Tech Guide DH 36-72 3ph
036-21506-004-A-1105
®
DESCRIPTION
YORK Sunline Ultra® units are convertible single package air
conditioners with a common cabinet and a common roof curb
for the 3, 4 and 5 ton sizes. The units were designed for light
commercial and commercial applications. They can easily be
installed on a roof curb, slab, roof jack or frame.
TECHNICAL GUIDE
SINGLE PACKAGE GAS/ELECTRIC UNITS
All units include:
•
Powder Paint finish that meets ASTM-B-117 1000 hour
salt spray standards
AIR CONDITIONERS
•
Permanently lubricated motors
DH 036, 048 & 060
•
Bottom or side air discharge configuration capability
(field convertible)
•
Manufactured under the quality standards of ISO9001
•
SimplicityTM Control Board
•
Copper tube/aluminum fin coils
•
Easy access to all components
•
Rigging holes in base rails for lifting
•
Fork lift slots on three sides
•
Single point power connection
•
Complete factory package - tested, charged and wired
•
Belt Drive Indoor Blower
•
CSA agency listing on all units
AND SINGLE PACKAGE
3, 4 & 5 NOMINAL TONS
12.2 THROUGH 13.2 SEER
WARRANTY
•
Factory Limited Parts Warranty
•
One-year parts warranty
•
A Five-year parts warranty on the compressor and
electric heat elements.
•
Ten-year parts warranty on the gas-fired heat
exchangers.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21506-004-A-1105
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3
LIST OF TABLES
Tbl. #
Pg. #
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1
SOUND POWER RATING . . . . . . . . . . . . . . . . . . . . . . 15
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . 12
2
CAPACITY RATINGS - (ARI 210/240) . . . . . . . . . . . . 15
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . 13
3
GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . 15
4
2 STAGE GAS HEAT RATINGS . . . . . . . . . . . . . . . . . 15
5
DH036 COOLING CAPACITIES (3 TON) . . . . . . . . . . 16
6
DH048 COOLING CAPACITIES (4 TON) . . . . . . . . . . 17
7
DH060 COOLING CAPACITIES (5 TON) . . . . . . . . . . 18
8
SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT
DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . . 19
9
SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT
DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . . 20
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 33
LIST OF FIGURES
Fig. #
Pg. #
1
UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2
TYPICAL FIELD POWER & CONTROL WIRING . . . . 26
3
UNIT DIMENSIONS (3 - 5 TON COOLING ONLY/
ELECTRIC HEAT) FRONT VIEW . . . . . . . . . . . . . . . . 27
4
UNIT DIMENSIONS (3 - 5 TON COOLING/GAS HEAT)
FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5
UNIT WITH ECONOMIZER RAINHOOD . . . . . . . . . . . 28
6
UNIT WITH FIXED OUTDOOR AIR/MOTORIZED
DAMPER RAINHOOD . . . . . . . . . . . . . . . . . . . . . . . . . 28
13 ELECTRIC HEATER CFM LIMITATIONS . . . . . . . . . . 22
7
UNIT DIMENSIONS (REAR VIEW) . . . . . . . . . . . . . . . 29
14 ELECT DATA - DH036, 048 & 060 BELT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . . . . . 23
8
DISCONNECT/BLOWER ACCESS LOCATION . . . . . 29
9
TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . 30
15 ELECT DATA - DH036, 048 & 060 BELT DRIVE WITH
POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . . 24
10 FOUR AND SIX POINT LOADING . . . . . . . . . . . . . . . . 31
16 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
11 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . . . . . 32
17 ELECTRIC HEAT CORRECTION FACTORS . . . . . . 25
10 SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT
DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . . 21
11 BELT DRIVE BLOWER MOTOR AND DRIVE DATA . 21
12 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . . . . 22
18 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . 25
19 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
20 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . . . . 29
21 DH 4 AND 6 POINT LOADS WEIGHT
DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
22 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . . 31
23 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . . . . . . 32
2
Unitary Products Group
036-21506-004-A-1105
PRODUCT NOMENCLATURE
7RQ6XQOLQH8OWUD0RGHO1XPEHU1RPHQFODWXUH
' + 1 1 $ $$ 3URGXFW*HQHUDWLRQ
3URGXFW&DWHJRU\
)LUVW*HQHUDWLRQ
6HFRQG*HQHUDWLRQ
' $LU&RQG6LQJOH3DFNDJH
9ROWDJH
3URGXFW,GHQWLILHU
+ 5+LJK(IILFLHQF\'+*'+(
1RPLQDO&RROLQJ
&DSDFLW\0%+
,QVWDOODWLRQ2SWLRQV
$ 1R2SWLRQV,QVWDOOHG
% 2SWLRQ
& 2SWLRQ
' 2SWLRQV
( 2SWLRQ
) 2SWLRQ
* 2SWLRQV
+ 2SWLRQV
- 2SWLRQV
. 2SWLRQV
/ 2SWLRQV
0 2SWLRQV
1 2SWLRQV
3 2SWLRQV
4 2SWLRQV
5 2SWLRQV
6 2SWLRQ
7 2SWLRQV
8 2SWLRQV
9 2SWLRQV
: 2SWLRQV
; 2SWLRQV
< 2SWLRQV
= 2SWLRQV
7RQ
7RQ
7RQ
+HDW7\SH1RPLQDO+HDW&DSDFLW\
& &RROLQJ2QO\6XLWDEOHIRUILHOGLQVWDOOHGHOHFWULFKHDW
*DV+HDW2SWLRQV
1
1
1
1
'
'
6
6
6
6
7
7
0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
0%+2XWSXW6WDLQOHVV6WHHO6WDJH
0%+2XWSXW6WDLQOHVV6WHHO6WDJH
0%+2XWSXW6WDLQOHVV6WHHO6WDJH
0%+2XWSXW6WDLQOHVV6WHHO6WDJH
0%+2XWSXW6WDLQOHVV6WHHO6WDJH
0%+2XWSXW6WDLQOHVV6WHHO6WDJH
(
(
(
(
(
(
N:(OHFWULF+HDW
N:(OHFWULF+HDW
N:(OHFWULF+HDW
N:(OHFWULF+HDW
N:(OHFWULF+HDW
N:(OHFWULF+HDW
(OHFWULF+HDW2SWLRQV
$GGLWLRQDO2SWLRQV
6HH1H[W3DJH
2SWLRQV
'LVFRQQHFW
1RQ3ZU
G&RQY2XOWHW
6PRNH'HWHFWRU6$
6PRNH'HWHFWRU5$
3ZU
G&RQY2XWOHW
'7 0%+2XWSXWRQ0RGHOV
$LUIORZ
1
3
5
<
%HOW'ULYH
%HOW'ULYH6LQJOH,QSXW(FRQR
%HOW'ULYH0RWRUL]HG'DPSHU
%HOW'ULYH%$65HDG\(FRQ1R%$6&RQWUROOHUZ3OHDWHG)LOWHUV
!,,()'(%&&)#)%.#9-/$%,3#/-%34!.$!2$7)4("%,4$2)6%
Unitary Products Group
3
036-21506-004-A-1105
PRODUCT NOMENCLATURE - Continued
3-6T Sunline Model Number Nomenclature
Standard Cabinet
AA
AB
AC
AD
AE
AF
AG
AH
AJ
AK
AL
AM
AN
AS
CA
CB
CC
CD
CE
CF
CG
CH
CJ
CK
CL
CM
CN
CP
CQ
CR
CS
CT
CU
CV
CW
CX
JA
JB
JC
JD
JE
JF
JG
JH
JJ
JK
JL
JM
JN
JP
JQ
4
None
Phase Monitor
Coil Guard
Dirty Filter Switch
Phase Monitor & Coil Guard
Phase Monitor & Dirty Filter Switch
Coil Guard & Dirty Filter Switch
Phase Monitor, Coil Guard, & Dirty Filter Switch
SS Drain Pan
SS Drain Pan & Phase Monitor
SS Drain Pan & Coil Guard
SS Drain Pan & Dirty Filter Switch
SS Drain Pan, Phase Monitor, Coil Guard & Dirty Filter Switch
Bottom Drain Connection
CPC Controller with Dirty Filter Switch & Air Proving Switch
CPC Controller, DFS, APS & Phase Monitor
CPC Controller, DFS, APS & Coil Guard
CPC Controller, DFS, APS, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS & Technicoat Cond. Coil
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS & Technicoat Evap. Coil
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS, SS Drain Pan
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
Johnson UNT Controller, DFS, APS & Phase Monitor
Johnson UNT Controller, DFS, APS & Coil Guard
Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
Unitary Products Group
036-21506-004-A-1105
Standard Cabinet
JR
JS
JT
JU
JV
JW
JX
HA
HB
HC
HD
HE
HF
HG
HH
HJ
HK
HL
HM
HN
HP
HQ
HR
HS
HT
HU
HV
HW
HX
NA
NB
NC
ND
NE
NF
NG
NH
NJ
NK
NL
NM
NN
NP
NQ
NR
NS
NT
NU
NV
NW
NX
TA
TB
TC
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS, SS Drain Pan
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
Honeywell Excel 10 Controller, DFS, APS & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
Novar ETC-3 Controller, DFS, APS & Phase Monitor
Novar ETC-3 Controller, DFS, APS & Coil Guard
Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS, SS Drain Pan
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Technicoat Condenser Coil
Technicoat Condenser Coil & Phase Monitor
Technicoat Condenser Coil & Coil Guard
Unitary Products Group
5
036-21506-004-A-1105
Standard Cabinet
TD
TE
TF
TG
TH
TJ
TK
TL
TM
TN
TP
TQ
TR
TS
TT
TU
TV
TW
TX
TY
TZ
T1
T3
T4
T6
T7
T9
LA
LB
LC
LD
LE
LF
LG
LH
LJ
LK
LL
LM
LN
LP
LQ
LR
LS
LT
LU
LV
LW
LX
WA
WB
WC
WD
WE
6
Technicoat Condenser Coil & Dirty Filter Switch
Technicoat Condenser Coil, Phase Monitor, & Coil Guard
Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch
Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator Coil
Technicoat Evaporator Coil & Phase Monitor
Technicoat Evaporator Coil & Coil Guard
Technicoat Evaporator Coil & Dirty Filter Switch
Technicoat Evaporator Coil, Phase Monitor, & Coil Guard
Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch
Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils
Technicoat Evaporator & Condenser Coils & Phase Monitor
Technicoat Evaporator & Condenser Coils & Coil Guard
Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Condenser & SS Drain Pan
Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & SS Drain Pan
Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils & SS Drain Pan
Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
Simplicity Intelli-Comfort Controller
Simplicity Intelli-Comfort Controller, & Phase Monitor
Simplicity Intelli-Comfort Controller, & Coil Guard
Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, SS Drain Pan
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Intelli-Comfort w/Mod Link Controller
Intelli-Comfort w/Mod Link Controller, & Phase Monitor
Intelli-Comfort w/Mod Link Controller, & Coil Guard
Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil
Unitary Products Group
036-21506-004-A-1105
Standard Cabinet
WF
WG
WH
WJ
WK
WL
WM
WN
WP
WQ
WR
WS
WT
WU
WV
WW
WX
Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor
Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard
Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, SS Drain Pan
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Hinged Filter Door & Toolless Access Cabinet
BA
BB
BC
BD
BE
BF
BG
BH
BJ
BK
BL
BM
BN
BS
DA
DB
DC
DD
DE
DF
DG
DH
DJ
DK
DL
DM
DN
DP
DQ
DR
DS
DT
DU
DV
DW
Hinged Filter Door & Toolless Access Panels
Phase Monitor, Hinged Filter Door & Toolless Access Panels
Coil Guard, Hinged Filter Door & Toolless Access Panels
Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels
Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Phase Monitor, Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Coil Guard, Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Phase Monitor & Coil Guard, Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Bottom Drain Connection, Hinged Filter Door & Toolless Access Panels
CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
Unitary Products Group
7
036-21506-004-A-1105
Hinged Filter Door & Toolless Access Cabinet
DX
EA
EB
EC
ED
EE
EF
EG
EH
EJ
EK
EL
EM
EN
EP
EQ
ER
ES
ET
EU
EV
EW
EX
GA
GB
GC
GD
GE
GF
GG
GH
GJ
GK
GL
GM
GN
GP
GQ
GR
GS
GT
GU
GV
GW
GX
PA
PB
8
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless
Access Panels
Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door &
Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels
Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access
Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless
Access Panels
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Honeywell Excel 10 Controller,DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Unitary Products Group
036-21506-004-A-1105
Hinged Filter Door & Toolless Access Cabinet
PC
PD
PE
PF
PG
PH
PJ
PK
PL
PM
PN
PP
PQ
PR
Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
PS Novar ETC-3 Controller, DFS, APS, SS Drain Pan
PT Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
PU Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
PV Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
PW Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
PX Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
UA Technicoat Condenser Coil, Hinged Filter Door & Toolless Access Panels
UB Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UC Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UD Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UE Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UJ Technicoat Evaporator Coil, Hinged Filter Door & Toolless Access Panels
UK Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UL Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UM Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
US Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Toolless Access Panels
UT Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UU Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access Panels
UV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U1 Technicoat Condenser & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U3 Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U4 Technicoat Evaporator & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U6 Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U7 Technicoat Evaporator & Condenser Coils & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U9 Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless
Access Panels
QA Simplicity Intelli-Comfort Controller with Hinged Filter Door & Toolless Access Panels
QB Simplicity Intelli-Comfort Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
QC Simplicity Intelli-Comfort Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Unitary Products Group
9
036-21506-004-A-1105
Hinged Filter Door & Toolless Access Cabinet
QD
QE
QF
QG
QH
QJ
QK
QL
QM
QN
QP
QQ
QR
QS
QT
QU
QV
QW
QX
Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolles
Simplicity Intelli-Comfort Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels
XA Intelli-Comfort w/Mod Link Controller, Hinged Filter Door & Toolless Access Panels
XB Intelli-Comfort w/Mod Link Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XC Intelli-Comfort w/Mod Link Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XD Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XE Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
XF Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XG Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XH Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
XJ Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
XK Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XL Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XM Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
XN Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
XP Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan
XQ Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XR Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolles
XS Intelli-Comfort w/Mod Link Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels
XT Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
XU Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
XV Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
XW Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
XX Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels
10
Unitary Products Group
036-21506-004-A-1105
FEATURES
switch on gas heat units. The unit control board will
alarm on ignition failures, compressor lockouts and
repeated limit switch trips.
All models are available with a wide variety of factorymounted options such as stainless steel heat exchangers,
electric heaters, phase monitor, convenience outlet, dirty filter
switch, disconnect switch, smoke detectors, and coil guard to
make them suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with forklift holes on three sides and holes for overhead rigging. Every unit is completely piped, wired, charged
and tested at the factory to simplify the field installation and to
provide years of dependable operation.
All models (including those with an economizer) are suitable for
either bottom or horizontal duct connections. For bottom duct,
remove the sheet metal panels from the supply and return air
openings through the base of the unit. For horizontal duct,
remove the supply and return air panels on the rear of the unit.
•
Nuisance Trip Protection- To prevent nuisance
trouble calls, the control board uses a “three strikes,
you’re out” philosophy. The high and low-pressure
switches and the freezestats must trip three times
within two hours before the unit control board will
lock out the compressor.
•
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
All models are available with these “factory mounted” outdoor
air damper options:
All units have long lasting powder paint cabinets with 1000
hour salt spray test approval under ASTM-B117 procedures.
•
Single enthalpy economizer
All models are CSA listed.
•
Motorized outdoor air damper
•
Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.
•
Gas Heat Operation - All single phase models with gas
heat have minimum annual fuel utilization efficiency
(AFUE) of 80%. All three phase models with gas heat
have minimum steady state efficiency of 80%. Each section includes a durable heat exchanger with aluminized
steel or optional stainless steel tubes, a redundant gas
valve, spark ignition, power venting, an ignition module
for 100% shut-off and all of the safety controls required
to meet the latest ANSI standards.
Supply air blowers are equipped with a belt drive that can be
adjusted to meet the exact requirements of the job.
All compressors are equipped with internal pressure relief.
Every refrigerant circuit includes a liquid line filter-drier, a high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch to protect all system components.
•
Simplicity™ Controls - Simplicity™ control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
•
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
•
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
•
Fan Delays - Fan on and fan off delays are fully programmable and are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
•
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
Unitary Products Group
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
•
Electric Heat Operation - All electric heat models are
wired for a single power source and include a bank of
nickel chromium elements mounted at the discharge of
the supply air blower to provide a high velocity and uniform distribution of air across the heating elements.
Every element is fully protected against excessive temperature by thermal limit switches.
The power supply wiring can be routed into the control
box through a threaded pipe connection (field supplied)
in the base pan of the unit or through a knockout in the
wiring panel on the side of the unit.
•
BAS Controls - York’s Sunline™ series units offer factory
mounted BAS controls such as SImplicity™ INTELLIComfort™, Novar, Honeywell, Johnson, and CPC.
11
036-21506-004-A-1105
FIGURE 1 -
UNIT CUTAWAY
FACTORY-INSTALLED OPTIONS
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
12
PHENOLIC COATED EVAPORATOR AND CONDENSER COILS - Special coating process that utilizes
Technicoat 10-1TM processes. Coating is applied by total
immersion of the complete coil for maximum protection.
•
ELECTRIC HEATERS - Wired for single point power
supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.
•
FILTER OPTIONS - Standard units are shipped with 1”
throw-away filters installed. 2” pleated filters are offered
as a factory installed option.
•
CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or the
unit may be ordered with a “non-powered” convenience
outlet that can be wired in the field.
•
DISCONNECT SWITCH - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
•
BAS - Building Automation System Controls
Simplicity™ INTELLI-Comfort™ CONTROL - The York®
Simplicity™ INTELLI-Comfort™ control is factory
installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a
field installed dirty filter indicator switch, an air-proving
switch, an Outside Air Humidity sensor, a Return Air
Humidity sensor, an Inside IAQ sensor, and an Outside
Air IAQ sensor. Construction mode operation, 365-day
real time clock with 7 day programming plus holiday
Unitary Products Group
036-21506-004-A-1105
•
•
•
•
scheduling is built-in. Two different modes of demand
ventilation are achieved through the INTELLI-Comfort™using CO2 sensors. It uses an inside CO2 sensor to
perform Demand Ventilation. It can also use an Outside
CO2 sensor to perform Differential Demand Ventilation. It
uses a Patented Comfort Ventilation algorithm to provide
comfortable ventilation air temperature. The patented
economizer-loading algorithm will protect the equipment
when harsh operating conditions exist. Humidity in the
occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection
for hot gas re-heat system. It uses the INTELLI-Start™
algorithm to maximize energy savings by recovering the
building from the Unoccupied Setpoints to the Occupied
Setpoints just in time for the Occupied Time Period to
begin. The Simplicity™ INTELLI-Comfort™ balances
space temperature, ventilation air temperature, CO2 and
humidity for ultimate comfort.
•
STAINLESS STEEL DRAIN PAN - An optional rustproof stainless steel drain pan is available to provide
years of trouble-free operation in corrosive environments.
•
BOTTOM DRAIN CONNECTION - An optional bottom
drain connection is available for inside the curb connections for applications in cold environments to reduce
freezing drain lines.
•
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.
•
DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
Simplicity™ INTELLI-Comfort™ with MOD LINK CONTROL - The York® Simplicity™ INTELLI-Comfort™ with
Mod Link control is factory installed. It includes all the
features of the INTELLI-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.
•
HINGED FILTER DOOR/“TOOLLESS” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
Novar® BAS CONTROL - The Novar® ETC-3 building
automation system controller is factory installed.
Includes supply air sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
NOTE:Knobs are shipped inside the unit to prevent shipping damage. These must be field installed for
tool-less operation.
FIELD-INSTALLED ACCESSORIES
•
JOHNSON CONTROLS BAS CONTROL - The Johnson
Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor,
return air sensor, dirty filter indicator switch, and air proving switch.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
CPC BAS CONTROL - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
•
HONEYWELL BAS CONTROL - The Honeywell
W7750C building automation system controller is factory
installed. Includes air supply sensor, return air sensor,
dirty filter indicator switch, and air proving switch.
•
SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
•
STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a
full stainless steel heat exchanger assembly.
Unitary Products Group
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.
13
036-21506-004-A-1105
•
•
•
•
•
Roof curbs are designed to fit inside the base rails of the
unit and include both a wood nailing strip and duct
hanger supports.
BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
•
HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.
ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
•
BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
•
FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this
kit can be installed to prevent the flue exhaust from
entering nearby fresh air intakes.
•
CO2 SENSOR - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
present limits.
ROOF CURBS - Eight and fourteen-inch high roof curbs
provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association
(NRCA) and are shipped knocked-down for field assembly.
PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.
HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.
•
LOW NOX KIT - Required to reduce the emission of
nitrogen oxides below 40 nano grams per joule.
•
POWER EXHAUST - Our single input economizer
options are available with power exhaust. Whenever the
outdoor air intake dampers are opened for free cooling,
the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
•
HAIL GUARD - Hail Guard kit is available to prevent unit
from hail damage. This is a sloped hood that fits above
the coil.
The power exhaust option can only be used on bottom duct configurations.
•
GAS PIPING KIT - This kit supplies all necessary fittings
and shut off valve.
14
Unitary Products Group
036-21506-004-A-1105
TABLE 1: SOUND POWER RATING1
UNIT
SIZE
ESP
SOUND POWER (db 10-12 Watts)
BLOWER
Octave Band Centerline Frequency (Hz)
CFM
IWG
SPEED
KW
63
125
250
500
1,000
2,000
4,000
8,000
SWL
dB(A)
dB(A)
@
10Ft.2
036
1,200
0.6
LOW
0.60
84
84
74
67
69
62
57
52
74
41
048
1,600
0.55
HIGH
0.80
85
85
75
68
70
63
58
53
75
42
060
2,000
0.45
HIGH
1.00
86
86
76
69
71
64
59
54
76
43
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
TABLE 3: GAS HEAT RATINGS1
TABLE 2: CAPACITY RATINGS - (ARI 210/240)1
MODEL
MBH
EER2
SEER3
DH036
42.5
11.1
12.25
DH048
46.5
11.4
13.20
DH060
57.0
10.6
12.20
1. 80/67°F Indoor and 95°F outdoor.
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
3. SEER = Seasonal Energy Efficiency Ratio.
MODEL
MBH
INPUT
MBH
OUTPUT
AFUE
(%)
TEMP
RISE ºF
DH036N04
DH036N08
50
100
40
80
80.9
80.5
15 - 45
40 - 70
DH048N06
DH048N10
75
125
60
100
80.9
80.3
25 - 55
45 - 75
DH060N08
DH060N10
100
125
80
100
80.5
80.3
25 - 55
35 - 65
1. All units are single-stage heating.
TABLE 4: 2 STAGE GAS HEAT RATINGS
MODEL1
MBH INPUT
MBH OUTPUT
1ST STAGE 2ND STAGE 1ST STAGE 2ND STAGE
STEADY STATE EFFICIENCY
1ST STAGE
2ND STAGE
RISE
MIN.
MAX.
MINIMUM HEATING
AIRFLOW (CFM)
DH036D06
45
75
35.8
60.8
79.4
81.1
35
70
790
DH036D10
69
115
55.2
92
80.0
80.2
55
90
950
DH048D06
45
75
35.7
60.8
79.4
81.1
25
70
790
DH048D10
75
125
60.4
100.6
80.5
80.5
45
75
1230
DH060D06
45
75
35.8
60.8
79.4
81.1
35
70
1010
DH060D10
75
125
60.4
100.6
80.5
80.5
45
75
1230
1. Models are 3Ø only.
Unitary Products Group
15
036-21506-004-A-1105
TABLE 5: DH036 COOLING CAPACITIES (3 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
85°F
TOTAL
1
CFM
1500
1350
1200
1050
900
POWER
CAP.
MBH
INPUT2 kW
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
55.2
49.1
44.7
42.4
55.2
49.1
44.7
42.4
51.9
46.1
42.0
39.8
49.4
43.9
40.0
37.9
46.9
41.7
38.0
36.0
3.18
3.13
3.05
3.05
3.18
3.13
3.05
3.05
3.15
3.10
3.02
3.03
3.12
3.07
2.99
3.00
3.09
3.04
2.96
2.97
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
TOTAL
1
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
83
80
77
74
71
68
CAP.
MBH
INPUT2 kW
86
35.2
41.7
44.7
42.4
35.2
41.7
44.7
42.4
30.0
35.7
41.2
39.8
27.3
32.6
37.7
37.9
24.6
29.5
34.2
36.0
30.7
37.2
43.6
42.4
30.7
37.2
43.6
42.4
26.5
32.2
37.7
39.8
24.3
29.6
34.7
37.0
22.1
26.9
31.6
34.2
26.2
32.8
39.1
42.4
26.2
32.8
39.1
42.4
23.0
28.7
34.2
37.3
21.2
26.5
31.6
34.5
19.5
24.4
29.1
31.7
21.8
28.3
34.6
37.9
21.8
28.3
34.6
37.9
19.5
25.2
30.7
33.8
18.2
23.5
28.6
31.4
16.9
21.8
26.5
29.1
17.3
23.8
30.1
33.4
17.3
23.8
30.1
33.4
21.7
27.2
30.3
20.5
25.6
28.4
14.4
19.2
23.9
26.5
19.4
25.7
29.0
19.4
25.7
29.0
16.0
18.2
23.7
26.8
15.2
17.4
22.5
25.4
16.7
21.4
24.0
14.9
21.2
24.5
14.9
21.2
24.5
14.7
20.2
23-3
14.4
19.5
22.3
14.1
18.8
21.4
51.5
45.8
41.2
39.9
50.0
44.5
40.0
38.8
48.6
43.2
38.9
37.6
46.4
41.2
37.1
35.9
44.2
39.3
35.4
34.2
3.44
3.35
3.30
3.35
3.41
3.32
3.27
3.32
3.38
3.29
3.23
3.29
3.36
3.27
3.21
3.27
3.34
3.25
3.20
3.25
86
83
80
77
74
71
68
34.1
40.2
41.2
39.9
31.5
37.2
40.0
38.8
28.9
34.2
38.9
37.6
26.2
31.1
36.2
35.9
23.6
28.0
33.5
34.2
29.7
35.7
41.2
39.9
27.5
33.2
39.2
38.8
25.4
30.7
37.2
37.6
23.2
28.1
34.1
34.9
21.0
25.4
30.9
32.1
25.2
31.3
38.8
39.9
23.6
29.2
36.3
37.5
21.9
27.2
33.7
35.1
20.2
25.0
31.1
32.3
18.4
22.9
28.4
29.5
20.7
26.8
34.3
35.4
19.6
25.3
32.3
33.5
18.4
23.7
30.2
31.6
17.2
22.0
28.0
29.3
15.9
20.3
25.8
27.0
16.2
22.3
29.8
31.0
15.6
21.3
28.3
29.6
14.9
20.2
26.7
28.1
14.1
19.0
25.0
26.3
13.3
17.7
23.2
24.4
17.8
25.3
26.5
17.3
24.3
25.6
16.7
23.2
24.6
16.0
22.0
23.2
15.2
20.7
21.8
13.4
20.9
22.0
13.3
20.3
21.6
13.2
19.8
21.1
12.9
18.9
20.2
12.6
18.1
19.3
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
105°F
TOTAL
1
CFM
1500
1350
1200
1050
900
POWER
CAP.
MBH
INPUT2 kW
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
47.6
42.5
38.0
37.4
46.5
41.6
37.1
36.5
45.4
40.6
36.2
35.7
43.2
38.7
34.5
34.0
41.1
36.7
32.8
32.3
3.65
3.56
3.49
3.54
3.62
3.53
3.46
3.52
3.60
3.51
3.44
3.49
3.57
3.48
3.41
3.47
3.54
3.45
3.39
3.44
115°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
TOTAL
1
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
83
80
77
74
71
68
CAP.
MBH
INPUT2 kW
86
32.3
39.0
38.0
37.4
29.7
36.0
37.1
36.5
27.2
33.0
36.2
35.7
24.6
29.9
33.9
34.0
22.0
26.8
31.5
32.3
27.8
34.5
38.0
37.4
25.8
32.0
36.6
36.5
23.7
29.5
35.2
35.7
21.6
26.9
32.1
32.9
19.4
24.2
28.9
30.1
23.3
30.0
36.6
37.4
21.8
28.0
34.1
35.2
20.2
26.0
31.7
33.0
18.5
23.8
29.0
30.3
16.8
21.7
26.4
27.5
18.9
25.6
32.1
32.9
17.8
24.0
30.1
31.2
16.7
22.5
28.2
29.5
20.8
26.0
27.2
14.3
19.1
23.8
24.9
14.4
21.1
27.6
28.5
13.8
20.1
26.1
27.2
12.2
19.0
24.7
26.0
12.5
17.8
23.0
24.2
11.7
16.5
21.2
22.4
16.6
23.1
24.0
16.1
22.2
23.3
15.5
21.2
22.5
14.7
19.9
21.2
14.0
18.7
19.8
12.1
18.7
19.5
12.1
18.2
19.3
12.0
17.7
19.0
11.7
16.9
18.1
11.4
16.1
17.2
43.6
39.3
34.8
34.9
42.9
38.6
34.2
34.3
42.2
37.9
33.6
33.7
40.1
36.1
32.0
32.1
38.0
34.2
30.3
30.4
3.85
3.76
3.67
3.73
3.83
3.74
3.66
3.72
3.82
3.73
3.64
3.70
3.78
3.69
3.61
3.67
3.75
3.66
3.58
3.64
86
83
80
77
74
71
68
30.4
37.8
34.8
34.9
28.0
34.8
34.2
34.3
25.5
31.8
33.6
33.7
22.9
28.7
31.6
32.1
20.4
25.6
29.5
30.4
26.0
33.3
34.8
34.9
24.0
30.8
34.0
34.3
22.0
28.3
33.1
33.7
19.9
25.7
30.0
30.9
17.8
23.0
26.9
28.0
21.5
28.8
34.4
34.9
20.0
26.8
32.0
32.9
18.5
24.8
29.6
30.9
16.9
22.6
27.0
28.2
15.2
20.4
24.4
25.4
17.0
24.3
29.9
30.5
16.0
22.8
28.0
28.9
15.0
21.3
26.1
27.4
13.8
19.6
23.9
25.1
12.7
17.9
21.8
22.9
12.5
19.9
25.4
26.0
12.0
18.8
24.0
24.9
11.5
17.8
22.6
23.9
10.8
16.6
20.9
22.1
10.1
15.3
19.2
20.3
15.4
20.9
21.5
14.9
20.0
21.0
14.3
19.1
20.4
13.5
17.9
19.1
12.7
16.7
17.7
10.9
16.5
17.0
10.9
16.0
17.0
10.8
15.6
16.9
10.5
14.9
16.0
10.2
14.1
15.2
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower from the SUPPLY AIR BLOWER PERFORMANCE
Tables, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor
power input is 0.36kW. Refer to SUPPLY AIR BLOWER PERFORMANCE Tables for the kW of the supply air blower motor.
NOMINAL RATING
16
Unitary Products Group
036-21506-004-A-1105
TABLE 6: DH048 COOLING CAPACITIES (4 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
TOTAL
INPUT2 kW
CFM
WB °F
CAP.1
MBH
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
59
53
47
47
58
53
47
46
57
52
46
45
54
49
43
43
51
46
41
40
3.3
3.2
3.2
3.1
3.3
3.2
3.2
3.1
3.3
3.2
3.2
3.1
3.2
3.1
3.1
3.1
3.2
3.1
3.1
3.0
2000
1800
1600
1400
1200
85°F
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
TOTAL
86
83
80
77
74
71
68
CAP.1
MBH
46
53
47
47
42
50
47
46
39
47
46
45
35
43
43
43
32
39
41
40
40
49
47
47
37
46
47
46
34
42
46
45
31
39
43
43
29
35
41
40
34
43
47
47
32
41
46
46
30
38
45
45
27
35
42
41
25
32
38
38
28
38
42
41
27
35
41
41
25
33
41
40
23
31
38
37
22
28
35
34
23
32
36
35
22
30
36
35
21
29
36
36
19
27
34
33
18
25
31
31
26
30
29
25
31
30
24
32
31
23
30
29
21
28
27
21
25
24
20
26
25
19
27
27
19
26
25
18
24
24
55
49
44
43
54
48
43
42
53
48
42
41
51
45
40
39
48
42
38
37
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
INPUT2 kW
3.5
3.4
3.4
3.3
3.5
3.4
3.4
3.3
3.5
3.4
3.4
3.3
3.5
3.4
3.4
3.3
3.5
3.5
3.4
3.4
86
83
80
77
74
71
68
43
49
44
43
40
47
43
42
37
45
42
41
34
41
40
39
30
37
38
37
37
47
44
43
35
44
43
42
33
41
42
41
30
37
40
39
27
34
38
37
32
41
44
43
30
39
43
42
28
36
43
41
26
33
40
38
23
30
36
35
26
35
38
37
25
33
38
37
23
32
39
37
22
29
36
34
20
27
33
31
20
30
32
31
20
28
33
32
19
27
34
32
17
25
32
30
16
23
29
28
24
26
26
23
28
27
22
30
28
21
28
26
20
26
24
-
-
-
-
-
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
105°F
TOTAL
1
CFM
1500
1350
1200
1050
900
POWER
CAP.
MBH
INPUT2 kW
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
50
45
39
39
50
44
39
38
49
44
39
38
47
42
37
36
44
40
35
34
3.8
3.7
3.6
3.6
3.8
3.7
3.6
3.6
3.8
3.7
3.6
3.6
3.8
3.7
3.6
3.5
3.7
3.7
3.6
3.5
115°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
TOTAL
1
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
83
80
77
74
71
68
CAP.
MBH
INPUT2 kW
86
41
45
39
39
38
44
39
38
35
43
39
38
32
39
37
36
29
36
35
34
35
44
39
39
33
41
39
38
31
39
39
38
28
35
37
36
25
32
35
34
30
39
39
39
28
36
40
38
26
34
41
38
24
31
38
35
22
29
34
32
24
33
34
33
23
31
35
33
21
30
37
33
20
27
33
31
18
25
30
28
18
27
28
27
18
26
30
28
17
25
32
29
16
23
29
27
15
21
27
25
22
22
22
21
25
23
20
27
24
19
25
23
18
23
21
16
17
16
16
20
18
16
23
19
15
21
18
14
20
18
45
40
35
35
45
40
35
34
45
40
35
34
43
38
33
33
41
36
32
31
4.0
4.0
3.8
3.8
4.0
4.0
3.9
3.8
4.1
4.1
3.9
3.8
4.0
4.0
3.8
3.7
3.9
3.9
3.8
3.7
86
83
80
77
74
71
68
39
40
35
35
36
40
35
34
33
40
35
34
30
37
33
33
27
34
32
31
33
40
35
35
31
39
35
34
29
37
35
34
26
34
33
33
24
30
32
31
28
37
35
35
26
34
37
34
24
32
39
34
22
29
35
31
20
27
32
29
22
31
30
29
21
29
32
29
20
27
34
30
18
25
31
27
17
23
28
25
16
25
24
23
16
24
27
24
15
23
30
25
14
21
27
23
13
20
25
22
20
18
18
19
22
19
18
25
20
17
23
19
16
21
18
-
-
-
-
-
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower from the SUPPLY AIR BLOWER PERFORMANCE
Tables, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor
power input is 0.36kW. Refer to SUPPLY AIR BLOWER PERFORMANCE Tables for the kW of the supply air blower motor.
NOMINAL RATING
Unitary Products Group
17
036-21506-004-A-1105
TABLE 7: DH060 COOLING CAPACITIES (5 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
TOTAL
INPUT2 kW
CFM
WB °F
CAP.1
MBH
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
82
70
67
66
78
67
64
63
75
64
61
60
72
62
59
58
69
59
56
55
4.3
4.2
4.0
4.0
4.3
4.2
4.0
4.0
4.3
4.2
4.0
4.0
4.3
4.2
4.0
4.0
4.2
4.1
4.0
4.0
2500
2250
2000
1750
1500
85°F
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
TOTAL
86
83
80
77
74
71
68
CAP.1
MBH
56
67
67
66
53
63
64
63
49
58
61
60
44
53
59
58
40
48
56
55
50
61
67
66
47
57
64
63
43
53
61
60
40
49
57
57
36
44
53
54
43
54
66
66
41
51
62
63
38
48
58
59
35
44
53
55
32
40
49
50
37
48
59
59
35
45
56
57
33
42
52
54
30
39
48
50
28
36
44
46
30
41
52
52
29
39
50
51
27
37
47
49
25
34
44
45
24
32
40
42
34
46
46
33
44
45
32
42
43
30
39
40
28
36
37
28
39
39
27
38
39
26
36
38
25
34
36
23
32
33
76
65
62
61
73
62
60
58
70
60
57
56
67
58
55
54
65
56
53
52
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
INPUT2 kW
4.6
4.5
4.5
4.4
4.6
4.5
4.4
4.4
4.6
4.5
4.4
4.4
4.6
4.5
4.4
4.4
4.6
4.5
4.4
4.4
86
83
80
77
74
71
68
54
65
62
61
50
60
60
58
46
56
57
56
43
51
55
54
39
46
53
52
48
58
62
61
44
54
60
58
41
50
57
56
38
46
54
54
34
42
51
51
41
51
62
61
38
48
59
58
36
45
55
56
33
41
51
51
30
38
47
47
34
45
55
54
32
42
53
52
30
39
50
50
28
37
46
47
26
34
43
43
28
38
49
47
26
36
47
46
25
34
45
45
24
32
42
42
22
30
39
39
31
42
41
30
41
40
29
39
39
27
37
37
26
35
35
25
35
34
24
35
34
23
34
34
22
32
32
21
30
30
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
105°F
TOTAL
1
CFM
2500
2250
2000
1750
1500
POWER
CAP.
MBH
INPUT2 kW
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
68
60
56
55
67
58
55
54
65
57
53
52
62
54
51
50
59
52
48
47
5.0
4.8
4.8
4.7
4.9
4.8
4.7
4.7
4.9
4.8
4.7
4.7
4.9
4.8
4.7
4.6
4.9
4.7
4.7
4.6
115°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
TOTAL
1
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
83
80
77
74
71
68
CAP.
MBH
INPUT2 kW
86
51
60
56
55
48
57
55
54
44
54
53
52
40
49
51
50
36
44
48
47
44
55
56
55
42
52
55
54
39
48
53
52
35
44
50
50
32
40
47
47
38
49
56
55
36
46
54
53
33
43
52
52
31
40
48
48
28
36
43
43
31
42
49
48
30
40
48
47
28
38
46
46
26
35
43
43
24
32
39
39
25
35
43
42
24
34
42
41
23
32
41
41
21
30
38
38
20
28
35
35
29
36
35
28
36
35
27
36
36
25
33
33
24
31
31
22
29
28
22
30
29
22
30
30
21
29
29
20
27
27
61
55
50
49
60
54
49
49
60
54
49
48
56
51
46
46
53
48
43
43
5.3
5.1
5.1
5.0
5.3
5.1
5.0
5.0
5.2
5.1
5.0
5.0
5.2
5.0
5.0
4.9
5.2
5.0
4.9
4.9
86
83
80
77
74
71
68
48
55
50
49
45
53
49
49
42
52
49
48
38
47
46
46
34
43
43
43
41
53
50
49
39
50
49
49
36
47
49
48
33
42
46
46
30
38
43
43
35
46
50
49
33
44
49
49
31
41
48
48
28
38
44
44
26
34
40
40
28
39
43
43
27
38
43
43
26
36
43
42
24
33
39
39
22
30
36
36
21
33
37
36
21
32
37
37
20
30
37
37
19
28
34
34
18
26
32
31
26
30
29
26
31
31
25
32
32
23
30
29
22
27
27
20
23
23
20
25
25
20
26
26
19
25
25
18
23
23
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower from the SUPPLY AIR BLOWER PERFORMANCE
Tables, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor
power input is 0.36kW. Refer to SUPPLY AIR BLOWER PERFORMANCE Tables for the kW of the supply air blower motor.
NOMINAL RATING
18
Unitary Products Group
036-21506-004-A-1105
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
TONNAGE
3
1
UNIT
TONNAGE
3
1
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 2
0.60
0.40
0.50
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2000
843
860
880
925
919
1005
956
1065
993
1145
1030
1195
1067
1235
1900
817
775
854
850
893
920
930
995
970
1065
1008
1125
1046
1170
1800
790
700
828
760
867
840
906
905
944
980
985
1040
1025
1100
1700
-
-
802
670
840
745
881
815
920
900
961
970
1001
1030
1600
-
-
-
-
818
665
858
740
898
820
940
890
980
950
1500
-
-
-
-
-
-
842
695
882
755
922
835
962
895
1400
-
-
-
-
-
-
833
650
867
705
904
765
942
820
1300
-
-
-
-
-
-
-
-
858
665
893
725
932
785
1200
-
-
-
-
-
-
-
-
847
640
880
680
916
730
0.20
0.30
0.70
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 2
1.10
1.20
1.30
0.80
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2000
1103
1270
-
-
-
-
-
-
-
-
-
-
-
-
1900
1085
1210
-
-
-
-
-
-
-
-
-
-
-
-
1800
1064
1145
1102
1180
-
-
-
-
-
-
-
-
-
-
1700
1040
1075
1081
1115
1121
1140
-
-
-
-
-
-
-
-
1600
1020
1005
1060
1050
1100
1085
-
-
-
-
-
-
-
-
1500
1003
945
1044
995
1086
1035
-
-
-
-
-
-
-
-
1400
982
880
1024
920
1067
965
1107
1000
-
-
-
-
-
-
1300
970
835
1010
870
1053
920
1099
960
-
-
-
-
-
-
1200
953
780
992
815
1034
855
1080
905
-
-
-
-
-
-
0.90
1.00
1.40
1.50
1. For 208 Volts multiply values by 0.95.
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table
for resistance values on applications other than gas / electric units with side duct airflows.
Unitary Products Group
19
036-21506-004-A-1105
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
TONNAGE
4
1
UNIT
TONNAGE
4
1
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 2
0.60
0.40
0.50
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2000
843
860
880
925
919
1005
956
1065
993
1145
1030
1195
1067
1235
1900
817
775
854
850
893
920
930
995
970
1065
1008
1125
1046
1170
1800
790
700
828
760
867
840
906
905
944
980
985
1040
1025
1100
1700
-
-
802
670
840
745
881
815
920
900
961
970
1001
1030
1600
-
-
-
-
818
665
858
740
898
820
940
890
980
950
1500
-
-
-
-
-
-
842
695
882
755
922
835
962
895
1400
-
-
-
-
-
-
833
650
867
705
904
765
942
820
1300
-
-
-
-
-
-
-
-
858
665
893
725
932
785
1200
-
-
-
-
-
-
-
-
847
640
880
680
916
730
0.20
0.30
0.70
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 2
1.10
1.20
1.30
0.80
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2000
1103
1270
-
-
-
-
-
-
-
-
-
-
-
-
1900
1085
1210
-
-
-
-
-
-
-
-
-
-
-
-
1800
1064
1145
1102
1180
-
-
-
-
-
-
-
-
-
-
1700
1040
1075
1081
1115
1121
1140
-
-
-
-
-
-
-
-
1600
1020
1005
1060
1050
1100
1085
-
-
-
-
-
-
-
-
1500
1003
945
1044
995
1086
1035
-
-
-
-
-
-
-
-
1400
982
880
1024
920
1067
965
1107
1000
-
-
-
-
-
-
1300
970
835
1010
870
1053
920
1099
960
-
-
-
-
-
-
1200
953
780
992
815
1034
855
1080
905
-
-
-
-
-
-
0.90
1.00
1.40
1.50
1. Models shown at 230/460 Volts with side duct connections.
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table
for resistance values on applications other than gas / electric units with side duct airflows.
20
Unitary Products Group
036-21506-004-A-1105
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
TONNAGE
5
1
UNIT
TONNAGE
5
1
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 2
0.60
0.40
0.50
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2500
1059
1560
1077
1590
1095
1630
1114
1650
1134
1660
1158
1685
1181
1720
2400
1032
1405
1054
1470
1074
1525
1094
1560
1116
1595
1140
1620
1167
1640
2300
1005
1260
1024
1275
1049
1370
1069
1440
1090
1475
1116
1505
1142
1535
2200
980
1160
1002
1170
1022
1190
1044
1250
1066
1350
1090
1410
1117
1440
2100
930
1060
957
1070
983
1080
1010
1100
1039
1160
1064
1260
1092
1340
2000
877
950
908
975
941
1000
976
1020
1009
1050
1040
1100
1070
1225
1900
-
-
-
-
894
885
940
940
980
980
1014
1020
1047
1095
1800
-
-
-
-
855
815
903
860
950
905
988
940
1022
970
1700
-
-
-
-
-
-
884
815
925
850
964
880
1001
910
1600
-
-
-
-
-
-
864
770
908
805
948
835
987
870
1500
-
-
-
-
-
-
-
-
882
740
926
780
965
830
0.20
0.30
0.70
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 2
1.10
1.20
1.30
0.80
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
2500
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2400
1193
1665
-
-
-
-
-
-
-
-
-
-
-
-
2300
1170
1580
1202
1620
-
-
-
-
-
-
-
-
-
-
2200
1148
1480
1180
1530
-
-
-
-
-
-
-
-
-
-
2100
1121
1385
1155
1425
1190
1475
-
-
-
-
-
-
-
-
2000
1100
1285
1133
1340
1169
1385
1205
1445
-
-
-
-
-
-
1900
1079
1180
1110
1240
1143
1280
1178
1330
1222
1375
-
-
-
-
1800
1058
1060
1090
1135
1122
1190
1158
1240
1196
1295
-
-
-
-
1700
1035
960
1071
1030
1103
1100
1134
1140
1164
1175
1197
1205
-
-
1600
1020
900
1056
965
1088
1035
1118
1065
1145
1105
1170
1130
1198
1150
1500
1004
860
1038
880
1070
925
1101
980
1130
1045
1158
1075
1184
1110
0.90
1.00
1.40
1.50
WATTS
1. Models shown at 230/460 Volts with side duct connections.
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table
for resistance values on applications other than gas / electric units with side duct airflows.
TABLE 11: BELT DRIVE BLOWER MOTOR AND DRIVE DATA
MOTOR1
ADJUSTABLE MOTOR PULLEY
BELT
(NOTCHED)
FIXED BLOWER PULLEY
MODEL
SIZE
BLOWER
RANGE
(RPM)
HP
FRAME
DESIGNATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIGNATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIGNATION
PITCH
LENGTH
(IN.)
QTY.
3 TON
790/1120
1 1/2
56
1VL40
2.7-3.7
2.4-3.4
5/8
AK61
5.9
5.7
1
A36
37.3
1
4 TON
790/1120
1 1/2
56
1VL40
2.7-3.7
2.4-3.4
5/8
AK61
5.9
5.7
1
A36
37.3
1
5 TON
850/1220
1 1/2
56
1VL40
2.7-3.7
2.4-3.4
5/8
AK56
5.4
5.2
1
A36
37.3
1
1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located
in the moving air, upstream of any heating device.
Unitary Products Group
21
036-21506-004-A-1105
TABLE 12: STATIC RESISTANCES
RESISTANCE, IWG
DESCRIPTION
CFM
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
3000
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.23
0.26
0.30
7-15KW
0.04
0.05
0.06
0.07
0.08
0.10
0.12
0.14
0.16
0.19
0.22
20-30KW
0.06
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.23
0.26
BOTTOM DUCT CONNECTIONS1
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.14
0.16
0.19
0.22
COOLING ONLY2
0.08
0.10
0.12
0.14
0.16
0.18
0.20
0.23
0.26
0.29
0.32
ECONOMIZER1 3
ELECTRIC
HEATERS1
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.
3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 13: ELECTRIC HEATER CFM LIMITATIONS
MINIMUM SUPPLY AIR CFM
UNITMODEL SIZE NOMINAL
TONS
3
4
5
22
VOLTAGE
HEATER SIZE NOMINAL KW
5
7
10
15
20
30
208/230-3-60
1100
1100
1200
1200
1300
-
460-3-60
-
1100
1200
1200
1300
-
575-3-60
-
-
1200
1200
1300
-
208/230-3-60
1300
1300
1300
1300
1300
-
460-3-60
-
1300
1300
1300
1300
-
575-3-60
-
-
1300
1300
1400
-
208/230-3-60
1600
1600
1600
1600
1600
1600
460-3-60
-
1600
1600
1600
1600
1600
575-3-60
-
-
1600
1600
1600
1800
Unitary Products Group
036-21506-004-A-1105
TABLE 14: ELECT DATA - DH036, 048 & 060 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
0RGHO
7RQQDJH
&RPSUHVVRUV
9ROWDJH
5/$
(DFK
/5$
(DFK
2')DQ ,'%ORZHU &RQY
0RWRU
0RWRU
2XWOHW
)/$
)/$
$PSV
(OHFWULF+HDWHU
0RGHO1R
+HDWHU
N:
+HDWHU
$PSV
0LQLPXP
&LUFXLW
$PSDFLW\
$PSV
0D[)XVH
%5.5 6L]H
$PSV
121(
&( &(
&(
&(
&(
121(
&(
&( &(
&(
&(
121(
&(
&(
&(
&(
121(
&(
&( &(
&(
&(
121(
&(
&(
&(
&(
&(
121(
&(
&( &( &( 121(
&(
&(
&(
121(
&( &(
&(
&(
&(
&(
121(
&(
&( &(
&(
&(
&(
121(
&(
&( &(
&( &(
121(
&(
&(
&(
&(
+$&57\SHSHU1(&
7KHVHHOHFWULFKHDWHUV'2127LQFOXGHDIXVHER[,IDIXVHER[LVUHTXLUHGWRPHHWDORFDOFRGHLH&KLFDJRWKHIXVHEORFNDFFHVVRULHV
)%DQG)%DUHDYDLODEOHIRUILHOGLQVWDOODWLRQ
Unitary Products Group
23
036-21506-004-A-1105
TABLE 15: ELECT DATA - DH036, 048 & 060 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
-ODEL
4ONNAGE
#OMPRESSORS
6OLTAGE
2,!
%ACH
,2!
%ACH
/$&AN
-OTOR
&,!
)$"LOWER
-OTOR
&,!
#ONV
/UTLET
!MPS
%LECTRIC(EATER
-ODEL.O
121(
&(
&(
&(
&(
&(
121(
&(
&(
&(
&(
&(
121(
&(
&(
&(
&(
121(
&( &(
&(
&(
&(
121(
&(
&(
&(
&(
&(
121(
&( &(
&(
&(
121(
&(
&(
&(
121(
&(
&( &(
&(
&(
&(
121(
&(
&(
&(
&(
&(
&(
121(
&(
&(
&(
&(
&(
121(
&(
&(
&(
&(
(EATER
K7
(EATER
!MPS
-INIMUM
#IRCUIT
!MPACITY
!MPS
-AX&USE
"2+2 3IZE
!MPS
+$&57\SHSHU1(&
7KHVHHOHFWULFKHDWHUV'2127LQFOXGHDIXVHER[,IDIXVHER[LVUHTXLUHGWRPHHWDORFDOFRGHLH&KLFDJRWKHIXVHEORFNDFFHVVRULHV
)%DQG)%DUHDYDLODEOHIRUILHOGLQVWDOODWLRQ
24
Unitary Products Group
036-21506-004-A-1105
TABLE 16: PHYSICAL DATA
DH
MODELS
EVAPORATOR
BLOWER
EVAPORATOR
COIL
CONDENSER
FANS
CONDENSER
COILS
COMPRESSOR
(Qty. Per Unit)
AIR
FILTERS
CHARGE
036
048
060
Centrifugal Blower (Dia. x Wd. in.)
12 X 10
12 X 10
12 X 10
Fan Motor HP (Belt Drive)
1 1/2
1 1/2
1 1/2
Rows Deep
4
4
4
Fins Per Inch
13
13
13
Face Area (Sq. Ft.)
4.3
5.1
5.1
Propeller Dia. (in.)
24
24
24
Fan Motor Hp
1/2
1/2
1/2
4200
Nom. CFM
4500
4200
Rows Deep
2
2
2
Fins Per Inch
18
18
18
Face Area (Sq. Ft.)
17.1
17.1
17.1
Recip. Type
1
1
1
Quantity Per Unit (15” X 20” X 1” or 2“)
2
2
2
Quantity Per Unit (14” X 25” X 1” or 2“)
1
1
1
Total Face Area (sq. ft.)
6.3
6.3
6.3
Refrigerant 22
(lbs./oz.)
10/8
10/4
10/14
TABLE 17: ELECTRIC HEAT CORRECTION FACTORS
NOMINAL VOLTAGE
VOLTAGE
kW CAP. MULTIPLIER
MAX.
208/230-3-60
187
253
0.92
460-3-60
414
506
0.92
575-3-60
540
630
208
1.00
240
230
0.92
600
460
575
VOLTAGE
POWER SUPPLY
MIN.
208
480
TABLE 18: VOLTAGE LIMITATIONS1
1. Utilization Range “A” in accordance with ARI Standard
110.
Unitary Products Group
25
036-21506-004-A-1105
TYPICAL POWER WIRING
REFER TO THE ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, OVERCURRENT PROTECTION AND WIRING.
TYPICAL CONTROL WIRING
COOLING / HEATING (24 VOLT THERMOSTAT)
COOLING ONLY (24 VOLT THERMOSTAT)
THERMOSTAT 1
TERMINALS
THERMOSTAT1 UNIT TERMINAL
TERMINALS
STRIP TB1
ADD
JUMPER
R
RV
UNIT TERMINAL
STRIP TB1
RC
R
Y
Y1
24 VOLT
TRANSFORMER
Y1
YC
RH
24 VOLT
TRANSFORMER
Y2
Y2
W
W1
G
GF
W2
C
1
G
C
24 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER
ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.
1
COOLING / HEATING (ELECTRONIC THERMOSTAT)
MULTI STAGE
THERMOSTAT1
TERMINALS
ADD
JUMPER
RC
UNIT TERMINAL
STRIP TB1
RH
R
Y1
Y1
2
Y2
W1
4
ADD
JUMPER
C
LED 1
X
NOT
USED
RH
ADD
JUMPER
OCC
A1
T
TO REMOTE SENSOR
2TH040702224 IF USED
2
SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.
3
SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE
ELECTRIC HEATER OR 2 STAGE GAS HEAT.
RC
R
Y
Y1
W
W1
G
G
24 VOLT
TRANSFORMER
A2
ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).
UNIT TERMINAL
STRIP TB1
C
4
1
4
THERMOSTAT1
TERMINALS
24 VOLT
TRANSFORMER
W2
G
T
1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT
2TH04700224.
REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.
FIGURE 2 -
26
3
B
COM
COOLING / HEATING (ELECTRONIC THERMOSTAT)
SINGLE STAGE
Y2
G
LED 2
24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF
HEAT, USE THERMOSTAT 2TH0471024.
W1
W2
G
TYPICAL FIELD POWER & CONTROL WIRING
Unitary Products Group
036-21506-004-A-1105
FIGURE 3 -
UNIT DIMENSIONS (3 - 5 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW
FIGURE 4 -
UNIT DIMENSIONS (3 - 5 TON COOLING/GAS HEAT) FRONT VIEW
Unitary Products Group
27
036-21506-004-A-1105
DETAIL “A”
FIGURE 5 -
UNIT WITH ECONOMIZER RAINHOOD
DETAIL “B”
FIGURE 6 -
28
UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD
Unitary Products Group
036-21506-004-A-1105
FIGURE 7 -
UNIT DIMENSIONS (REAR VIEW)
TABLE 20: MINIMUM CLEARANCES
FILTER
ACCESS
BLOWER MOTOR
ACCESS
LOCATION
CLEARANCE
Front
24” (Cooling/Electric Heat)
32” (Gas Heat)
Rear
12” (Less Economizer)
36” (With Economizer or Fixed
Air/Motorized Damper)
Left Side (Filter Access)
24” (Less Economizer)
36” (With Economizer)
Right Side (Cond. Coil)
24”
DOT PLUGS
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the
blower housing inside
the blower compartment)
Below Unit
A,B
WIRING ENTRY
(See Detail “B”)
0”
2
72” (For
Condenser Air Discharge)
Above Unit
CONTROL BOX
ACCESS
DISCONNECT SWITCH LOCATION
AND MOTOR ACCESS PANEL FOR
UNIT WITH “BELT-DRIVE” OPTION
FIGURE 8 -
1
DISCONNECT/BLOWER ACCESS
LOCATION
1. Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.
TABLE 19: UTILITIES ENTRY
HOLE
OPENING SIZE (DIA.)
USED FOR
A
7/8” KO1
Control Wiring2
B
2” KO1
Power Wiring
C
1-5/8” KO
Gas Piping (Front)
D
1-1/2” KO
Gas Piping (Bottom)
Side
Bottom
Side
Bottom
1. Opening in the bottom to the unit can be located by the
side in the insulation.
2. Do not remove the 2” knockout ring.
Unitary Products Group
29
036-21506-004-A-1105
FIGURE 9 -
30
TYPICAL APPLICATIONS
Unitary Products Group
036-21506-004-A-1105
BACK OF UNIT
A
447/8
BACK OF UNIT
A
447/8
821/4
821/4
D
B
F
X
X
B
APPROXIMATE
CENTER OF GRAVITY
CONDENSER COIL
END OF UNIT
C
Y
FRONT OF UNIT
C
E
APPROXIMATE
CENTER OF GRAVITY
CONDENSER COIL
END OF UNIT
D
Y
FRONT OF UNIT
FIGURE 10 - FOUR AND SIX POINT LOADING
TABLE 21: DH 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION
UNIT
TOTAL
4-Point Loading (lb)
6-Point Loading (lb)
A
B
C
D
A
B
C
D
E
F
123
157
160
84
83
82
104
105
107
DH036 Cooling/ Electric
565
125
DH036N04
605
134
132
168
171
90
89
88
112
113
114
DH036D06
615
137
134
171
174
91
90
89
113
115
116
DH036N08
625
139
136
173
177
93
92
91
115
117
118
DH036D10
635
141
138
176
179
94
93
92
117
119
120
DH048 Cooling/ Electric
610
135
133
169
172
91
89
88
112
114
115
DH048(D,N)06
660
147
144
183
186
98
97
96
122
123
125
DH048(D,N)10
680
151
148
189
192
101
100
99
125
127
128
DH060 Cooling/ Electric
645
143
141
179
182
96
95
93
119
120
122
DH060D06
695
154
152
193
196
103
102
101
128
130
131
DH060N08
705
157
154
196
199
105
103
102
130
132
133
DH060(D,N)10
715
159
156
198
202
106
105
104
132
133
135
TABLE 22: CENTER OF GRAVITY
DIMENSION
3 - 5 TON
X
40-¾”
Y
19-¾”
Unitary Products Group
31
036-21506-004-A-1105
TABLE 23: OPERATING WEIGHTS (LBS.)
MODEL SIZE
3 TON
4 TON
5 TON
565
610
645
N04
605
-
-
N06
-
660
-
N08
625
-
705
DH (Cooling Only)
BASIC
UNIT
DH
(Gas/Electric)
N10
-
680
715
D06
615
660
695
D10
635
680
715
Economizer
Motorized Damper
OPTIONS
5 - 7 kW
Electric Heater
10 - 15 kW
20 - 30 kW
Roof Curb
ACCY.
Barometric Relief / Fixed Air Damper
50
26
18
23
28
92
10
5
Belt-Drive Blower
FIGURE 11 - ROOF CURB DIMENSIONS
32
Unitary Products Group
036-21506-004-A-1105
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.
York's Sunline Ultra® units are convertible single package
units. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at ground
level or set on steel beams above a finished roof. Cooling
only, cooling with gas heat and cooling with electric heat
models are available with a wide variety of factory-mounted
options and field-installed accessories to make them suitable
for almost every application. All units are self-contained and
assembled on full perimeter base rails with holes in the four
corners for overhead rigging. Every unit is completely piped,
wired, charged and tested at the factory to simplify the field
installation and to provide years of dependable operation. All
models (including those with an economizer) are suitable for
either bottom or horizontal duct connections. Models with
power exhaust are suitable for bottom duct connections only.
For bottom duct, remove the sheet metal panels from the
supply and return air openings through the base of the unit.
For horizontal duct, remove the supply and return air panels
on the rear of the unit.
All non-Scroll compressors include crankcase heaters and all
compressors have internal pressure relief. Every refrigerant
circuit includes a liquid line filter-drier, a discharge line high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch.The unit control circuit
includes a 75 VA transformer, a 24-volt circuit breaker and a
relay board with a compressor lockout circuit, a terminal strip
for thermostat wiring, plus an additional set of pin connectors
to simplify the interface of additional field controls. All units
have long lasting powder paint cabinets with 1000 hour salt
spray test approval under ASTMB117 procedures. All models
are CSA listed. All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater elements carry a 5-year warranty. Aluminized steel and Stainless
steel tubular heat exchangers carry a 10-year warranty.
DESCRIPTION
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat
and designed for outdoor mounted installation.
The 3 ton, 4 ton and 5 ton units shall have minimum SEER
ratings of 12.2, 13.2 and 12.2 respectively. They shall have
built-in field convertible duct connections for down discharge
supply/return or horizontal discharge supply/return, and be
available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with
R-22 refrigerant and factory tested prior to shipment. All unit
wiring shall be both numbered and color coded. All units the
cooling performance shall be rated in accordance with DOE
and ARI test procedures. Units shall be CSA listed, classified
to ANSI Z21.47, UL 1995/CSA No. 236 standards.
Unitary Products Group
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel,
with exterior surfaces coated with a non-chalking, powdered
paint finish, certified at 1000 hours salt spray test per
ASTMB117 standards. Indoor blower section shall be insulated with a minimum 1/2” thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the
furnace compartment and be fastened with ridged fasteners
to prevent insulation from entering the air stream. Cabinet
panels shall be “large” size, easily removable for servicing
and maintenance. Full perimeter base rails shall be provided
to assure reliable transit of equipment, overhead rigging and
proper sealing on roof curb applications. Disposable 1" filters
shall be furnished and be accessible through a removable
access door, sealed airtight. Units filter track shall be
designed to accommodate either 1" or 2" filters. Fan performance measuring ports shall be provided on the outside of
the cabinet to allow accurate air measurements of evaporator
fan performance without removing panels or creating air bypass of the coils. Condensate pan shall be internally sloped
and conform to ASHRAE 62-89 self-draining standards. Condensate connection shall be a minimum of 3/4” I.D. female
and be a ridged mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
The indoor fan shall be a factory installed belt drive assembly
that includes an adjustable pitch motor pulley. Job site
selected (B.H.P.) brake horsepower shall not exceed the
motors nameplate horsepower rating, plus the service factor.
Units shall be designed not to operate above service factor.
Fan wheel shall be double-inlet type with forward-curved
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
air volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to a
corrosion resistant steel spider bracket and shall be dynamically balanced for smooth operation. The outdoor fan motor
shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and
staged independently.
REFRIGERANT COMPONENTS
Compressor:
a.
Shall be internally protected with internal high-pressure relief and over temperature protection.
b.
Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent
mounting.
33
036-21506-004-A-1105
Coils:
GAS HEATING SECTION (SINGLE OR 2 STAGE)
a.
Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless
internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
b.
Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a.
Thermal expansion devices (TXV’s).
b.
Filter drier/strainer to eliminate any moisture or foreign matter.
c.
Accessible service gage connections on both suction and liquid lines to charge, evacuate, and measure refrigerant pressure during any necessary
servicing or troubleshooting, without losing charge.
d.
Shall be designed with induced draft combustion with post
purge logic, energy saving direct spark ignition, and redundant main gas valve. Venter wheel shall be constructed of
stainless steel for corrosion resistance. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 25°F. Burners shall be of the
inshot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit
cabinet at a single location through either the side or curb
without any field modifications. Integrated control boards
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the following minimum protection:
The refrigeration system shall provide at least 15°F
of sub-cooling at design conditions.
a.
Primary and auxiliary high-temperature limit
switches.
b.
Induced draft motor speed sensor.
c.
Flame roll out switch.
d.
Flame proving controls.
ELECTRIC HEATING SECTION
UNIT CONTROLS
34
a.
Unit shall be complete with self-contained low-voltage control circuit protected by a resetable circuit
breaker on the 24-volt transformer side.
b.
Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor.
c.
Loss-of-charge/Low-pressure switch.
An electric heating section, with nickel chromium elements,
shall be provided in a range of 5 thru 30 KW, offering two
stages of capacity - 16 KW and above on 208/230 volt heaters
and 20 KW and above on 460 and 575 volt heaters. The heating section shall have a primary limit control(s) and automatic
reset to prevent the heating element system from operating at
an excessive temperature. The heating section assembly
shall slide out of the unit for easy maintenance and service.
Units with Electric Heating shall be wired for a single point
power supply with branch circuit fusing (where required).
d.
High-pressure switch.
UNIT OPERATING CHARACTERISTICS
e.
Freeze-protection thermostat, evaporator coil.
f.
If any of the above safety devices trip, a LED (lightemitting diode) indicator shall flash a diagnostic
code that indicates which safety switch has tripped.
g.
Unit shall incorporate “AUTO RESET” compressor
over temperature, over current protection.
h.
Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.
i.
Unit control board shall have on-board diagnostics
and fault code display.
j.
Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation
down to 0°F.
a.
Unit shall be capable of starting and running at 125°F
outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240. The compressor, with
standard controls, shall be capable of operation
down to 0°F outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery
before heat exchanger warms up (Gas heat only).
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
STANDARD LIMITED WARRANTIES
k.
Control board shall monitor each refrigerant safety
switch independently.
•
Compressor 5 Years
•
Heat Exchanger 10 Years
l.
Control board shall retain last 5 fault codes in non
volatile memory which will not be lost in the event of
a power loss.
•
Electric Heat Element 5 Years
•
Other Parts 1 Year
Unitary Products Group
036-21506-004-A-1105
OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):
•
•
ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER- Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully
close on power loss.
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air
dampers are positioned by a 2-position, spring-return
damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when
dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor damper
assembly to take in the design CFM of outdoor air to
meet the ventilation requirements of the conditioned
space during normal operation. Whenever the indoor fan
motor is energized, the dampers open up to one of two
pre-selected positions - regardless of the outdoor air
enthalpy. Dampers return to the fully closed position
when the indoor fan motor is de-energized. Dampers
shall fully close on power loss.
•
HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude. Must be used with propane conversion kit.
•
LOW NOX - Required to reduce the emission of nitrogen
oxides below 40 nanograms per joule.
•
GAS PIPING - Contains 1/2” pipe nipples, fittings and
gas cock (including panel assess gaskets) required for
bottom gas supply connection with external shut off.
•
POWER EXHAUST OPTION - To work in conjunction
with economizers.
•
ELECTRIC HEATERS
•
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD Contains all hood panels and the hardware for assembling.
•
MANUAL OUTDOOR AIR DAMPER
•
COIL GUARD KIT - Guard for cooling coil.
•
HAIL GUARD
•
FLUE EXHAUST EXTENSION
OTHER FACTORY INSTALLED OPTIONS
•
POWER EXHAUST OPTION - To work in conjunction
with economizers.
•
STAINLESS STEEL HEAT EXCHANGER
•
STAINLESS STEEL DRAIN PAN
•
BOTTOM DRAIN CONNECTION
•
TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL
•
ELECTRONIC SINGLE ENTHALPY ECONOMIZER
•
DIRTY FILTER SWITCH
•
PHASE MONITOR
•
COIL GUARD
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•
POWERED GFI CONVENIENCE OUTLET
•
•
NON-POWERED GFI CONVENIENCE OUTLET
•
BAS CONTROLS (Simplicity™ INTELLI-Comfort™,
CPC, JOHNSON, HONEYWELL, NOVAR)
•
BAS READY ECONOMIZER (BELIMO ACTUATOR
WITHOUT A CONTROLLER)
•
HINGED FILTER DOOR ACCESS AND TOOLESS
ACCESS PANELS
•
2" PLEATED FILTERS
•
DISCONNECT SWITCH
•
SUPPLY AIR SMOKE DETECTOR
•
RETURN AIR SMOKE DETECTOR
•
•
•
ROOF CURB - 14"and 8” high, full perimeter curb with
wood nailer (shipped knocked-down).
BAROMETRIC RELIEF DAMPER - Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit.
PROPANE CONVERSION KIT - Contains new orifices
and gas valve parts to convert from natural to L.P. gas.
One per unit required.
HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude.
Unitary Products Group
35
Subject to change without notice. Printed in U.S.A.
Copyright © 2005 by Unitary Products Group. All rights reserved.
Unitary
Products
Group
5005
York
Drive
036-21506-004-A-1105