Installation Instructions prior to Feb. 9, 2015

Installation Instructions prior to Feb. 9, 2015
AL6003X220
Triple Output Access Control Power Supply/Charger
Overview:
The AL6003X220 triple output access control power supply/charger is specifically designed for use with access control
systems and accessories. The AL6003X220 converts a 220VAC 50/60Hz input into three individually PTC protected
5VDC, 12VDC and 24VDC regulated outputs (see specifications).
Specifications:
Input:
Battery Backup (cont’d):
• Input 220VAC (working range 198VAC - 256VAC), 50/60Hz, 1.25 amp.
• Zero voltage drop when switched over to
battery backup.
Output:
• 1.75 amp continuous supply current @ 5VDC.
• 1.75 amp continuous supply current @ 12VDC. • 3 amp continuous supply current @ 24VDC.
• Filtered and electronically regulated outputs, 100mV peak output voltage ripple.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when AC fails.
• Maximum charge current 0.7 amp.
Supervision:
• AC fail supervision (form “C” contacts).
• Low battery supervision (form “C” contacts).
Additional Features:
• Thermal and short circuit protection with auto reset.
• Power supply is complete with enclosure, cam lock, and battery leads.
Enclosure Dimensions (H x W x D approximate):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
Stand-by Specifications
(current is specified on AL3XB input):
Output
4 hr. of Stand-by &
5 Minutes of Alarm
24 hr. of Stand-by &
5 Minutes of Alarm
60 hr. of Stand-by &
5 Minutes of Alarm
24VDC / 12AH Battery
--------
Stand-by = 200mA
Alarm = 6.0 amp
--------
24VDC / 40AH Battery
Stand-by = 6.0 amp
Alarm = 6.0 amp
Stand-by = 1.0 amp
Alarm = 6.0 amp
Stand-by = 300mA
Alarm = 6.0 amp
Installation Instructions:
The AL6003X220 should be installed in accordance with article 760 of The National Electrical Code or NFPA 72, as
well as all applicable Local Codes.
1. Mount the AL6003X220 in the desired location.
2. Connect AC power to the two black and two white flying leads of the transformer. Secure green wire lead to
earth ground (Fig. 1). Use 18 AWG or larger for all power connections (Battery, DC output).
3. Measure output voltage before connecting devices. This helps avoiding potential damage.
4. Connect devices to be powered at 5VDC to the terminals marked [+ Out 3 - ].
5. Connect devices to be powered at 12VDC to the terminals marked [+ Out 2 - ].
6. Connect devices to be powered at 24VDC to the terminals marked [+ Out 1 - ].
7. Connect two (2) 12V Stand-by batteries.
Note: For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in
the loss of output voltage. Batteries must be lead acid or gel type if used. Two (2) 12V Stand-by batteries
connected in series to terminals marked [+ BAT -- ] (Fig. 1, pg. 3).
8. It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, LOW BAT] (Fig. 1, pg. 3).
Use 22 AWG to 18 AWG for AC Fail & Low Battery reporting. AC Failure will report in 5 minutes.
RL2
AC FAIL
BAT FAIL
NC C NO NC C NO
RL3
XFMR
IC2
AC TROUBLE
DELAY OPTION
Fig. 1
OPEN = 24V SW1 CLOSED = 12V
XFMR
IC3
RLY1
PTC2
DC
AC
J2
+ DC ---
+ BAT ---
AC
AC
White
Lead
Black
Leads
White
Lead
+ INPUT1 ---
220VAC input
50/60 Hz,
1.25 amp
+ OUT1 ---
+ OUT2 ---
+ OUT3 ---
Green
Lead
(ground)
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
(see power supply output specifications table).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at the battery
terminals and at the board terminals marked [- BAT +] to ensure that there is no break in the battery connection wires.
Note: Maximum charge current under discharge is 0.7 amp.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if necessary.
- 2 -
AL6003X220
LED Diagnostics:
Power Supply Board
Red (DC)
Green (AC)
Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC, Stand-by battery supplying power.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
Terminal Identification:
AL600ULB - Power Supply
Terminal Legend Function/Description
AC/AC
Low voltage AC input (28VAC / 200VA).
+ DC ---
12VDC / 24VDC @ 6 amp continuous non power-limited output.
AC Fail
NC, C, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally
energized when AC power is present. Contact rating 1 amp @ 28VDC.
Bat Fail
NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC
power is present. Contact rating 1 amp @ 28VDC.
+ BAT ---
Stand-by battery connections. Maximum charge current 0.7 amp.
AL3XB - Power Output Module
Terminal Legend Function/Description
- Input +
24VDC from power supply.
- OUT 1 +
24VDC @ 3 amp continuous power limited output.
- OUT 2 +
12VDC @ 1.75 amp continuous power limited output.
- OUT 3 +
5VDC @ 1.75 amp continuous power limited output.
AL6003X220
-3-
Enclosure Dimensions (H x W x D approximate):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
1.5”
(38.1mm)
4.615”
(117.22mm)
4.615”
(117.22mm)
1.5”
(38.1mm)
1.75”
(44.45mm)
1.375”
(34.925mm)
1.125”
(28.575mm)
1.25”
(31.75mm)
4.5”
(114.3mm)
12.23”
(310.64mm)
1.1”
(27.94mm)
0.91”
(23.114mm)
1.5”
(38.1mm)
4.5”
(114.3mm)
1.1”
(27.94mm)
1.25”
(31.75mm)
0.91”
(23.114mm)
2.0”
(50.8mm)
1.5”
(38.1mm)
15.5”
(393.7mm)
2.0”
(50.8mm)
5.0”
(127.0mm)
5.0”
(127.0mm)
1.1”
(27.94mm)
1.25”
(31.75mm)
0.79”
(20.06mm)
1.25”
(31.75mm)
1.75”
(44.45mm)
1.5”
(38.1mm)
4.615”
(117.22mm)
4.615”
(117.22mm)
1.5”
(38.1mm)
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A.
IIAL6003X220 - Rev. 092807
- 4 -
G02M
MEMBER
AL6003X220
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising