abc200.0-4d4y
GLOBAL POWER INTERFACE® SERIES 2000
SPECIFICATIONS
General Specifications - Model ABC200.0-4D4Y
Input Voltage
400
Output Voltage
400/230
Frequency
50/60 Hz.
Continuous Capacity
200 kVA
BTU/Hr. Output
10,242
Efficiency
> 98.5% (at full load, unity power factor)
Step Load Change
+ 0.8% (at unity power factor)
Noise Rejection
With unit under power and the isolation transformer configured for a transformation
ratio of 1:1 and with an ANSI/IEEE C62.41, Category A pulse applied either normal mode
or common mode at the input, the noise output voltage will be less than 10 volts normal
mode and less than .5 volts (½ of one volt) common mode in all four quadrants
(CM-NM, NM-NM, CM-CM, NM-CM).
Surge Voltage Withstand
Tested under power to ANSI/IEEE C62.41, Category A & B (formerly IEEE587-1980).
Power conditioner tested to withstand up to 6000 volts @ 3000 amp ringwave and unipo
lar impulse.
Construction Materials
Transformer wires are copper and insulated with Class H materials. Windings are insu
lated with Nomex paper insulation before vacuum varnishing. Internal wiring is a mini
mum of 200 degree C rated and sleeved with Class H materials. Grain oriented
silicon iron cores are constructed using 14 mil. laminations interleaved one to one. Eddy
currents are minimized and external magnetic fields are below 0.1 oersted (at 12 inches
distance in any direction). Unit is RoHS compliant.
Physical Dimensions
H x W x D - mm (inches)
1625 x 711 x 990 (64 x 28 x 39)
Weight
1355 (2981)
Input Connection Requirements*
Input
Voltage
Input
Current
(FLA)
Supply
Breaker Rating
@ Switchgear
AIC (Current Interrupt
Capacity of Input
Circuit Breaker
Minimum Input
Conductor Size
(includes
ground)
Input Lug
Maximum Wire
Size
400
289
400
35 kAmps
500 kCMIL or
equivalent
500 kCMIL
Output Connection Requirements*
Output
Voltage
Output Current
(FLA)
Minimum Output
Conductor Size
(includes ground)
Output Lug
Maximum
Wire Size
400/230
289
250 kCMIL
350 kCMIL
* Supply breaker ratings are determined by NEC guidelines limiting breaker loading to 80% of rated breaker capacity. Calculations for supply breaker recommended ratings are based on
input full load amps multiplied by 1.25 and then selecting the next larger standard size breaker. Wire sizes shown in the input and output connection tables of this specification sheet are the
minimum sizes allowed by electrical codes for each supply breaker rating and are taken from the 2002 National Electrical Code Article 310.16 table references for use in 900 C installations.
1450 Lakeside Drive, Waukegan, IL 60085
(847) 596 - 7000 - (Outside Illinois 800 - 369-7179), Fax (847) 596 - 7100
www.powervar.com
SM2035
GLOBAL POWER INTERFACE® SERIES 2000
SPECIFICATIONS