a remote control to pilot this accessory.
➤ Installation
• Ordinys® 3 : It has to be installed outside of the security zone that it serves. It can be installed outside (IP 65).
• The rearmament case must be in the security zone corresponding to the controlled DAS. When the fan serves several zones,
1 box can be used, in this case, it must be installed in a protected premises.
• The control box of the fireman control device : it must be placed in a protected premises.
It is often placed in the CMSI premises, or any other place recommended by firemen.
• The proximity switch : it will be at least 2 meters from the fan and will have a position report.
• Use only for rearmament cases and remoted controlled fireman control device cases of the France Air range to respect the compliance.
• Reminder : complying to §8.4.1 of the NF-S-61932, the box has to be installed outside the security zone(s) served by the fan that it
controls.
Guide created by France Air 2010 – All rights reserved.
www.france-air.com
783
ordinys® 3
1. Ordinys® 3 complies to the NFS 61-937
. Rearmament case with key enables the bringing back of Ordinys® 3 from it’s security position to it’s stand by position.
2
It’s a switch with key level 2 access.
3. Air flow control (control with pallet or differential pressostat).
4. Remote control case of the fireman control device. It’s a switch with key level 2 access.
5. Padlockable proximity switch with information return imposed by the work regulation.
6. Smoke extraction fan.
7. Comfort control accessory ensuring a comfort ventilation when Ordinys® 3 is in stand by position.
8. CMSI : Removal from fire area centralizer. It receives information from fire detection systems and transmits to Ordinys® 3 the smoke extraction
order (security passage). This order is a remote control signal 24 or 48 Vcc TBTS (Very low Security voltage) pulse or break of current.
Its US (signalisation Unit) also receives information transmitted by Ordinys® 3.
9. TGBT : General low voltage board.
10. Magnetic protection : only the magnetic protection is authorised on the supply line of a smoke extraction fan contrary to its comfort line
where the thermal protection is to be foreseen.